4.5100333-01 - Salwico Cargo Addressable - Installation Manual - M - EN - 2013 - H
4.5100333-01 - Salwico Cargo Addressable - Installation Manual - M - EN - 2013 - H
Addressable
Fire Detection System
Installation Manual
Consilium Marine & Safety AB
Fire & Gas Marine Division
Phone: +46 31 710 77 00
Fax: +46 31 710 78 00
E-mail: Service: [email protected]
Spares: [email protected]
Consilium Marine & Safety AB
Navigation Division
Phone: +46 8 563 05 100
Fax: +46 8 563 05 199
E-mail: Service, APT: [email protected]
Spares: [email protected]
Consilium Marine & Safety AB
Transport Division
Phone: +46 31 710 77 00
Fax: +46 31 710 78 00
E-mail: Service: [email protected]
Spares: [email protected]
The contents of this document are subject to revision without notice
due to continued progress in methodology, design and manufacturing.
Consilium assumes no legal responsibility for any error or damage
resulting from the usage of this document.
April 2013
Document no. 5100333-01_Salwico Cargo Addressable_Installation Manual_M_EN_2013_H
Part no. 5100333-01
1 Introduction ...................................................................................... 1
1.1 About this Manual ........................................................................... 1
1.2 Symbols used in the manual ............................................................ 2
1.3 Approvals .......................................................................................... 3
3 Installation ....................................................................................... 7
3.1 Prerequisites for Installation ........................................................... 7
3.2 Mechanical Installation ................................................................... 7
3.2.1 Installation Order ........................................................................... 7
3.2.2 Control Panels ................................................................................ 7
3.2.3 Loop Units ..................................................................................... 7
3.2.4 Mounting of Modules on a DIN rail .............................................. 7
4 Verification ....................................................................................... 21
4.1 Prerequisites for Verification ........................................................... 21
4.2 Loops ................................................................................................. 21
4.2.1 Verification of Loops ..................................................................... 21
4.2.2 Testing of System Parts .................................................................. 22
7 Appendix ........................................................................................... 49
7.1 General alarm on the CCP panel .................................................... 49
7.2 EN54 Functions ............................................................................... 50
7.3 Address List and Test Report ........................................................... 52
7.4 ID List ............................................................................................... 55
Table of contents
Index ................................................................................................. 74
Table of contents
Installation Manual 1 Introduction
1 Introduction
NOTE!
This user guide has been revised based on version 1.6.0 but is valid for Control
panel software versions beginning with version 1.0.0.
Chapter Verification describes how to test the installed system. After the
installation is completed, the system is verified, which must be performed by a
person with good knowledge of the various functions. This chapter also includes
verification and troubleshooting.
WARNING!
Risk of personal injury and/or damage to the product if the instructions are not
followed.
CAUTION!
Risk of minor or moderate personal injury. Risk of equipment damage, loss of data,
extra work, or unexpected results, if the instructions are not followed.
NOTE!
Note symbols alert you to important facts and conditions.
Hint!
Tip symbols direct you to specific instructions, such as where to find additional
information and tell you how to perform a certain operation in an easier way.
1.3 Approvals
2 General Description
NOTE!
System boot-time is kept to a minimum during normal operation, but it can be
extra-long after a new installation, commissioning or major maintenance work
(depending on the configuration of the data definition file).
Hint!
For detailed requirements, refer to the data sheets.
3 Installation
The different parts of the system, the control and system modules, should first be
mechanically installed. The different loop units are thereafter electrically installed
and set up according to the definition of the loops and drawings.
The cables must be tested separately before the loops are connected to the loop
module. This eliminates any problem with the cable and electrical installation of
the loop units.
The installation is completed with the electrical installation of the the control and
system modules.
The mechanical installation of the different types of loop and zone units are
described in their respective data sheets.
The cables connecting from the backbone bus to the control panels or stretched
central part must meet the following requirements:
Channel 1 & 2
• Min 2 x 2 x 0.3 mm2, twisted pair shielded
(RS485 + backup signal, one conductor)
NOTE!
The backup signal is only needed for one channel. (The back up signal
is optional.)
• Max allowed cable length is 700 m
• Optional: Power supply (24 VDC) 1 x 2 x 0.75 mm2
Refer to the system connection drawing
NOTE!
Channel 1 and Channel 2 should be routed separately for improved safety if both
channels are used.
Detector loops
Detector loop cables must meet the following minimum requirements. We refer to
current regulations for the rest of the specification.
• cable type
• shielded or unshielded cable
• power consumption
A cable is considered shielded if the shielded part is more than 10% of the cable's
total length.
CAUTION!
Never exceed the recommended cable lengths as listed in table Loop cable lengths.
Loop units are divided into three types. These types (1, 2 and 3) are based on the
individual load on the loop.
NOTE!
When calculating the number of loop units, consider the future expansion of new
loop units. Make sure there are at least 10% in spare addresses evenly distributed
among the intervals between short circuit isolators.
For example, if using type 1A loop units:
254 addresses x 0.9 = Max. 228 loop units/loops.
CAUTION!
Short circuit isolators and sounders
Under investigation, preliminary limitations: The maximum no. of above units to
be mounted on any loop are 20 sounders and 35 devices of short circuit isolators
(short circuit isolators or units with built-in short circuit isolator).
your system. Some of the loop units are connected directly to the loop and some
are connected through address units.
For more details about their connection, see Connections for Loop Units, page
56.
The information about the electrical installation of each type of loop unit is
provided in its respective data sheet.
NOTE!
• Set the address switch on each loop unit before connecting them to the loop. If
an address unit is used, set its ID switch. See Setting the Address on Loop
Units, page 16 later in this chapter and also Address List and Test Report,
page 52 and ID List, page 55.
• Bypass all separate short circuit isolators (if there are any in the setup) before
testing the loop. Join the cores leading to terminals 2 and 4 and the cores
leading to terminals 1 and 3 using a temporary connector block inside the short
circuit isolators.
CAUTION!
Do not remove dust protection covers from the smoke detectors until all polluting
activities (such as construction work) are finished and the area has been cleaned.
The cable can only be tested if all short circuit isolators are bypassed.
Measure the resistance between the + and - poles. Connect an ohm-meter between
the + poles as shown in the following figure. Measure and repeat the procedure for
the - poles.
The measured value should be less then 185 Ohm for a cable with a maximum
length of 3 km.
The cable break is located between the “last” unit on the A side and the “first” unit
on the B side.
Measure the resistance between the + pole and the - pole. Connect an ohm-meter
between the two poles, as shown in the following figure.
The measured value should be more than 100 kOhm for a cable with a maximum
length of 3 km.
The control unit will report which short circuit isolators have been activated. The
short circuit failure is located between the activated short circuit isolators.
Measure between the + and - pole and earth to detect an earth fault. Connect the
ohm meter between the + pole and earth as shown in the following figure. Measure
and repeat the procedure for the - pole.
The measured value should be more than 50 kOhm for a cable with a maximum
length of 3 km. Values below 8 kOhm (±2 kOhm) will be indicated as earth fault.
The control unit reports the detector loop or central where the earth failure occurs.
The value of the address is set according to the switches set to ON position as
shown in the following figure:
By setting the switches numbered 1,2,3,4 and 6 to the ON position, the address is
configured as 1+2+4+8+32 = 47.
NOTE!
After setting the address, remove the label attached to the detector and use it to seal
the address switch.
Address units
In addition to the loop address, address units and I/O units are equipped with an ID
DIP switch. This ID DIP switch determines the unit’s functionality.
Addressable timers
The addressable timers are located on the detector loop in the same way as any
loop unit.
For UR-2/UR-2K type timers, three DIP switches are set as follows:
NOTE!
Timers do not affect the function of the manual call points or heat detectors.
1 For detailed information, refer to the data sheet for corresponding unit.
Follow this instruction to set address for the Repeater M 4.3 module in the system
and set the panel functions.
1 Press both arrow keys + to open the Use the arrow keys to scroll
Enter Access Code menu. and select the digits for the
Approximate 4-5 seconds. Access Code.
Confirm with the Local Mute
button (= Next digit or
Enter).
( = Previous.)
2 Proceed to choose address and layout for For all menu alternatives use
the Repeater module: the arrow keys to scroll and
• Enter Central Address select.
Confirm with the Local Mute
• Enter Module Address
button.
• Enter Layout Follow the instructions on the
Reboot the Repeater module (it will take lower part of the screen.
the module about 20 seconds to restart).
Refer to Central Unit Terminal & Cabling Layout, page 59 for more information.
For other electrical installations, such as Printer and Basic Backup Signal (BBU),
refer to the specific project drawings.
Control Panel
If the Control Panel is placed outside of the Fire detection cabinet, connection to
the Central Unit is made via the external Backbone Bus channel (BBE), as shown
in the System Block Diagram, page 5. Each cable should be routed seperately
for maximum security.
4 Verification
Hint!
To verify cable status and loop unit addresses, it is possible to confirm the
addressable detector loops with a SE3000 test device before making connections to
the central unit.
4.2 Loops
4.2.1 Verification of Loops
NOTE!
Once the loop cable has been tested and is free from faults, the next step is to
connect it to the central.
5 Verify that the correct number and type of If the list reports (?/?) the
loop units are installed in the correct place. answering side status will be
The system will provide you with the updated if pressing “1. Update
requested information if you use the Menu list”. The system will scan the
» 6 Service Menu » 5 Loops, choose the loop to determine answering
relevant loop, and then press “2=Loop side. The loop is disabled
Units”. during the scan and the
Each loop unit will report on which side A procedure may take several
(primary) or B (secondary) it answers: minutes (access code 3 is
OK (A/B) = Answer on both sides. required).
OK (A/-) = Answer only on A side. If a loop unit is missing, see
Wrong Number of Loop Units
OK (-/B) = Answer only on B side.
(only for Addressable Loops
OK (?/?) = The loop unit answers but the on Loop M X), page 25.
loop module doesn’t know on
which side until an update is
made.
Press “1. Update list” to
perform an update.
No answer The loop unit does not answer
(-/-) = on either side.
6 One loop is now verified and tested. Repeat steps 3-5 for all other
Continue with the next loop. loops.
7 Make a fire detector test of the complete See Testing of System Parts,
Fire detection system. page 22.
Use appropriate test equipment (smoke
detector test gas, heat detector tester) to test
each detector and loop unit.
See section Recommended Test Equipment,
page 24.
Print out the “Fire alarm history list” found
under Menu » 7 History » 1 Fire History
List. This list contains the 500 latest fire
alarms, and is cleared each time the system
is restarted.
8 Use a top to bottom procedure if you have
any problem with the verification of the
loop function.
Start by solving the problems that affect the
whole loop and then continue with the
problems with each address.
The system has a special test mode function which makes the testing easier.
• External alarm devices and controls are by default not activated in case of a fire.
Hint!
This functionality can be turned off.
• The alarm level is lowered to give a quick response to detector test equipment.
• LED indicators on loop units begin to blink.
• Each tested loop unit will indicate activation by its LED indicator.
• If a printer is connected to the system, alarms will automatically be printed as a
result of the tested units.
• The units in alarm are automatically reset if the heat or smoke concentration is
under the alarm level, or if the manual call point is reset.
NOTE!
The system handles fire alarms from zones not in test mode in the usual way.
The tested zone will automatically return to normal operation after two hours.
CAUTION!
During system start-up Loop modules performs a 15 minutes calibration period for
pollution level of smoke. No tests should be done during this period.
It is now safe to test each detector and manual call point in this fire zone during the
next two hours.
All alarms are listed under: Menu » 7 History » 1 Fire History List.
NOTE!
Use appropriate test equipment.
See section Recommended Test Equipment, page 24.
For detailed information, please refer to the data sheets for the products.
1 The zones in test mode are listed in the Disablement List, found under:
Menu » 3 Disablements » 2 List disablements.
2 Choose the zone in the disablement list and then press .
• The display
• All indications on the control panel
1 To test the control panel display, use: Menu » 5 Settings » 4 Test display.
Hint!
* The system is equipped with a Hot Plug&Play function enabling the user to add
or delete detectors during normal operation without needing to change the
configuration file with a PC and restarting the system.
The configuration file may be updated during normal operation from Service Menu
(Menu » 6 Service Menu » 5 Loops) or directly from the Fault List (Menu » 1 Fault
Alarms » 1 Fault List). For additional information, please refer to the Service and
Maintenance Manual.
Address error
Use Menu » 6 Service Menu » 5 Loops, choose the relevant loop, and then press
“2=Loops Units” to list all found units on the loop. Compare the found loop units
with the ones configured.
There is a possibility that two or more loop units with the same address will
answer. Possible reports include “double address”, “no answer”, “bad
communication” or “abnormal condition”.
1 No answer is received on a single fed loop? The cable is broken before the
first loop unit.
2 The loop is a double fed loop? The cable is broken before the
first loop unit and after the
last loop unit.
Refer to Test 1: Test for Cable Break, page 13, to measure the resistance with a
ohm-meter.
1 The cable break is located between the “last” unit on the A side and the
“first” unit on the B side.
Refer to Test 1: Test for Cable Break, page 13, to measure the resistance with a
ohm-meter.
1 Examine the faulty loop to locate the earth Refer to Test 3: Test for Earth
fault. Failure, page 15 for more
details.
If the earth fault still remains after this step, examine the cables to all other devices
connected to the Fire detection system.
1 Search for the short circuits between the Refer to Test 2: Test for Short
central unit and the first short circuit Circuits, page 14 for more
isolator. details.
1 The control unit displays which short Refer to Test 2: Test for Short
circuit isolators have been activated. Search Circuits, page 14 for more
for the short circuit between the fault details.
reported short circuit isolators to find the
exact location of the fault.
The faults are reset from the Fault list under Menu » 1 Fault Alarms » 1 Fault List.
Hint!
Recommendations for centrals containing many control modules/repeaters and/or
distributed centrals can be found in section Upgrading Large Systems, page 32.
Prerequisites
• USB memory stick
• CCP software release
• Laptop running Windows XP/2000/Vista/7 and an Ethernet Cable (necessary for
Control M X)
NOTE!
Primarily, use a USB memory stick to upgrade firmware in in a Control M 4.3,
Repeater M 4.3 or Control M 2.2.
To Control M X you have to use the Ethernet connection.
Prerequisites
• Laptop running Windows XP/2000/Vista/7 and an Ethernet Cable.
• CCP software release image file (i.e. uImage).
• The Control Module must have at least Firmware 1.2.0 in order to support
update via Ethernet.
1 Go to Tools » Options.
2 Select manual configuration.
3 In the drop down list. Select the network adapter that you connect your
cable to.
4 Select OK to confirm your selection.
1 The tool should now automatically attempt to establish connection with the
target and print out detected Central and Card address together with current
flashed firmware version.
2 The tool should now be ready to download new firmware.
1 Press the Program Firmware button and This may take some time to
wait. complete.
2 Target will reboot. If the target hardware has a
version before 1.2.0 you may
still be able to program it by
manually rebooting the target
when requested by the tool. (If
the bootloader supports
booting over Ethernet.)
3 Target will then re-establish connection
with the tool and start downloading the new
firmware.
4 Target will be reflashed.
5 Target will reboot and start the new
firmware.
Hint!
Before following the instructions below it might be a good idea to understand the
basics of what the instructions are trying to achieve and that is to avoid excessive
master/slave switches and to minimize the traffic that occurs when the system is
trying to synchronize its state between all control modules.
In order to reduce the number of master/slave switches the ordering of the upgrade
is to start with the control modules on the primary system bus and then proceed
with the control modules on the secondary system bus.
To further reduce traffic on extension buses. Upgrade and restart the control
modules owning an extension bus before the repeaters on the extension bus.
Finally, for really large systems (more than 5000 detectors) it will further reduce
the traffic to disconnect the system buses completely at 1.1 and 1.2 during the
upgrade.
Upgrade for control panel modules (Control M4.3 and Control M2.2)
The system log file can be downloaded using an approved USB memory stick
(available from an authorized dealer).
CAUTION!
Do not remove the USB memory stick until the download is finished.
1 Connect the USB memory stick to the USB port on the Control M 4.3
panel.
2 Choose Menu » 6 Service Menu » 8 System Log.
5 Commissioning Requirements
5.1 Prerequisite
The procedure described below in Loop Requirements is to be followed by the
installation team.
If nothing else is agreed, no commissioning engineer will be sent before the steps
below are confirmed and the appropriate papers are signed and sent to your local
Consilium office or authorized representative.
The list in Part A: Loop Configuration includes all data you need when configuring
the loops. Part B: Loop Status is more like a checklist - follow it point by point.
When you have completed this part you should have filled in, signed and faxed the
special document Address List and Test Report, page 52, one for each loop in the
system. Part C: Central Status is also a checklist, but it deals with the status of the
central unit.
6 When testing loop units, follow the testing instructions provided with the
testing device.
NOTE!
Use appropriate test equipment.
See section Recommended Test Equipment, page 24.
7 Check the addresses of all loop units one at a time, according to Address
List and Test Report.
8 A test report must be filled in for each loop as described in Address List
and Test Report. Check each single detector and tick off on each checked
address.
9 After each loop is completely tested, the person in charge of the loop
installation must sign the test report as described in Address List and Test
Report.
10 Send one copy of the signed test protocol to your local Consilium office or
authorized representative.
11 When all loops are tested and all protocols are signed, your local Consilium
office or authorized representative may be requested to come and make the
final control and adjustment of the system.
NOTE!
Deviations from the above criteria may cause time delays. These time delays will
be invoiced.
5.6 Summary
For each loop, a test report as described in Address List and Test Report, page 52
must be filled in and sent to your local Consilium office or authorized
representative before commissioning of the system starts.
CAUTION!
Always refer to and act according to current local rules and regulations.
• Prior to installation, program all addressable loop units with a loop address.
Refer to the Address List, page 52.
• After the loop address is set, place the adhesive label over the address's DIP
switch to seal it. (Only applicable for detectors equipped with DIP switch.)
• For conventional (non-addressable) detectors, an end of line resistor must be
installed in the last detector/unit base of each section. The type of resistor
depends mainly on how the fire detection system is configured.
• Make sure that smoke detectors maintain their protective dust covers until
polluting activities such as construction have been completed and the area have
been cleaned.
• Mark each loop unit with zone and address number. Suitable marking location
for a detector is on its base. Special adhesive labels for marking are available
from the authorized organization.
• Each unit requires an IP class suitable for its operational environment.
• To help maintain the correct IP class, plug any unused cable glands.
• Keep the detectors protection caps on as long as possible. The protection caps
should be removed after commissioning is completed and the system is handed
over.
NOTE!
For detailed connection and installation information, refer to the data sheet for each
unit.
• Do not install a smoke detector in areas with temperature below 5°C or where
condensation is likely.
• A smoke detector shall not be installed where it may be exposed to direct air
flow > 20 m/s.
• A smoke detector’s minimum distance from a wall or a bulkhead is 0.5 m.
• The maximum distance for a smoke detector from a wall or a bulkhead is 5.5 m.
The maximum distance between two detectors is 11 m.
• When placed in engine spaces, smoke detectors shall have 2 m extra cable slack
to enable relocation within the space.
• In cabins and in lockers, mount the detector with its LEDs facing toward the
door.
• Avoid shadow areas from objects in the room, by placing a second detector
facing the opposite side of the object, see Figure 12. Flame detector mounting.
• Mount the flame detector to give it clear access to the location of the anticipated
fire. A detector has a typical cone of vision of 100° from the central axis, see
data sheet of flame detector for more information. Place the detector beside, but
not directly above, the protected object to prevent the risk that black smoke may
block the flames. Place the detector at an angle of 45° downwards. This way the
detector will project both downward and forward and catch the least amount of
dirt. For more information about its angle of projection, refer to the flame
detector’s data sheet.
• A general rule is to install the detector on a height that is twice the height of the
highest object in the supervised area, if possible.
• Avoid sources for false alarm (e.g. flares) from entering the detector’s cone of
vision.
• Connect the detector to an address unit located outside the hot area and in as
good of environment as possible, and where it can easily be accessed for
service. The maximum cable length between the detector and the address unit is
25 m.
• The address should be set on the address unit and the function ID switch (small
DIP switch) should be set.
• An end-of-line resistor shall be fitted inside the detector base if the detector is
the last unit on the line.
• Installation shall preferably be hidden from the public but easily accessible for
service.
• The short circuit isolators must be connected with correct polarity.
6.1.11 Timers
• The timer unit is used for the temporary disablement of detectors in areas where
smoke or heat can occur under normal circumstances.
• The timer should be mounted for easy access and operation and well marked
with its function.
• For UR-2 type timers:
In addition to the loop address, the address interval for the detectors to be
disabled must be set on the timer’s extra DIP switches.
6.1.12 Bells
• Installation height is normally 0.2 m from the ceiling and max 2.2 m from the
floor.
• After installation, make sure that the gong is free from the cables, otherwise the
sound output may be reduced.
• Should be mounted with cable entrance facing downwards.
When installing metal cable tubes – following must be taken into account:
• If there is more than one cable in the same tube, the cross section (counted of
mutual external diameters) may be max 40% of the inner cross section of the
tube.
• If the tube is more than 10 m long, drafting holes has to be done.
• Tubes must be installed on support so that the background may be painted.
• Tube installation must be done by welding or by tube joints. Fastening distances
are located 100 mm from the tube end and afterwards every 1.5 m.
• Bending radius must be at least 6 times the external diameter of the tube.
• The upper tube end in open decks must be sealed up, this to prevent water from
coming in.
When installing plastic cable tubes – following must be taken into account:
• Bending radius must be at least six times external diameter of the tube.
• Installation must be done onto the warm side of a thermal insulation and at least
100 mm from a hot surface, preferably below it. Piping is not allowed inside a
thermal insulation.
• The tubes are tied with galvanized wire clips. The first clip is located
approximately 100 mm from the tube end and afterwards every 1 m.
6.2.4 Cabling
When installing the cables – take into account the minimum internal bending
radius, that has nominal value of six times the external diameter of the cable.
• If two separate routes for the cables are required – all supplies and involved
control cables must be passed by separate routes according to the drawings and
cable passing list.
• Do not bundle low voltage cables together with power cables, they have to be
separated from each other.
• When cable bundles are mounted on trays this can be done as follows:
• On the trays along the ship – the power cables on the left side (Port-side)
and the low voltage cables on the right side (Starboard-side) of the tray.
• On the trays across the ship – the power cables to the fore side and the low
voltage cables in the stern side of the tray.
• On the fore or stem bulkhead trays in vertical shaft – the power cables to the
Port-side or the Starboard-side bulkhead trays, the power cables to the fore
side and the low voltage cables to the stern side of the tray.
• In cable junctions and when exiting the cable trays bridges with fastening bolts
have to be used – low voltage cables for alarm, communication, navigational
and measuring equipment have to be installed in their own bundles.
• Each fire detector installed in engine room areas shall have two (2) meters extra
cables, this to make it possible to relocate the detector position when
performing “real” smoke tests with fans etc. running.
• Wet spaces:
• Cables are penetrated from the bellow or from the side with diaphragm
seals.
• Let the cables enter the sealing at a right angle (or as near a right angle as
possible).
• Dry spaces:
• Free entering
No cables are to be installed below 50 mm distance from bottom or fuel oil tank,
except cables ending in these spaces.
• When installing cables without plastic tube inside the lining, the cables are
fastened to supporting construction of the ceiling with plastic bundle-ties.
6.2.7 Markings
• Cables entering terminal boxes and equals shall be marked with identification
markings.
• The cable identification is to be done with a metal dymo-tape – on open decks
the dymo-tape must be of stainless steel.
• Cable markings are the same as the identification marks in the drawings.
• The cable is passed in switchboards, decks and terminals unpeeled as near the
connection place as possible.
• Mark extra wires (not used) and do not cut them.
• Earthing wire is marked with yellow/green sleeve.
• Cable wire ends of 0.5–2.5 mm2 shall be equipped with compression-type
collar, if the contact screw presses direct wires.
• A cable eye shall be installed at the end of a conductor, connected by means of
a screw or a bolt.
• No more than two conductors shall be connected onto one side of the same
terminal.
7 Appendix
In addition to meeting the DNV requirements and regulation 6.4.2 of Chapter III in
the SOLAS the general alarm functionality meets the requirements of paragraph
7.2.1 of the LSA Code and IMO Resolution A.830(19): Code on Alarms and
Indicators, 1995. The CCP fire alarm system also conforms to the requirements in
IEC-90945.
In general, the sound level during general alarm should be a least 10 dB(A) above
the ambient noise level in all accommodation spaces, service spaces, control
stations and engine room spaces. Inside the cabins, the sound level should be at
least 75dB(A) at the sleeping position. In no case should alarm level in a space
exceed 120dB(A).
To comply with the DNV requirements the alarm devices must either have one
fused alarm circuit pr. deck or be connected to a ring loop as shown in Figure 13.
Figure 14. shows the redundancy in power supply to all units in the system. The
system is power supplied both from the main 230 V supply and the emergency 230
V supply. The backup batteries must be calculated to last for at least 30 minutes.
Figure 15. shows the functionality of the general alarm system and the priority of
alarms.
7.4 ID List
7.4.1 Prerequisite
The ID switch must be set on the address unit type AE and NS-AIN. The ID
defines the function and the type of the unit connected to the address unit.
The value of the ID is according to the switches set to the “ON” position as shown
in the following figure:
The switches numbered 1 and 3 are set to the ON position. The values for these
switches are 1+4=5.
(NS-AIN1 has constant sub-loop voltage, while NS-AIN2 has pulse voltage).
Charger M
A Module that supervises and controls the power and battery functions.
For complete information, see the data sheet for each module.
The Control M 4.3 and Control M 2.2 can act as a Control Panel, i.e. they have an
Control Panel
HMI and the rights to manipulate and supervise the System.
Control Modules can run in Controller Mode, i.e. being Master or Hot Standby Master
within a central. Control Modules can also be in managed mode, that is being a module
Controller Mode
that is managed by the master. All other modules are always running in managed
mode.
A Control Module that is in Controller Mode (master or hot standby) in a Central or
Controller Module
System.
DCS Distributed Central System (see also Stretched Central).
Detector A device capable of detecting fire or gas alarms.
Disablement of devices such as a Zones or Detectors. Alarms from disabled devices
Disablement
will be inhibited.
Emergency Shut Down System, embedded system taking care of safety procedures in
ESD System
case of emergency, for example shut down of fire doors, ventilation etc.
An additional (RS485) bus used inside a central for intra-central communication. The
Extension Bus is typically used for connecting Repeater Modules (that does not require
Extension Bus
redundant communication and power) and should not be confused with the Backbone
Bus.
Communication to external entities is called external communication, using for
External Communication
example MODBUS, NMEA or TCMS protocols.
External Control Outputs used to control external equipment, for example fire doors.
Fault Condition The state of the system when a fault is detected.
Automatically generated signal according to a pre-defined pattern (e.g. 7 short 1 long
GA-auto
signal) for alarm devices or the PA system.
GA-Morse Signal pattern generated manually via the GA button.
GA General alarm, common activation of alarm devices and activation of the PA system.
Controller Modules in Hot Standby Mode can take over the responsibilities of the
Hot Standby Mode
Controller Module managing a Central.
An Input/Output type providing a different function depending on the configuration of
the system. The programmable functions are:
• General Input
I/O 70 • Fault Input
• Conventional Fire Alarm Zone
• Output (24 VDC/70 mA)
A module with inputs and/or outputs. I/O modules always run in Managed Mode, that
I/O Module
is they must be managed by a Controller Module.
I/O Pin or I/O Signal An I/O Pin or an I/O Signal is a logical signal, compare to terminal.
Inter-central Communication Communication between centrals is called inter-central communication.
A communication channel used to interface the systems with external devices.
Interface Channel
Interface channels can be configured to communicate on different protocols.
A module that is a part of the Platform, that is can be used to build Centrals. Modules
Module within the platform generally supply a Backbone Bus interface. Controller Modules
also have a System Bus Interface.
Module Address Module Addresses are set via DIP switches on the Modules.
Mute Acknowledge and silence the local buzzer and in some cases the alarm devices.
PA Public Addressing.
Power Output Output providing power supply, normally used to power external devices.
A condition preceding the Alarm Condition to give early warning for potentially
Pre-Alarm Condition
dangerous situations like a smouldering fire.
Programmable Output Output which signal behaviour is configurable via the Configuration Program.
PSU Power Supply Unit.
Rate of Rise functionality by using C/E commands for setting of a different alarm
Rate of Rise
threshold and temperature rise threshold for heat detectors.
Refers to the quality or state of being redundant, that is exceeding what is necessary or
Redundancy normal. In the System the term is used to describe backup functionality like in Hot
Standby Controller Modules.
Electrically operated switch output, normally providing C/NO/NC contacts for
Relay
connection of signal receiver.
The main attribute for Repeater Panels is that they can show information but not affect
Repeater Panel
the Central (or System) they belong to. The Repeater M 4.3 is a Repeater Panel.
Modules enter 'safe state' when they detect system faults. Modules in Safe State put
Safe State their I/O in a predefined state and stop all communication in order to avoid disturbing
system integrity.
SCS Single Central System.
Salwico Safety Management interactive graphics, a PC-based software package
SMig system
providing graphical presentation and control of the System.
A central that is physically distributed to two or more physical locations. One location
Stretched central (DCS) may or may not supply power to another location (segmented) and two locations may
or may not have isolated communication lines.
A signal in the Backbone Bus that is used for transmitting synchronization signal used
Synchronization Signal
by system Modules to synchronize there behaviour.
System A System consists of one or more Centrals.
The communication bus used for connecting multi-central systems. The System Bus is
used for inter-central communication but can also be used for external communication.
System Bus
If inter-central communication redundancy is required, the system bus will consist of a
primary and a secondary System Bus.
Terminal A Terminal is a physical point of connection, compare I/O pin.
Detectors put in the Test Condition (or Test Mode) are inhibited from generating the
Test Condition Alarm Condition but the alarms are displayed on the Control Panels to prove that the
tested Detectors are operational.
Universal Serial Bus, a communications bus that may be used to connect flash
USB
memories, keyboards, mice or other devices.
The state of the system when a warning is detected. Warnings are not as serious as
Warning Condition faults and only of informative nature, for example that a Gas Detector is in need of
calibration.
Zone A group of detectors located in a geographical area.
Index
A F
About testing.......................................................... 22 Fault list ................................................................. 26
Address programming tool, Instructions for.......... 17 Fault list ................................................................. 27
Address units, Setting the address ......................... 16 Fault report............................................................. 35
Address units, ID for AE type................................ 56 Fault list ................................................................. 27
Address units, ID for NS-AIN type ....................... 55 Fire detection system, System description............. 5
Address units, Installation guidelines .................... 42 Fire detection system, System data........................ 6
Addressable indication units, Setting the address.. 16 Fire history list ....................................................... 22
Addressable timers, Setting the address................. 17 Fire history list ....................................................... 23
Firmware Update Tool, Troubleshooting............... 32
Firmware, Upgrade in a complete CCP system ..... 28
B Firmware, Upgrade in a control module via
Backbone Bus External (BBE), Electrical
Ethernet .................................................................. 30
installation.............................................................. 8
Flame detectors, Installation guidelines................. 40
Bells, Installation guidelines.................................. 43
Bus Isolator M........................................................ 59
G
Guidelines, Loop units installation ........................ 39
C
Cable break, Trouble shooting ............................... 26
Cable requirements, Electrical installation ............ 8 H
Cabling, Installation guidelines ............................. 44 Heat detector, Installation guidelines..................... 40
Central status.......................................................... 38
Central unit terminal layout with cabling .............. 59
Change Over M Ext ............................................... 59
I
I/O M 70................................................................. 59
Charger M .............................................................. 59
I/O M 70, Connection to ........................................ 13
Cold room Heat detectors, Installation guidelines. 42
I/O M 700............................................................... 59
Commissioning requirements ................................ 37
Installation guidelines, Cabling and electrical
Control M 2.2......................................................... 59
installation.............................................................. 44
Control M X........................................................... 59
Installation order, Mechanical installation............. 7
Control Panel M 4.3............................................... 59
IS Smoke detector for EX areas, Installation
Control Panel M 4.3, Installation order ................. 7
guidelines ............................................................... 41
Control panel display, Testing................................ 25
Control panels, Mechanical installation................. 7
Control panels, Electrical installation .................... 19 L
Conventional high temperature Heat detectors, Loop lengths, Electrical installation ...................... 8
Installation guidelines ............................................ 41 Loop M X............................................................... 59
Loop M X, Connection to ...................................... 12
Loop units without address switches, Setting the
D address.................................................................... 16
Detector loops, Cable requirements....................... 8
Loop units, Setting the address .............................. 16
Detector loops, Electrical installation .................... 10
Loop configuration................................................. 37
DIP switch, Setting the ID ..................................... 55
Loop status ............................................................. 37
Disablement list ..................................................... 24
Loop units with address switches, Setting the
Door holder magnet 130kp, Installation
address.................................................................... 16
guidelines ............................................................... 43
Loop units, Connections for................................... 56
Door holder magnet 65kp, Installation guidelines. 43
Loop units, Mechanical installation....................... 7
Door release switch, Installation guidelines .......... 43
Loops, Verification of ............................................ 21
Download system log file ...................................... 34
E M
Manual call points, Installation guidelines ............ 42
Earth fault, Trouble shooting ................................. 27
Muting faults, Trouble shooting............................. 27
Electrical siren, Installation guidelines .................. 43
Electrical equipment, Location of.......................... 47
P
Polarity fault........................................................... 25
PSU M AC/DC 5A ................................................ 59
R
Relay M 8............................................................... 59
Repeater M 4.3....................................................... 59
Report a fault.......................................................... 35
Reset faults, Trouble shooting ............................... 27
Reset test mode ...................................................... 24
RS485 Termination ................................................ 61
RS485, Application examples for installation ....... 61
S
Short circuit isolators, Setting the address............. 17
Short circuit, Trouble shooting .............................. 27
Short circuit isolator, Installation guidelines ......... 42
Smoke detector, Installation guidelines ................. 39
Start the Firmware updater tool ............................. 30
System log file ....................................................... 34
System modules, Description................................. 59
T
Terminal layout, Electrical installation .................. 18
Test Equipment ...................................................... 24
Test for earth failure............................................... 15
Test for short circuits ............................................. 14
Test mode overview ............................................... 23
Test for cable break ................................................ 13
Test the control panel display ................................ 25
Testing a fire-detecting zone .................................. 23
Timers, Installation guidelines............................... 43
U
Upgrade firmware in Control M 4.3, Repeater M
4.3, Control M 2.2.................................................. 28
Upgrade firmware in Control M X ........................ 28
Upgrade firmware in remaining CCP modules...... 28
Upgrade for control modules i large systems ........ 33
Upgrade modules in the following order in large
systems................................................................... 33
Upgrade strategy large systems ............................. 32
W
Wrong number of loop units, Trouble shooting..... 25
Z
Zone, Test mode..................................................... 23
Own companies
Sales- and service representatives
Consilium is constantly increasing and improving its global sales and service
organisation in order to provide our customers with the most competent
service and support. Today Consilium has established own companies in
16 countries plus sales and service representatives in more than 50 countries.
You will find updated contact information on our web-site www.consilium.se.
www.consilium.se