Ee6401 Electrical Machines I
Ee6401 Electrical Machines I
ENGINEERING COLLEGE
(Approved by AICTE and Affiliated to Anna University Chennai)
TRICHY – PUDUKKOTTAI ROAD, TIRUCHIRAPPALLI – 620 007
COURSE MATERIAL
II YEAR - IV SEMESTER
EE6401 ELECTRICAL MACHINES I
AIM
To expose the students to the basic principles of Electro mechanical Energy
Conversion in Electrical Apparatus and the operation of Transformers and DC Machines.
OBJECTIVES:
To introduce techniques of magnetic-circuit analysis and introduce magnetic
materials
To familiarize the constructional details, the principle of operation, prediction of
performance, the methods of testing the transformers and three phase transformer
connections.
To study the working principles of electrical machines using the concepts of
electromechanical energy conversion principles and derive expressions for
generated voltage and torque developed in all Electrical Machines.
To study the working principles of DC machines as Generator types,
determination of their no load / load characteristics, starting and methods of speed
control of motors.
To estimate the various losses taking place in D.C. Motor and to study the
different testing methods to arrive at their performance.
UNIT I MAGNETIC CIRCUITS AND MAGNETIC MATERIALS
Magnetic circuits –Laws governing magnetic circuits - Flux linkage, Inductance
and energy – Statically and Dynamically induced EMF - Torque – Properties of magnetic
materials, Hysterisis and Eddy Current losses - AC excitation, introduction to permanent
magnets-Transformer as a magnetically coupled circuit..
UNIT II TRANSFORMERS 9
Construction – principle of operation – equivalent circuit parameters – phasor
diagrams, losses – testing – efficiency and voltage regulation-all day efficiency-Sumpner’s
test, per unit representation – inrush current - three phase transformers-connections – Scott
Connection – Phasing of transformer– parallel operation of three phase transformers-auto
transformer – tap changing transformers- tertiary Winding
UNIT III ELECTROMECHANICAL ENERGY CONVERSION AND CONCEPTS IN
ROTATING MACHINES
Energy in magnetic systems – field energy, co energy and mechanical force –
singly and multiply excited systems. Energy in magnetic system – Field energy and coenergy
-force and torque equations – singly and multiply excited magnetic field systems-mmf of
distributed windings – Winding Inductances-, magnetic fields in rotating machines – rotating
mmf waves – magnetic saturation and leakage fluxes.
UNIT IV DC GENERATORS
Construction and components of DC Machine – Principle of operation - Lap and
wave windings-EMF equations– circuit model – armature reaction –methods of excitation-
commutation and inter poles - compensating winding –characteristics of DC generators.
UNIT V DC MOTORS 9
Principle and operations - types of DC Motors – Speed Torque Characteristics of
DC Motors-starting and speed control of DC motors –Plugging, dynamic and regenerative
braking- testing and efficiency – Retardation test- Swinburne’s test and Hopkinson’s test -
Permanent magnet dc motors(PMDC)-DC Motor applications
TEXT BOOKS
1. Nagrath I. J and Kothari D. P. ‘Electric Machines’, Tata McGraw Hill Publishing
Company Ltd,1990.
2. P.S. Bimbhra, ‘Electrical Machinery’, Khanna Publishers, 2003.
REFERENCES
1. Fitzgerald.A.E., Charles KingselyJr, Stephen D.Umans, ‘Electric Machinery’,
McGraw Hill BooksCompany, 1992.
2. P. C. Sen., ‘Principles of Electrical Machines and Power Electronics’, John
Wiley&Sons, 1997.
3. K. Murugesh Kumar, ‘Electric Machines’, Vikas publishing house Pvt Ltd, 2002.
CHAPTER- 1
MAGNETIC CIRCUITS AND MAGNETIC MATERIALS
1.1 Introduction
The law of conservation of energy states that the energy cannot be related or
destroyed but it can be converted from one form to other. An electrical energy does not occur
naturally and also cannot be stored. Hence the efforts are made to generate it continuously to
meet the large demands. But to generate an electrical energy means to convert some other
form of energy into an electrical form, according to law of conservation of energy. A
commonly used method to generate an electrical energy is converting mechanical energy into
electrical with the help of a rotating device. Such a machine which converts the mechanical
energy into an electrical energy is called a generator. The input mechanical energy can be
achieved from steam turbines, steam engines or using potential energy of water to run
hydraulic turbines. Such a device which inputs a mechanical energy to a generator is called a
prime mover. While converting energy from mechanical to electrical form, some losses take
place. The losses are kept to minimum value by properly designing the machine. Practically
the efficiencies of large generators are above 90 %
Ampere’s law
c Bc Ac c: flux in core,
Bc : flux density in the core
Ac : cross-sectional area of the core.
B
c
H. dl Hl c c
lNi
c
F lF
c
A
C c
F lc : reluctance
Ac
l g
c c g c A
C 0 Ac 0 g
F
F ( c g )
c g
Permanent Magnet
Permanent magnet means, the magnetic materials which will retain the magnetic
property at a] l times permanently. This type of magnets is manufactured by aluminum,
nickel, iron, cobalt steel (ALNICO).
To make a permanent magnet a coil is wound over a magnetic material and DC supply is
passed through the coil.
Electro Magnet
Insulated wire wound on a bobbin in many turns and layers in which current is
flowing and a soft iron piece placed in the bobbin is called electromagnet.
Figure 1.2
This is used in all electrical machines, transformers, electric bells. It is also used in a
machine used by doctors to pull out iron filing from eyes, etc.
H=
Where,
Φ - total flux
N - number of turns
I - current in amperes
S - reluctance
µ - permeability of free space
µ0 - relative permeability
a - magnetic path cross-sectional area in m2
l - lengh of magnetic path in metres
1.3 Laws Governing Magnetic Circuits
1.3.1. Magnetic flux:
1.3.3.Flux density
The total number of lines of force per square metre of the cross-sectional area of the
magnetic core is called flux density, and is represented by the symbol B. Its SI unit (in the
MKS system) is testa (weber per metre square).
B=
where
φ-total flux in webers
A - area of the core in square metres
S=
Where, S - reluctance
I - length of the magnetic path in meters
o- permeability of free space µ r - relative permeability
a - cross-sectional area
1.3.6. Residual Magnetism
It is the magnetism which remains in a material when the effective magnetizing force
has been reduced to zero.
1.3.7. Magnetic Saturation
The limit beyond which the strength of a magnet cannot be increased is called
magnetic saturation.
When an emf is induced in a circuit electromagnetically the current set up always opposes
the motion or change in current which produces it.
There are two laws of Faraday's laws of electromagnetic induction. They are,
First Law
Whenever a conductor cuts the magnetic flux lines an emf is induced in the conductor.
Second Law
The magnitude of the induced emf is equal to the rate of change of flux-linkages.
This rule is used to find out the direction of dynamically induced emf. According to the
rule hold out the right hand with the Index finger middle finger and thumb at the right angels
to each others. If the index finger represents the direction of the lines of flux, the thumb
points in the direction of motion then middle finger points in the direction of induced current.
A coil wound on a magnetic core, is used frequently used in electric circuits. The coil
may be representsd by an ideal circuit element called inductance which is defined as the flux
linkage of the coil per ampere of its circuit
Uses:
Flux density with “V” velocity, then the dynamically induced emf is induced in the
conductor. This induced emf is utilized in the generator. The quantity of the emf can be
calculated using the equation
emf= Blv volt
Ph=B16maxfV watts
where Bmax = Maximum flux density in armature f =
Frequency of magnetic reversals
V = Volume of armature in m3
h = Steinmetz hysteresis co-efficient
The coil carries an alternating current i varying sinusoidally. Thus the flux produced by
the exciting current I is also sinusoidally varying with time.
According to Faraday’s law as flux changes with respect to coli, the e.m.f gets induced in the
coil given by,
e= N =N
Em = Maximum value = N
E= r.m.s value = =
E= = 4.44 fN
But = Ac Bm
The sign of e.m.f induced must be determined according to len’s law, opposing the
changes in the flux. The current and flux are in phase as current produces flux
instantaneously. Now induced e.m.f is cosine term and thus leads the flux and current
by .this is called back e.m.f as it opposes the applied voltage. The resistance drops is very
small and is neglecte3d in most of the electromagnetic devices
Total flux = ɸ 1 + ɸ 21
Assume that the core is of infinite permeability ( ) and neglect the effects of fringing fields at
the air gap and leakage flux. (a) Calculate the reluctance of the core
R and that of the gap Rg . For a current of i = 1.5 A, calculate (b) the total flux , (c)
c
the flux linkages λ of the coil, and (d) the coil inductance L.
Solution:
g 2.3 10 3 6
R 1.017 10 A/Wb
R 0 since g A4 10 7 1.8 10 3
c 0 c
Ni 83 1.5
R R 1.017 106 1.224 10 4 Wb
c g
N 1.016 10 2 Wb
1.016 10 2
L 6.773 mH
i 1.5
Eg .No.2
Consider the magnetic circuit of with the dimensions of Problem 1.1. Assuming infinite core
permeability, calculate (a) the number of turns required to achieve an inductance of 12 mH
and (b) the inductor current which will result in a core flux density of 1.0 T.
Solution:
N2
L 12 10 3 mH N12 10 3 1.017 106 110.47 N 110 turns
Rg
B B 1.0 T B A 1.8 10 3 Wb
c g g c
N 110 1.8 10 3
i 16.5 A
L L 12 10 3
Eg .No.3
A square voltage wave having a fundamental frequency of 60 Hz and equal positive and
negative half cycles of amplitude E is applied to a 1000-turn winding surrounding a closed
iron core of 1.25 x 10-3m2 cross section. Neglect both the winding resistance and any effects
of leakage flux.
(a) Sketch the voltage, the winding flux linkage, and the core flux as a function
of time.
(b) Find the maximum permissible value of E if the maximum flux density is not to
exceed 1.15 T.
e voltage
T
E
max Φ
max
E
( )
d e( t ).dt E max max
4f 4 fN max 4 fNAc Bmax
e(t) max
dt T/2
E 4 60 1000 1.25 10 3 1.15 345 V
Eg.No.4
EE2251 ELECTRICAL MACHINES I
Eg.no.5
CHAPTER- 2
TRANSFORMER
2.1 Principle Of Operation
A transformer is a device that transfers electrical energy from one circuit to another
through inductively coupled conductor. A varying current in the first or primary winding
creates a varying magnetic flux in the transformer core, and thus a varying magnetic field
through the secondary winding. This varying magnetic field induces a varying electromotive
force EMF or voltage in the secondary winding. This effect is called mutual induction.
If a load is connected to the secondary, an electric current will flow in the secondary
winding and electrical energy will be transferred from the primary circuit through the
transformer to the load. In an ideal transformer, the induced voltage in the secondary winding
is in proportion to the primary voltage , and is given by the ratio of the number of turns in the
secondary to the number of turns in the primary as follows:
By appropriate selection of the ratio of turns, a transformer thus allows an alternating
current (AC) voltage to be "stepped up" by making greater than , or "stepped down" by
making less than .
2.1.1 Basic Principle
Construction
Distribution transformers can achieve low no-load losses by using cores made with low-loss
high-permeability silicon steel or amorphous (non-crystalline) metal alloy. The higher initial
cost of the core material is offset over the life of the transformer by its lower losses at light
load.
Solid cores
Powdered iron cores are used in circuits such as switch-mode power supplies that
operate above mains frequencies and up to a few tens of kilohertz. These materials
combine high magneticpermeancehigh bulk electrical resistivity. For frequencies
extending beyondthe VHFband, cores madefrom non-conductive
magnetic ceramic materials called ferrites are common. Some radio-frequency
transformers also have movable cores (sometimes called 'slugs') which allow adjustment of
the coupling coefficient (and bandwidth) of tuned radio-frequency circuits.
Toroidal cores
Ferrite toroidal cores are used at higher frequencies, typically between a few tens of
kilohertz to hundreds of megahertz, to reduce losses, physical size, and weight of a switched-
mode power supply. A drawback of toroidal transformer construction is the higher labor cost
of winding. This is because it is necessary to pass the entire length of a coil winding through
the core aperture each time a single turn is added to the coil. As a consequence, toroidal
transformers are uncommon above ratings of a few kVA. Small distribution transformers may
achieve some of the benefits of a toroidal core by splitting it and forcing it open, then
inserting a bobbin containing primary and secondary windings.
Air cores
A physical core is not an absolute requisite and a functioning transformer can be
produced simply by placing the windings near each other, an arrangement termed an "air-
core" transformer. The air which comprises the magnetic circuit is essentially lossless, and so
an air-core transformer eliminates loss due to hysteresis in the core material.[41] The leakage
inductance is inevitably high, resulting in very poor regulation, and so such designs are
unsuitable for use in power distribution. They have
however very high bandwidth, and are frequently employed in radio-frequency applications,
for which a satisfactory coupling coefficient is maintained by carefully overlapping the
primary and secondary windings. They're also used for resonant transformers such as Tesla
coils where they can achieve reasonably low loss in spite of the high leakage inductance.
Windings
Figure 2.4 Windings are usually arranged concentrically to minimize flux leakage.
The conducting material used for the windings depends upon the application, but in
all cases the individual turns must be electrically insulated from each other to ensure that the
current travels throughout every turn.For small power and signal transformers, in which
currents are low and the potential difference between adjacent turns are there.
Cooling
Though it is not uncommon for oil-filled transformers to have today been in operation
for over fifty years high temperature damages winding insulation, the accepted rule of thumb
being that transformer life expectancy is halved for every 8 degree C increase in operating
temperature. At the lower end of the power rating range, dry and liquid-immersed
transformers are often self-cooled by natural convection and radiation heat dissipation. As
power ratings increase, transformers are often cooled by such other means as forced-air
cooling, force-oil cooling, water-cooling, or a combinations of these. The dialectic coolant
used in many outdoor utility and industrial service transformers is transformer oil that both
cools and insulates the windings. Transformer oil is a highly refined mineral oil that
inherently helps thermally stabilize winding conductor insulation, typically paper, within
acceptable insulation temperature rating limitations. However, the heat removal problem is
central to all electrical apparatus such that in the case of high value transformer assets, this
often translates in a need to monitor, model, forecast and manage oil and winding conductor
insulation temperature conditions under varying, possibly difficult, power loading conditions.
Indoor liquid-filled transformers are required by building regulations in many jurisdictions to
either use a non-flammable liquid or to be located in fire-resistant rooms. Air-cooled dry
transformers are preferred for indoor applications even at capacity ratings where oil-cooled
construction would be more economical, because their cost is offset by the reduced building
construction cost.
The oil-filled tank often has radiators through which the oil circulates by natural
convection. Some large transformers employ electric-operated fans or pumps for forced-air or
forced-oil cooling or heat exchanger-based water-cooling. Oil-filled transformers undergo
prolonged drying processes to ensure that the transformer is completely free of water before
the cooling oil is introduced. This helps prevent electrical breakdown under load. Oil-filled
transformers may be equipped with Buchholz relays, which detect gas evolved during
internal arcing and rapidly de-energize the transformer to avert catastrophic failure. Oil-filled
transformers may fail, rupture, and burn, causing power outages and losses. Installations of
oil-filled transformers usually include fire protection measures such as walls, oil containment,
and fire-suppression sprinkler systems.
Insulation drying
Construction of oil-filled transformers requires that the insulation covering the
windings be thoroughly dried before the oil is introduced. There are several different methods
of drying. Common for all is that they are carried out in vacuum environment. The vacuum
makes it difficult to transfer energy (heat) to the insulation. For this there are several different
methods. The traditional drying is done by circulating hot air over the active part and cycle
this with periods of hot-air vacuum (HAV) drying. More common for larger transformers is
to use evaporated solvent which condenses on the colder active part. The benefit is that the
entire process can be carried out at lower pressure and without influence of added oxygen.
This process is commonly called vapor-phase drying (VPD).
For distribution transformers, which are smaller and have a smaller insulation weight,
resistance heating can be used. This is a method where current is injected in the windings to
heat the insulation. The benefit is that the heating can be controlled
very well and it is energy efficient. The method is called low-frequency heating (LFH) since
the current is injected at a much lower frequency than the nominal of the grid, which is
normally 50 or 60 Hz. A lower frequency reduces the effect of the inductance in the
transformer, so the voltage needed to induce the current can be reduced. The LFH drying
method is also used for service of older transformers.
Terminals
Very small transformers will have wire leads connected directly to the ends of the
coils, and brought out to the base of the unit for circuit connections. Larger transformers may
have heavy bolted terminals, bus bars or high-voltage insulated bushings made of polymers
or porcelain. A large bushing can be a complex structure since it must provide careful control
of the electric field gradient without letting the transformer leak oil.
An ideal transformer is shown in the adjacent figure. Current passing through the
primary coil creates a magnetic field. The primary and secondary coils are wrapped around a
core of very high magnetic, such as iron, so that most of the magnetic flux passes through
both the primary and secondary coils. If a load is connected to the secondary winding, the
load current and voltage will be in the directions indicated, given the primary current and
voltage in the directions indicated (each will be alternating current in practice).
Taking the ratio of the two equations for Vs and Vp gives the basic equation for stepping up or
stepping down the voltage
Np/Ns is known as the turns ratio, and is the primary functional characteristic of any
transformer. In the case of step-up transformers, this may sometimes be stated as the
reciprocal, Ns/Np. Turns ratio is commonly expressed as an irreducible fraction or ratio: for
example, a transformer with primary and secondary windings of, respectively, 100 and 150
turns is said to have a turns ratio of 2:3 rather than 0.667 or 100:150.
An elementary transformer consists of a soft iron or silicon steel core and two
windings, placed on it. The windings are insulated from both the core and each other. The
core is built up of thin soft iron or low reluctance to the magnetic flux. The winding
connected to the magnetic flux. The winding connected to the supply main is called the
primary and the winding connected to the load circuit is called the secondary.
Although in the actual construction the two windings are usually wound one over the
other, for the sake of simplicity, the figures for analyzing transformer theory show the
windings on opposite sides of the core, as shown below Simple Transformer .
When primary winding is connected to an ac supply mains, current flows through it.
Since this winding links with an iron core, so current flowing through this winding produces
an alternating flux in the core. Since this flux is alternating and links with the secondary
winding also, so induces an emf in the secondary winding.
The frequency of induced emf in secondary winding is the same as that of the flux or
that of the s supply voltage. The induced emf in the secondary winding enables it to deliver
current to an external load connected across it. Thus the energy is transformed from primary
winding to the secondary winding by means of electro-magnetic induction without anychange
in frequency. The flux of the iron core links not only with the secondary winding but also
with the primary winding, so produces self-induced emf in the primary winding:
This induced in the primary winding opposes the applied voltage and therefore
sometimes it is known as back emf of the primary. In fact the induced emf in the primary
winding limits the primary current in much the same way that the back emf in a dc motor
limits the armature current.
Transformation ratio.
The ratio of secondary voltage to primary voltage is known as the voltage
transformation ratio and is designated by letter K. i.e. Voltage transformation ratio.
Current ratio.
The ratio of secondary current to primary current is known as current ratio and is
reciprocal of voltage transformation ratio in an ideal transformer.
2.2 Equivalent Circuit
The electrical circuit for any electrical engineering device can be drawn if
theequations describing its behavior are known. The equivalent circuit for
electromagneticdevice is a combination of resistances, inductances, capacitances, voltages
etc. In theequivalent circuit, (R1+jX1) and (R2+jX2) are the leakage impedances of the
primary andsecondary windings respectively. The primary current I1 consists of two
components.One component, I1´ is the load component and the second is no-load current Io
which iscomposed of Ic and Im. The current Ic is in phase with E1 and the product of these
twogives core loss. Ro represents the core loss and is called core-loss resistance. The
currentIm is represented by a reactance Xo and is called magnetizing reactance. The
transformermagnetization curve is assumed linear, since the effect of higher order harmonics
can’t berepresented in the equivalent circuit. In transformer analysis, it is usual to transfer
thesecondary quantities to primary side or primary quantities to secondary side.
Figure 2.8 Equivalent Circuit
The iron losses contain two components - Hysteresis loss and Eddy current loss. The
Hysteresis loss is a function of the material used for the core.Ph = KhB1.6f For constant
voltage and constant frequency operation this can be taken to be constant. The eddy current
loss in the core arises because of the induced emf in the steel lamination sheets and the eddies
of current formed due to it. This again producesa power loss Pe in the lamination.wheret is
the thickness of the steel lamination used. As the lamination thickness is much smaller than
the depth of penetration of the field, the eddy current loss can be reduced by reducing the
thickness of the lamination. Present day laminations are of 0.25 mm thickness and are capable
of operation at 2 Tesla.
These reduce the eddy current losses in the core.This loss also remains constant due to
constant voltage and frequency of operation. The sum of hysteresis and eddy current losses
can be obtained by the open circuit test.The dielectric losses take place in the insulation of the
transformer due to the large electric stress. In the case of low voltage transformers this can be
neglected. For constant voltage operation this can be assumed to be a constant. The stray load
losses arise out of the leakage fluxes of the transformer. These leakage fluxes link the
metallic structural parts, tank etc. and produce eddy current losses in them. Thus they take
place ’all round’ the transformer instead of a definite place , hence the name ’stray’. Also the
leakage flux is directly proportional to the load current unlike the mutual flux which is
proportional to the applied voltage. Hence this loss is called ’stray load’ loss.This can also be
estimated experimentally.
It can be modeled by another resistance in the series branch in the equivalent circuit.
The stray load losses are very low in air-cored transformers due to the absence of the metallic
tank. Thus, the different losses fall in to two categories Constant losses (mainly voltage
dependant) and Variable losses (current dependant). The expression for the efficiency of the
transformer operating at a fractional load x of its rating, at a load power factor of 2, can be
written as losses and Pvar the variable losses at full load.For a given power factor an
expression for in terms of the variable x is thus obtained.Bydifferentiating with respect to x
and equating the same to zero, the condition formaximum efficiency is obtained. The
maximum efficiency it can be easily deduced that thismaximum value increases with increase
in power factor and is zero at zero power factor of the load. It may be considered a good
practice to select the operating load point to be at the maximum efficiency point. Thus if a
transformer is on
Figure2.9
Transformer on No
Load
Im is used to create the flux
in the core and Ie is used to
Transformer on Load
The transformer is said to be loaded, when its secondary circuit is completed through
an impedance or load. The magnitude and phase of secondary current (i.e. current flowing
through secondary) with respect to secondary terminals depends upon the characteristic of the
load i.e. current will be in phase, lag behind and lead the terminal voltage respectively when
the load is non-inductive, inductive and capacitive. The net flux passing through the core
remains almost constant from no-load to full load irrespective of load conditions and so core
losses remain almost constant from no-load to full load.
Secondary windings Resistance and Leakage Reactance In actual practice, both of the
primary and have got some ohmic resistance causing voltage drops and copper losses in the
windings. In actual practice, the total flux created does not link both of the primary and
secondary windings but is divided into three components namely the main or mutual flux
linking both of the primary and secondary windings, primary leakage flux linking with
primary winding only and secondary leakage flux linking with secondary winding only.
i.e. E = 2fπ
The applied voltage to the primary, say Vs’ is gradually increased till the ammeter A
indicates the full load current of the side in which it is connected. The reading Ws of the
wattmeter gives total copper loss (iron losses being negligible due to very low applied voltage
resulting in very small flux linking with the core) at full load. Le the ammeter reading be Is.
These aspects are briefly mentioned under section load test.The losses that take place
inside the machine expressed as a fraction of the input is sometimes termed as deficiency.
Except in the case of an ideal machine, a certain fraction of the input power gets lost inside
the machine while handling the power. Thus the value for the efficiency is always less than
one. In the case of a.c. machines the rating is expressed in terms of apparent power. It is
nothing but the product of the applied voltage and the current drawn. The actual power
delivered is a function of the power factor at which this current is drawn.
As the reactive power shuttles between the source and the load and has a zero average
value over a cycle of the supply wave it does not have any direct effect on the efficiency. The
reactive power however increases the current handled by the machine and the losses resulting
from it. Therefore the losses that take place inside a transformer at any given load play a vital
role in determining the efficiency. The losses taking place inside a transformer can be
enumerated as below:
1. Primary copper loss
2. Secondary copper loss
3. Iron loss
4. Dielectric loss
5. Stray load loss
These are explained in sequence below.
Primary and secondary copper losses take place in the respective winding resistancesdue to
the flow of the current in them. The primary and secondary resistances differ from their d.c.
values due to skin effect and the temperature rise of the windings. While the average
temperature rise can be approximately used, the skin effect is harder to get analytically. The
short circuit test gives the value of Re taking into account the skin effect.The iron losses
contain two components Hysteresis loss and Eddy current loss. The Hysteresis loss is a
function of the material used for the core.Ph = KhB1.6f For constant voltage and constant
frequency operation this can be taken to be constant. The eddy current loss in the core arises
because of the induced emf in the steel lamination sheets and the eddies of current formed
due to it. This again producesa power loss Pe in the lamination. Where t is the thickness of
the steel lamination used. As the lamination thickness is much smaller than the depth of
penetration of the field, the eddy current loss can be reduced by reducing the thickness of the
lamination. Present day laminations are of 0.25 mm thickness and are capable of operation at
2 Tesla.
These reduce the eddy current losses in the core.This loss also remains constant due to
constant voltage and frequency of operation. The sum of hysteresis and eddy current losses
can be obtained by the open circuit test.The dielectric losses take place in the insulation of the
transformer due to the large electric stress. In the case of low voltage transformers this can be
neglected. For constant voltage operation this can be assumed to be a constant. The stray load
losses arise out of the leakage fluxes of the transformer. These leakage fluxes link the
metallic structural parts, tank etc. and produce eddy current losses in them. Thus they take
place ’all round’ the transformer instead of a definite place, hence the name ’stray’. Also the
leakage flux is directly proportional to the load current unlike the mutual flux which is
proportional to the applied voltage.
Hence this loss is called ’stray load’ loss.This can also be estimated experimentally. It
can be modeled by another resistance in the series branch in the equivalent circuit. The stray
load losses are very low in air-cored transformers due to the absence of the metallic tank.
Thus, the different losses fall in to two categories Constant losses (mainly voltage dependant)
and Variable losses (current dependant). The expression for the efficiency of the transformer
operating at a fractional load x of its rating, at a load power factor of 2 can be written as
losses and Pvar the variable losses at full load. For a given power factor an expression for _
in terms of the variable x is thus obtained. By differentiating _ with respect to x and equating
the same to zero, the condition for maximum efficiency is obtained. The maximum efficiency
it can be easily deduced that this Maximum value increases with increase in power factor and
is zero at zero power factor of the load. It may be considered a good practice to select the
operating load point to be at the maximum efficiency point.
Thus if a transformer is on full load, for most part of the time then the max can be
made to occur at full load by proper selection of constant and variablelosses.However, in the
modern transformers the iron losses are so low that it is practically impossible to reduce the
full load copper losses to that value. Such a design wastes lot of copper. This point is
illustrated with the help of an example below. Two 100 kVA transformers A and B are taken.
Both transformers have total full load losses to be 2 kW. The breakup of this loss is chosen to
be different for the two transformers. Transformer A: iron loss 1 kW, and copper loss is 1
kW. The maximum efficiency of 98.04%occurs at full load at unity power factor.
Transformer B: Iron loss =0.3 kW and full load copper loss =1.7 kW. This also has a full load
of 98.04%. Its maximum occurs at a fractional load of q0.31.7 = 0.42. The maximum
efficiency at unity power factor being at the corresponding point the transformer A has an
efficiency of Transformer A uses iron of more loss per kg at a given flux density, but
transformer B uses lesser quantity of copper and works at higher current density.
% Efficiency = ×100
All day efficiency
Large capacity transformers used in power systems are classified broadly into Power
transformers and Distribution transformers. The former variety is seen in generating stations
and large substations. Distribution transformers are seen at the distribution substations. The
basic difference between the two types arises from the fact that the power transformers are
switched in or out of the circuit depending upon the load to be handled by them. Thus at 50%
load on the station only 50% of the transformers need to be connected in the circuit. On the
other hand a distribution transformer is never switched off. It has to remain in the circuit
irrespective of the load connected. In such cases the constant loss of the transformer
continues to be dissipated. Hence the concept of energy based efficiency is defined for such
transformers. It is called ’all day’ efficiency. The all day efficiency is thus the ratio of the
energy output of the transformer over a day to the corresponding energy input. One day is
taken as duration of time over which the load pattern repeats itself. This assumption,
however, is far from being true. The power output varies from zero to full load depending on
the requirement of the user and the load losses vary as the square of the fractional loads. The
no-load losses or constant losses occur throughout the 24 hours. Thus, the comparison of
loads on different days becomes difficult. Even the load factor, which is given by the ratio of
the average load to rated load, does not give satisfactory results. The calculation of the all day
efficiency is illustrated below with an example. The graph of load on the transformer,
expressed as a fraction of the full load is plotted against time. In an actual situation the load
on the transformer continuously changes. This has been presented by a stepped curve for
convenience. For the same load factor different average loss can be there depending upon the
values of xi and ti. Hence a better option would be to keep the constant losses very low to
keep the all day efficiency high. Variable losses are related to load and are associated with
revenue earned. The constant loss on the other hand has to be incurred to make the service
available. The concept of all day efficiency may therefore be more useful for comparing two
transformers subjected to the same load cycle. The concept of minimizing the lost energy
comes into effect right from the time of procurement of the transformer. The constant losses
and variable losses are capitalized and added to the material cost of the transformer in order
to select the most competitive one, which gives minimum cost taking initial cost and running
cost put together. Obviously the iron losses are capitalized more in the process to give an
effect to the maximization of energy efficiency. If the load cycle is known at this stage, it can
also be incorporated in computation of the best transformer.
2.6.2 Procedure:
• Connect the circuit diagram as shown in fig (a)
• Apply full load and note down the readings of wattmeter, voltmeter and ammeter.
2.6.4 Calculation
= V2 I2 / Wi * 100
% Reg = E – V * 100 / V
2.6.5 Discussion
By calculating the voltage regulation the figure of merit which determines the
voltage characteristics of a transformer can be determined. Also the transformer efficiency
can’t be determined with high precision since the losses are of order of only 1 to 4%. The
best and accurate method of determining the efficiency of a transformer would be to compute
losses from open circuit and short circuit test and then determine the efficiency.
V1 : V2 = T1 : T2 (76)
For simplifying analysis, the magnetizing current of the transformer is neglected. When the
secondary winding delivers a load current of I2 ampere the
demagnetizing ampere turns is I2T2 . This will be countered by a current I1 flowing from the
source through the T1 turns such that,
I1T1 = I2T2 (77)
A current of I1 ampere flows through the winding between B and C . The current in the
winding between A and B is (I2 − I1) ampere. The cross section of the wire to be selected for
AB is proportional to this current assuming a constant current density for the whole winding.
Thus some amount of material saving can be achieved compared to a two winding
transformer. The magnetic circuit is assumed to be identical and hence there is no saving in
the same. To quantify the saving the total quantity of copper used in an auto transformer is
expressed as a fraction of that used in a two winding transformer as,
This means that an auto transformer requires the use of lesser quantity of copper
given by the ratio of turns. This ratio therefore denotes the savings in copper. As the space for
the second winding need not be there, the window space can be less for an auto transformer,
giving some saving in the lamination weight also. The larger the ratio of the voltages, smaller
is the savings. As T2 approaches T1 the savings become significant. Thus auto transformers
become ideal choice for close ratio transformations. The savings in material is obtained,
however, at a price. The electrical isolation between primary and secondary
Requirements. The additional opportunity of a so called zigzag connection can be used on the
secondary side. The separation of the windings into two parts and their application on two
different cores characterize this type of connection. This wiring is particularly suitable for
single-phase loads. Significant disadvantage is the additional copper expense on thesecondary
side increased about a factor 2/3compared to Y– or D
– connection. A conversion from line-to-line quantities to phase quantities and the usage of
single-phase ecdand phasor diagram is reasonable for the calculation of the operational
behavior of balanced loaded three-phase transformers.
The method of symmetrical components (see 2.6) is suited for calculations in case of
unbalanced load conditions. In a parallel connection of two three-phase transformers the
transformation ratio as well as the phase angle multiplier of the according vector group needs
to be adapted.
Examples for vector groups (based on VDE regulations):
Figure2.17 Table showing phasor diagrams and ecd according to vector group and
multiplier
With:
· upper case letter à vector group on primary side
· lower case letter à vector group on secondary side
· Y, y à star connection
· D, d à delta connection (?)
· z à zigzag connection
The multiplier gives the number of multiples of 30°, defining the total phase shift, of
which the low voltage (secondary side) lags behind the higher voltage (same
orientation of reference arrow assumed).
Mnemonic: clock
higher voltageμ 12 o’clock
lower voltage: number of multiplier (on the clock)
Where,
V1=Load bus voltage
V2=Supply voltage
These conditions are examined first with reference to single phase transformers and
then the three phase cases are discussed. Same voltage ratio generally the turns ratio and
voltage ratio are taken to be the same. If the ratio is large there can be considerable error in
the voltages even if the turns ratios are the same. When the primaries are connected to same
bus bars, if the secondaries do not show the same voltage, paralleling them would result in a
circulating current between the secondaries. Reflected circulating current will be there on the
primary side also. Thus even without connecting a load considerable current can be drawn by
the transformers and they produce copper losses. In two identical transformers with
percentage impedance of 5 percent, a no-load voltage difference of one percent will result in
a circulating current of 10 percent of full load current. This circulating current gets added to
the load current when the load is connected resulting in unequal sharing of the load. In such
cases the combined full load of the two transformers can never be met without one
transformer getting overloaded.
Per unit impedance Transformers of different ratings may be required to operate in
parallel. If they have to share the total load in proportion to their ratings the larger machine
has to draw more current. The voltage drop across each machine has to be the same by virtue
of their connection at the input and the output ends. Thus the larger machines have smaller
impedance and smaller machines must have larger ohmic impedance. Thus the impedances
must be in the inverse ratios of the ratings. As the voltage drops must be the same the per unit
impedance of each transformer on its own base, must be equal. In addition if active and
reactive powers arerequired to be shared in proportion to the ratings the impedance angles
also must be the same. Thus we have the requirement that per unit resistance and per unit
reactance of both the transformers must be the same for proper load sharing. Polarity of
connection The polarity of connection in the case of single phase transformers can be either
same or opposite. Inside the loop formed by the two secondaries the resulting voltage must be
zero.
If wrong polarity is chosen the two voltages get added and short circuit results. In the
case of polyphase banks it is possible to have permanent phase error between the phases with
substantial circulating current. Such transformer banks must not be connected in parallel. The
turn’s ratios in such groups can be adjusted to give very close voltage ratios but phase errors
cannot be compensated. Phase error of 0.6 degree gives rise to one percent difference in
voltage. Hence poly phase transformers belonging to the same vector group alone must be
taken for paralleling. Transformers having −30degree angle can be paralleled to that having
+30 angle by reversing the phase sequence of both primary and secondary terminals of one of
the transformers.
This way one can overcome the problem of the phase angle error. Phase sequence the
phase sequence of operation becomes relevant only in the case of poly phase systems. The
poly phase banks belonging to same vector group can be connected in parallel. A transformer
with +30◦ phase angle however can be paralleled with the one with −30∙ phase angle; the
phase sequence is reversed for one of them both at primary and secondary terminals. If the
phase sequences are not the same then the two transformers cannot be connected in parallel
even if they belong to same vector group.
The phase sequence can be found out by the use of a phase sequence indicator.
Performance of two or more single phase transformers working in parallel can be computed
using their equivalent circuit. In the case of poly phase banks also the approach is identical
and the single phase equivalent circuit of the same can be used. Basically two cases arise in
these problems. Case A: when the voltage ratio of the two transformers is the same and Case
B: when the voltage ratios are not the same. These are discussed now in sequence.
In view of this requirement it normally costs more. A few schemes of on-load tap
changing are now discussed. Reactor method The diagram of connections is shown in Fig.
43. This method employs an auxiliary reactor to assist tap changing. The switches for the taps
and that across the reactor(S) are connected as shown. The reactor has a center tapped
winding on a magnetic core. The two ends of the reactor are connected to the two bus bars to
which tapping switches of odd/even numbered taps are connected. When only one tap is
connected to the reactor the shorting switch S is closed minimizing the drop in the reactor.
The reactor can also be worked with both ends connected to two successive taps. In that case
the switch ’S’ must be kept open. The reactor limits the circulating current between the taps
in such a situation. Thus a four step tapped winding can be used for getting seven step
voltage on the secondary(see the table of switching).
Generally, parallel circuits are needed in primary and secondary to carry the large
current in a big transformer. Provision of taps switches and circuit breakers are to be
additionally provided to achieve tap changing in these machines. Series booster method in
this case a separate transformer is used to buck/boost the voltage of the main transformer.
The main transformer need not be having a tapped arrangement. This arrangement can be
added to an existing system also. It shows the booster arrangement for a single phase supply.
The reverser switch reverses the polarity of the injected voltage and hence a boost is
converted into a buck and vice versa. The power rating of this transformer need be a small
fraction of the main transformer as it is required to handle only the power associated with the
injected voltage.
The advantage of this type of tap changer are The major objection to this scheme
seems to be that the reactor is in the circuit always generating extra loss. Parallel winding,
transformer method In order to maintain the continuity of supply the primary winding is split
into two parallel circuits each circuit having the taps. Two circuit breakers A and B are used
in the two circuits. Initially tap 1a and 1b are closed and the transformer is energized with full
primary voltage. To change the tap the circuit breaker A is opened momentarily and tap is
moved from 1a to 2a. Then circuit breaker A is closed. When the circuit A is opened whole
of the primary current of the transformer flows through the circuit B. A small difference in
the number of turns between the two circuits exists. This produces a circulating current
between them. Next, circuit breaker B is opened momentarily, the tap is changed from1b to
2b and
the breaker is closed. In this position the two circuits are similar and there is no circulating
current. The circulating current is controlled by careful selection of the leakage reactance.
Generally, parallel circuits are needed in primary and secondary to carry the large current in a
big transformer. Provision of taps switches and circuit breakers are to be additionally
provided to achieve tap changing in these machines. Series booster method in this case a
separate transformer is used to buck/boost the voltage of the main transformer. The main
transformer need not be having a tapped arrangement.
This arrangement can be added to an existing system also. It shows the booster
arrangement for a single phase supply. The reverser switch reverses the polarity of the
injected voltage and hence a boost is converted into a buck and vice versa. The power rating
of this transformer need be a small fraction of the main transformer as it is required to handle
only the power associated with the injected voltage. One precaution to be taken with this
arrangement is that the winding must output side. In smaller ratings this is highly cost
effective. Two winding arrangements are also possible. The two winding arrangement
provides electrical isolation. Not be open circuited. If it gets open circuited the core (B in fig)
gets highly saturated.
In spite of the small ratings and low voltages and flexibility, this method of voltage
control costs more mainly due to the additional floor space it needs. The methods of voltage
regulation discussed so far basically use the principle of tap changing and hence the voltage
change takes place in steps. Applications like a.c. and D.C. motor speed control, illumination
control by dimmers, electro-chemistry and voltage stabilizers need continuous control of
voltage. This can be obtained with the help of moving coil voltage regulators. Moving coil
voltage regulator shows the physical arrangement of one such transformer. a, b are the two
primary windings wound on a long core, wound in the opposite sense. Thus the flux produced
by each winding takes a path through the air to link the winding. These fluxes link their
secondaries a2 and b2. A short circuited moving coil s is wound on the same limb and is
capable of being held at any desired position. This moving coil alters the inductances of the
two primaries. The sharing of the total applied voltage thus becomes different and also the
induced emf in the secondaries a2
and b2.
The total secondary voltage in the present case varies from 10 percent to 20 percent
of the input in a continuous manner. The turn’s ratios of a1μ a2 and b1μ b2 are 4.8θ and 10.θ
respectively. 5 4.86 + 95 10.6 = 10% when s is in the top position. In the bottom position it
becomes 95 4.86 + 5 10.6 = 20%. By selecting proper ratios for the secondaries a2 and b2
one can get the desired voltage variation. Sliding contact regulators these have two winding
or auto transformer like construction. The winding from which the output is taken is bared
and a sliding contact taps the voltage. The minimum step size of voltage change obtainable is
the voltage across a single turn. The conductor is chosen on the basis of the maximum load
current on the output side. In smaller ratings this is highly cost effective. Two winding
arrangements are also possible. The two winding arrangement provides electrical isolation
also.
2.11 SOLVED PROBLEMS
Example 1:
A source which can be represented by a voltage source of 8 V rms in series with an internal
resistance of 2 kΩ is connected to a η0-Ω load resistance through an ideal transformer.
Calculate the value of turns ratio for which maximum power is supplied to the load and the
corresponding load power? Using MATLAB, plot the the power in milliwatts supplied to the
load as a function of the transformer ratio, covering ratios from 1.0 to 10.0.
Solution:
For maximum power transfer, the load resistance (referred to the primary) must be equal to
the source resistance.
2
Vs Vs 2 2 Vs
I P RI n R
1 R R R n2R load L 1 LR n2R
For a general turns ratio n: s L s L s L
Example 2
A 460-V:2400-V transformer has a series leakage reactance of 37.2 Ω as referred to
the high-voltage side. A load connected to the low-voltage side is observed to be absorbing
25 kW, unity power factor, and the voltage is measured to be 450 V. Calculate the
corresponding voltage and power factor as measured at the high-voltage terminals.
Solution:
Secondary current:
P
load 25000 460
I 2 55.55 A Primary current I1 55.55 10.65 A
V
load 450 2400
V1 j 37.2 I 1 V2 V2 2400 450 2347.8 V
Primary voltage: 460
R1 = 0.68 Ω R2 = 0.00θ8 Ω
Xl1 = 7.8 Ω Xl2 = 0.0780 Ω
where subscript 1 denotes the 2400-V winding and subscript 2 denotes the 240-V winding.
Each quantity is referred to its own side of the transformer.
a. Draw the equivalent circuit referred to (i) the high- and (ii) the low-voltage sides.
Label the impedances numerically.
b. Consider the transformer to deliver its rated kVA to a load on the low-voltage side
with 230 V across the load. (i) Find the high-side terminal voltage for a load
power factor of 0.85 lagging. (ii) Find the high-side terminal voltage for a load
power factor of 0.85 leading.
Solution:
(a)
(i) referred to the HV side 0.68 j7.8 0.68 j7.8
240 : 2400
+ Z +
H
VL VH
_ _
+ +
ZL
VL VH
_ _
53
I 30000
Load current: load
230 93.8 A where is the pf angle ( 0 for leading pf).
Example 4:
A single-phase load is supplied through a 35-kV feeder whose impedance is 95 + j360 Ω and
a 35-kV:2400-V transformer whose equivalent impedance is (0.23 + j1.27) Ω referred to its
low-voltage side. The load is 160 kW at 0.89 leading power factor and 2340 V.
Solution:
feeder 35 : 2.4
+ Zf = 95+j360 + +
V V V
send H load
_ _ _
+ +
I
load V
V' H
160 103 76.83 A
load
V
_ _ PL load . I load .cos I
load
2340 0.89
cos 1 0.89 27.13 leading I load 76.83 27.13 A
Example 5:
The following data were obtained for a 20-kVA, 60-Hz, 2400:240-V distribution transformer
tested at 60 Hz:
a. Compute the efficiency at full-load current and the rated terminal voltage at 0.8 power
factor.
b. Assume that the load power factor is varied while the load current and secondary
terminal voltage are held constant. Use a phasor diagram to determine the load power
factor for which the regulation is greatest. What is this regulation?
Solution:
(a) Rated current on the HV side = 20 kVA / 2400 = 8.33 A. Therefore, total power loss
at full load current:
PL= 122 + 257 = 379 W. Load power at full load, 0.8 pf = 0.8 × 20 kW = 16 kW.
Therefore, input power = 16 + 0.379 = 16.379 kW efficiency = (16 / 16.379) × 100% =
97.7 %.
Z R jX
eq , H eq , H eq ,H
(b) The equivalent impedance of the transformer:
P Z V
R sc 257 eq sc 61.3
eq , H 3.7 ,H I 7.36
I sc 2 8.332 sc 8.33
X (Z )2 (R )2 6.36
eq , H eq , H eq ,H
V
Let load current and voltage referred to the HV side: lH V0 I lH I
Z I
V V Z I eq V V Z I
s lH eq lH V lH ( Z) V d d eq lH and Z
V
s
V
lH
V 2 2VV cos d
V2
d
V 2V cos
d
V 2 d
Regulation V V 1 V V2 1
lH
Maximum regulation:
Example 6:
A three-phase generator step-up transformer is rated 26-kV:345-kV, 850 MVA and has a
series impedance of 0.0035 + j0.087 per unit on this base. It is connected to a 26-kV, 800-
MVA generator, which can be represented as a voltage source in series with a reactance of
j1.57 per unit on the generator base.
(a) Convert the per unit generator reactance to the step-up transformer base.
(b) The unit is supplying 700 MW at 345 kV and 0.95 power factor lagging to the system
at the transformer high-voltage terminals.
(i) Calculate the transformer low-side voltage and the generator internal voltage
behind its reactance in kV.
(ii) Find the generator output power in MW and the power factor.
Solution:
850
X
(a) On the transformer base gen 1.57 800 1.668 pu
_ 56 _
(i) Transformer low-side voltage and generator internal voltage:
V 345 kV, V
base , H base ,L 26 kV, VAbase 850 MVA
VH 1.0 0 pu.
I I VA
700 base 850
s kA 1.233 kA base ,H kA 1.4225 kA
3V
3 345 0.95 base ,H 3 345
1.233
Is 0.8668 pu. Is 0.8668 18.2 pu.
1.4225
700 P 0.8235
OR P 0.8235 pu. Is pu 0.8668 pu.
850 V 1 0.95
H pu cos
V V
L (0.0035 j 0.087)I s 1.0264
H j0.071 pu. 1.0289 3.94
VL 1.0289 pu. 26.75 kV
EG VL ( j1.668)I s 1.478 j1.4442 pu. 2.0664 44.34 pu. EG 26 2.0664 53.73 kV
S
VL I s 1.0289 3.94 0.8668 18.2 0.8261 j0.3361 pu.
G
The principles of electromechanical energy conversion are investigated. The motivation for
this investigation is to show how the governing equations of an electromechanical device can
be derived from a magnetic circuit analysis. An expression for the mechanical force will be
derived in terms of the magnetic system parameters.
3.1.1Electromechanical-Energy-Conversion Principles
The electromechanical-energy-conversion process takes place through the medium of the
electric or magnetic field of the conversion device of which the structures depend on their
respective functions.
Transducers: microphone, pickup, sensor, loudspeaker
Force producing devices: solenoid, relay, electromagnet
Continuous energy conversion equipment: motor, generator
This chapter is devoted to the principles of electromechanical energy conversion and the
analysis of the devices accomplishing this function. Emphasis is placed on the analysis of
systems that use magnetic fields as the conversion medium.The concepts and techniques can
be applied to a wide range of engineering situations involving electromechanical energy
conversion.Based on the energy method, we are to develop expressions for forces and
torques in magnetic-field-based electromechanical systems.
For situations where large numbers of charged particles are in motion F=J*V most
electromechanical-energy-conversion devices contain magnetic material.
Forces act directly on the magnetic material of these devices which are constructed of rigid,
nondeforming structures. The performance of these devices is typically determined by the net
force, or torque, acting on the moving component. It is rarely necessary to calculate the
details of the internal force distribution.Just as a compass needle tries to align with the earth’s
magnetic field, the two sets of fields associated with the rotor and the stator of rotating
machinery attempt to align, and torque is associated with their displacement from alignment.
In a motor, the stator magnetic field rotates ahead of that of the rotor, pulling on it and
performing work.For a generator, the rotor does the work on the stator.
The ability to identify a lossless-energy-storage system is the essence of the energy method. This
is done mathematically as part of the modeling process. For the lossless magnetic-energy-storage
system of Fig. 3.3(a), rearranging (3.9) in form of (3.10) gives
dWelec=dmech+dfld
Here E is the voltage induced in the electric terminals by the changing magnetic stored
energy. It is through this reaction voltage that the external electric circuit supplies power to the
coupling magnetic field and hence to the mechanical output terminals. The basic energy-conversion
process is one involving the coupling field and its action and reaction on the electric and mechanical
systems.
dWelec=eidt=dmech+dfld
3.3 The Co Energy
The magnetic stored energy is a state function, determined uniquely by the values of the
independent state variables and x
Coenergy: Here the force can be obtained directly as a function of the current. The selection
of energy or coenergy as the state function is purely a matter of convenience.
For a magnetically-linear system, the energy and coenergy (densities) are numerically equal:
Wfld+W’fld=λi
.
Figure 3.4 Graphical interpretation of energy and coenergy in a singlyexcitedsystem.
The force acts in a direction to decrease the magnetic field stored energy at constant
flux or to increase the coenergy at constant current. In a singly-excited device, the force acts
to increase the inductance by pulling on members so as to reduce the reluctance of the
magnetic path linking the winding.
3.4 Force In A Singly Excited Magnetic Field System
3.4.1 Model& Analysis
The conversion of electrical energy to mechanical energy follows the law of conservation of
energy. In general, the law of conservation of energy states that energy is neither created nor
destroyed. Equation (1) describes the process of electromechanical energy conversion for a
differential time interval dt, where dW e is the change in electrical energy, dWm is the change
in mechanical energy, and dWf is the change in magnetic field energy. Energy losses in the
form of heat are neglected.
dWe = dWm + dWf _____________________________ (1)
If the electrical energy is held constant, the dWe term is zero for Equation (1). The
differential mechanical energy, in the form of work, is the force multiplied by the differential
distance moved. The force due to the magnetic field energy is shown in Equation (2). The
negative sign implies that the force is in a direction to decrease the reluctance by making the
air gap smaller.
_____________________________(2)
An expression for the energy stored in the magnetic field can be found in terms of the
magnetic system parameters. This expression is then substituted into Equation
(2) for Wf to get an expression for the force. This derivation is shown in Appendix A. The
result is Equation (3), in terms of the current, i, the constant for the permeability of free
space, m0, the cross-sectional area of the air gap, Ag, the number of turns, N, and the air gap
distance, x .
________________________(3)
To verify this relationship in the lab, it is convenient to have an expression for the current
necessary to hold some constant force. In a design, the dimensions and force are often
known. So, the user of the reluctance machine needs to know how much current to supply.
Rearranging terms in Equation (3) yields Equation (4).
________________________(4)
3.4.2 Sample Calculations
For the simple magnetic system of Figure 1, the current necessary to suspend the armature
can be calculated using Equation (4).
Alternators, synchronous motors etc., multiply excited magnetic systems are used. In
practice ,doubly excited systems are very much in use.
Due to two sources, there are two sets of three independent variables
i.e. ( , ) or (i1,i2, )
Solve equation (3) and (4) to express i1 and i2interms of and asand
are independent variables.
Multiply equation (3) by L12 and equation (4) by L11,
L12 =L11L12 i1+L2 12 i2
i2 = -
i2 = + ………….(η)
i1 = + ………….(θ)
Where =
= =
Wf( , )= +
Wf( , )= + ………
(7)
The self and mutual inductances of the coils are dependent on the angular position of the
rotor.
Case :2 Independent Variables i1,i2, i.e., i1 and i2 are constants.
The torque developed can be expressed as ,
Tf = ……….(8)
= + ……….(λ)
= +
= + ………
(10)
F=
Where are constants which are the stator and rotor current respectively
F= + ]
F= +
3.6 Mmf Of Distributed Windings
3.6.1 Alternating Field Distribution
Spatial field distribution and zerocrossings remain the same, whereasthe field strength
amount changes periodically with current frequency.This kind of field is called alternating
field.
Figure4.9progressive wave
A sinusoidal alternating field can be split up into two sinusoidal rotating fields. Their
peakvalue is of half the value as of the according alternating field, their angular speeds
areoppositely signed
3.6.3 Three-phase winding
Most simple arrangement of a three-phase stator consist of:
k composed of laminations with approximately 0,5 mm thickness, mutual
insulation for a reduction of eddy currents
2. The number of pole pairs is p= 1 in Fig.138. In case of p>1, the configuration repeats p-
times along the circumference.
ELECTRICAL MACHINES I
Figure 4.12Coils
Sine wave current in each of the coils produces sine varying magnetic field on the
rotation axis. Magnetic fields add as vectors. Vector sum of the magnetic field vectors of the
stator coils produces a single rotating vector of resulting rotating magnetic field.
The result of adding three 120-degrees phased sine waves on the axis of the motor is a
single rotating vector. The rotor has a constant magnetic field. The N pole of the rotor will
move toward the S pole of the magnetic field of the stator, and vice versa. This magneto-
mechanical attraction creates a force which will drive rotor to follow the rotating magnetic
field in a synchronous manner.
A permanent magnet in such a field will rotate so as to maintain its alignment with the
external field. This effect was utilized in early alternating current electric motors. A rotating
magnetic field can be constructed using two orthogonal coils with a 90 degree phase
difference in their AC currents. However, in practice such a system would be supplied
through a three-wire arrangement with unequal currents.
This inequality would cause serious problems in the standardization of the conductor
size. In order to overcome this, three-phase systems are used where the three currents are
equal in magnitude and have a 120 degree phase difference. Three similar coils having
mutual geometrical angles of 120 degrees will create the rotating magnetic field in this case.
The ability of the three phase system to create the rotating field utilized in electric motors is
one of the main reasons why three phase systems dominate in the world electric power supply
systems.
Figure 4.13 Coil
Rotating magnetic fields are also used in induction motors. Because magnets degrade with
time, induction motors use short-circuited rotors (instead of a magnet) which follow the
rotating magnetic field of a multicoiled stator. In these motors, the short circuited turns of the
rotor develop eddy currents in the rotating field of stator which in turn move the rotor by
Lorentz force. These types of motors are not usually synchronous, but instead necessarily
involve a degree of 'slip' in order that the current may be produced due to the relative
movement of the field and the rotor.
The single coil of a single phase induction motor does not produce a rotating magnetic field,
but a pulsating 3-φmotor runs from 1-φ power, but does not start.
Figure 4.14 Single Phase Stator Produces a Non Rotating Pulsating Magnetic Field
Another view is that the single coil excited by a single phase current produces two
counter rotating magnetic field phasor, coinciding twice per revolution at 0o (Figure above-a)
and 180o (figure e). When the phasor rotate to 90o and -90o they cancel in figure b. At 45o
and -45o (figure c) they are partially additive along the +x axis and cancel along the y axis.
An analogous situation exists in figure d. The sum of these two phasor is a phasor stationary
in space, but alternating polarity in time. Thus, no starting torque is developed.
However, if the rotor is rotated forward at a bit less than the synchronous speed, It
will develop maximum torque at 10% slip with respect to the forward rotating phasor. Less
torque will be developed above or below 10% slip. The rotor will see 200% - 10% slip with
respect to the counter rotating magnetic field phasor. Little torque (see torque vs. slip curve)
other than a double frequency ripple is developed from the counter rotating phasor.
Thus, the single phase coil will develop torque, once the rotor is started. If the rotor is
started in the reverse direction, it will develop a similar large torque as it nears the speed of
the backward rotating phasor. Single phase induction motors have a copper or aluminum
squirrel cage embedded in a cylinder of steel laminations, typical of poly-phase induction
motors.
add up
to the resulting number of windings.
3.8 Rotating Mmf Waves
The principle of operation of the induction machine is based on the generation of a rotating
sine wave!
In a three phase induction machine, there are three sets of windings,phase A winding, phase
B and phase C windings. These are excited by a balanced three-phase voltage supply.
This would result in a balanced three phase current. Note that they have a 120◦ time lag
between them.Further, in an induction machine, the windings are not all located in the same
place.They are distributed in the machine 120◦ away from each other (more about this in the
section on alternators). The correct terminology would be to say that the windings havetheir
axes separated in space by 120◦. This is the reason for using the phase A, B and Csince waves
separated in space as well by 120◦. When currents flow through the coils, they generate
mmfs. Since mmf is proportional to current, these waveforms also represent the mmf
generated by the coils and the total mmf.Further, due to magnetic material in the machine
(iron), these mmfs generate magnetic flux,which is proportional to the mmf (we may assume
that iron is infinitely permeable and non-linear effects such as hysterisis are neglected). Thus
the waveforms seen above would also represent the flux generated within the machine. The
net result as we have seen is a travelling flux wave. The x-axis would represent the space
angle in the machine as one travels around the air gap. The first pulsating waveform seen
earlier would then represent the a-phase flux, the second represents the b-phase flux and the
third represents the c-phase.This may be better visualized in a polar plot. The angles of the
polar plot represent the space angle in the machine, i.e., angle as one travels around the stator
bore of the machine.
• This plot shows the pulsating wave at the zero degree axes. The amplitude is maximumat
zero degree axes and is zero at λ0◦ axis. Positive parts of the waveform are shown in red
while negative in blue. Note that the waveform is pulsating at the 0−180◦ axis and red and
blue alternate in any given side. This corresponds to the sinewave current changing polarity.
Note that the maximum amplitude of the sinewave is reached only along the 0−180◦ axis. At
all other angles, the amplitude does not reach a maximumof this value. It however reaches a
maximum value which is less than that of the peak occuring at the 0 − 180◦ axis. More
exactly, the maximum reached at any space angle would be equal to costimes the peak at the
0 − 180◦ axis. Further, at any space angle ,the time variation is sinusoidal with the frequency
and phase lag being that of the excitation, and amplitude being that corresponding to the
space angle.
• This plot shows the pulsating waveforms of all three cosines. Note that the first is pulsating
about the 0 − 180◦ axis, the second about the120◦− 300◦axis and the thirdat 240◦− 3θ0◦axis.
• This plot shows the travelling wave in a circular trajectory. Note that while individual
pulsating waves have maximum amplitude of 10, the resultant has amplitude of 15. If f1 is
the amplitude of the flux waveform in each phase.It is worthwhile pondering over the
following points.
1. what is the interpretation of the pulsating plots of the animation? If one wants to know
the ‘a’ phase flux at a particular angle for all instants of time, how can it be obtained?
2. What will this time variation look like? It is obviously periodic. What will be the
amplitude and frequency?
from spatial integration of the air gap flux density over one pole pitch.
air gap flux density, computes from variation of the flux linkage with time.Described
variation of flux linkage can be caused by both variation of currents iu(t), iv(t), iw(t) with
time, inside the exciting three-phase winding and also by rotary motion a(t) of the coil along
the air gap circumference.
Some aspects regarding induced voltage dependencies are listed below: the
amplitude of the induced voltage is proportional to the line frequency of the
statorand to the according slip.
frequency of induced voltage is equal to slip frequency
at rotor standstill (s= 1), frequency of the induced voltage is equal to line
frequency.
when rotating ( s
fundamental wave of the stator windings.
no voltage is induced into the rotor at synchronous speed (s= 0).
phase displacement of voltages to be induced into the rotor is only dependent
from thespatial position of the coil, represented by the (elec.) angle p R a .Is a
rotor also equipped with a three-phase winding, instead of a single coil similar
to thestator arrangement with phases being
greaterthan 1 (q>
follows for the induced voltage of single rotor phases.
3.9 Torque In Ac And Dc Machines
As fulfilled previous considerations, only the fundamental waves of the effects caused
by the air gap field are taken into account.Rotatingmmf, caused in stator windings,
isrevolving. An according rotating mmf is evoked in the rotor windings. Initially no
assumptions are made for the number of pole pairs, angular frequency and phaseangle of
rotating magneto-motive forces of stator- and rotor.With appliance of Ampere’s law, the
resulting air gap field calculates from superimposing ofboth rotating magneto-motive forces
of stator and rotor
A time-variant sinusoidal torque with average value equal to zero appears which is
called oscillation torque. Only if angular frequencies of the exciting currents agree,
rotating field agree (at equal number of pole pairs), a time-constant torque derives for
e -motive forces is porportional to their amplitudes and the sine-value of the enclosed angle.
M = maximum for e=
2. M
Magneto-motive force reflects the geometrical sum of stator and rotor mmf, which complies
with the resulting air gap field.Displacement between U1 und I1 is U1 is orientated in
the direction of the +Re-axis (real) whereas I0 is orientated in direction of the –Im-axis
(imaginary), for complex
coordinate presentation.
Torque In Ac Machines
Effective torque exerted on the shaft derives from transmitted air-gap power divided
by synchronous speed. Neglecting stator copper losses, the absorbed active power is equal to
the air-gap power.
/6
(valid only in the range ). The actuator dimensions are g = 0.8 mm, A0 = 6.0
mm2, and N = 650 turns.
(a) Assuming the coil to be carrying current i, write an expression for the magnetic
stored energy in the actuator as a function of angle θ for /6.
Figure 1 Actuator with rotating vane (a) Side view. (b) End view.
Solution
0Ni
(a) Flux density in the air-gap: Bg
2g
1 Bg2
Magnetic energy density
2 0
2
W
1 Bg2 V W
0 N 2 i2 4
fld ag Vag 2 gAg fld A0 1
2 0 4g
(b)
2W 2
W 1 L ( )i 2 L( ) fld 0N2 A 1 4
fld 2 i2 2g 0
Example 2:
As shown in Fig. 2, an N-turn (N = 100) electromagnet is to be used to lift a slab of
iron of mass M. The surface roughness of the iron is such that when the iron and the
electromagnet are in contact, there is a minimum air gap of gmin = 0.18 mm in each leg. The
electromagnet cross-sectional area Ac = 32 cm2 and coil resistance is 2.8
Ω. Calculate the minimum coil voltage which must be used to lift a slab of mass 95 kg
against the force of gravity. Neglect the reluctance of the iron.
ELECTRICAL MACHINES I
Solution
0
N2A 1 dL N2A
2
i2
0
L( g ) c
f i 2
c
v Ri
min min 1.08 V
Example :3
Solution
0
N2 A 1 dL 1 0
N2A i2L
2 2
L c
f i i c
g fld 2 dg 2 g2 2g
Since coil resistance and leakage inductance are negligible, the current in the coil
can be written as
V
m
i (t ) I m cos t where Im
L
f i2L I2L f I2 L V2 L V2
fld m
cos2 t fld rms rms rms
2g 2g 2g 2 g 2L2 2 2 N 2A
0 c
f 1202
fld
2 2 7 4 104.48 N
2(120 ) 525 4 10 14 10
where θ is the angle between the axes of the windings. The resistances of the windings may
be neglected. Winding 2 is short-circuited, and the current in winding 1 as a function of time
is il = 10 sin ωt A.
a. Derive an expression for the numerical value in newton-meters of the instantaneous torque
on the rotor in terms of the angle θ.
b. Compute the time-averaged torque in newton-meters when θ = 45°.
c. If the rotor is allowed to move, will it rotate continuously or will it tend to come to rest? If
the latter, at what value of θ0 ?
T i i dL( ) 2.8i i sin
(a) fld 12 d 12
Winding 2 short-circuited
L
e v 0 Li L i 0 i 21
i 1.12i cos
2 2 2 21 1 22 2 2 L 1 1
22
T 2.8i i sin 3.14i 2 sin cos 314sin 2 ( t) sin cos
fld 12 1
B H Ni
0 1
Ni1 H r ,1 g r ,1 0 r ,1
F 2 r NiB 2 r 0 0 N 1 N2 i i
0 22 r ,1 12
g
(b) Self-inductances:
0
N2 A
1 g
L
11 g Ag 2 r0 l
To find the self-inductance of coil 2, apply Ampere’s law to coil 2 at height z:
0 0 z x
B z x N i
r ,2
gh 0 2 2 x z x h
Ni
0 2 2
x h z l
g
(c) We can find the inductance of a section of coil 2 of length dz and then integrate with
respect to z. At a height z
l
2 (z)
L22 (z ) 2 ( z) N 2 Br ,2 (u ).2 r 0 du z x
I2 z
NI NI
l B ( u ) du 0 2 2
l ( u x )du 0 2 2 1 u 2 ux l
r ,2
z gh z gh 2 z
2 r N2 1 1
L (z ) 0 0 2 l2 lx z2 zx z
22
gh 2 2
2 r N2 x h 1 1 r N2
L 0 0 2
l2 lx z2 zx dz 0 0 2
( l x)2
22
gh x 2 2 g
CHAPTER -4
DC GENERATORS
4.1Principles Of D.C. Machines
D.C. machines are the electro mechanical energy converters which work from a D.C.
source and generate mechanical power or convert mechanical power into a D.C. power.
Figure.5.1D.C Machines
4.2.1 Frame
Frame is the stationary part of a machine on which the main poles and Commutator
poles are bolted and it forms the supporting structure by connecting the frame to the bed
plate. The ring shaped body portion of the frame which makes the magnetic path for the
magnetic fluxes from the main poles and interspoles is called frames.
4.2.2 Yoke.
Yoke was made up of cast iron but now it is replaced by cast steel.This is because
cast iron is saturated by a flux density of 0.8 Web/sq.mwhere as saturation
with cast iron steel is about 1.5 Web/sq.m.So for the same magnetic flux density the cross
section area needed for cast steel is less than cast iron hence the weight of the machine too.If
we use cast iron there may be chances of blow holes in it while casting.so now rolled steels
are developed and these have consistent magnetic and mechanical properties.
These are also fastened to the yoke by bolts. Sometimes the yoke may be slotted to
receive these poles. The inter poles could be of tapered section or of uniform cross section.
These are also called as commutating poles or com poles. The width of the tip of the com
pole can be about a rotor slot pitch.
4.2.5 Armature
The armature is where the moving conductors are located. The armature is
constructed by stacking laminated sheets of silicon steel. Thickness of this lamination
is kept low to reduce eddy current losses. As the laminations carry alternating flux the choice
of suitable material, insulation coating on the laminations, stacking it etc are to be done more
carefully. The core is divided into packets to facilitate ventilation. The winding cannot be
placed on the surface of the rotor due to the mechanical forces coming on the same. Open
parallel sided equally spaced slots are normally punched in the rotor laminations.
These slots house the armature winding. Large sized machines employ a spider on
which the laminations are stacked in segments. End plates are suitably shaped so as to serve
as ’Winding supporters’. Armature construction process must ensure provision of sufficient
axial and radial ducts to facilitate easy removal of heat from the armature winding. Field
windings: In the case of wound field machines (as against permanentmagnet excited
machines) the field winding takes the form of a concentric coil wound around the main poles.
These carry the excitation current and produce the main field in the machine. Thus the poles
are created electromagnetically.
Two types of windings are generally employed. In shunt winding large number of
turns of small section copper conductor isof Technology Madras used. The resistance of such
winding would be an order of magnitude larger than the armature winding resistance. In the
case of series winding a few turns of heavy cross section conductor is used. The resistance of
such windings is low and is comparable to armature resistance. Some machines may have
both the windings on the poles. The total ampere turns required to establish the necessary flux
under the poles is calculated from the magnetic circuit calculations.
The total mmf required is divided equally between north and south poles as the poles
are produced in pairs. The mmf required to be shared between shunt and series windings are
apportioned as per the design requirements. As these work on the same magnetic system they
are in the form of concentric coils. Mmf ’per pole’ is normally used in these calculations.
Armature winding as mentioned earlier, if the armature coils are wound on the surface of
Other mechanical parts End covers, fan and shaft bearings form other important
mechanical parts. End covers are completely solid or have opening for ventilation. They
support the bearings which are on the shaft. Proper machining is to be ensured for easy
assembly. Fans can be external or internal. In most machines the fan is on the non-
Commutator end sucking the air from the Commutator end and throwing the same out.
Adequate quantity of hot air removal has to be ensured.
Bearings Small machines employ ball bearings at both ends. For larger machines
roller bearings are used especially at the driving end. The bearings are mounted press-fit on
the shaft. They are housed inside the end shield in such a manner that it is not necessary to
remove the bearings from the shaft for dismantling.
1. The back and front pitches are odd and of opposite sign.But they can't be equal. They
differ by 2 or some multiple thereof.
2. Both YB and YF shpuld be nearly equal to a pole pitch.
3. The average pitch YA = (YB + YF)/2.It equals pole pitch = Z/P.
4. Commutator pitch YC = ±1.
5. Resultant pitch YR is even, being the arithmetical difference of two odd numbers i.e
YR = YB - YF.
6. The number of slots for a 2-layer winding is equal to the number of coils.The number
of commutator segments is also the same.
7. The number of parallel paths in the armature = mP where 'm' is the multiplicity of the
winding and 'P' the number of poles.Taking the first condition, we have YB = YF ±
2m where m=1 fo simplex lap and m =2 for duplex winding etc.
8. If YB > YF i.e YB = YF + 2, then we get a progressive or right-handed winding i.e a
winding which progresses in the clockwise direction as seen from the comutator
end.In this case YC = +1.
9. If YB < size="1">F i.e YB = YF - 2,then we get a retrogressive or left-handed
winding i.e one which advances in the anti-clockwise direction when seen from the
commutator side.In this case YC = -1.
10. Hence, it is obvious that for
2. Back and front pitches are nearly equal to the pole pitch and may be equal or differ by
2, in which case, they are respectively one more or one less than the average pitch.
7. It is obvious from 5 that for a wave winding, the number of armature conductors with
2 either added or subtracted must be a multiple of the number of poles of the
generator.This restriction eliminates many even numbers which are unsuitable for this
winding.
8. The number of armature parallel paths = 2m where 'm' is the multiplicity of the
winding.
However at rated armature current the increase of flux in one half of the pole is rather
less than the decrease in the other half due to presence of saturation. In other words there will
be a net decrease in flux per pole during sufficient loading of the machine. This will have a
direct bearing on the emf as well as torque developed affecting the performance of the
machine.
Apart from this, due to distortion in the flux distribution, there will be some amount
of flux present along the q-axis (brush axis) of the machine. This causes commutation
difficult. In the following sections we try to explain armature reaction in somewhat detail
considering motor and generator mode separately.
4.7 Methods Of Excitation
Various methods of excitation of the field windings are
Separately-excited generators
Self-excited generators: series generators, shunt generators, compound generators
In a motor the relation between the emfEagenerated in the armature and the armature
terminal voltage VaisVa=Ea+IaRa. The application of dc machines lie in the variety of
performance characteristics offered by the possibilities of shunt, series, and compound
excitation.
4.8 Commutation And Interpoles
I n larger machines the commutation process would involve too much sparking, which
causes brush wear, noxious gases (ozone) that promote corrosion, etc. In these cases it is
common to use separate commutation interpoles. These are separate, usually narrow or
seemingly vestigal pole pieces which carry armature current. They are arranged in such a way
that the flux from the interpole drives current in the commutated coil in the proper direction
Remember that the coil being commutated is located physically between the active
poles and the interpole is therefore in the right spot to influence commutation. The interpole
is wound with armature current (it is in series with the main brushes). It is easy to see that the
interpole must have a flux density proportional to the current to be commutated. Since the
speed with which the coil must be commutated is proportional to rotational velocity and so is
the voltage induced by the interpole, if the right numbers of turns are put around the
interpole, commutation can be made to be quite accurate.
The O.C.C curve for self-excited generators whether shunt or series wound is shown
in above Figure.Due to the residual magnetism in the poles, some emf (=OA) is generated
even when If =0.Hence, the curve starts a little way up. The slight curvature at the lower end
is due to magnetic inertia.It is seen that the first part of the curve is practically straight.This is
due to fact that at low flux densities reluctance of iron path being negligible,total reluctance
is given by the air gap reluctance which is constant.Hence,the flux and consequently, the
generated emfis directly proportional to the exciting current.However, at high flux densities,
where is small,iron path reluctance becomes appreciable and straight relation between E
and If no longer holds good.In other words,after point B, saturation of pole starts.However,
the initial slope
of the curve is determined by air-gap width.O.C.C for higher speed would lie above this
curve and for lower speed,would lie below it.
Separately-excited Generator Let we consider a separately-excited generator giving its
rated no-load voltage of E0 for a certain constant field current.If there were no armature
reaction and armature voltage drop,then this voltage would have remained constant as shown
in Figure by the horizontal line 1. But when the generator is loaded, the voltage falls due to
these two causes, therebygiving slightly dropping characteristics.If we subtract from E0 the
values of voltage drops due to armature reaction for different loads, then we get the value of
E-the emf actually induced in the armature under load conditions.Curve 2 is plotted in this
way and is known as the internal characteristic.
Figure.5.7Current Vs Voltage
In this generator, because field windings are in series with the armature, they carry
full armature current Ia. As Ia is increased, flux and hence generated emf is also increased as
shown by the curve. Curve Oais the O.C.C. The extra exciting current necessary to neutralize
the weakening effect of armature reaction at full load is given by the horizontal distance ab.
Hence, point b is on the internal characteristic.
4.9.6. External Characteristic (V/I)
It is also referred to as performance characteristic or sometimes voltage-regulating
curve. It gives relation between the terminal voltage V and the load current I.This curve lies
below the internal characteristic because it takes in to account the voltage drop over the
armature circuit resistance.The values of V are obtained by subtracting IaRa from
corresponding values of E.This characteristic is of great importance in judging the suitability
of a generator for a particular purpose.It may be obtained in two ways
Basically, there is no constructional difference between a d.c. motor and a d.c.generator. The
same d.c. machine can be run as a generator or motor.
5.2 Working of D.C. Motor
When the terminals of the motor are connected to an external source of d.c.
supply:
(i) the field magnets are excited developing alternate N and S poles;
(ii) the armature conductors carry currents.
All conductors under N-pole carry currents in one direction while all the conductors
under S-pole carry currents in the opposite direction. Suppose the conductors under N-pole
carry currents into the plane of the paper and those under S-pole carry currents out of the
plane of the paper as shown in Fig. Since each armature conductor is carrying current and is
placed in the magnetic field, mechanical force acts on it.
Applying Fleming’s left hand rule, it is clear that force on each conductor is tending
to rotate the armature in anticlockwise direction. All these forces add together to produce a
driving torque which sets the armature rotating. When the conductor moves from one side of
a brush to the other, the current in that conductor is reversed and at the same time it comes
under the influence of next pole which is of opposite polarity. Consequently, the direction of
force on the conductor remains the same.
5.3 Types of D.C. Motors
Like generators, there are three types of d.c. motors characterized by the connections of field
winding in relation to the armature viz.:
(i) Shunt-wound motor in which the field winding is connected in parallel with the armature.
The current through the shunt field winding is not the same as the armature current. Shunt
field windings are designed to produce the necessary m.m.f. by means of a relatively large
number of turns of wire having high resistance. Therefore, shunt field current is relatively
small compared with the armature current.
(ii) Series-wound motor in which the field winding is connected in series with the armature
Therefore, series field winding carries the armature current. Since the current passing through
a series field winding is the same as the armature current, series field windings must be
designed with much fewer turns than shunt field windings for the same m.m.f. Therefore, a
series field winding has a relatively small number of turns of thick wire and, therefore, will
possess a low resistance.
(iii) Compound-wound motor which has two field windings; one connected in parallel with
the armature and the other in series with it. There are two types of compound motor
connections (like generators). When the shunt field winding is directly connected across the
armature terminals it is called short-shunt connection. When the
shunt winding is so connected that it shunts the series combination of armature and
series field it is called long- shunt connection.
5.4 Motor Characteristics
5.4.1 Torque/Speed Curves
In order to effectively design with D.C. motors, it is necessary to understand their
characteristic curves. For every motor, there is a specific Torque/Speed curve and Power
curve.
Note that for shunt motor voltage applied to the field and armature circuit are sameand equal
to the supply voltage V. However, as the motor is loaded, IaRa drop increasesmaking speed a
little less than the no load speed n0. For a well designed shunt motor thisdrop in speed is
small and about 3 to 5% with respect to no load speed. This drop in speedfrom no load to full
load condition expressed as a percentage of no load speed is called theinherent speed
regulation of the motor. It is for this reason, a d.c shunt motor is said to be practically a
constant speed motorsince speed drops by a small amount fromno load to full load condition.
If flux φ will change, hence speed will vary. To change If an external resistance is
connected in series with the field windings. The field coil produces rated flux when no
external resistance is connected and rated voltage is applied across field coil. It should be
understood that we can only decrease flux from its rated value by adding external resistance.
Thus the speed of the motor will rise as we decrease the field current and speed control above
the base speed will be achieved. Speed versus armature current characteristic is shown in
figure for two flux valu es φ and φ1. Since φ1<φ, the no load speed no' for flux value φ1 is
more than the no load speed no corresponding to φ.
However, this method will not be suitable for constant load torque .To make this point
clear, let us assume that the load torque is constant at rated value. So from the initial steady
condition, we have TL rated=Ta1= k=Ia rated .If load torque remains constant and flux is
reduced to φ1, new armature current in the steady state is obtained from kI a1=TL rated .
Therefore new armature current is but this fraction is less than 1. Hence new armature current
will be greater than the rated armature current and the motor will be overloaded. This method
therefore, will be suitable for a load whose torque demand decreases with the rise in speed
keeping the output power constant as shown in figure. Obviously this method is based on flux
weakening of the main field.
Figure 5.23 Speed Vs Armature Current Characteristics
There is a handle which can be moved in the clockwise direction against the spring
tension. The spring tension keeps the handle in the OFF position when no one attempts to
move it. Now let us trace the circuit from terminal L (supply + ve). The wire from L passes
through a small electro magnet called OLRC, (the function of which we shall discuss a little
later) and enters through the handle shown by dashed lines. Near the end of the handle two
copper strips are firmly connected with the wire.
The furthest strip is shown circular shaped and the other strip is shown to be
rectangular. When the handle is moved to the right, the circular strip of the handle will make
contacts with resistance terminals 1, 2 etc. Progressively. On the other hand, the rectangular
strip will make contact with the continuous arc copper strip. The other end of this strip is
brought as terminal F after going through an electromagnet coil (called NVRC). Terminal F is
finally connected to motor field terminal Fl.
Working principle
In the operation of the starter, initially the handle is in the OFF position. Neither
armature nor the field of the motor gets supply. Now the handle is moved to stud number 1.
In this position armature and all the resistances in series gets connected to the supply. Field
coil gets full supply as the rectangular strip makes contact with arc copper strip. As the
machine picks up speed handle is moved further to stud number 2. In this position the
external resistance in the armature circuit is less as the first resistance is left out. Field
however, continues to get full voltage by virtue of the continuous arc strip. Continuing in this
way, all resistances will be left out when stud number 12 (ON) is reached. In this position, the
electromagnet (NVRC) will attract the soft iron piece attached to the handle. Even if the
operator removes his hand from the handle, it will still remain in the ON position as spring
restoring force will be balanced by the force of attraction between NVRC and the soft iron
piece of the handle. The no volt release coil (NVRC) carries same current as that of the field
coil. In case supply voltage goes off, field coil current will decrease to zero. Hence NVRC
will be de-energized and will not be able to exert any force on the soft iron piece of the
handle. Restoring force of the spring will bring the handle back in the OFF position.
The starter also provides over load protection for the motor. The other electromagnet,
OLRC overload release coil along with a soft iron piece kept under it, is used to achieve this.
The current flowing through OLRC is the line current IL drawn by the motor. As the motor is
loaded, Ia hence IL increases. Therefore, IL is a measure of loading of the motor. Suppose we
want that the motor should not be over loaded beyond rated current. Now gap between the
electromagnet and the soft iron piece is so adjusted that for IL≤Irated the iron piece will not
be pulled up. However, if IL≤Irated force of attraction will be sufficient to pull up iron piece.
This upward movement of the iron piece of OLRC is utilized to de-energize NVRC. To the
iron a copper strip is attached. During over loading condition, this copper strip will also move
up and put a short circuit between two terminals B and C. Carefully note that B and C are
nothing but the two ends of the NVRC. In other words, when over load occurs a short circuit
path is created across the NVRC. Hence NVRC will not carry any current now and gets
deenergized. The moment it gets deenergised, spring action will bring the handle in the OFF
position thereby disconnecting the motor from the supply. Three point starter has one
disadvantage. If we want to run the machine at higher speed (above rated speed) by field
weakening (i.e., by reducing field current), the strength of NVRC magnet may become so
weak that it will fail to hold the handle in the ON position and the spring action will bring it
back in the OFF position. Thus we find that a false disconnection of the motor takes place
even when there is neither over load nor any sudden disruption of supply.
5.8 Four-Point Starter
The possibility of accidentally opening the field circuit is quite remote. The four - point
starter provides the no-voltage protection to the motor. If the power fails, the motor is
disconnected from the line.
5.9 Swinburne’s Test
For a d.c shunt motor change of speed from no load to full load is quite small.
Therefore, mechanical loss can be assumed to remain same from no load to full load.
Also if field current is held constant during loading, the core loss too can be assumed
to remain same.
In this test, the motor is run at rated speed under no load condition at rated voltage.
The current drawn from the supply IL0 and the field current If are recorded (figure
40.3). Now we note that:
106
SCE ELECTRICAL AND ELECTRONICS ENGINEERING
ELECTRICAL MACHINES I
Since the motor is operating under no load condition, net mechanical output power is
zero. Hence the gross power developed by the armature must supply the core loss and
friction & windage losses of the motor. Therefore,
Since, both P core and P friction for a shunt motor remains practically constant from no
load to full load, the sum of these losses is called constant rotational loss i.e.,
In the Swinburne's test, the constant rotational loss comprising of core and friction
loss is estimated from the above equation.
After knowing the value of P rot from the Swinburne's test, we can fairly estimate the
efficiency of the motor at any loading condition. Let the motor be loaded such that
new current drawn from the supply is IL and the new armature current is Ia as shown
in figure 40.4. To estimate the efficiency of the loaded motor we proceed as follows:
The estimated value of P rot obtained from Swinburne’s test can also be used to
estimate the efficiency of the shunt machine operating as a generator. In figure 40.5 is
shown to deliver a
load current IL to a load resistor RL. In this case output power being known, it is
easier to add the losses to estimate the input mechanical power.
ELECTRICAL MACHINES I
The biggest advantage of Swinburne's test is that the shunt machine is to be run as
motor under no load condition requiring little power to be drawn from the supply;
based on the no load reading, efficiency can be predicted for any load current.
However, this test is not sufficient if we want to know more about its performance
(effect of armature reaction, temperature rise, commutation etc.) when it is actually
loaded. Obviously the solution is to load the machine by connecting mechanical load
directly on the shaft for motor or by connecting loading rheostat across the terminals
for generator operation. This although sounds simple but difficult to implement in the
laboratory for high rating machines (say above 20 kW), Thus the laboratory must
have proper supply to deliver such a large power corresponding to the rating of the
machine. Secondly, one should have loads to absorb this power.
This as an elegant method of testing d.c machines. Here it will be shown that while
power drawn from the supply only corresponds to no load losses of the machines, the
armature physically carries any amount of current (which can be controlled with
ease). Such a scenario can be created using two similar mechanically coupled shunt
machines. Electrically these two machines are eventually connected in parallel and
controlled in such a way that one machine acts as a generator and the other as motor.
In other words two similar machines are required to carry out this testing which is not
a bad proposition for manufacturer as large numbers of similar machines are
manufactured.
ELECTRICAL MACHINES I
Procedure
Connect the two similar (same rating) coupled machines as shown in figure 40.6.
With switch S opened, the first machine is run as a shunt motor at rated speed. It may
be noted that the second machine is operating as a separately excited generator
because its field winding is excited and it is driven by the first machine. Now the
question is what will be the reading of the voltmeter connected across the opened
switch S? The reading may be (i) either close to twice supply voltage or (ii) small
voltage. In fact the voltmeter practically reads the difference of the induced voltages
in the armature of the machines. The upper armature terminal of the generator may
have either + ve or negative polarity. If it happens to be +ve, then voltmeter reading
will be small otherwise it will be almost double the supply voltage
Since the goal is to connect the two machines in parallel, we must first ensure
voltmeter reading is small. In case we find voltmeter reading is high, we should
switch off the supply, reverse the armature connection of the generator and start
afresh. Now voltmeter is found to read small although time is still not ripe enough to
close S for paralleling the machines. Any attempt to close the switch may result into
large circulating current as the armature resistances are small. Now by adjusting the
field current Ifg of the generator the voltmeter reading may be adjusted to zero (Eg ≈
Eb) and S is now closed. Both the machines are now connected in parallel
Calculation of efficiency
Let field currents of the machines be are so adjusted that the second machine is acting as
generator with armature current Iag and the first machine is acting as
motor with armature current Iam as shown in figure 40.7. Also let us assume the current
drawn from the supply be I1. Total power drawn from supply is VI1 which
goes to supply all the losses (namely Cu losses in armature & field and rotational losses)
of both the machines
Since speed of both the machines are same, it is reasonable to assume the rotational
losses of both the machines are equal; which is strictly not correct as the field current
of the generator will be a bit more than the field current of the motor, Thus, Once P rot
is estimated for each machine we can proceed to calculate the efficiency of the
machines as follows,
As pointed out earlier, for efficiency calculation of motor, first calculate the input
power and then subtract the losses to get the output mechanical power as shown
below,
EFFICIENCY OF GENERATOR
Let with S in position 1, motor runs at n rpm, drawing an armature current Ia and the
back emf is Eb = kφ n. Note the polarity of Eb which, as usual for motor mode in
opposition with the supply voltage. Also note Te and n have same clock wise direction.
Now if S is suddenly thrown to position 2 at t = 0, the armature gets disconnected from
the supply and terminated by Rb with field coil remains energized from the supply.
Since speed of the rotor can not change instantaneously, the back emf value Eb is still
maintained with same polarity prevailing at t = 0-. Thus at t = 0+, armature current will
be Ia = Eb/(r a + Rb) and with reversed direction compared to direction prevailing
during motor mode at t
= 0-.
Obviously for t > 0, the machine is operating as generator dissipating power to Rb and now the
electromagnetic torque Te must act in the opposite direction to that of n since Ia has changed direction
but φ has not (recall Te ∝ φ Ia ). As time passes after switching, n decreases reducing K.E and as a
consequence both Eb and Ia decrease. In other words value of braking torque will be highest at t = 0+,
and it decreases progressively and becoming zero when the machine finally come to a stop.
SOLUTION:
No-load input power = V × W)
= 240× 5.2
=1248 W
This no-load input power to meet all kinds of no-load losses is armature copper
loss and constant loss
Shunt field current= =
= 1.5 A
% Efficiency = = ×100
= 83.52%
Ans: = λ8.40%
ELECTRONICS ENGINEERING
2. In a brake test the efficiency load on the branch pulley was 40Kg, the effective
diameter of the pulley 73.5 cm and speed 15 rps. The motor takes 60A at 230V.
Calculate the output power and efficiency at this load.
3. A 480 V, 20kW, shunt motor of rows 2.5A, when running at with light load
.Taking the armature resistance to be 0.θΩ,field resistance to be 800 Ω and brush
drops at 2V and find full load efficiency.
Ans μ = λ4.83%
GLOSSARY
1. Magnetic Circuit: The circuit which produces the magnetic field is known as
magnetic circuit.
2. Stacking Factor: It is the ratio between the net cross sectional areas of the core to
the cross section occupied by the magnetic material.
3. MMF:MMF is the work done in moving a unit magnetic pole once around the
magnetic circuit.
5. Self Inductance: The e.m.f induced in a coil due to change of flux in the same coil is
known as self inductance
6. Mutual Inductance: When two coils are kept closed together, due to the change in
flux in one coil , an emf is induced in the another coil
7. Coupling Coefficient: The ratio of mutual inductance to the square root of the
product of two self inductances.
10. Critical field resistance: the resistance of the field circuit which will cause the shunt
generator just to build up its emf at a specified field.
11. Geometric neutral axis (GNA): GNA is the axis which is situated geometrically or
physically in the mid way between adjacent main poles.
12. Magnetic neutral axis (MNA):MNA is the axis which passes through the zero
crossing of the resultant magnetic field waveform in the air gap.
14. Chorded coils: The coil span is less than full pitched winding by an angle 180
degree.
15. Slot angle:It is defined as the ratio of the 180degree to the pole pitch.
16. Slot pitch: It is the distance between the two coil sides of the same commutator
segments
17. Pole pitch: It is the ratio of the total no. of armature coils to the total no of poles.
18. Distributed windings: Windings which are spread over a number of slots around the
air gap periphery.
19. Back pitch: It is defined as the distance between two sides of the same coil is
expressed in term so coils sides and denoted by Yb.
21. Commutator: The Commutator converts the alternating emf into unidirectional or
direct emf.
22. DC Motor: D.C motor converts electrical energy into mechanical energy.
23. Torque: Torque is nothing but turning or twisting force about the axis.
27. Self Excited: Field winding supplied from the armature itself.
28. Separately Excited: Field winding supplied from the separate supply
30. Back emf: In dc motor as the armature rotates inside magnetic flux an emf is induced
in the armature conductor. This emf acts opposite to applied voltage known as back
emf.
TWO MARKS QUESTION WITH ANSWER
CHAPTER I
MAGNETIC CIRCUITS AND MAGNETIC MATERIAL 1.
Mention the types of electrical machines.
There are three basic rotating machines types, namely a.
The dc machines
b. the poly phase synchronous machine (ac), and
c. Poly and single phase induction machine (ac)and a stationary machine,
namely Transformer
2. State Ohm’s law for magnetic circuit.
It states that the magneto motive force across the magnetic element is equal to the
product of the magnetic flux through the magnetic element and the reluctance of the
magnetic material. It is given by
MMF = Flux X Reluctance
3. Define leakage flux
The flux setup in the air paths around the magnetic material is known as
leakage flux.
6. What is fringing?
In the air gap the magnetic flux fringes out into neighboring air paths due to the
reluctance of air gap which causes a non uniform flux density in the air gap of a machine.
This effect is called fringing effect.
9. What is magnetostriction?
When ferromagnetic materials are subjected to magnetizing mmf, these may
undergo small changes in dimension; this phenomenon is known as magnetostriction.
UNIT II
TRANSFORMERS
3. Give the emf equation of a transformer and define each term (April –99) Emf
induced in primary coil E1 = 4.44 fΦ mN1 volt
Emf induced in secondary coil E2 = 4.44fΦ mN2 volt
4. Does the transformer draw any current when secondary is open ? Why ?
Yes,it (primary) will draw the current from the main supply in order to magnetise the
core and to supply iron and copper losses on no load . There will not be any current in the
secondary since secondary is open.
12. Explain on the material used for core construction. (Oct 02)
The core is constructed of transformer sheet steel laminations assembled to provide a
continuous magnetic path with a minimum of air gap included. The steel used is of high silicon
content sometimes heat-treated to produce a high permeability and a low hysteresis loss at the
usual operating flux densities. The eddy current loss is minimized by laminating the core, the
laminations being insulated from each other by light coat of core-plate vanish or by an oxide
layer on the surface .the thickness of laminations varies from 0.35 mm for a frequency of 59 Hz
and 0.5 mm for a frequency of 25 Hz.
14. How does change in frequency affect the operation of a given transformer?
With a change in frequency, iron loss, copper loss, regulation, efficiency and heating varies
and thereby the Operation of the transformer is affected
15. What is the angle by which no-load current will lag the ideal applied voltage?
In an ideal transformer, there are no copper loss and no core loss,(i.e. loss free core).The
no load current is only magnetizing current. Therefore the no-load current lags behind by an
angle of 90°. However the windings possess resistance and leakage reactance and therefore the
no-load current lags the applied voltage slightly less than 90°.
19. A 1100/400 V, 50 Hz single phase transformer has 100 turns on the secondary
winding. Calculate the number of turns on its primary.
We know that V1 / V2 = k = N2 / N1
Substituting in above equation 400/1100 = 100/N1 N1
= 100/400 x 1100
= 275 turns.
20. What are the functions of no-load current in a transformer?
No-load current produces flux and supplies iron loss and copper loss on no-load.
21. How will you transfer the quantities from one circuit to another circuit in a
transformer?
1.Secondary to primary 2.Primary to secondary
Symbol Value Symbol Value
V2 V2/k VL kV1 I
2 kI2 IL I1 /k
R2 R2/k2 RL k2R1
X2 X2/k2 XL’ k2X1
ZL ZL/k2
22. Can the voltage regulation of a transformer go to negative? If so under what
condition?
Yes. If the load has leading power factor.
24. What is the purpose of providing ‘taps’ in transformer and where these are provided? In
order to attain the required voltage, ‘taps’ are provided. Normally it will be
provided at low voltage sides
25. Give the method of reducing iron loss in a Transformer (Oct –98)
The iron losses are minimized by using high-grade core material like silicon steel having
very low hysteresis loop and by manufacturing the core in the form of laminations.
UNIT III
ELECTROMECHANICAL ENERGY CONVERSION AND CONCEPT IN
ROTATING MACHINES
28. What is an electromechanical system?
The system in which the electromechanical energy conversion takes palace via the
medium of a magnetic or electric field is called electromechanical system.
35. Draw the graphical relation between field energy and coenergy
(iii) As high frequency harmonics get eliminated, eddy current and hysteresis losses
which depend on frequency also get minimized. This increases the efficiency.
41. Explain the following terms with respect to rotating electrical machines.
a) Pole pitch
b) Chording angle.
Pole pitch: The distance between the centres of two adjacent poles is called pole
pitch.One pole pitch is equal to 180 electrical degrees. It is also defined as the number of slots
per pole.
Chording angle: It is defined as that angle by which the coil pitch departs from 180
electrical degrees.
UNIT IV
DC GENERATOR
49. How will you change the direction of rotation of a d.c motor?
Either the direction of the main field or the direction of current through the
armature conductors is to be reserved.
51. Under what condition the mechanical power developed in a dc motor will be
maximum?
Condition for mechanical power developed to be maximum is Eb
= Ua /2
or I a= Ua / 2Ra
52. What is the function of a no-voltage release coil provided in a dc motor starter? As long as
the supply voltage is on healthy condition the current through the NVR coil produce enough
magnetic force of attraction and retain the starter handle in the ON position against spring
force. When the supply voltage fails or becomes lower than a prescribed value the
electromagnet may not have enough force and the handle will come back to OFF position due
to spring force automatically. Thus a no-voltage or under voltage protections given to the
motor.
53. Name the two types of automatic starters used for dc motors.
Back emf type starter
Time delay type starter
54. Enumerate the factors on which the speed of a dc motor depends. N =
1/CE (Ua-IaRm)/ф
The speed of dc motor depends on three factors.
Flux in the air gap
Resistance of the armature circuit
Voltage applied to the armature
55. List the different methods of speed control employed for dc series motor(APR’04,AU) Field
diverter method
Regrouping of field coild\s
Tapped field control
Armature resistance control
Armature voltage control for single motor
Series parallel control for multiple identical motors
58. Under what circumstances does a dc shunt generator fail to build up?
Absence of residual flux.
Initial flux set up by the field winding may be in opposite direction to
residual flux
Shunt filed circuit resistance may be higher than its critical field
Resistance
Load circuit resistance may be less than its critical load resistance.
UNIT V
DC MOTOR
59. To what polarity the interpoles excited in dc motors?
For motor operation the polarity of the interpoles must be that of the previous main pole
along the direction of rotation.
67. What type of DC motors are suitable for various torque operations?
1. DC series motor
2. DC cumulatively compound motor
24. Define speed regulation.
% Speed regulation= NL speed- FL speed x 100 FL
speed
68. What are the performance curves?
Output Vs torque
Output Vs current
Output Vs speed
Output Vs efficiency