User Manual: M-Bus Master / Modbus Slave - Converter
User Manual: M-Bus Master / Modbus Slave - Converter
User Manual
Revision 3.001
English
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 2 of 43
Industrial Electronic Devices
Page Dear customer, we thank you for your attention and we remind you that
INDEX 2 you need to check that the following document is:
UPDATED DOCUMENTATION 2 Updated
REVISION LIST 2
Related to the product you own
WARNING 2
TRADEMARKS 2
To obtain the most recently updated document, note the “document code”
SECURITY ALERT 3
that appears at the top right-hand corner of each page of this document.
EXAMPLE OF CONNECTION 4
CONNECTION SCHEME 5
With this “Document Code” go to web page www.adfweb.com/download/
CHARACTERISTICS 7
and search for the corresponding code on the page. Click on the proper
CONFIGURATION 7
“Document Code” and download the updates.
POWER SUPPLY 8
FUNCTION MODES 9
LEDS 10
REVISION LIST:
RS232 11
RS485 12
Revision Date Author Chapter Description
M-BUS 13
2.053 04/03/2013 Nt All Added new chapters
ETHERNET 13
2.054 12/12/2013 Ff All Revision
USE OF COMPOSITOR SW67029 14
3.000 15/12/2017 Ff All New hardware version
NEW CONFIGURATION / OPEN CONFIGURATION 15
3.001 03/07/2018 Ff All Revision
SOFTWARE OPTIONS 16
SET COMMUNICATION 17
M-BUS 19
MANUFACTURER SPECIFIC DATA 33 WARNING:
UPDATE DEVICE 34
ADFweb.com reserves the right to change information in this manual about
SCAN & DECODE 38
our product without warning.
MECHANICAL DIMENSIONS 39
ADFweb.com is not responsible for any error this manual may contain.
ORDERING INFORMATIONS 40
ACCESSORIES 41
DISCLAIMER 42
OTHER REGULATIONS AND STANDARDS 42
TRADEMARKS:
WARRANTIES AND TECHNICAL SUPPORT 43
All trademarks mentioned in this document belong to their respective
RETURN POLICY 43
owners.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 3 of 43
Industrial Electronic Devices
SECURITY ALERT:
GENERAL INFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device, legal and
safety regulation are required for each individual application. The same applies also when using accessories.
INTENDED USE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e.
independent limit switches, mechanical interlocks, etc.).
QUALIFIED PERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications.
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and
who have appropriate qualifications for their job.
RESIDUAL RISKS
The device is state-of-the-art and is safe. The instruments can represent a potential hazard if they are inappropriately installed and
operated by untrained personnel. These instructions refer to residual risks with the following symbol:
This symbol indicates that non-observance of the safety instructions is a danger for people that could lead to serious injury or
death and / or the possibility of damage.
CE CONFORMITY
The declaration is made by our company. You can send an email to [email protected] or give us a call if you need it.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 4 of 43
Industrial Electronic Devices
EXAMPLE OF CONNECTION:
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 5 of 43
Industrial Electronic Devices
CONNECTION SCHEME:
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 6 of 43
Industrial Electronic Devices
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 7 of 43
Industrial Electronic Devices
CHARACTERISTICS:
At the Converter can be connected up to 250 standard M-Bus devices. This number depends of the code expressed by the xxx number:
HD67029-B2-232-20 or HD67029-B2-485-20 support up to 20 M-Bus devices;
HD67029-B2-232-40 or HD67029-B2-485-40 support up to 40 M-Bus devices;
HD67029-B2-232-80 or HD67029-B2-485-80 support up to 80 M-Bus devices;
HD67029-B2-232-160 or HD67029-B2-485-160 support up to 160 M-Bus devices;
HD67029-B2-232-250 or HD67029-B2-485-250 support up to 250 M-Bus devices.
In the case of HD67029-B2-xxx-160 the device must be mounted on 35mm DIN rail which is horizontally mounted on a wall or cabinet
back-plate. To avoid obstructions to the airflow around the unit it is recommended to not cover the paths of air.
In the case of HD67029-B2-xxx-250 the device must be mounted on 35mm DIN rail which is horizontally mounted on a wall or cabinet
back-plate. These units have a fan in the top of the enclosure. To avoid obstructions to the airflow around the unit it is recommended
to not cover the paths of air. Take care to not cover the fan. It is recommended to put the device into a ventilated cabinet.
CONFIGURATION:
You need Compositor SW67029 software on your PC in order to perform the following:
Define the parameter of Modbus and M-Bus line;
Define which M-Bus variables are readable on Modbus ;
Update the device.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 8 of 43
Industrial Electronic Devices
POWER SUPPLY:
The devices can be powered at 15…21V AC and 18…35V DC. The consumption depends to the code of the device. For more details see the
two tables below.
VAC VDC
Vmin Vmax Vmin Vmax
15V 21V 18V 35V
HD67029
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 9 of 43
Industrial Electronic Devices
FUNCTION MODES:
The device has got two functions mode depending of the position of the Dip1 of ‘Dip-Switch A’ of HD67029-B2-xxx-xxx:
The first, with Dip1 of ‘Dip-Switch A’ at OFF position, is used for the normal working of the device.
The second, with Dip1 of ‘Dip-Switch A’ at ON position, is used for uploading the Project and/or Firmware.
For the operations to follow for the updating, see ‘UPDATE DEVICE’ section.
According to the functioning mode, the LEDs will have specifics functions, see ‘LEDS’ section.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 10 of 43
Industrial Electronic Devices
LEDS:
The device has got five LEDs that are used to give information of the functioning status.
The various meanings of the LEDs are described in the table below.
4: Modbus comm. Blinks when a Modbus request is Blinks quickly: Boot state
(green) received Blinks very slowly (~0.5Hz): update in progress
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 11 of 43
Industrial Electronic Devices
RS232:
The connection from RS232 socket to a serial port (example one from a personal computer) must be made with a Null Modem cable (a serial
cable where the pins 2 and 3 are crossed).
It is recommended that the RS232 cable not exceed 15 meters.
The HD67029 is provided with a D-sub connector type DE-9 Male (also called DB-9). The cable must use a DE-9 Female connector.
The serial port is used for programming the device (HD67029M-xxx-20) and for Modbus communication.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 12 of 43
Industrial Electronic Devices
RS485:
To terminate the RS485 line with a 120Ω resistor, it is necessary to put dip 1 ON, like in figure.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 13 of 43
Industrial Electronic Devices
M-BUS:
ETHERNET:
The Ethernet connection must be made using Connector3 with at least a Category 5E cable. The
maximum length of the cable should not exceed 100m. The cable has to conform to the T568 norms
relative to connections in cat.5 up to 100 Mbps. To connect the device to an Hub/Switch is recommended
the use of a straight cable, to connect the device to a PC/PLC/other is recommended the use of a cross
cable.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 14 of 43
Industrial Electronic Devices
To configure the Converter, use the available software that runs with Windows called SW67029. It is downloadable from the site
www.adfweb.com and its operation is described in this document (this manual is referenced to the last version of the software present on the
web site). The software works with MSWindows (XP, Vista, Seven, 8, 10; 32/64bit).
When launching the SW67029, the window below appears (Fig. 2).
Note:
It is necessary to have installed .Net Framework 4.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 15 of 43
Industrial Electronic Devices
The “New Configuration” button creates the folder which contains the entire device’s configuration.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 16 of 43
Industrial Electronic Devices
SOFTWARE OPTIONS:
By pressing the “Settings” ( ) button there is the possibility to change the language of the software and check the updatings for the
compositor.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 17 of 43
Industrial Electronic Devices
SET COMMUNICATION:
This section define the fundamental communication parameters of two buses, Modbus and M-Bus.
By Pressing the “Set Communication” button from the main window for SW67029 (Fig. 2) the window
“Set Communication” appears (Fig. 3).
The window is divided in three sections, one for the Modbus line (Modbus slave), one for the M-Bus and
the other for Ethernet.
The means of the fields for “Ethernet” are (programming port for ‘HD67029-B2’):
In the field “IP Address” the IP address of the converter is defined;
In the field “Subnet Mask” the Subnet Mask of the converter is defined;
In the fields “GATEWAY” the default gateway of the net is defined. This feature can be enabled or disabled pressing the Check Box
field. This feature is used for going out of the net.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 19 of 43
Industrial Electronic Devices
M-BUS
By Pressing the “M-Bus” button from the main window for SW67029 (Fig. 2) the window “M-Bus Network” appears (Fig. 4).
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 20 of 43
Industrial Electronic Devices
If the field “Send SND_NKE” is checked, the Converter send the “SND_NKE” frame to start the communication.
In the field “Send Reset App.” Is checked the Converter send the “Application Reset” command to the slave.
In the field “Variables List” it is possible to select which type of variables definition to use. If is selected “By Type” it is necessary to
fill all fields, in the section Variables, with the correct values; otherwise if “By Position” is selected you can insert the progressive
number of the variable that you need (page 27 for more information).
In the field “Cut after” it is possible to select after how many frames stops data requests. It is used when the slave has got many
data frames and you don’t need to read all them.
In the field “Manufacturing Specific Data” is possible to insert the starting address Modbus from which you want to save the
information of Manufacturer Specific (after DIF=0x0F or DIF=0x1F).
In the field “Length (MSD) [1 - 241]” is possible to insert the length of the data you need to save.
In the field “Offset (MSD) [0 - 240]” is possible to insert the offset from where save the data;
In the field “Access Number” is possible to define a Modbus register where saving the number of accesses to the meter.
For more information about “Manufacturer Specific Data” functions, see page 33.
After that, pressing the “ADD NODE” button, a new node appears in the left side of the window. In order to modify a created node it is
necessary to select the desired node, change the wrong items and then press the “MODIFY NODE” button.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 21 of 43
Industrial Electronic Devices
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 22 of 43
Industrial Electronic Devices
In the field “Tariff” if it is necessary it is possible to insert the value of the tariff of that variable. The Tariff is used for indicates from
which device the data come;
In the field “VIFE” it is possible to select a sub-type of “Type of Data”;
If the field “Use Six Modbus Register” and the “Type of Data” is “Time Point” it is possible to read the information of Year, Month,
Day, Hour, Minutes, Seconds on six consecutive Modbus registers without decoding the data (if not selected the values are the same
of the reply of the slave device, so coded with a determinate structure). You have to insert the first Modbus Register.
If the field “From BCD to Integer” is checked the Converter converts the BCD value of variable in Integer format. This happens only
if the variable is in BCD format; if it isn’t nothing changes.
If the field “Convert in Float” is checked the Converter converts the data into Float type. Every variable occupies two consecutive
Modbus Registers and the first one is the one defined in “Modbus Register”. In this case the float value is multiplied by the “Modbus
Re Scale” automatically;
If the field “Force Integer 32” is checked the Converter maps the variables with a dimension <32 bit in two consecutive Modbus
registers as a 32 bit variables;
In the field “Post Operation” it is possible to define an operation on the data read before mapping them on Modbus registers.
Having completed this fields, to add the variable the button “ADD VARIABLE” must be pressed.
In order to modify a created variable it is necessary to select the desired variable, change the wrong items and then press the “MODIFY
VARIABLE” button.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 23 of 43
Industrial Electronic Devices
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 24 of 43
Industrial Electronic Devices
If the field “Force Integer 32” is checked the Converter maps the variables with a dimension <32 bit in two consecutive Modbus
registers as a 32 bit variables;
In the field “Post Operation” it is possible to define an operation on the data read before mapping them on Modbus registers.
In the field “Position” insert the number of the variable that you want on Modbus.
Having completed this fields, to add the variable the button “ADD VARIABLE” must be pressed.
In order to modify a created variable it is necessary to select the desired variable, change the wrong items and then press the “MODIFY
VARIABLE” button.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 25 of 43
Industrial Electronic Devices
Example:
0x04 - DIF
0x06 - VIF Energy
0x00 - Data (Byte 4of4)
0x00 - Data (Byte 3of4)
Second Variable ( 2 ) To be use in the “Position” field
0x00 - Data (Byte 2of4)
0x00 - Data (Byte 1of4)
0x44 - DIF
0x06 - VIF Energy
0x00 - Data (Byte 4Of4)
0x00 - Data (Byte 3Of4) Third Variable ( 3 )
0x00 - Data (Byte 2Of4)
0x00 - Data (Byte 1Of4)
…
… Other Variables
…
0x55 - Check Sum
0x16 - Stop Byte
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 26 of 43
Industrial Electronic Devices
Note:
By pressing the “Import Network” button is possible
to import the file generated by the Analyzer HD67031.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 27 of 43
Industrial Electronic Devices
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 28 of 43
Industrial Electronic Devices
VIFE:
|_ Not Selected |_ Period of tariff months(s)
|_ Credit of the nominal local legal currency units |_ Period of tariff year(s)
|_ Debit of the nominal local legal currency units |_ dimensionless/ no VIF
|_ Access Number (transmission count) |_ Volts
|_ Medium (as in fixed header) |_ Ampere
|_ Manufacturer (as in fixed header) |_ Reset counter
|_ Parameter set identification |_ Comulation counter
|_ Model/Version |_ Control signal
|_ Hardware Version # |_ Day of week
|_ Firmware Version # |_ Week number
|_ Software Version # |_ Time point of day change
|_ Customer Location |_ State of parameter activation
|_ Customer |_ Special supplier information
|_ Access Code User |_ Duration since last comulation [hour(s)..year(s)]
|_ Access Code Operator |_ Operation time battery [hour(s)..year(s)]
|_ Access Code System Operator |_ Date and time of battery change
|_ Access Code Developer |_ Energy MWh
|_ Password |_ Energy GJ
|_ Error flags (binary) |_ Volume
|_ Error mask |_ Mass
|_ Digital Output (binary) |_ Volume 0,1 feet^3
|_ Digital Input (binary) |_ Volume 0,1 american gallon
|_ Baudrate [Baud] |_ Volume 1 american gallon
|_ response delay time [bittimes] |_ Volume flow 0,001 american gallon/min
|_ Retry |_ Volume flow 1 american gallon/min
|_ First storage # for cyclic storage |_ Volume flow 1 american gallon/h
|_ Last storage # for cyclic storage |_ Power MW
|_ Size of storage block |_ Power GJ/h
|_ Storage interval [sec(s)..day(s)] |_ Flow Temperature
|_ Storage interval month(s) |_ Return Temperature
|_ Storage interval year(s) |_ Temperature Difference
|_ Duration since last readout[sec(s)..day(s)] |_ External Temperature
|_ Start (date/time) of tariff |_ Cold/Warm Temperature Limit °F
|_ Duration of tariff (nn=01..11:min to day) |_ Cold/Worm Temperature Limit °C
|_ Period of tariff [sec(s) to day(s)] |_ Cumul. count max power
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 29 of 43
Industrial Electronic Devices
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 30 of 43
Industrial Electronic Devices
Swap Identification:
This field is used for select the Swap mode of Identification Number.
Examples:
- Identification Number (Secondary Address): 12345678; Address Register 1000; Convert BCD in Integer Identification Num. not checked.
None Type 1
1000: 0x1234 1000: 0x5678
1001: 0x5678 1001: 0x1234
- Identification Number (Secondary Address): 12345678; Address Register 1000; Convert BCD in Integer Identification Num. checked.
None Type 1
1000: 0x00BC 1000: 0x614E
1001: 0x614E 1001: 0x00BC
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 31 of 43
Industrial Electronic Devices
To know the meaning of value read in the “Modbus Re Scale” field, you must follow this table (x = Value read in Modbus Re Scale):
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 32 of 43
Industrial Electronic Devices
Data type F:
7 6 5 4 3 2 1 0
2 2 2 2 2 2 2 2
15 14 13 12 11 0 9 8
2 2 2 2 2 21 2 2
23 22 21 0 19 18 17 16
2 2 2 22 2 2 2 2
31 30 29 28 27 26 25 24
2 2 2 2 2 2 2 2
Min (0 … 59);
Hour (0 … 23);
Day (1 … 31);
Month (1 … 12);
Year (0 … 99);
Time Invalid (0=Valid, 1=Invalid);
Summer Time (0=Standard Time, 1=Summer Time);
Reserved (0).
Data type G:
7 6 5 4 3 2 1 0
2 2 2 2 2 2 2 2
15 14 13 12 11 0 9 8
2 2 2 2 2 21 2 2
Day (1 … 31);
Month (1 … 12);
Year (0 … 99).
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 33 of 43
Industrial Electronic Devices
Using this function is possible to save into Modbus registers the part of M-Bus frame that is coded like Manufacturer Specific Data. Usually
these data are at the end of the frame and after a DIF byte with the value 0x0F of 0x1F.
If you want to save all ten bytes from Modbus register 200 you have to compile the fields “Manufacturer Specific Data”, “Length (MSD) [1 –
241]” and Offset (MSD) [0 - 240] in this way: Manufacturer Specific Data: 200 | Length: 10 | Offset: 0.
On Modbus you will have this result: reg.200=1122h, reg.201=3344h, reg.202=5566h, reg.203=7788h, reg.204=99AAh
If you want to save only the byte 33 and 44 in the Modbus register 200 you have to compile the fields “Manufacturer Specific Data”, “Length
(MSD) [1 – 241]” and Offset (MSD) [0 - 240] in this way: Manufacturer Specific Data: 200 | Length: 2 | Offset: 2.
On Modbus you will have this result: reg.200=3344h
If you want to save only the byte 66 in the Modbus register 200 you have to compile the fields “Manufacturer Specific Data”, “Length (MSD)
[1 – 241]” and Offset (MSD) [0 - 240] in this way: Manufacturer Specific Data: 200 | Length: 1 | Offset: 5.
On Modbus you will have this result: reg.200=6600h
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 34 of 43
Industrial Electronic Devices
By pressing the “Update Device” button it is possible to load the created Configuration into the
device, and also the Firmware if is necessary, using the RS232 port.
In order to load the parameters or update the firmware in the device, follow these instructions:
Turn OFF the Device;
Connect the RS232 cable from your PC to the Converter;
Put Dip2 of ‘Dip-Switch A’ in ON position;
Select the “COM port” and press the “Connect” button;
Turn ON the device;
Check the “Boot state” Led. It must blink quickly;
Press the “Next” button;
Select which operations you want to do.
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” turn OFF the device;
Put Dip2 of ‘Dip-Switch A’ in OFF position;
Disconnect the USB/RS232 cable;
Turn ON the device.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 35 of 43
Industrial Electronic Devices
By pressing the “Update Device” button, it is possible to load the created Configuration into the
device; and also the Firmware, if necessary. This by using the Ethernet port.
If you don’t know the actual IP address of the device you have to use this procedure:
Turn OFF the Device;
Put Dip1 of ‘Dip-Switch A’ in ON position;
Turn ON the device
Connect the Ethernet cable;
Insert the IP “192.168.2.205”;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” turn OFF the Device;
Put Dip1 of ‘Dip-Switch A’ in OFF position;
Turn ON the device.
If you know the actual IP address of the device, you have to use this procedure:
Turn ON the Device with the Ethernet cable inserted;
Insert the actual IP of the Converter;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” the device automatically goes at Normal Mode.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 36 of 43
Industrial Electronic Devices
Note:
When you receive the device, for the first time, you also have to update the Firmware in the HD67029 device.
Warning:
If Fig. 6 appears when you try to do the Update try these points before seeking
assistance:
Check if the serial COM port selected is the correct one;
Check if the serial cable is connected between the PC and the device;
Try to repeat the operations for the updating;
Try with another PC;
Try to restart the PC;
Check the LAN settings;
If you are using the program inside a Virtual Machine, try to use in the main Operating
System;
If you are using Windows Seven, Vista, 8 or 10 make sure that you have the
administrator privileges;
In case you have to program more than one device, using the "UDP Update", you have to
cancel the ARP table every time you connect a new device on Ethernet. For do this you
have to launch the "Command Prompt" and write the command "arp -d". Pay attention
that with Windows Vista, Seven, 8, 10 you have to launch the "Command Prompt" with
Administrator Rights;
Pay attention at Firewall lock. Figure 6: “Error” window
Warning:
In the case of HD67029 you have to use the software “SW67029”: www.adfweb.com\download\filefold\SW67029.zip.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 37 of 43
Industrial Electronic Devices
“SCAN & DECODE” functions are integrated in the configurator software SW67029. It is possible to access to these functions by simple click
on the “ ” button.
For the description of the function, it is possible to refer to this manual: www.adfweb.com/download/filefold/SCAN&DECODE_ENG.pdf
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 38 of 43
Industrial Electronic Devices
MECHANICAL DIMENSIONS:
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 39 of 43
Industrial Electronic Devices
ORDERING INFORMATIONS:
Serial port
232: RS232
485: RS485
Connectors Type
2: Fixed Screw Terminal
Enclosure Type
B: Modulbox 4M DIN Rail mounting
Device Family
HD67029: M-Bus / Modbus – Converter
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 40 of 43
Industrial Electronic Devices
Order Code: HD67029-B2-232-20 - M-Bus master / Modbus slave (RS232) - Converter (up to 20 slaves connected to M-Bus)
Order Code: HD67029-B2-232-40 - M-Bus master / Modbus slave (RS232) - Converter (up to 40 slaves connected to M-Bus)
Order Code: HD67029-B2-232-80 - M-Bus master / Modbus slave (RS232) - Converter (up to 80 slaves connected to M-Bus)
Order Code: HD67029-B2-232-160 - M-Bus master / Modbus slave (RS232) - Converter (up to 160 slaves connected to M-Bus)
Order Code: HD67029-B2-232-250 - M-Bus master / Modbus slave (RS232) - Converter (up to 250 slaves connected to M-Bus)
Order Code: HD67029-B2-485-20 - M-Bus master / Modbus slave (RS485) - Converter (up to 20 slaves connected to M-Bus)
Order Code: HD67029-B2-485-40 - M-Bus master / Modbus slave (RS485) - Converter (up to 40 slaves connected to M-Bus)
Order Code: HD67029-B2-485-80 - M-Bus master / Modbus slave (RS485) - Converter (up to 80 slaves connected to M-Bus)
Order Code: HD67029-B2-485-160 - M-Bus master / Modbus slave (RS485) - Converter (up to 160 slaves connected to M-Bus)
Order Code: HD67029-B2-485-250 - M-Bus master / Modbus slave (RS485) - Converter (up to 250 slaves connected to M-Bus)
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 41 of 43
Industrial Electronic Devices
ACCESSORIES:
Order Code: APW020 - Power Supply for M-Bus Master device that supports up to 20 Slaves
Order Code: APW040 - Power Supply for M-Bus Master device that supports up to 40 Slaves
Order Code: APW080 - Power Supply for M-Bus Master device that supports up to 80 Slaves
Order Code: APW160 - Power Supply for M-Bus Master device that supports up to 160 Slaves
Order Code: APW250 - Power Supply for M-Bus Master device that supports up to 250 Slaves
Order Code: AC34107 - Null Modem Cable Fem/Fem DSub 9 Pin 1,5 m
Order Code: AC34114 - Null Modem Cable Fem/Fem DSub 9 Pin 5 m
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 42 of 43
Industrial Electronic Devices
DISCLAIMER:
All technical content within this document can be modified without notice. The content of the document is a under continual renewal.
For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal
conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such
as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.
WEEE INFORMATION
Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate
collection systems).
This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead, it
should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed
correctly, you will help prevent potential negative environmental factors and impact of human health, which could otherwise be
caused by inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about
recycling this product, please contact your local city office, your household waste disposal service or the shop where you purchased
the product.
CE MARKING
The product conforms with the essential requirements of the applicable EC directives.
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG Revision 3.001 Page 43 of 43
Industrial Electronic Devices
For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.
Otherwise contact us at the address [email protected]
RETURN POLICY:
If while using your product you have any problem and you wish to exchange or repair it, please do the following:
Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to
provide detailed information about the problem.
Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be
accepted).
If the product is within the warranty of twelve months, it will be repaired or exchanged and returned within three weeks. If the product is no
longer under warranty, you will receive a repair estimate.