www.siemens.

com/protection

SIPROTEC 5 Application Note


SIP5-APN-008:
Enhanced IEC 61850 GOOSE features in SIPROTEC 5 devices

Answers for infrastructure and cities.


SIPROTEC 5 Application
Enhanced IEC 61850 GOOSE features in SIPROTEC 5 devices

SIPROTEC 5 - Application:
SIP5-APN-008
Enhanced IEC 61850 GOOSE features in
SIPROTEC 5 devices

Content

1 Enhanced IEC 61850 GOOSE features in SIPROTEC 5 devices 3


1.1 Summary 3
1.2 Application Introduction 3
1.2.1 Flexible GOOSE engineering via the GOOSE Editor 4
1.2.2 Advanced testing features 7
1.2.3 Diagnostics feature 11
1.3 Conclusion 11

SIP5-APN-008 2
SIPROTEC 5 Application
Enhanced IEC 61850 GOOSE features in SIPROTEC 5 devices

1 Enhanced IEC 61850 GOOSE features in SIPROTEC


5 devices
1.1 Summary
This application describes enhanced IEC61850 GOOSE features available in SIPROTEC5 devices together with
DIGSI 5. It intends to make Siemens users aware about new engineering and testing possibilities of their
GOOSE configurations in order to use new GOOSE functionalities and speed up the project delivery with the
highest project quality.

1.2 Application Introduction


GOOSE communication has been used successfully in the past years in a lot of different applications.
SIPROTEC 5 devices with IEC61850 provide you not only the same GOOSE possibilities than SIPROTEC 4
devices, but also offer you additionally new features, especially helpful for testing or interoperability.

Following GOOSE applications have been field proven in the past years:
ƒ Busbar protection schemes with overcurrent (reverse interlocking)
ƒ Substation Interlocking
ƒ Intertripping
ƒ Load shedding
ƒ …
Besides being conform to IEC 61850 Ed1 and Ed2 and therefore interoperable with other IEDs (including
SIPROTEC 4 devices), SIPROTEC 5 devices together with DIGSI 5 offer following new features:
ƒ Flexible GOOSE engineering via the GOOSE Editor
ƒ Advanced testing features via the support of more quality bits
ƒ Diagnostics

3 SIP5-APN-008
SIPROTEC 5 Application
Enhanced IEC 61850 GOOSE features in SIPROTEC 5 devices

1.2.1 Flexible GOOSE engineering via the GOOSE Editor


Integrated IEC61850 System Configurator
No need to jump anymore from an IED tool to a separated System Configurator. Intuitive engineering in few
steps.

Figure 1: DIGSI 5 – Integrated GOOSE Editor


Use of different communication modules.
For users who want to separate physically the GOOSE communication or run different communication
protocols (GOOSE; MMS, DNP 3 TCP), SIPROTEC 5 support several communication modules. One module
could be used e.g. exclusively for GOOSE.
During your GOOSE engineering you have the possibility to send the GOOSE in any of those subnets.

SIP5-APN-008 4
SIPROTEC 5 Application
Enhanced IEC 61850 GOOSE features in SIPROTEC 5 devices

Highest flexibility at GOOSE publisher


As used in DIGSI 4, GOOSE applications remain fully configurable.
GOOSE Datasets can be now assigned to any LLN0 of the IEC61850 structure.
Any Data Attributes (including. stSeld, t) can be published if required by IED subscribers (for example if
timestamp needed)
Information can even be send as complete Data Objects at the Functional Constraint level (ST or MX).

Figure 2: DIGSI 5 and SIPROTEC 5 – High flexibility for configuration of GOOSE Data Attributes

2-in-one: Edition 1 or Edition 2


SIPROTEC 5 devices can be configured in Edition 1 mode in case of extensions of existing IEC61850
substations, or support by default Edition 2.
The use of LDname provides you further engineering flexibility and makes a step forward to the concept of
interchangeability.

5 SIP5-APN-008
SIPROTEC 5 Application
Enhanced IEC 61850 GOOSE features in SIPROTEC 5 devices

Automatic creation of signals on subscriber side


No need to create external signals or use virtual outputs anymore, advanced GOOSE engineering according
IEC 61850-6 is now available via drag&drop of a Logical Node to the published signal.

Figure 3: DIGSI 5 with full support of IEC 61850-6 for GOOSE subscription

Bandwidth estimator
In an IEC61850 system, GOOSE messages cause most of the communication traffic. DIGSI 5 provides an
indicator monitoring the expected GOOSE bandwidth depending on what is configured. This makes the user
easily aware of the situation to let him decide if configuration optimization or network segregation as defined
in IEC 61850-90-4 should be used.

Figure 4: DIGSI 5 - Bandwidth estimation of GOOSE messages

SIP5-APN-008 6
SIPROTEC 5 Application
Enhanced IEC 61850 GOOSE features in SIPROTEC 5 devices

SED – export and import for intersubstation GOOSE


IEC 61850-90-1 communication goes beyond the substation communication by supporting substation to
substation communication. SCL files - called Substation Exchange Descriptions (SED) support the exchange of
GOOSE – messages between substations.

Figure 5: Support of Edition 2 SCL files for easy GOOSE exchange via SED

1.2.2 Advanced testing features

Several modes of operation


Additionally to the default standard process mode, DIGSI 5 allows you online to switch the IED to a mode
which supports enhanced testing (commissioning mode and simulation mode).

Figure 6: DIGSI 5 online – choice of operating mode for the device


In commissioning mode, values can be forced to all their states, which make a point-to-point test of signals at
communication level easily possible without interacting with the process values.

7 SIP5-APN-008
SIPROTEC 5 Application
Enhanced IEC 61850 GOOSE features in SIPROTEC 5 devices

Figure 7: Commissioning mode for point to point communication test


The simulation mode allows you to test real conditions without changing the process values neither binary
inputs nor analog measurements. The values are generated by the simulation unit which simulates analogue
input value and binary input values. Also CFC input signals can be simulated.

Figure 8: Simulation mode for sequence testing during maintenance

SIP5-APN-008 8
SIPROTEC 5 Application
Enhanced IEC 61850 GOOSE features in SIPROTEC 5 devices

Functional Logout
Before going to maintenance, a SIPROTEC 5 can be set in functional logout state via binary input to alert its
neighbours.

Figure 9: Activation of the Functional Logout state via binary input

GOOSE messages are then send with the quality bit operator Blocked. IED subscribers – which are alerted –
can process the quality bits accordingly.

9 SIP5-APN-008
SIPROTEC 5 Application
Enhanced IEC 61850 GOOSE features in SIPROTEC 5 devices

Quality processing for GOOSE subscriber


SIPROTEC 5 provides an advanced testing feature to allow the use to substitute values when the signal quality
at GOOSE subscriber is invalid or operator blocked.

Figure 10: Setting of substitution values for Quality ´Invalid or ´Operator blocked´

SIP5-APN-008 10
SIPROTEC 5 Application
Enhanced IEC 61850 GOOSE features in SIPROTEC 5 devices

1.2.3 Diagnostics feature


GOOSE Monitoring
GOOSE Inspector provides you not only with SIPROTEC 4 but also with SIPROTEC 5 the analysis about the
GOOSE traffic based on the SCL files. Actually it will decode Ed1 GOOSE messages. A further version will
support the monitoring of Ed. 2 of IEC 61850 GOOSE – messages.
Simple Network Monitoring Protocol
DIGSI 5 allows you to activate SNMPv3 in SIPROTEC5 relays for an optimal network monitoring with a secure
standard.
Used with Netview, you can easily monitor over SNMP the relevant SIPROTEC 5settings (e.g. RSTP or GOOSE
mismatch). Additionally, firmware version, product code or fabrication number is available to support you
while doing your asset management.

Figure 11: Monitoring of SIPROTEC 5 devices with Netview over SNMP V3 protocol

1.3 Conclusion
Advanced features in SIPROTEC 5 and DIGSI 5 support users efficiently with the GOOSE handling over the
lifecycle of the system from the GOOSE communication possibilities and engineering to the testing.

11 SIP5-APN-008
SIPROTEC 5 Application
Fehler! Verweisquelle konnte nicht gefunden werden.
Published by and copyright © 2013:

Siemens AG

Infrastructure & Cities Sector

Smart Grid Division

Humboldtstr. 59

90459 Nuremberg, Germany

Siemens AG

Infrastructure & Cities Sector

Smart Grid Division

Energy Automation

Humboldtstr. 59

90459 Nuremberg, Germany

www.siemens.com/protection

Printed on elementary chlorine-free bleached paper.

All rights reserved.

If not stated otherwise on the individual pages of this catalog, we reserve


the right to include modifications, especially regarding the stated values,
dimensions and weights. Drawings are not binding.

All product designations used are trademarks or product names of Siemens


AG or other suppliers.
If not stated otherwise, all dimensions in this catalog are given in mm.

Subject to change without prior notice.


The information in this document contains general descriptions of the
technical options available, which may not apply in all cases. The required
technical options should therefore be specified in the contract.

For more information, please contact Application note: SIP5-APN-008


our Customer Support Center.
Tel.: +49 180 524 8437
Fax: +49 180 524 24 71
(Charges depending on provider)
E-mail: [email protected]