ASSH Air Cooled Scroll Chiller Manual en Oct 16 2017
ASSH Air Cooled Scroll Chiller Manual en Oct 16 2017
Climate 5000
ASSH-035D3AE | ASSH-070D3AE | ASSH-135D3AE |
Read the manual carefully prior to installation and operation of the unit!
WELCOME
Distinguished users:
Important prompt:
Table of contents
1 Key to symbols and safety instructions ..... 3 5.4 Error query interface ................................ 33
1.1 Explanation of symbols ............................. 3 5.5 Parameter check interface ....................... 33
1.2 Safety information ..................................... 3
1.3 Product description ................................... 3 6 Unit commissioning and operation ............ 35
1.4 Operating limits ......................................... 4 6.1 Preparation .............................................. 35
6.2 Single unit commissioning ....................... 35
2 Unit information............................................. 5 6.3 Joint commissioning................................. 35
2.1 Naming rule............................................... 5
2.2 Working principle....................................... 5 7 Maintenance.................................................. 36
2.2.1 Cooling ............................................... 5
2.2.2 Heating............................................... 5 8 Common faults and solutions ..................... 38
2.3 Unit characteristics.................................... 6
2.4 Component characteristics ....................... 6 9 Error code and dialed code setting ............ 41
2.5 Specifications ............................................ 8 9.1 Error code ................................................ 41
2.6 Performance correction table.................... 9 9.2 Dialed code setting .................................. 42
2.6.1 Cooling capacity and power correction 9.2.1 Address code setting SM1 (DIP1~DIP4)
table ................................................... 9 ........................................................... 42
2.6.2 Heating capacity and power correction 9.2.2 Unit type setting SM1 (DIP5~DIP8) .. 42
table ................................................... 9 9.2.3 Unit model setting SM2 (DIP1~DIP2) 42
2.7 Operating range ....................................... 10
2.8 Curves of loss of pressure at the water side 11 10 Packing list ................................................. 43
2.9 Outlines and dimensions.......................... 12
2.10 Installation foundation ............................ 13
3 Engineering installation............................... 15
3.1 Unit installation......................................... 15
3.1.1 Preparation before installation .......... 15
3.1.2 Installation position ........................... 15
3.1.3 Handling and lifting ........................... 17
3.2 Electrical installation ................................ 18
3.3 Equipment installation.............................. 23
3.3.1 Water pipe installation....................... 23
3.3.2 Installation of filter............................. 23
3.3.3 Installation of flow switch .................. 24
3.4 Water pipe connection diagram ............... 24
2 Unit introduction
The air cooled scroll chiller system is used to cool Fin heat exchanger
down and heat up with the principle of reverse
Carnot cycle by making use of cheap air and a
small amount of power.
2.1 Nomenclature
Bosch Climate 5000 AS S H - Four-way
valve
1 2 3 4 5 6 Water inlet
Plate HEx
Compressor
135 D 3 A E
7 8 9 10 11 12 13 Water
outlet
1 Bosch: brand
Figure 1: Cooling operation diagram
2 Climate: category
Drain the high-temperature and high-pressure
3 5000: value level
refrigerant gas compressed by compressor to fin
Energy: AS - air source; WL - water loop; GW - heat exchanger through four-way valve. In the
4
ground water; GL - ground loop process, heat is drained to the atmosphere and
Compressor: R - rotary; S - scroll; W - screw; C intermediate-temperate and high-pressure liquid
5
- centrifugal; T - turbolor refrigerant is generated. Then throttle with the
electronic expansion valve to generate low-tem-
6 Unit function: C - cooling only; H - heat pump
perature and low-pressure gas liquid mixture, and
7
Cooling capacity: kW (double digit at least, such exchange it with circulating water in the plate heat
as 08 = 8 kW) exchanger to return to the compressor. A cycle is
Heat recovery: PHx– partial heat recovery x%; completed. After exchange with refrigerant, the
8 TH -total heat recovery100%; omit - no heat circulating water reaches the temperature required
recovery
and then exchanges with indoor air. Cooling is
Refrigerant: A-R22; B-R407C; C-R134a; D- realized.
9
R410A
Power supply: 2.2.2 Heating
• 220~230V/50Hz/1 Phase
Fin heat exchanger
• 220~230V/60Hz/1 Phase
10 • 380~400V/50Hz/ 3 Phase
• 380~400V/60Hz/ 3 Phase
• 110~115V/60Hz/ 1 Phase
• 460V/60Hz/ 3 Phase
Product sequence: A, B, C, D…N; A1, B1, C1, D1…N1
11
Nx=customized product, x=null,1,2,3… Four-way
valve
12 Climate condition: T-T3; T1- omit
Water inlet
Plate HEx
2.5 Specifications
Model ASSH-035D3AE ASSH-070D3AE ASSH-135D3AE
Cooling capacity kW 32.5 66.5 133
Heating capacity kW 33 67.5 135
Power supply V/Ph/Hz 380V/3Ph/50Hz 380V/3Ph/50Hz 380V/3Ph/50Hz
Cooling kW 10.2 19.9 39.8
Input power
Heating kW 10.3 20.2 40.4
Rated current A 18.4 35.9 71.8
Startup
A 128 152.1 200.3
Current current
Maximum operating
A 24 45.8 92.5
current
Type Scroll
Compressor
Quantity 1 2 4
Refrigerant R410A kg 9.85 9.5×2 9.5×4
Internally ribbed tube and high-efficiency hydrophilic type
Type
louvered aluminum fin
Type of fan Axial flow fan
Air side
Quantity of fans 1 2 4
3
Air volume m /h 13000 13000×2 13000×4
Fan motor input kW 0.75 0.75×2 0.75×4
Type Plate
Water flow volume m3/h 5.6 11.4 22.9
water resistance loss kPa 28 36 36
Net dimension
Dimension mm 1050*1293*2030 1050*2150*2030 1909*2150*2030
(W* D* H)
Environment temperature °C
Water
outlet 15 20 25 30 35 40 46
temp.
°C
Cap- Cap- Cap- Cap- Cap- Cap- Cap-
Power acity Power Power acity Power Power Power acity Power
acity acity acity acity
5 1.11 0.75 1.05 0.80 1.00 0.85 0.96 0.92 0.91 0.98 0.84 1.08 0.77 1.17
7 1.18 0.77 1.13 0.82 1.07 0.87 1.04 0.94 1.00 1.00 0.91 1.09 0.83 1.19
9 1.25 0.79 1.20 0.84 1.14 0.89 1.10 0.96 1.06 1.02 0.98 1.12 0.89 1.21
12 1.35 0.83 1.30 0.88 1.25 0.92 1.20 0.99 1.16 1.06 1.07 1.15 0.98 1.24
15 1.45 0.86 1.40 0.91 1.35 0.95 1.30 1.02 1.26 1.09 1.17 1.19 1.08 1.28
Environment temperature °C
Water
outlet -15 -10 -5 0 7 10 15 21 25
temp.
°C
Cap- Cap- Cap- Cap- Cap- Cap- Cap- Cap- Cap-
Power Power Power Power Power Power Power Power Power
acity acity acity acity acity acity acity acity acity
30 0.54 0.72 0.64 0.73 0.72 0.74 0.83 0.75 1.06 0.76 1.08 0.76 1.10 0.77 1.22 0.77 1.27 0.78
35 0.52 0.80 0.62 0.80 0.70 0.81 0.82 0.82 1.04 0.83 1.06 0.84 1.08 0.84 1.21 0.85 1.26 0.87
40 0.50 0.87 0.60 0.88 0.68 0.88 0.79 0.90 1.02 0.91 1.04 0.92 1.06 0.92 1.19 0.93 1.24 0.96
45 0.48 0.96 0.58 0.97 0.66 0.98 0.77 0.99 1.00 1.00 1.02 1.01 1.04 1.02 1.17 1.03 1.22 1.06
50 - - - - - - 0.75 1.09 0.97 1.10 0.98 1.10 1.02 1.11 1.14 1.13 1.19 1.17
55 - - - - - - - - 0.93 1.20 0.95 1.21 0.99 1.21 1.12 1.24 1.16 1.25
25
15, 20 46, 20
Outlet water temperature(°C)
20
15
10
15, 5 46, 5
5
0
10 15 20 25 30 35 40 45 50
Ambient temperature (°C)
60
10, 55 25, 55
55
Outlet water temperature(°C)
50
-15, 45
45
40
35
-15, 30 25, 30
30
25
-20 -10 0 10 20 30
Ambient temperature (°C)
55
50
45
40
35
30
25
20
15
10
3 5 7 9
Water flow (m /h)
3
45
40
35
30
25
20
8 9 10 11 12 13 14
Water flow (m3/h)
Figure 6: ASSH-070D3AE curves of loss of pressure at the water side
45
40
35
30
25
20
16 18 20 22 24 26 28
Water flow (m3/h)
Figure 7: ASSH-135D3AE curves of loss of pressure at the water side
ASSH-035D3AE 68 162.5 900 1293 1050 470 154 2030 645 DN40 Thread
ASSH-070D3AE 100 450 1150 2150 1050 470 153 2030 645 DN50
Flange
ASSH-135D3AE 100 330 1390 2150 1909 398 154 2030 986 DN80
Table 6: Outline and dimension table
Water inlet
Water inlet
Water inlet
Unit bolt hole Water outlet
Water inlet
Water outlet
300
≥100
≥(n-1)x1440+1790
Water inlet
Water outlet
300
Unit bolt
Unit bolt hole M12 M12×220
≥400 970 ≥450 970 970 ≥400
≥100
≥550
≥2250
1150
≥550
≥100
≥(n-1)x1420+1770
Water inlet
Water outlet
300
≥100
≥430 1390 ≥430
≥2250
≥100
≥(n-1)x2271+2621
3 Engineering installation
≥3000mm
form of install, and the distance between
unit and walls should exceed 1800mm in
order to get more airflow.
The installation position of module unit shall be
selected reasonably to ensure its operating
efficiency meets the objectives and requirements.
It shall be selected from the following aspects:
• Air cooled sroll chiller unit shall be installed on
steady and firm bearing surface.
• Air cooled sroll chiller unit and indoor heat
exchanger shall be as close as possible to
reduce the length of cooling pipe and the ≥1800mm ≥1800mm
quantity of bends as far as possible. However,
certain distance is required.
• Air cooled sroll chiller unit shall not be installed
by the window or among buildings to prevent
normal operating noise from entering rooms. Figure 14: Single unit installation
Row R
than 2000mm, when H Less than or equal
2300, the C and D bigger than (H-300) mm.
- When N=1, 2 and R≥2 or 2≤R≤4 and N≥3, the
B is 400mm.
Column N
When N=3 and R≥5, the B is 600mm.
When N=4 and R≥5 or N=5 and R≥5, the B is
800mm.
When R=6 and N≥5, the B is1200mm.
When N=5 and R≥7 or R=8 and N≥7, the B is
1600mm.
When N=7, 8 and R≥8 or R=9 and N≥9, the B
is 2000mm.
- When the two walls connect each other, like
the first chart, the row need plus 2 and the
column need plus 1 on original numerical.
Lifting hook
Lifting sling
Lifting bar
Figure 15: Modular unit installation Figure 16: Handling and lifting
R S T N
Slave unit 1
R S T N
Unit model
Start- Ground-
Rated Max. Firing Null
ing ing
ASSH-
18.4 24 128 10×3 6 10
035D3AE
ASSH-
35.9 45.8 152.1 25×3 6 16
070D3AE
ASSH-
71.8 92.5 200.3 70×3 6 35
135D3AE
TSa
3
TCa
TDa
Te
TOa
Tr
CC-Ha
1
Crankcase Heater System A
5 1 2
• ASSH-035D3A
空调辅助电加热
AH
PSc/TH1 TH3 TH5 TH7 TH9 TH11 TH13 TH15 TH17 TH19 TH21 TH23 TH24 TH26
Eletrical Assisted Heater
1 2 3 T PSd/TH2 TH4 TH6 TH8 TH10 TH12 TH14 TH16 TH18 TH20 TH22 TH25
8736862413(2017/05)en
S CN401 系统A四通阀
A B C R 4WVa
4 Way Valve System A
EVd
B N 6.3A/250VAC
7 主板
8 9
2 CT1
输出报警信号
电源指示灯 2 CT2
CN432 ALARM
Main Board
EVc
5 A 5 Output Alarm
Power Light A2 L1 ON
20 | Engineering installation
A2 L1 21 CT3
CN434
SW1
CT4 1 2 3 4 5 6 7 8
U14
ON
EVb
KM1
KM2
CT5 1 2 3 4 5 6 7 8
A1 A1 CN433
CT6 SW2 代号ABR 对照表 Table
CT7
EVa
CN435 接上位机监控 To PC 系统A低压开关
A B C CT8
5
LPa
GND
CN426 CN439 Low Pressure Switch System A
D_IN1
D_IN2
D_IN3
D_IN4
D_IN5
D_IN6
D_IN7
PSa
CN427
CN451 CN469 CN466 CN462 CN457 CN450 CN443 系统A高压开关
8 HPa
D_OUT9
D_OUT8
D_OUT7
D_OUT6
D_OUT5
D_OUT4
D_OUT3
D_OUT2
D_OUT1
1 CN440 CN441 4 High Pressure Switch System A
D_OUT23
D_OUT22
D_OUT21
D_OUT20
D_OUT19
D_OUT18
D_OUT17
D_OUT16
D_OUT15
D_OUT14
D_OUT13
D_OUT12
D_OUT11
D_OUT10
PSb
2 CN431
3 2
系统A风机保护
2 FPa
3 4 4 4 Fan Protection System A
FANa
COMPa
CT1 联动开关
CT2 EVa
LS Line Switch
A 空调测流量开关
COMPa
FS
Flow Switch
4 8 3 备选件 Optional
4 4
FPa
LS
FS
端子排接口板 Terminal Interface Board 2 BA Board TDa
4
Discharge Comp Temp System A
PSa
CN27 CN29
A-L1 A-L2 A-L3 B-L1 B-L2 B-L3 CN28 室外环境温传
N
Wpump
WAH
4WVa2
Eva3
N
N
PUMP
N
ALARM
N
4WVb2
Eva1
N
Eva2
Evb1
N
Evb2
Evb3
N
CC-Ha
N
4WVa
4WVb
Eva4
Evb4
CC-Hb
AH
Te
FPab
FS
OV
LS
OV
OV
A1
B1
GND
+5V
WCV
DIN9
DIN10
GND
Aout
+12V
WIREC
Ambient Temp
MOUDBUS通讯接口
MOUDBUS Communication
Interface
MODBUS 系统回水温传
B2
OV
A2
OV
GND
+5V
OV
+5V
GND
Tr
HPb
Bout
LPb
LPa
HPa
CN15 CN16 CN17 CN18 CN19 CN20 CN21 CN22 CN23 CN24 CN25 CN26 Water In Temp
DIN11
DIN12
SW1地址设置: 系统A出水温传
TOa Water Out Temp System A
手操器 (Address Set:)
Handset DIP1 DIP2 DIP3 DIP4 地址(Address) 系统A室外盘管出口温传
TCa
ON ON ON ON 主机0(master0) Coli Out Temp System A
NEXT
HPa
LPa
ON ON ON OFF 从机1(slave1) 系统A吸气温传
AH
CC-Ha
4WVa
ALARM
备注 ON ON OFF ON 从机2(slave2) TSa
Suction Temp System A
FANa
Remarks ON ON OFF OFF 从机3(slave3)
1.正常出厂设置:联动开关短接
ON OFF ON ON 从机4(slave4)
水泵接触器线圈 ON OFF ON OFF 从机5(slave5)
EX-factory setting: Air terminal unit interlock
Pump Contactor Coil ON OFF OFF ON 从机6(slave6)
control short connected,
ON OFF OFF OFF 从机7(slave7)
2.拨码设置 Dialed code setting: OFF ON ON ON 从机8(slave8)
DIP1-4:地址设置 address setting, OFF ON ON OFF 从机9(slave9)
代号ABR 对照表 Table DIP5: ON-单冷 cooling only、OFF-热泵 heat pump OFF ON OFF ON 从机10(slave10) ASSH035D3AE 模块机线路图
CT Current Sampling Board DIP : 6 7 8 机型 type OFF ON OFF OFF 从机11(slave11) ASSH035D3AE Module Wiring Diagram
电流采样板
OFF OFF OFF 35 OFF OFF ON ON 从机12(slave12)
COMPa 系统A压缩机 Compresser System A OFF OFF ON OFF 从机13(slave13)
3.后期如有改动,不另通知
FANa 系统A风机 Fan Motor System A OFF OFF OFF ON 从机14(slave14) 博世热力技术(山东)有限公司
No special notice is given if there is any change Bosch Thermo Technology (Shandong) Co., Ltd.
EVa 系统A电子膨胀阀 Electronic Expansion Valve System A OFF OFF OFF OFF 从机15(slave15)
Climate 5000
代号ABR 对照表 Table
线束规格 Wire Specifications 线束规格 Wire Specifications 线束规格 Wire Specifications
380V~400V/50Hz/3PH 系统A曲轴加热
1 黄色 Yellow,4.0m㎡ 6 黄/绿色 Y/G,4.0m㎡ B 绿色 Green,0.75m㎡
L1 L2 L3 N PE 导线标识 Wire Graphic
CC-Ha
2 绿色 Green,4.0m㎡ 7 黄色 Yellow,1.5m㎡ C 红色 Red,0.75m㎡ Crankcase Heater System A
供应商接线 Supplier Wiring
3 红色 Red,4.0m㎡ 8 绿色 Green,1.5m㎡
工厂接线 Factory Wiring 系统B曲轴加热
X1 R S T N 4 蓝色 Blue,1.5m㎡ 9 红色 Red,1.5m㎡ CC-Hb
6 4
Climate 5000
5 蓝色 Blue,0.75m㎡ A 黄色 Yellow,0.75m㎡
用户接线 User Wiring Crankcase Heater System B
空调辅助电加热
AH
Eletrical Assisted Heater
TSa
TSb
TCa
TDa
TDb
TCb
Te
TOab
Tr
系统A四通阀
5
4WVa
1 2 3 4 Way Valve System A
• ASSH-070D3A
1 1
系统B四通阀
A B C PSc/TH1 TH3 TH5 TH7 TH9 TH11 TH13 TH15 TH17 TH19 TH21 TH23 TH24 TH26 4WVb
PSd/TH2 TH4 TH6 TH8 TH10 TH12 TH14 TH16 TH18 TH20 TH22 TH25 4 Way Valve System B
QF1
T
QF2
S CN401
1 2 3 R 输出报警信号
ALARM
EVd
B N 6.3A/250VAC
7 A 5 1 主板 Output Alarm
2 CT1
2 CT1
电源指示灯 2 CN432 系统A低压开关
3 5 CT2 Main Board LPa
EVc
8 9 5 Low Pressure Switch System A
Power Light A2 L1 A2 2 CT3 ON SW1
L1 21 A
A2 L1
21 CN434
2 CT4 1 2 3 4 5 6 7 8
ON
U14 系统A高压开关
EVb
KM1
HPa
KM3
KM2
CT5 1 2 3 4 5 6 7 8 High Pressure Switch System A
A1 A1 A1 CN433
CT6 SW2 5
CT7
系统B低压开关
EVa
CN435 接上位机监控 To PC LPb
A B C CT8 Low Pressure Switch System B
GND
CN426 CN439 5
D_IN1
D_IN2
D_IN3
D_IN4
D_IN5
D_IN6
D_IN7
PSa 系统B高压开关
CN427
CN451 CN469 CN466 CN462 CN457 CN450 CN443 HPb
8 High Pressure Switch System B
D_OUT9
D_OUT8
D_OUT7
D_OUT6
D_OUT5
D_OUT4
D_OUT3
D_OUT2
D_OUT1
1 1 CN440 CN441 4
D_OUT23
D_OUT22
D_OUT21
D_OUT20
D_OUT19
D_OUT18
D_OUT17
D_OUT16
D_OUT15
D_OUT14
D_OUT13
D_OUT12
D_OUT11
D_OUT10
PSb 系统AB风机保护
2 2 CN431
FPab
3 2 3 2
Fan Protection System AB
2 2
3 3 4 4 4
联动开关
COMPb
FANa
COMPa
LS
CT1 CT3 Line Switch
CT2 CT4 空调测流量开关
EVb
EVa
FS
A A Flow Switch
COMPb
COMPa
系统A压力传感器
C PSa
B Pressure Sensor System A
A
4 8 3 3 备选件 Optional 系统B压力传感器
4 4 PSb
FPab
LS
FS
Discharge Comp Temp System B
PSa
端子排接口板 Terminal Interface Board 2 BA Board
4
CN27 CN29 室外环境温传
A-L1 A-L2 A-L3 B-L1 B-L2 B-L3 CN28 Te
N
Wpump
WAH
4WVa2
Eva3
N
N
PUMP
N
N
4WVb2
Eva1
N
Eva2
N
ALARM
Evb1
N
Evb2
Evb3
N
CC-Ha
N
4WVa
4WVb
Eva4
Evb4
CC-Hb
AH
FPab
OV
LS
FS
OV
OV
A1
B1
Ambient Temp
WCV
GND
+5V
DIN9
DIN10
GND
Aout
+12V
WIREC
MOUDBUS通讯接口
MOUDBUS Communication
Interface
MODBUS
系统回水温传
Tr
OV
B2
A2
OV
GND
+5V
OV
+5V
GND
Water In Temp
HPb
Bout
LPb
LPa
HPa
CN15 CN16 CN17 CN18 CN19 CN20 CN21 CN22 CN23 CN24 CN25 CN26
DIN11
DIN12
系统出AB水温传
SW1地址设置: TOab
Water Out Temp System AB
水泵接触器线圈 手操器 (Address Set:) 系统A室外盘管出口温传
TCa
PSb
Pump Contactor Coil Handset DIP1 DIP2 DIP3 DIP4 地址(Address) Coli Out Temp System A
ON ON ON ON 主机0(master0)
NEXT
系统B室外盘管出口温传
HPb
HPa
LPb
LPa
ON ON ON OFF 从机1(slave1) TCb
AH
Coli Out Temp System B
CC-Ha
CC-Hb
4WVa
4WVb
ALARM
ON ON OFF ON 从机2(slave2)
FANb
系统A吸气温传
FANa
水泵接触器线圈 备注 ON ON OFF OFF 从机3(slave3) TSa
Pump Contactor Coil Remarks ON OFF ON ON 从机4(slave4) Suction Temp System A
代号ABR 对照表 Table 1.正常出厂设置:联动开关短接 ON OFF ON OFF 从机5(slave5) 系统B吸气温传
EX-factory setting: Air terminal unit interlock ON OFF OFF ON 从机6(slave6) TSb
Suction Temp System B
CT 电流采样板 Current Sampling Board control short connected, ON OFF OFF OFF 从机7(slave7)
COMPa 系统A压缩机 Compresser System A 2.拨码设置 Dialed code setting: OFF ON ON ON 从机8(slave8)
COMPb Compresser System B DIP1-4:地址设置 address setting, OFF ON ON OFF 从机9(slave9)
系统B压缩机 OFF ON OFF ON 从机10(slave10)
DIP5: ON-单冷 cooling only、OFF-热泵 heat pump ASSH070D3AE模块机线路图
FANa 系统A风机 Fan Motor System A OFF ON OFF OFF 从机11(slave11) ASSH070D3AE Module Wiring Diagram
DIP : 6 7 8 机型 type OFF OFF ON ON 从机12(slave12)
FANb 系统B风机 Fan Motor System B OFF OFF ON 70 OFF OFF ON OFF 从机13(slave13)
EVa 系统A电子膨胀阀 Electronic Expansion Valve System A 3.后期如有改动,不另通知 OFF OFF OFF ON 从机14(slave14) 博世热力技术(山东)有限公司
EVb Electronic Expansion Valve System B No special notice is given if there is any change OFF OFF OFF OFF 从机15(slave15) Bosch Thermo Technology (Shandong) Co., Ltd.
系统B电子膨胀阀
Engineering installation | 21
8736862413(2017/05)en
380V~400V/50Hz/3PH 线束规格 Wire Specifications 线束规格 Wire Specifications 线束规格 Wire Specifications
L1 L2 L3 N PE 1 黄色 Yellow,4.0m ㎡ 6 黄/绿色 Y/G,4.0m ㎡ B 绿色 Green,0.75m ㎡ 导线标识 Wire Graphic
2 绿色 Green,4.0m ㎡ 7 黄色 Yellow,1.5m ㎡ C 红色 Red,0.75m ㎡ 供应商接线 Supplier wiring
代号ABR 对照表 Table
3 红色 Red,4.0m ㎡ 8 绿色 Green,1.5m ㎡ 工厂接线 Factory wiring
X1 R S T N CC-Ha Crankcase Heater System A
6
系统A曲轴加热
4 蓝色 Blue,1.5m ㎡ 9 红色 Red,1.5m ㎡ 用户接线 User wiring
3 4 5 蓝色 Blue,0.75m ㎡ A 黄色 Yellow,0.75m ㎡
CC-Hb 系统B曲轴加热 Crankcase Heater System B
A B C 5
CC-Hc 系统C曲轴加热 Crankcase Heater System C
CC-Hd 系统D曲轴加热 Crankcase Heater System D
7
EVd
EVc
EVb
EVa
5 AH Eletrical Assisted Heater
TDd
TCa
TCc
TDb
TOcd
空调辅助电加热
TDa
TDc
TCb
TCd
TOab
Te
Tr
TSa
TSb
TSc
TSd
8 4WVa A系统四通阀 4 Way Valve System A
4WVb B系统四通阀 4 Way Valve System B
• ASSH-135D3A
9
4WVc C系统四通阀 4 Way Valve System C
TH3 TH5 TH7 TH9 TH11 TH13 TH15 TH17 TH19 TH21 TH23 TH24 TH26
1 1 1 1 1 T TH4 TH6 TH8 TH10 TH12 TH14 TH16 TH18 TH20 TH22 TH25 5 5 5 5 4WVd D系统四通阀 4 Way Valve System D
8736862413(2017/05)en
1 2 S CN401 EVc EVd ALARM Output Alarm
R
输出报警信号
B QF1 QF2 QF3 QF4 QF5 N 6.3A/250VAC 主板
2 4
3 CT1
2 2 CN432
电源指示灯 1 CT2 Main Board 代号ABR 对照表 Table
2 4
Power Light 3 CT3 ON
SW1
2 2 2 2 2 2 CN434 EVa EVb FPab 系统AB风机保护 Fan Protection System AB
1 3 1 3 1 3 1 3 7 1
CT4 1 2 3 4 5 6 7 8
22 | Engineering installation
8 ON
U14
2 4 FPcd Fan Protection System CD
1 4 5 8
4
系统CD风机保护
2 2 SW2 CN426 CN440
1 CT6 LS Line Switch
2 2 2 2 联动开关
2 4 接上位机监控 To PC
4 3
CT7
2
CN435 FS 空调测流量 Flow Switch
A2 L1 A2 L1 2 CT8 4
1 CN439
CN1 CN2 CN3 CN4 LPa 系统A低压开关 Low Pressure Switch System A
GND
KM5
KM6
2 2 2 2
D_IN1
D_IN2
D_IN3
D_IN4
D_IN5
D_IN6
D_IN7
A A A A PSa PSc/TH1 CN441
5 5 5 5 A1 A1 CN427 HPa 系统A高压开关 High Pressure Switch System A
21 21 A2 L1 21 CN451 CN469 CN466 CN462 CN457 CN450 CN443 4
A2 L1 A2 L1 A2 L1 21 LPb 系统B低压开关 Low Pressure Switch System B
8
KM5-A1
KM6-A1
GND
D_OUT9
D_OUT8
D_OUT7
D_OUT6
D_OUT5
D_OUT4
D_OUT3
D_OUT2
D_OUT1
PSb PSd/TH2
D_OUT14
CT
D_OUT19
D_OUT15
D_OUT13
D_OUT12
D_OUT10
D_OUT23
D_OUT22
D_OUT21
D_OUT20
D_OUT18
D_OUT17
D_OUT16
D_OUT11
D_IN8
D_IN9
KM1
KM3
KM4
KM2
HPb High Pressure Switch System B
D_IN10
D_IN11
D_IN12
A1 A1 A1 A1 CN431
系统B高压开关
LPc 系统C低压开关 Low Pressure Switch System C
3 3 3 3 6
KM1-A1
KM2-A1
KM3-A1
KM4-A1
FANcd
COMPa
FANab
HPc High Pressure Switch System C
COMPd
COMPb
COMPc
2 2 2 2 3 3 33 2 4 系统C高压开关
1 1 1 1 A A A A LPd Low Pressure Switch System D
系统D低压开关
KM4-A1
KM3-A1
KM6-A1
KM2-A1
KM1-A1
KM5-A1
B B B B
A C C C C
HPd 系统D高压开关 High Pressure Switch System D
COMPd
A
COMPc
A
COMPb
COMPa
A
FS
HPa
LS
LPa
系统B定频排气温传
LPc
HPc
PSb
PSa
端子排接口板 Terminal Interface Board 2 4 TDc 系统C定频排气温传 Discharge Comp Temp System C
4 BA板
3 3
TDd 系统D定频排气温传 Discharge Comp Temp System D
A-L1 A-L2 A-L3 B-L1 B-L2 B-L3 C-L1 C-L2 C-L3 D-L1 D-L2 D-L3 CN27
PUMP
AH
N
N
N
N
N
N
4WVa
4WVc
CC-Hc
CC-Hd
4WVb
4WVd
CC-Hb
ALARM
OV
CC-Ha
+5V
+12V
A1
B1
Aout
+5V
GND
0V
LPa
FS
HPa
HPc
Bout
LS
0V
LPc
0V
Ambient Temp
NEXT
WIREC BA Board Te 室外环境温传
CN25 CN26 Water In Temp
MODBUS Tr 系统回水温传
OV
B2
A2
+5V
GND
+5V
0V
0V
0V
+5V
TOab Water Out Temp System AB
Dout
Cout
系统AB出水温传
LPb
HPb
LPd
HPd
CN15 CN16 CN17 CN18 CN19 CN20 CN21 CN22 CN23 CN24
FPab
FPcd
3 3 3 手操器 TOcd 系统CD出水温传 Water Out Temp System CD
Handset TCa 系统A室外盘管出口温传 Coli Out Temp System A
TCb 系统B室外盘管出口温传 Coli Out Temp System B
PSd
PSc
TCc 系统C室外盘管出口温传 Coli Out Temp System C
TCd 系统D室外盘管出口温传 Coli Out Temp System D
SW1地址设置: Suction Temp System A
TSa 系统A吸气温传
FPcd
FPab
LPb
HPb
LPd
HPd
(Address Set:) Suction Temp System B
AH
TSb
CC-Ha
CC-Hb
4WVa
4WVd
CC-Hc
CC-Hd
4WVb
4WVc
系统B吸气温传
ALARM
FANa
FANb
FANc
FANd
Interface DIP1 DIP2 DIP3 DIP4 地址(Address)
水泵接触器线圈 TSc 系统C吸气温传 Suction Temp System C
ON ON ON ON 主机0(master0)
Pump Contactor Coil ON ON ON TSd 系统D吸气温传 Suction Temp System D
OFF 从机1(slave1)
MOUDBUS通讯接口
Climate 5000
Engineering installation | 23
► The space inside the plate heat exchanger is - “-” It is not recommended to operate under the
very small. Therefore, the filter must be installed environment.
at the inlet of water pipe to prevent impurities • Installation of filter
from entering. The water pipeline filter is used to control the
► The pipeline shall be arranged horizontally and impurities in the water loop to prevent impurities
vertically to minimize bend and reduce the from entering the system, blocking the plate heat
resistance of water system. exchanger and water pump, damaging the system.
The filter is installed in the following mode: signal to make the unit shut down to protect
► Note the water flowing direction and filter direc- compressor, water pump and other important
tion during installation to ensure consistency. components.
► The bottom of target piece should exceed
► The sewage outlet of filter is downward for
convenience of sewage discharge and cleaning. 10%~20% of pipe center line. The target
piece shall not collide with the inner wall of
► The filter shall be installed in front of the equip- pipeline and other objects inside the pipeline.
ment that are sensitive to impurities, such as
water pump, pressure gage, plate type heat Other valves
exchanger, etc., so as to play the effect of Flow switch
filtering.
• Manage of water system
A A
It is very important for system operation and unit
‘s lifetime through clear and chemical treatment
the water system, various water system need use
different manage forms. Flow direction
Item Direct flow water system Opened recirculation system Closed recirculation system
- Surfactant
- Exhaust
- Enhance of acid
- surfactant
Scale - PH regulation
- PH regulation Need not control
control - Other problem: Surface
- Enhance of acid
temperature, water temperature,
- Soften
cleaning system, etc.
- Low concentration of corrosion - High concentration of corrosion
inhibitor inhibitor (200~500ppm) - High concentration of corrosion
Corrosion - Coating of calcium carbonate - Low concentration of corrosion inhibitor
control scale inhibitor (20~30ppm) - Suitable manufacturing
- PH regulation - PH regulation materials
- Suitable manufacturing materials - Suitable manufacturing materials
- Oxidation phenol - Oxidation phenol
Mud and algae - Others chemical medicament - Others chemical medicament
Need not control
control - The chlorine formation by chloric - The chlorine formation by chloric
acid root or liquid chlorine acid root or liquid chlorine
Table 9: Water pipe connection diagram
Legend
Stop valve Filter Floation ball Corrugated pipe Check valve
Differential pressure
Circulating pump P
Pressure guage Solenoid valve Thermometer bypass valve
Modular operation: due to the return water temperature sensor of the main module controls the start
and stop of all the units, so need to ensure the accuracy of the return water temperature sensor of the
main module.The main module of the water must be kept clear, or the main module of the return water
temperature sensor install In the blind tube that on the total water, and the blind tube filled need with
heat conduction silica gel, the bottom of blind pipe must exceed the center position of total water line.
• Single-unit operation
FCU
FCU
FCU
FCU
Expansio
Sewage outlet
FCU
Electrical
heater
P
Sewage outlet
Sewage outlet
• Modular operation
Expansio
Sewage outlet
FCU
FCU
FCU
FCU
P
FCU
FCU
P
Electrical
heater
Figure 24: Modular operation (Control room temperature by adjusting end air flow)
Expansio
Sewage outlet
FCU
Differential pressure bypass valve
FCU
FCU
FCU
P
FCU
FCU
P
Electrical
heater
Figure 25: Modular operation (Control room temperature by adjusting end water flow)
4 Equipment selection
the pipeline and loss of partial resistance. The loss
4.1 Selection of water pipe of resistance along the pipeline and loss of partial
resistance should be obtained through hydraulic
The water pipe of air cooled scroll chiller unit is
calculation. During calculation, take 5 m water
selected by ensuring the flow rate within the
column for the loss of partial resistance and about
range specified in the following table.
5 m water column per 100 m pipe for the loss of
Nominal dia- resistance along the pipeline. Given the length of
meter (mm) 15~2 0 25~40 50~70 ≥80
pipeline is L, the empirical formula is as below:
Water flow
rate (m/s) ≤1.0 ≤1.2 ≤1.5 ≤1.8 H=(5+Z+0.05L)×1.1 or 1.2
Figure 11: Flow velocity meter
4.3 Selection of electrical heater
Above table takes Code for Design of Building
A set of electrical assisted heater can be installed
Water Supply and Drainage for reference
as standby system according to engineering
By the formula:
needs: it can be started as standby system during
V=Q/S partial equipment maintenance and temporary
V - flow rate of water inside the pipe; equipment fault; meanwhile, it can also guarantee
Q - rated flow of unit; the quantity of heated water in the system to
S - section area of connecting water pipe; make up the unit capacity attenuation when the
The following table shows the specifications ambient temperature is very low.
recommended for PP-R pipe: The outdoor ambient environment in winter and
Quantity of units Inlet Outlet the capacity of standby system are mainly consid-
mains mains ered during selection of electrical assisted heater.
1 DN40 DN40 Find out the corresponding capacity value
Q1based on the local average temperature in
2 units in parallel DN50 DN50 winter, outlet water temperature of the unit and
3 units in parallel DN65 DN65 "relation curve of outdoor ambient temperature,
ASSH- outlet water temperature and unit capacity". Then
4~6 units in parallel DN80 DN80 compare it with the standard unit capacity value Q
035D3AE
7~9 units in parallel DN100 DN100 to reach the unit capacity attenuation value
Q2:Q2=Q-Q1.
10~14 units in parallel DN125 DN125
Capacity of common electrical assisted heater:
15~16 units in parallel DN150 DN150
W=a×Q2=a×(Q-Q1)
1 DN50 DN50
(Wherein, a refers to margin coefficient within limit
2~3 units in parallel DN80 DN80 of 1.0~1.5. a shall be larger in the northern area.)
ASSH-
4~5 units in parallel DN100 DN100 We generally recommend to install electrical
070D3AE
6~7 units in parallel DN125 DN125 assisted heater where the average temperature in
winter is below zero.
8~10 units in parallel DN150 DN150
1 DN80 DN80
4.4 Selection of expansion tank
Warning:
ASSH- 2 units in parallel DN100 DN100
Installation position of expansion tank
135D3AE 3~4 units in parallel DN125 DN125 must have 1.5m higher than the highest
of water pipe, and from the water pump
5~6 units in parallel DN150 DN150
inlet nearly as much as possible.
Figure 12: Specifications for recommended PP-R pipe Volume calculation of expansion tank:
Vp = α * Δt * Vs
4.2 Selection of water pump
Vp - Effective volume of expansion tank, m3.
The ordinary circulating pump is usually selected α - Volume expansion coefficient of water,
for the engineering. The lift H shall be 1.1~1.2 α = 0.0006/°C.
times the sum of height difference Z between Δt - Maximum temperature change, °C.
outlet and pipeline end, loss of resistance along Vs - System water content, m3.
5 Electrical control
• [MODE]: The key is used to operate the system
5.1 Description of Handset operating modes. When it is operated, the
Startup ON/OFF system operating modes can be switched
indicator button between cooling and heating.
• [SAVE MODE]: The key is used to operate the
system energy saving mode. When it is operat-
ed, the targeted return water temperature to
00/00/00 00:00:00 Fri cool and heat up system is 15°C and 37°C
Set mode:Cooling respectively.
Set temp.: 10°C
• [CHANGE]: The key is used to regulate setting
Sys error: --
parameters. Press [CORRECT] ▲ or ▼ to
increase or decrease during parameter setting.
Set Mode
The key can also be used to set the water-in
Save Check Select Change Enter ESC
temperature of system when the Handset is not
mode in the setting state.
• The system operating mode is generally select- • If several error occur on a module, the error
ed by pressing [MODE] key before startup, but with smaller code will be reported at first.
can also be switched during operating. After the
• If several modules have faults, the module with
mode is switched, the system will stop automat-
smaller address will be reported at first.
ically and then start to operate in the new
operating mode.
5.3 Setting interface
• In the main interface, the targeted water-in
temperature can be changed directly by press- ► Press [SET] to enter the setting interface. The
ing [CHANGE]. The setting range for cooling previous three items in the interface are com-
mode is 10~25°C and that for heating mode is monly used for the user, and the fourth one is
25~50°C. special setting item for professionals.
Set parameter
5.2 Initial interface
Figure 28: Setting interface
14/02/11 14:59:12 Tue
5.3.1 Time setting interface
Set mode: Cooling☆
► Press [CHANGE] to select the time setting item.
Set temp.: 25°C [Timer] Then the setting time is black in the reverse
type. Press [ENTER] to enter the time setting
Sys error: -- interface.
Mon Timer 1 Off: 01:00 Figure 30: Week timing setting interface
► Detailed operating process:
Mon Timer 2 On: 02:00
During time setting, press [CHANGE]
Mon Timer 2 Off: 03:00 ▲ or ▼ for one second and then time will
increase or decrease continuously.
Thu Timer 2 On: --:-- When the timing setting is valid, the
[Timer] icon will be displayed on the main
Thu Timer 2 Off: --:-- interface of Handset.
Figure 31: Timing setting interface of cycle timing Comp Status: 0000
C Coil-out: 25°C
D Coil-out: 25°C
Abnormal
galvanized Loose galvanized plate Fasten the galvanized plate
plate sound
• Non-fault phenomena:
Fault type Phenomena Cause
Continuous hiss during cooling The sound of gaseous refrigerant flowing in the unit
Noise of air-
Hiss during startup and shutdown The sound of gaseous refrigerant flow stop
condition
Continuous slight hiss during and after operation The sound of drainage system operating
10 Packing list
Packing List
CTN: 1