Technical data sheet                                                               NR24A-SR
Modulating rotary actuator for ball valves
• Torque motor 10 Nm
• Nominal voltage AC/DC 24 V
• Control modulating 2...10 V
• Position feedback 2...10 V
 Technical data
                                 Electrical data    Nominal voltage                               AC/DC 24 V
                                                    Nominal voltage frequency                     50/60 Hz
                                                    Nominal voltage range                         AC 19.2...28.8 V / DC 19.2...28.8 V
                                                    Power consumption in operation                2.5 W
                                                    Power consumption in rest position            0.4 W
                                                    Power consumption for wire sizing             5 VA
                                                    Connection supply / control                   Cable 1 m, 4 x 0.75 mm²
                                                    Parallel operation                            Yes (note the performance data)
                                Functional data     Torque motor                                  10 Nm
                                                    Operating range Y                             2...10 V
                                                    Input Impedance                               100 kΩ
                                                    Position feedback U                           2...10 V
                                                    Position feedback U note                      Max. 1 mA
                                                    Position accuracy                             ±5%
                                                    Manual override                               with push-button, can be locked
                                                    Running time motor                            90 s / 90°
                                                    Sound power level, motor                      35 dB(A)
                                                    Position indication                           Mechanically, pluggable
                                    Safety data     Protection class IEC/EN                       III, Safety Extra-Low Voltage (SELV)
                                                    Power source UL                               Class 2 Supply
                                                    Degree of protection IEC/EN                   IP54
                                                    Degree of protection NEMA/UL                  NEMA 2
                                                    Enclosure                                     UL Enclosure Type 2
                                                    EMC                                           CE according to 2014/30/EU
                                                    Certification IEC/EN                          IEC/EN 60730-1 and IEC/EN 60730-2-14
                                                    Certification UL                              cULus according to UL60730-1A, UL60730-2-14
                                                                                                  and CAN/CSA E60730-1
                                                                                                  The UL marking on the actuator depends on
                                                                                                  the production site, the device is UL-compliant
                                                                                                  in any case
                                                    Mode of operation                             Type 1
                                                    Rated impulse voltage supply / control        0.8 kV
                                                    Pollution degree                              3
                                                    Ambient temperature                           -30...50°C
                                                    Storage temperature                           -40...80°C
                                                    Ambient humidity                              Max. 95% RH, non-condensing
                                                    Servicing                                     maintenance-free
                                        Weight      Weight                                        0.75 kg
www.belimo.com                                     NR24A-SR • en-gb • 2021-04-23 • Subject to change                                        1/3
                                                      Technical data sheet                                                                 NR24A-SR
 Safety notes
                                                    • This device has been designed for use in stationary heating, ventilation and air-conditioning
                                                      systems and must not be used outside the specified field of application, especially in aircraft or
                                                      in any other airborne means of transport.
                                                    • Outdoor application: only possible in case that no (sea) water, snow, ice, insolation or
                                                      aggressive gases interfere directly with the device and that it is ensured that the ambient
                                                      conditions remain within the thresholds according to the data sheet at any time.
                                                    • Only authorised specialists may carry out installation. All applicable legal or institutional
                                                      installation regulations must be complied during installation.
                                                    • The switch for changing the direction of rotation may only be operated by authorised
                                                      specialists. The direction of rotation must not in particular be reversed in a frost protection
                                                      circuit.
                                                    • The device may only be opened at the manufacturer's site. It does not contain any parts that
                                                      can be replaced or repaired by the user.
                                                    • Cables must not be removed from the device.
                                                    • The device contains electrical and electronic components and must not be disposed of as
                                                      household refuse. All locally valid regulations and requirements must be observed.
 Product features
                             Mode of operation       The actuator is connected with a standard modulating signal of 0...10 V and drives to the
                                                     position defined by the positioning signal. Measuring voltage U serves for the electrical display
                                                     of the valve position 0.5...100% and as slave control signal for other actuators.
                     Simple direct mounting          Straightforward direct mounting on the ball valve with only one central screw. The assembly
                                                     tool is integrated in the plug-in position indication. The mounting orientation in relation to the
                                                     ball valve can be selected in 90° steps.
                               Manual override       Manual override with push-button possible (the gear is disengaged for as long as the button is
                                                     pressed or remains locked).
                 Adjustable angle of rotation        Adjustable angle of rotation with mechanical end stops.
                    High functional reliability      The actuator is overload protected, requires no limit switches and automatically stops when the
                                                     end stop is reached.
 Accessories
                           Electrical accessories    Description                                                                    Type
                                                     Feedback potentiometer 10 kΩ add-on                                            P10000A
                                                     Feedback potentiometer 1 kΩ add-on                                             P1000A
                                                     Feedback potentiometer 140 Ω add-on                                            P140A
                                                     Feedback potentiometer 200 Ω add-on                                            P200A
                                                     Feedback potentiometer 2.8 kΩ add-on                                           P2800A
                                                     Feedback potentiometer 5 kΩ add-on                                             P5000A
                                                     Feedback potentiometer 500 Ω add-on                                            P500A
                                                     Auxiliary switch 1 x SPDT add-on                                               S1A
                                                     Auxiliary switch 2 x SPDT add-on                                               S2A
 Electrical installation
                                                     Supply from isolating transformer.
                                                     Parallel connection of other actuators possible. Observe the performance data.
                                                     Direction of rotation switch is covered. Factory setting: Direction of rotation Y2.
www.belimo.com                                      NR24A-SR • en-gb • 2021-04-23 • Subject to change                                            2/3
                                              Technical data sheet                                                  NR24A-SR
 Wiring diagrams
 AC/DC 24 V, modulating                                               Override control (frost protection circuit)
                                  Cable colours:
                                  1 = black
                                  2 = red
                                  3 = white
                                  5 = orange
 Dimensions
                     Dimensional drawings
 Further documentation
                                             • The complete product range for water applications
                                             • Data sheets for ball valves
                                             • Installation instructions for actuators and/or ball valves
                                             • General notes for project planning
www.belimo.com                              NR24A-SR • en-gb • 2021-04-23 • Subject to change                           3/3