User Manual: PROFIBUS Master / Modbus Slave - Converter
User Manual: PROFIBUS Master / Modbus Slave - Converter
User Manual
Revision 2.002
English
for Price information: For others PROFIBUS devices, see also the following links:
www.adfweb.com/?Price=HD67580-A1
PROFIBUS Slave from/to …
www.adfweb.com?Product=HD67045 (… Serial)
www.adfweb.com?Product=HD67053 (… M-Bus Master)
Benefits and Main Features: www.adfweb.com?Product=HD67551 (… CANopen)
www.adfweb.com?Product=HD67552 (… CAN)
Very easy to configure www.adfweb.com?Product=HD67553 (… J1939)
www.adfweb.com?Product=HD67554 (… DeviceNet Slave)
Industrial temperature range: www.adfweb.com?Product=HD67555 (… DeviceNet Master)
www.adfweb.com?Product=HD67561 (… Modbus Master)
-40°C / 85°C (-40°F / 185°F) www.adfweb.com?Product=HD67562 (… Modbus Slave)
www.adfweb.com?Product=HD67563 (… Ethernet Server)
www.adfweb.com?Product=HD67564 (… Modbus TCP Client)
www.adfweb.com?Product=HD67565 (… Modbus TCP Server)
Page Dear customer, we thank you for your attention and we remind you that
INDEX 2 you need to check that the following document is:
UPDATED DOCUMENTATION 2
Updated
REVISION LIST 2
WARNING 2 Related to the product you own
TRADEMARKS 2
SECURITY ALERT 3 To obtain the most recently updated document, note the “document code”
EXAMPLE OF CONNECTION 4 that appears at the top right-hand corner of each page of this document.
CONNECTION SCHEME 5
CHARACTERISTICS 6 With this “Document Code” go to web page www.adfweb.com/download/
CONFIGURATION 6 and search for the corresponding code on the page. Click on the proper
POWER SUPPLY 7 “Document Code” and download the updates.
FUNCTION MODES 8
LEDS 9
PROFIBUS 10 REVISION LIST:
ETHERNET 10
RS485 11 Revision Date Author Chapter Description
USE OF COMPOSITOR SW67580 12 1.000 28/11/2011 Fl All First release version
NEW PROJECT / OPEN PROJECT 13 2.000 22/08/2012 Fl All Software changed (v1.300)
SOFTWARE OPTIONS 14 2.001 09/01/2013 Nt All Added new chapters
SET COMMUNICATION 15 2.002 14/04/2017 Ff All Revision
PROFIBUS NETWORK 16
MASTER PROFIBUS OPTIONS 17
PROFIBUS DEVICE 18 WARNING:
UPDATE DEVICE 26
MODBUS MAP 28 ADFweb.com reserves the right to change information in this manual about
MECHANICAL DIMENSIONS 30 our product without warning.
ORDER CODE 31 ADFweb.com is not responsible for any error this manual may contain.
ACCESSORIES 31
DISCLAIMER 32
OTHER REGULATIONS AND STANDARDS 32 TRADEMARKS:
WARRANTIES AND TECHNICAL SUPPORT 33
RETURN POLICY 33 All trademarks mentioned in this document belong to their respective
Pagina 2 di 33 owners.
SECURITY ALERT:
GENERAL INFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device, legal and
safety regulation are required for each individual application. The same applies also when using accessories.
INTENDED USE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e.
independent limit switches, mechanical interlocks, etc.).
QUALIFIED PERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications.
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and
who have appropriate qualifications for their job.
RESIDUAL RISKS
The device is state-of-the-art and is safe. The instruments can represent a potential hazard if they are inappropriately installed and
operated by untrained personnel. These instructions refer to residual risks with the following symbol:
This symbol indicates that non-observance of the safety instructions is a danger for people that could lead to serious injury or
death and / or the possibility of damage.
CE CONFORMITY
The declaration is made by our company. You can send an email to [email protected] or give us a call if you need it.
EXAMPLE OF CONNECTION:
CONNECTION SCHEME:
CHARACTERISTICS:
The configurable “PROFIBUS Master / Modbus Slave - Converter” allows the following characteristics:
Triple isolation between Modbus/PROFIBUS, Modbus/Power Supply, PROFIBUS/Power Supply.
Mountable on 35mm Rail DIN;
Power Supply 8...24V AC or 12...35V DC;
Temperature range -40°C to 85°C.
CONFIGURATION:
You need Compositor SW67580 software on your PC in order to perform the following:
Define the parameter of the PROFIBUS;
Define the parameter of the Modbus line;
Define the PROFIBUS network.
POWER SUPPLY:
The devices can be powered between a wide range of tensions. For more details see the two tables below.
VAC VDC
Vmin Vmax Vmin Vmax
HD67580-A1 8V 24V 12V 35V
Device W/VA
HD67580-A1 4
HD67580-A1
FUNCTION MODES:
The device has got two functions mode depending of the position of the Dip2 of ‘Dip-Switch A’:
The first, with Dip2 in Off position (factory setting), is used for the normal working of the device.
The second, with Dip2 in On position, is used for upload the Project/Firmware.
For the operations to follow for the updating see ‘UPDATE DEVICE’ section.
According to the functioning mode, the LEDs will have specifics functions see ‘LEDS’ section.
Note:
Dip1 of ‘Dip-Switch A’ must be at ON to work even if the Ethernet cable is not inserted.
LEDS:
The device has got five LEDs that are used to give information of the functioning status.
The various meanings of the LEDs are described in the table below.
PROFIBUS:
The PROFIBUS uses a 9-pin D-SUB connector. The pin assignment is defined like in the right figure.
ETHERNET:
The Ethernet connection must be made using Connector3 of HD67580-A1 with at least a Category 5E cable. The maximum length of the
cable should not exceed 100m. The cable has to conform to the T568 norms relative to connections in cat.5 up to 100 Mbps. To connect the
device to an Hub/Switch is recommended the use of a straight cable, to connect the device to a PC/PLC/other is recommended the use of a
cross cable.
RS485:
For terminate the RS485 line with a 120Ω resistor it is necessary that the Dip1 of Dip-Switch B is at ON position.
To configure the Converter, use the available software that runs with Windows called SW67580. It is downloadable on the site
www.adfweb.com and its operation is described in this document. (This manual is referenced to the last version of the software present on
our web site). The software works with MSWindows (XP, Vista, Seven, 8, 10; 32/64bit).
When launching the SW67580, the window below appears (Fig. 2).
Note:
It is necessary to have installed .Net Framework 4.
The “New Configuration” button creates the folder which contains the entire device’s configuration.
SOFTWARE OPTIONS:
By pressing the “Settings” ( ) button there is the possibility to change the language of the software and check the updatings for the
compositor.
SET COMMUNICATION:
This section defines the fundamental communication parameter of two buses, PROFIBUS and Modbus.
And also the parameter of the Ethernet port used for programming the device.
By pressing the “Set Communication” button from the main window for SW67580 (Fig. 2) the
window “Set Communication” appears (Fig. 3).
The window is divided in three sections, one for the PROFIBUS, one for the Modbus and the other for
Ethernet.
The means of the fields for “Ethernet (Program port)” are: Figure 3: “Set Communication” window
In the field “IP ADDRESS” the IP address of the Converter for programming of it is
defined;
In the field “SUBNET Mask” the SubNet Mask of the network is defined.
PROFIBUS NETWORK:
By pressing the “PROFIBUS Network” button from the main window for SW67580 (Fig. 2) the window “PROFIBUS Network” (Fig. 4)
appears.
By pressing the “Master PROFIBUS Options” button from the “PROFIBUS Network” window (Fig. 4) the “PROFIBUS Master Options”
window appears (Fig. 5).
In this window is possible to set the WatchDog Time for the PROFIBUS Slaves.
Note:
Fact1 and Fact2 could be write in decimal o hexadecimal (with prefix “0x” or “$”) and the values must between 1 and 255
Warning:
The WatchDog time must be between 200 and 650250 milliseconds.
PROFIBUS DEVICE:
By pressing the “Add Slave PROFIBUS” and “Modify Slave PROFIBUS” button (or double click above an existent PROFIBUS Slave) from
the “PROFIBUS Network” window (Fig. 4) the “PROFIBUS Device” window appears (Fig. 6).
MODULE SELECTION:
By pressing the “Manual Module” button from the “PROFIBUS Device” window (Fig. 6) the “Add Module Manually” window appears (Fig. 8).
In this window is possible to add a Module manually, i.e. writing the configuration of the module (in hexadecimal).
To modify a Module inserted manually, is neccessary to do a double click on the module to change in the “Select Module” list (Fig. 7, point
(1)). It is possible to change only the module inserted manually.
Note:
The Values inserted in the table must between 00 and FF
USER PARAMETERS:
The section “User Parameters” is used to modify the parameters of the PROFIBUS slave (Fig. 9).
By pressing the “Modify User Parameters Manually” button from the “PROFIBUS Device” window (Fig. 6) the “Add Module Manually”
window appears (Fig. 10).
In this window is possible to add/modify the User and/or Modules Parameters manually, i.e. writing the configuration of the parameters (in
hexadecimal).
Note:
The Values inserted in the table must between 00 and FF
MODULE PARAMETERS:
The section “Module Parameters” is used to modify the parameters of the Modules (Fig. 11).
CAPABILITIES:
The section “Capabilities” is used only to show which features/baudrates available in the PROFIBUS device. The Green Icon indicate that
capability/baudrate is available, the Red Icon indicate no compatibilities with that capability/baudrate (Fig. 12).
OPTIONS:
The section “Options” is used to enable some option for each PROFIBUS device (Fig. 13).
UPDATE DEVICE:
By pressing the “Update Device” button it is possible to load the created Configuration into the
device; and also the Firmware, if is necessary.
If you don’t know the actual IP address of the device you have to use this procedure:
Turn OFF the Device;
Put Dip2 of ‘Dip-Switch A’ at ON position;
Turn ON the device
Connect the Ethernet cable;
Insert the IP “192.168.2.205”;
Press the “Ping” button, must appear “Device Found!”;
Press the “Next” button;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” turn OFF the Device;
Put Dip2 of ‘Dip-Switch A’ at OFF position;
Turn ON the device.
If you know the actual IP address of the device you have to use this procedure:
Turn ON the Device with the Ethernet cable inserted;
Insert the actual IP of the Converter;
Press the “Ping” button, must appear “Device Found!”;
Press the “Next” button;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” the device automatically goes at Normal Mode.
Note:
When you install a new version of the software it is better if the first time you do the update of the Firmware in the HD67580 device.
Note:
When you receive the device, for the first time, you have to update also the Firmware in the HD67580 device.
Warning:
If Fig. 15 appears when you try to do the Update try these points before seeking
assistance:
Try to repeat the operations for the updating;
Try with another PC;
Try to restart the PC;
Check the LAN settings;
Check the Wi-Fi settings;
If you are using the program inside a Virtual Machine, try to use in the main Operating System; Figure 15: “Protection” window
If you are using Windows Seven, Vista, 8 or 10 make sure that you have the administrator privileges;
In case you have to program more than one device, using the "UDP Update", you have to cancel the ARP table every time you
connect a new device on Ethernet. For do this you have to launch the "Command Prompt" and write the command "arp -d". Pay
attention that with Windows Vista, Seven, 8, 10 you have to launch the "Command Prompt" with Administrator Rights;
Pay attention at Firewall lock.
In the case of HD67580 you have to use the software “SW67580”: www.adfweb.com\download\filefold\SW67580.zip.
MODBUS MAP:
On Modbus side, the map is created automatically. In relation to the configuration defined, it is possible to have two different maps. Each
PROFIBUS Slave will be mapped into a different virtual Modbus ID (in relation to the field “ID Slave Modbus” of “PROFIBUS Network ->
PROFIBUS Device” section)
Data in reading:
.
Holding Register 121 03 Input Bytes 242-243 of PROFIBUS side
Data in writing:
.
Holding Register 121 06/16 Output Bytes 242-243 of PROFIBUS side
Note:
The data can be read/written as single bits too using Coil Status (Function 01 and Functions 05/15).
Data in reading:
.
Input Register 121 04 Input Bytes 242-243 of PROFIBUS side
Data in writing:
Note:
The data can be read/written as single bits too using Input/Coil Status (Function 02 and Functions 01/05/15).
MECHANICAL DIMENSIONS:
ORDERING INFORMATIONS:
Connectors Type
1: Removable 5mm Screw Terminal
Enclosure Type
A: 1M, 35mm DIN Rail mounting
Device Family
HD67580: PROFIBUS Master / Modbus Slave - Converter
ACCESSORIES:
DISCLAIMER:
All technical content within this document can be modified without notice. The content of the document is a under continual renewal.
For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal
conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such
as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.
WEEE INFORMATION
Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate
collection systems).
This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead, it
should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed
correctly, you will help prevent potential negative environmental factors and impact of human health, which could otherwise be
caused by inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about
recycling this product, please contact your local city office, your household waste disposal service or the shop where you purchased
the product.
CE MARKING
The product conforms with the essential requirements of the applicable EC directives.
For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.
Otherwise contact us at the address [email protected]
RETURN POLICY:
If while using your product you have any problem and you wish to exchange or repair it, please do the following:
Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to
provide detailed information about the problem.
Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be
accepted).
If the product is within the warranty of twelve months, it will be repaired or exchanged and returned within three weeks. If the product is no
longer under warranty, you will receive a repair estimate.