User Manual PROFIBUS Master / Modbus Slave - Converter

Document code: MN67580_ENG Revision 2.002 Page 1 of 33


Industrial Electronic Devices

User Manual
Revision 2.002
English

PROFIBUS Master / Modbus Slave - Converter


( Order Code: HD67580-A1 )

for Website information:


www.adfweb.com/?Product=HD67580

for Price information: For others PROFIBUS devices, see also the following links:
www.adfweb.com/?Price=HD67580-A1
PROFIBUS Slave from/to …
www.adfweb.com?Product=HD67045 (… Serial)
www.adfweb.com?Product=HD67053 (… M-Bus Master)
Benefits and Main Features: www.adfweb.com?Product=HD67551 (… CANopen)
www.adfweb.com?Product=HD67552 (… CAN)
Very easy to configure www.adfweb.com?Product=HD67553 (… J1939)
www.adfweb.com?Product=HD67554 (… DeviceNet Slave)
Industrial temperature range: www.adfweb.com?Product=HD67555 (… DeviceNet Master)
www.adfweb.com?Product=HD67561 (… Modbus Master)
-40°C / 85°C (-40°F / 185°F) www.adfweb.com?Product=HD67562 (… Modbus Slave)
www.adfweb.com?Product=HD67563 (… Ethernet Server)
www.adfweb.com?Product=HD67564 (… Modbus TCP Client)
www.adfweb.com?Product=HD67565 (… Modbus TCP Server)

PROFIBUS Master from/to …


www.adfweb.com?Product=HD67575 (… Ethernet)
www.adfweb.com?Product=HD67577 (… CAN)
www.adfweb.com?Product=HD67579 (… Modbus TCP Slave)

Do you have an your customer protocol?


See the following links:
www.adfweb.com?Product=HD67003

Do you need to choose a device? do you want help?


Ask it to the following link:
www.adfweb.com?Cmd=helpme
User Manual

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 2 of 33
Industrial Electronic Devices

INDEX: UPDATED DOCUMENTATION:

Page Dear customer, we thank you for your attention and we remind you that
INDEX 2 you need to check that the following document is:
UPDATED DOCUMENTATION 2
Updated
REVISION LIST 2
WARNING 2 Related to the product you own
TRADEMARKS 2
SECURITY ALERT 3 To obtain the most recently updated document, note the “document code”
EXAMPLE OF CONNECTION 4 that appears at the top right-hand corner of each page of this document.
CONNECTION SCHEME 5
CHARACTERISTICS 6 With this “Document Code” go to web page www.adfweb.com/download/
CONFIGURATION 6 and search for the corresponding code on the page. Click on the proper
POWER SUPPLY 7 “Document Code” and download the updates.
FUNCTION MODES 8
LEDS 9
PROFIBUS 10 REVISION LIST:
ETHERNET 10
RS485 11 Revision Date Author Chapter Description
USE OF COMPOSITOR SW67580 12 1.000 28/11/2011 Fl All First release version
NEW PROJECT / OPEN PROJECT 13 2.000 22/08/2012 Fl All Software changed (v1.300)
SOFTWARE OPTIONS 14 2.001 09/01/2013 Nt All Added new chapters
SET COMMUNICATION 15 2.002 14/04/2017 Ff All Revision
PROFIBUS NETWORK 16
MASTER PROFIBUS OPTIONS 17
PROFIBUS DEVICE 18 WARNING:
UPDATE DEVICE 26
MODBUS MAP 28 ADFweb.com reserves the right to change information in this manual about
MECHANICAL DIMENSIONS 30 our product without warning.
ORDER CODE 31 ADFweb.com is not responsible for any error this manual may contain.
ACCESSORIES 31
DISCLAIMER 32
OTHER REGULATIONS AND STANDARDS 32 TRADEMARKS:
WARRANTIES AND TECHNICAL SUPPORT 33
RETURN POLICY 33 All trademarks mentioned in this document belong to their respective
Pagina 2 di 33 owners.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 3 of 33
Industrial Electronic Devices

SECURITY ALERT:

GENERAL INFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device, legal and
safety regulation are required for each individual application. The same applies also when using accessories.

INTENDED USE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e.
independent limit switches, mechanical interlocks, etc.).

QUALIFIED PERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications.
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and
who have appropriate qualifications for their job.

RESIDUAL RISKS
The device is state-of-the-art and is safe. The instruments can represent a potential hazard if they are inappropriately installed and
operated by untrained personnel. These instructions refer to residual risks with the following symbol:

This symbol indicates that non-observance of the safety instructions is a danger for people that could lead to serious injury or
death and / or the possibility of damage.

CE CONFORMITY
The declaration is made by our company. You can send an email to [email protected] or give us a call if you need it.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 4 of 33
Industrial Electronic Devices

EXAMPLE OF CONNECTION:

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 5 of 33
Industrial Electronic Devices

CONNECTION SCHEME:

Figure 1: Connection scheme for HD67580-A1


ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 6 of 33
Industrial Electronic Devices

CHARACTERISTICS:

The configurable “PROFIBUS Master / Modbus Slave - Converter” allows the following characteristics:
Triple isolation between Modbus/PROFIBUS, Modbus/Power Supply, PROFIBUS/Power Supply.
Mountable on 35mm Rail DIN;
Power Supply 8...24V AC or 12...35V DC;
Temperature range -40°C to 85°C.

CONFIGURATION:

You need Compositor SW67580 software on your PC in order to perform the following:
Define the parameter of the PROFIBUS;
Define the parameter of the Modbus line;
Define the PROFIBUS network.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 7 of 33
Industrial Electronic Devices

POWER SUPPLY:

The devices can be powered between a wide range of tensions. For more details see the two tables below.

VAC VDC
Vmin Vmax Vmin Vmax
HD67580-A1 8V 24V 12V 35V

Consumption at 24V DC:

Device W/VA
HD67580-A1 4

Caution: Not reverse the polarity power

HD67580-A1

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 8 of 33
Industrial Electronic Devices

FUNCTION MODES:

The device has got two functions mode depending of the position of the Dip2 of ‘Dip-Switch A’:
The first, with Dip2 in Off position (factory setting), is used for the normal working of the device.
The second, with Dip2 in On position, is used for upload the Project/Firmware.

For the operations to follow for the updating see ‘UPDATE DEVICE’ section.

According to the functioning mode, the LEDs will have specifics functions see ‘LEDS’ section.

Note:
Dip1 of ‘Dip-Switch A’ must be at ON to work even if the Ethernet cable is not inserted.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 9 of 33
Industrial Electronic Devices

LEDS:

The device has got five LEDs that are used to give information of the functioning status.
The various meanings of the LEDs are described in the table below.

LED Normal Mode Boot Mode

ON: Powered ON: Powered


1: Power (green)
OFF: Not powered OFF: Not powered

Blinks quickly: Boot state


2: Modbus comm (green) Blinks quickly when receive Modbus frames
Blinks very slowly (~0.5Hz): update in progress

Blinks quickly: Boot state


3: Device State (green) Blinks slowly (~1Hz)
Blinks very slowly (~0.5Hz): update in progress

Blinks quickly when there is PROFIBUS Blinks quickly: Boot state


4: PROFIBUS comm (green)
communication Blinks very slowly (~0.5Hz): update in progress

ON: Ethernet cable connected ON: Ethernet cable connected


5: Ethernet Link (green)
OFF: Ethernet cable disconnected OFF: Ethernet cable disconnected

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 10 of 33
Industrial Electronic Devices

PROFIBUS:

The PROFIBUS uses a 9-pin D-SUB connector. The pin assignment is defined like in the right figure.

Here some codes of cables:


Belden: p/n 183079A - Continuous Armor DataBus® ISA/SP-50 PROFIBUS Cable.

ETHERNET:

The Ethernet connection must be made using Connector3 of HD67580-A1 with at least a Category 5E cable. The maximum length of the
cable should not exceed 100m. The cable has to conform to the T568 norms relative to connections in cat.5 up to 100 Mbps. To connect the
device to an Hub/Switch is recommended the use of a straight cable, to connect the device to a PC/PLC/other is recommended the use of a
cross cable.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 11 of 33
Industrial Electronic Devices

RS485:

For terminate the RS485 line with a 120Ω resistor it is necessary that the Dip1 of Dip-Switch B is at ON position.

The maximum length of the cable should be 1200m (4000 feet).

Here some codes of cables:


Belden: p/n 8132 - 2x 28AWG stranded twisted pairs conductor + foil shield + braid shield;
Belden p/n 82842 - 2x 24AWG stranded twisted pairs conductor + foil shield + braid shield;
Tasker: p/n C521 - 1x 24AWG twisted pair conductor + foil shield + braid shield;
Tasker: p/n C522 - 2x 24AWG twisted pairs conductor + foil shield + braid shield.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 12 of 33
Industrial Electronic Devices

USE OF COMPOSITOR SW67580:

To configure the Converter, use the available software that runs with Windows called SW67580. It is downloadable on the site
www.adfweb.com and its operation is described in this document. (This manual is referenced to the last version of the software present on
our web site). The software works with MSWindows (XP, Vista, Seven, 8, 10; 32/64bit).

When launching the SW67580, the window below appears (Fig. 2).

Note:
It is necessary to have installed .Net Framework 4.

Figure 2: Main window for SW67580

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 13 of 33
Industrial Electronic Devices

NEW CONFIGURATION / OPEN CONFIGURATION:

The “New Configuration” button creates the folder which contains the entire device’s configuration.

A device’s configuration can also be imported or exported:


To clone the configurations of a Programmable “PROFIBUS Master / Modbus Slave -
Converter” in order to configure another device in the same manner, it is necessary to
maintain the folder and all its contents;
To clone a project in order to obtain a different version of the project, it is sufficient to
duplicate the project folder with another name and open the new folder with the button
“Open Configuration”.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 14 of 33
Industrial Electronic Devices

SOFTWARE OPTIONS:

By pressing the “Settings” ( ) button there is the possibility to change the language of the software and check the updatings for the
compositor.

In the section “Language” it is possible to change the language of the software.

In the section “Connection Options”, it is possible to check if there are some


updatings of the software compositor in ADFweb.com website.
Checking the option “Check Software Update at Start of Program”, the
SW67580 check automatically if there are updatings when it is launched.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 15 of 33
Industrial Electronic Devices

SET COMMUNICATION:

This section defines the fundamental communication parameter of two buses, PROFIBUS and Modbus.
And also the parameter of the Ethernet port used for programming the device.

By pressing the “Set Communication” button from the main window for SW67580 (Fig. 2) the
window “Set Communication” appears (Fig. 3).

The window is divided in three sections, one for the PROFIBUS, one for the Modbus and the other for
Ethernet.

The means of the fields for “PROFIBUS” are:


In the field “ID Dev.” the address of the PROFIBUS side is defined;
In the field “Baud rate” the baud rate for the PROFIBUS side is defined;

The means of the fields for “Modbus” are:


In the field “Baudrate” the data rate of the serial line is defined;
In the field “Parity” the parity of the serial line is defined;
In the field “Answer Delay” the time (expressed in milliseconds) that the converter waits
before sending the reply to the request is defined;
If the field “Read with Input Register / Status Function” is checked, it is possible to read
the Input bytes of PROFIBUS side with Input Registers (Function 04) and write the Output
bytes of PROFIBUS side with Holding Registers (Function 06/16). The Output bytes are
readable with Function 03. Otherwise, only Holding Registers will be used and the Output bytes
of PROFIBUS side cannot be read back.

The means of the fields for “Ethernet (Program port)” are: Figure 3: “Set Communication” window
In the field “IP ADDRESS” the IP address of the Converter for programming of it is
defined;
In the field “SUBNET Mask” the SubNet Mask of the network is defined.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 16 of 33
Industrial Electronic Devices

PROFIBUS NETWORK:

By pressing the “PROFIBUS Network” button from the main window for SW67580 (Fig. 2) the window “PROFIBUS Network” (Fig. 4)
appears.

In this window is possible to:


Modify the PROFIBUS Master Options (“Master PROFIBUS Options”);
Add a PROFIBUS Slave in the Network of the Master (“Add Slave PROFIBUS”);
Modify a PROFIBUS Slave in the Network (“Modify Slave PROFIBUS”);
Remove a PROFIBUS Slave from the Network (“Remove Slave PROFIBUS”).

Figure 4: “PROFIBUS Network” window


ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 17 of 33
Industrial Electronic Devices

MASTER PROFIBUS OPTIONS:

By pressing the “Master PROFIBUS Options” button from the “PROFIBUS Network” window (Fig. 4) the “PROFIBUS Master Options”
window appears (Fig. 5).

In this window is possible to set the WatchDog Time for the PROFIBUS Slaves.

Figure 5: “PROFIBUS Master Options” window

Note:
Fact1 and Fact2 could be write in decimal o hexadecimal (with prefix “0x” or “$”) and the values must between 1 and 255

Warning:
The WatchDog time must be between 200 and 650250 milliseconds.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 18 of 33
Industrial Electronic Devices

PROFIBUS DEVICE:

By pressing the “Add Slave PROFIBUS” and “Modify Slave PROFIBUS” button (or double click above an existent PROFIBUS Slave) from
the “PROFIBUS Network” window (Fig. 4) the “PROFIBUS Device” window appears (Fig. 6).

In this window is possible to:


Set the PROFIBUS Slave ID (“ID Slave
PROFIBUS”);
Set the Modbus Slave ID (“ID Slave
Modbus”);
Select the Modules present in the
PROFIBUS Slave from the Available
Modules in GSD file (“Module
Selection”);
Modify the User Parameters (if present)
of the PROFIBUS device (“User
Parameters”);
Modify the Parameters (if present) of the
Module Selected (“Module
Parameters”);
Watch Features and Baudrate supported
from the PROFIBUS device
(“Capabilities”);
Select the Sync, Freeze and Reset of
Data Options (“Options”).

Figure 6: “PROFIBUS Device” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 19 of 33
Industrial Electronic Devices

MODULE SELECTION:

The section “Module Selection” is used to select which


Modules are present in the Slave (Fig. 7).

In this section is possible to:


Check the list of the Modules selected (“Select
Modules”) (Fig. 7, point (1)) and the list of Modules
Available in GSD file (“Available Modules") (Fig. 7,
point (7));
Add a Module from the list of GSD file (Fig. 7, point
(6));
Remove a Module from selected list (Fig. 7, point
(5));
Add all Modules present in the GSD file (Fig. 7, point
(4));
Remove all Modules from selected list (Fig. 7, point
(3));
Insert a Module not present in the GSD file (“Manual
Module”) (Fig. 7 point (2)). For more info see the
section “Manual Module” below;
Enable the read of configuration directly from the
PROFIBUS Slave (“Use module configuration
readed from device”) (Fig 7, point (8)). If this
option is enable the configuration of the modules is
discorded and the device read the correct
configuration directly to the PROFIBUS slave.

Figure 7: “PROFIBUS Device – Module Selection” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 20 of 33
Industrial Electronic Devices

By pressing the “Manual Module” button from the “PROFIBUS Device” window (Fig. 6) the “Add Module Manually” window appears (Fig. 8).

In this window is possible to add a Module manually, i.e. writing the configuration of the module (in hexadecimal).

Figure 8: “Add/Modify Module Manually” window

The means of the fields are:


In the field “Description of Module” a name of the Module is defined;
In the field “Insert the Configuration of Module (HEX)” the configuration of the module is defined. The configuration must be
write in hexadecimal mode (without prefix “0x” o “$”).

To modify a Module inserted manually, is neccessary to do a double click on the module to change in the “Select Module” list (Fig. 7, point
(1)). It is possible to change only the module inserted manually.

Note:
The Values inserted in the table must between 00 and FF

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 21 of 33
Industrial Electronic Devices

USER PARAMETERS:

The section “User Parameters” is used to modify the parameters of the PROFIBUS slave (Fig. 9).

In this section there are:


The List of all Parameters available for the
PROFIBUS device (“User Parameters”) (Fig.
9, point (1));
The Configuration of all parameters in RAW
(“Parameters in RAW (Hex)”) (Fig. 9,
point(2));
The “Use Parameter Inserted Manually”,
enable this option is possible to insert
manually the parameters of Device and also
of the Modules. Using the “Modify User
Parameters Manually” button is possible to
insert/modify the parametrization of the
device (and/or modules). For more info see
below. (Fig. 9, point(3));
The admited value for the selected
parameter. It is possible to select the value
desired and confirm it with the “Apply”
button. If no value appears in this table, the
“Min Value” and “Max Value” are the limit of
the parameter. (Fig. 9, point(4));
The “Apply” button is used to confirm the
new value of the parameter, the “Default”
button is used to load the factory value for
the parameter. In “New Value” edit box it is
possible to set the new value. (Fig. 9,
point(5)).

Figure 9: “PROFIBUS Device – User Parameters” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 22 of 33
Industrial Electronic Devices

By pressing the “Modify User Parameters Manually” button from the “PROFIBUS Device” window (Fig. 6) the “Add Module Manually”
window appears (Fig. 10).

In this window is possible to add/modify the User and/or Modules Parameters manually, i.e. writing the configuration of the parameters (in
hexadecimal).

The means of the fields are:


In the field “Insert the number of User Parameter” the number
of byte for the parameter have to be inserted;
In the field “Insert the Configuration of Module (HEX)” the
configuration of the User and/or Modules Parameters is defined. The
configuration must be write in hexadecimal mode (without prefix
“0x” o “$”).

Note:
The Values inserted in the table must between 00 and FF

Figure 10: “Add/Modify User Parameters Manually” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 23 of 33
Industrial Electronic Devices

MODULE PARAMETERS:

The section “Module Parameters” is used to modify the parameters of the Modules (Fig. 11).

In this section there are:


The List of all Module selected in the GSD file
(“Available modules”) (Fig. 11, point (1));
The List of all Parameters available for the
Module selected (“Parameters of module”)
(Fig. 11, point (2));
The Configuration of all parameters in RAW
for the Module selected (“Parameters in RAW
(Hex)”) (Fig. 11, point(3));
The admited value for the selected parameter.
It is possible to select the value desired and
confirm it with the “Apply” button. If no value
appears in this table, the “Min Value” and
“Max Value” are the limit of the parameter.
(Fig. 11, point(4));
The “Apply” button is used to confirm the
new value of the parameter, the “Default”
button is used to load the factory value for
the parameter. In “New Value” edit box it is
possible to set the new value. (Fig. 11,
point(5));

Figure 11: “PROFIBUS Device – Module Parameters” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 24 of 33
Industrial Electronic Devices

CAPABILITIES:

The section “Capabilities” is used only to show which features/baudrates available in the PROFIBUS device. The Green Icon indicate that
capability/baudrate is available, the Red Icon indicate no compatibilities with that capability/baudrate (Fig. 12).

Figure 12: “PROFIBUS Device – Capabilities” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 25 of 33
Industrial Electronic Devices

OPTIONS:

The section “Options” is used to enable some option for each PROFIBUS device (Fig. 13).

The means of the fields are:


In the field “Enable Sync” the
PROFIBUS Sync command is
enable. This option is enable only
if the “Sync Mode” is supported
by the device (see Capabilities
section to check it);
In the field “Enable Freeze” the
PROFIBUS Freeze command is
enable. This option is enable only
if the “Freeze Mode” is supported
by the device (see Capabilities
section to check it);
In the field “Reset data if
PROFIBUS master loses
communication with the
slave” is possible to select to
cancel the data of the slave if the
Master lost the connection with
the device;
In the field “Reset data if
Modbus Master doesn’t poll
data the slave in ...
milliseconds” is possible to
select to cancel the data sended
to the slave PROFIBUS if the
Converter don’t receive a
Ethernet frame within the time
expressed in the field. Figure 13: “PROFIBUS Device – Options” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 26 of 33
Industrial Electronic Devices

UPDATE DEVICE:

By pressing the “Update Device” button it is possible to load the created Configuration into the
device; and also the Firmware, if is necessary.

If you don’t know the actual IP address of the device you have to use this procedure:
Turn OFF the Device;
Put Dip2 of ‘Dip-Switch A’ at ON position;
Turn ON the device
Connect the Ethernet cable;
Insert the IP “192.168.2.205”;
Press the “Ping” button, must appear “Device Found!”;
Press the “Next” button;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” turn OFF the Device;
Put Dip2 of ‘Dip-Switch A’ at OFF position;
Turn ON the device.

If you know the actual IP address of the device you have to use this procedure:
Turn ON the Device with the Ethernet cable inserted;
Insert the actual IP of the Converter;
Press the “Ping” button, must appear “Device Found!”;
Press the “Next” button;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” the device automatically goes at Normal Mode.

At this point the configuration/firmware on the device is correctly update.

Figure 14: “Update device” windows


ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 27 of 33
Industrial Electronic Devices

Note:
When you install a new version of the software it is better if the first time you do the update of the Firmware in the HD67580 device.

Note:
When you receive the device, for the first time, you have to update also the Firmware in the HD67580 device.

Warning:
If Fig. 15 appears when you try to do the Update try these points before seeking
assistance:
Try to repeat the operations for the updating;
Try with another PC;
Try to restart the PC;
Check the LAN settings;
Check the Wi-Fi settings;
If you are using the program inside a Virtual Machine, try to use in the main Operating System; Figure 15: “Protection” window
If you are using Windows Seven, Vista, 8 or 10 make sure that you have the administrator privileges;
In case you have to program more than one device, using the "UDP Update", you have to cancel the ARP table every time you
connect a new device on Ethernet. For do this you have to launch the "Command Prompt" and write the command "arp -d". Pay
attention that with Windows Vista, Seven, 8, 10 you have to launch the "Command Prompt" with Administrator Rights;
Pay attention at Firewall lock.

In the case of HD67580 you have to use the software “SW67580”: www.adfweb.com\download\filefold\SW67580.zip.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 28 of 33
Industrial Electronic Devices

MODBUS MAP:

On Modbus side, the map is created automatically. In relation to the configuration defined, it is possible to have two different maps. Each
PROFIBUS Slave will be mapped into a different virtual Modbus ID (in relation to the field “ID Slave Modbus” of “PROFIBUS Network ->
PROFIBUS Device” section)

Read with Input Register / Status Function not enabled

Data in reading:

Type Address Function Description


Holding Register 0 03 Input Bytes 0-1 of PROFIBUS side

Holding Register 1 03 Input Bytes 2-3 of PROFIBUS side

Holding Register 2 03 Input Bytes 4-5 of PROFIBUS side

.
Holding Register 121 03 Input Bytes 242-243 of PROFIBUS side

Data in writing:

Type Address Function Description


Holding Register 0 06/16 Output Bytes 0-1 of PROFIBUS side

Holding Register 1 06/16 Output Bytes 2-3 of PROFIBUS side

Holding Register 2 06/16 Output Bytes 4-5 of PROFIBUS side

.
Holding Register 121 06/16 Output Bytes 242-243 of PROFIBUS side

Note:
The data can be read/written as single bits too using Coil Status (Function 01 and Functions 05/15).

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 29 of 33
Industrial Electronic Devices

Read with Input Register / Status Function enabled

Data in reading:

Type Address Function Description


Input Register 0 04 Input Bytes 0-1 of PROFIBUS side

Input Register 1 04 Input Bytes 2-3 of PROFIBUS side

Input Register 2 04 Input Bytes 4-5 of PROFIBUS side

.
Input Register 121 04 Input Bytes 242-243 of PROFIBUS side

Data in writing:

Type Address Function Description


R: 03
Holding Register 0 Output Bytes 0-1 of PROFIBUS side
W: 06/16
R: 03
Holding Register 1 Output Bytes 2-3 of PROFIBUS side
W: 06/16
R: 03
Holding Register 2 Output Bytes 4-5 of PROFIBUS side
W: 06/16
.
R: 03
Holding Register 121 Output Bytes 242-243 of PROFIBUS side
W: 06/16

Note:
The data can be read/written as single bits too using Input/Coil Status (Function 02 and Functions 01/05/15).

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 30 of 33
Industrial Electronic Devices

MECHANICAL DIMENSIONS:

Figure 16: Mechanical dimensions scheme

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 31 of 33
Industrial Electronic Devices

ORDERING INFORMATIONS:

The ordering part number is formed by a valid combination of the following:


HD67580 – A 1

Connectors Type
1: Removable 5mm Screw Terminal

Enclosure Type
A: 1M, 35mm DIN Rail mounting

Device Family
HD67580: PROFIBUS Master / Modbus Slave - Converter

Order Code: HD67580-A1 - PROFIBUS Master / Modbus Slave - Converter

ACCESSORIES:

Order Code: AC34001 - Rail DIN - Power Supply 220/240V AC 50/60Hz – 12 V AC


Order Code: AC34002 - Rail DIN - Power Supply 110V AC 50/60Hz – 12 V AC

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 32 of 33
Industrial Electronic Devices

DISCLAIMER:

All technical content within this document can be modified without notice. The content of the document is a under continual renewal.
For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal
conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such
as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.

OTHER REGULATIONS AND STANDARDS:

WEEE INFORMATION
Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate
collection systems).
This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead, it
should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed
correctly, you will help prevent potential negative environmental factors and impact of human health, which could otherwise be
caused by inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about
recycling this product, please contact your local city office, your household waste disposal service or the shop where you purchased
the product.

RESTRICTION OF HAZARDOUS SUBSTANCES DIRECTIVE


The device respects the 2002/95/EC Directive on the restriction of the use of certain hazardous substances in electrical
and electronic equipment (commonly referred to as Restriction of Hazardous Substances Directive or RoHS).

CE MARKING
The product conforms with the essential requirements of the applicable EC directives.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFIBUS Master / Modbus Slave - Converter
Document code: MN67580_ENG Revision 2.002 Page 33 of 33
Industrial Electronic Devices

WARRANTIES AND TECHNICAL SUPPORT:

For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.
Otherwise contact us at the address [email protected]

RETURN POLICY:

If while using your product you have any problem and you wish to exchange or repair it, please do the following:
Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to
provide detailed information about the problem.
Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be
accepted).

If the product is within the warranty of twelve months, it will be repaired or exchanged and returned within three weeks. If the product is no
longer under warranty, you will receive a repair estimate.

ADFweb.com S.r.l.
Via Strada Nuova, 17
IT-31010 Mareno di Piave
TREVISO (Italy)
Phone +39.0438.30.91.31
Fax +39.0438.49.20.99
www.adfweb.com