Cutler-Hammer Type Gi 125A Molded Case Circuit Breakers: Current in Multiple of in

This document contains time-current curves for Cutler-Hammer Type Gi125A and Fi100A molded case circuit breakers. [1] The curves show the relationship between tripping time and fault current for various breaker ratings, with notes on interrupting ratings, trip mechanisms, and other application data. [2] Breaker ratings range from 15-125 amps continuous for the Gi125A and 15-100 amps for the Fi100A. Interrupting ratings are provided for various voltages. [3] The curves allow for coordination of protection devices by ensuring circuit breakers trip in a minimum time for high overcurrents but provide a longer delay at currents just

Uploaded by

itamarpereira
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
423 views8 pages

Cutler-Hammer Type Gi 125A Molded Case Circuit Breakers: Current in Multiple of in

This document contains time-current curves for Cutler-Hammer Type Gi125A and Fi100A molded case circuit breakers. [1] The curves show the relationship between tripping time and fault current for various breaker ratings, with notes on interrupting ratings, trip mechanisms, and other application data. [2] Breaker ratings range from 15-125 amps continuous for the Gi125A and 15-100 amps for the Fi100A. Interrupting ratings are provided for various voltages. [3] The curves allow for coordination of protection devices by ensuring circuit breakers trip in a minimum time for high overcurrents but provide a longer delay at currents just

Uploaded by

itamarpereira
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Cutler-Hammer Type Gi125A Molded Case Circuit Breakers Application Data

Thermal/Magnetic Trip, Fixed Thermal-Fixed Magnetic 29-167i


Time-Current Curves for Coordination

Maximum AC Volts: 415 at 50/60 Hz Poles: 2 and 3

Breaker Rating Interrupting Ratings (IEC 947-2) Notes:


Instantaneous RMS Symmetrical Amperes (kA) (a) Fixed Inverse-Time Overcurrent Release.
Continuous Amperes Trip Amperes (b) Fixed Electromagnetic Release.
Volts Icu Ics (c) Total Operation Time.
15-60 700-1500
70-125 See Curve 220/240 AC 25 7 (d) Interrupting Rating determines end of
380/415 AC 18 5 curve.

CURRENT IN MULTIPLE OF In
10
0
2 3 4 5 6 7 8 9 101 2 3 4 5 6 7 8 9 102 2 3 4 5 6 7 8 9 103
10000 10000

1 HOUR
1 HOUR

5000 5000

2000 2000

1000 1000

500 500

(a)
200 200

100 100

50 50

Max. Trip Time


20 20

10 10
TIME IN SECONDS

TIME IN SECONDS
5 5
Min.
Trip
2 2
Time

1 1

.5 .5

.2 .2
(b)
.1 .1

.05 .05

(c) (d)
.02 .02

.01 .01

.005 .005

.002 .002

.001 .001
1 2 3
100 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10

CURRENT IN MULTIPLE OF In
Curve No. SC-5821-94
Cutler-Hammer Printed in U.S.A. October 1997
Cutler-Hammer Type Fi 100A Molded Case Circuit Breakers Application Data
Thermal/Magnetic Trip, Fixed Thermal-Fixed Magnetic 29-167i
Time-Current Curves for Coordination

Maximum AC Volts: 440 at 50/60 Hz Poles: 2 and 3


Maximum DC Volts: 250

Breaker Rating Interrupting Ratings (IEC 947-2) Notes:


Instantaneous RMS Symmetrical Amperes (kA) (a) Fixed Inverse-Time Overcurrent Release.
Continuous Amperes Trip Amperes (b) Fixed Electromagnetic Release (100 Amp
Volts Icu Ics Shown). See Chart for other ratings.
15-40 500-1000
50-70 600-1200 220/240 AC 25 13 (c) Total Operation Time.
80-100 700-1400 380/415 AC 18 9 (d) Interrupting Rating determines end of
440 AC 14 7 curve.
250 DC 10 5

CURRENT IN MULTIPLE OF In
10
0
2 3 4 5 6 7 8 9 101 2 3 4 5 6 7 8 9 102 2 3 4 5 6 7 8 9 103
10000 10000

1 HOUR
1 HOUR

5000 5000

2000 2000

1000 1000

500 500

(a)
200 200

100 100

50 50
Max. Trip Time
20 20

10 10
TIME IN SECONDS

TIME IN SECONDS
5 5

Min.
2 Trip 2
Time
1 1

.5 .5

.2 .2
(b)

.1 .1

.05 (c) .05


(d)

.02 .02

.01 .01

.005 .005

.002 .002

.001 .001
1 2 3
100 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10

CURRENT IN MULTIPLE OF In
Curve No. SC-5822-94
Cutler-Hammer Printed in U.S.A. October 1997
Cutler-Hammer Type Fi 160A Molded Case Circuit Breakers Application Data
Thermal/Magnetic Trip, Fixed Thermal-Fixed Magnetic 29-167i
Time-Current Curves for Coordination

Maximum AC Volts: 440 at 50/60 Hz Poles: 2 and 3


Maximum DC Volts: 250

Breaker Rating Interrupting Ratings (IEC 947-2) Notes:


Instantaneous RMS Symmetrical Amperes (kA) (a) Fixed Inverse-Time Overcurrent Release.
Continuous Amperes Trip Amperes (b) Fixed Electromagnetic Release.
Volts Icu Ics (c) Total Operation Time.
125, 150, 160 See Curve
220/240 AC 35 18 (d) Interrupting Rating determines end of
380/415 AC 25 13 curve.
440 AC 20 10
250 DC 10 5

CURRENT IN MULTIPLE OF In
10
0
2 3 4 5 6 7 8 9 101 2 3 4 5 6 7 8 9 102 2 3 4 5 6 7 8 9 103
10000 10000

1 HOUR
1 HOUR

5000 5000

2000 2000

1000 1000

500 500

(a)
200 200

100 100

50 50
Max. Trip Time
20 20

10 10
TIME IN SECONDS

TIME IN SECONDS
5 5

Min.
2 Trip 2
Time
1 1

.5 .5

.2 (b) .2

.1 .1

.05 (c) .05


(d)

.02 .02

.01 .01

.005 .005

.002 .002

.001 .001
1 2 3
100 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10

CURRENT IN MULTIPLE OF In
Curve No. SC-5823-94
Cutler-Hammer Printed in U.S.A. October 1997
Cutler-Hammer Type Fi 225A Molded Case Circuit Breakers Application Data
Thermal/Magnetic Trip, Fixed Thermal-Fixed Magnetic 29-167i
Time-Current Curves for Coordination

Maximum AC Volts: 440 at 50/60 Hz Poles: 2 and 3


Maximum DC Volts: 250

Breaker Rating Interrupting Ratings (IEC 947-2) Notes:


Instantaneous RMS Symmetrical Amperes (kA) (a) Fixed Inverse-Time Overcurrent Release.
Continuous Amperes Trip Amperes (b) Fixed Electromagnetic Release.
Volts Icu Ics (c) Total Operation Time.
175, 200, 225 See Curve
220/240 AC 35 18 (d) Interrupting Rating determines end of
380/415 AC 25 13 curve.
440 AC 20 10
250 DC 10 5

CURRENT IN MULTIPLE OF In
10
0
2 3 4 5 6 7 8 9 101 2 3 4 5 6 7 8 9 102 2 3 4 5 6 7 8 9 103
10000 10000

1 HOUR
1 HOUR

5000 5000

2000 2000

1000 1000

500 500

(a)
200 200

100 100

50 50
Max. Trip Time
20 20

10 10
TIME IN SECONDS

TIME IN SECONDS
5 Min. 5
Trip
Time
2 2

1 1

.5 .5

.2 (b) .2

.1 .1

.05 (c) .05

(d)
.02 .02

.01 .01

.005 .005

.002 .002

.001 .001
1 2 3
100 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10

CURRENT IN MULTIPLE OF In
Curve No. SC-5824-94
Cutler-Hammer Printed in U.S.A. October 1997
Cutler-Hammer Type Ji 250A Molded Case Circuit Breakers Application Data
Thermal/Magnetic Trip, Fixed Thermal-Fixed Magnetic 29-167i
Time-Current Curves for Coordination

Maximum AC Volts: 440 at 50/60 Hz Poles: 3


Maximum DC Volts: 250

Breaker Rating Interrupting Ratings (IEC 947-2) Notes:


Instantaneous RMS Symmetrical Amperes (kA) (a) Fixed Inverse-Time Overcurrent Release.
Continuous Amperes Trip Amperes (b) Adjustable Electromagnetic Release.
Volts Icu Ics (c) Total Operation Time.
250 1250-2500
220/240 AC 35 18 (d) Interrupting Rating determines end of
380/415 AC 25 13 curve.
440 AC 20 10
250 DC 10 5

CURRENT IN MULTIPLE OF In
10
0
2 3 4 5 6 7 8 9 101 2 3 4 5 6 7 8 9 102 2 3 4 5 6 7 8 9 103
10000 10000

1 HOUR
1 HOUR

5000 5000

2000 2000

1000 1000

500 500
(a)
200 200

100 Max. Trip Time 100

50 50
Min.
Trip
20 Time 20

10 10
TIME IN SECONDS

TIME IN SECONDS
5 5

2 2

1 1

.5 .5

.2 (b) .2

.1 .1

.05 .05
(c)

(d)
.02 .02

.01 .01

.005 .005

.002 .002

.001 .001
1 2 3
100 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10

CURRENT IN MULTIPLE OF In
Curve No. SC-5825-94
Cutler-Hammer Printed in U.S.A. October 1997
Cutler-Hammer Type Ki 400A Molded Case Circuit Breakers Application Data
Thermal/Magnetic Trip, Fixed Thermal-Fixed Magnetic 29-167i
Time-Current Curves for Coordination

Maximum AC Volts: 440 at 50/60 Hz Poles: 3


Maximum DC Volts: 250

Breaker Rating Interrupting Ratings (IEC 947-2) Notes:


Instantaneous RMS Symmetrical Amperes (kA) (a) Fixed Inverse-Time Overcurrent Release.
Continuous Amperes Trip Amperes (b) Adjustable Electromagnetic Release.
Volts Icu Ics (c) Total Operation Time.
300 1500-3000
350 1750-3500 220/240 AC 35 18 (d) Interrupting Rating determines end of
400 2000-4000 380/415 AC 25 13 curve.
440 AC 20 10
250 DC 10 5

CURRENT IN MULTIPLE OF In
10
0
2 3 4 5 6 7 8 9 101 2 3 4 5 6 7 8 9 102 2 3 4 5 6 7 8 9 103
10000 10000

1 HOUR
1 HOUR

5000 5000

2000 2000

1000 1000

500 500
(a)
200 200

100 Max. Trip Time 100

50 Min. 50
Trip
Time
20 20

10 10
TIME IN SECONDS

TIME IN SECONDS
5 5

2 2

1 1

.5 .5

.2 (b) .2

.1 .1

.05 .05
(c)

(d)
.02 .02

.01 .01

.005 .005

.002 .002

.001 .001
1 2 3
100 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10

CURRENT IN MULTIPLE OF In
Curve No. SC-5826-94
Cutler-Hammer Printed in U.S.A. October 1997
Cutler-Hammer Type Li 630A Molded Case Circuit Breakers Application Data
Thermal/Magnetic Trip, Fixed Thermal-Adjustable Magnetic 29-167i
Time-Current Curves for Coordination

Maximum AC Volts: 440 at 50/60 Hz Poles: 3


Maximum DC Volts: 250

Breaker Rating Interrupting Ratings (IEC 947-2) Notes:


Instantaneous RMS Symmetrical Amperes (kA) (a) Fixed Inverse-Time Overcurrent Release.
Continuous Amperes Trip Amperes (b) Adjustable Electromagnetic Release.
Volts Icu Ics (c) Total Operation Time.
500 2500-5000
600 3000-6000 220/240 AC 35 18 (d) Interrupting Rating determines end of
630 3150-6300 380/415 AC 25 13 curve.
440/480 AC 20 10
250 DC 10 5

CURRENT IN MULTIPLE OF In
10
0
2 3 4 5 6 7 8 9 101 2 3 4 5 6 7 8 9 102 2 3 4 5 6 7 8 9 103
10000 10000

1 HOUR
1 HOUR

5000 5000

2000 2000

1000 1000

500 500
(a)
200 200

100 Max. Trip Time 100

50 50

20 Min. 20
Trip
10 Time 10
TIME IN SECONDS

TIME IN SECONDS
5 5

2 2
(b)
1 1

.5 .5

.2 .2

.1 .1

.05 (c) .05


(d)

.02 .02

.01 .01

.005 .005

.002 .002

.001 .001
1 2 3
100 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10

CURRENT IN MULTIPLE OF In
Curve No. SC-5827-94
Cutler-Hammer Printed in U.S.A. October 1997
Cutler-Hammer Type Li 800A Molded Case Circuit Breakers Application Data
Thermal/Magnetic Trip, Fixed Thermal-Adjustable Magnetic 29-167i
Time-Current Curves for Coordination

Maximum AC Volts: 440 at 50/60 Hz Poles: 3


Maximum DC Volts: 250

Breaker Rating Interrupting Ratings (IEC 947-2) Notes:


Instantaneous RMS Symmetrical Amperes (kA) (a) Fixed Inverse-Time Overcurrent Release.
Continuous Amperes Trip Amperes (b) Adjustable Electromagnetic Release.
700 2800-5600 Volts Icu Ics (c) Total Operation Time.
800 3200-6400 220/240 AC 42 21 (d) Interrupting Rating determines end of
380/415 AC 35 18 curve.
440/480 AC 30 15
250 DC 10 5

CURRENT IN MULTIPLE OF In
10
0
2 3 4 5 6 7 8 9 101 2 3 4 5 6 7 8 9 102 2 3 4 5 6 7 8 9 103
10000 10000

1 HOUR
1 HOUR

5000 5000

2000 2000

1000 1000

500 500
(a)
200 200

100 Max. Trip Time 100

50 50

20 Min. 20
Trip
10 Time 10
TIME IN SECONDS

TIME IN SECONDS
5 5

2 2
(b)
1 1

.5 .5

.2 .2

.1 .1

.05 .05
(c)
(d)

.02 .02

.01 .01

.005 .005

.002 .002

.001 .001
1 2 3
100 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10

CURRENT IN MULTIPLE OF In
Curve No. SC-5828-94
Cutler-Hammer Printed in U.S.A. October 1997