Technical data sheet                                                          LF230-S
Spring-return actuator with emergency
control function for adjusting dampers
in technical building installations
•	 Air damper size up to approx. 0.8 m²
•	 Nominal torque 4 Nm
•	 Nominal voltage AC 230 V
•	 Control Open-close
•	 With integrated auxiliary switch
 Technical data
                         Electrical data    Nominal voltage                             AC 230 V
                                            Nominal voltage frequency                   50/60 Hz
                                            Nominal voltage range                       AC 198...264 V
                                            Power consumption in operation              5 W
                                            Power consumption in rest position          3 W
                                            Power consumption for wire sizing           7 VA
                                            Power consumption for wire sizing note      Imax 150 mA @ 10 ms
                                            Auxiliary switch                            1 x SPDT, 0...100%
                                            Switching capacity auxiliary switch         1 mA...3 (0.5 inductive) A, AC 250 V
                                            Connection supply / control                 Cable 1 m, 2 x 0.75 mm²
                                            Connection auxiliary switch                 Cable 1 m, 3 x 0.75 mm²
                                            Parallel operation                          Yes (note the performance data)
                       Functional data      Torque motor                                Min. 4 Nm
                                            Torque spring return                        Min. 4 Nm
                                            Direction of motion motor                   Selectable by mounting L / R
                                            Direction of motion emergency control       Selectable by mounting L / R
                                            function
                                            Manual override                         No
                                            Angle of rotation                       Max. 95°
                                            Angle of rotation note                  Adjustable 37...100% with integrated
                                                                                    mechanical limitation
                                            Running time motor                      40...75 s / 90°
                                            Running time emergency control position <20 s / 90°
                                            Running time emergency setting position <20 s @ -20...50°C / <60 s @ -30°C
                                            note
                                            Sound power level motor                 50 dB(A)
                                            Spindle driver                          Universal spindle clamp 8...16 mm
                                            Position indication                     Mechanical
                                            Service life                            Min. 60,000 emergency positions
                                 Safety     Protection class IEC/EN                     II Protective insulated
                                            Protection class auxiliary switch IEC/EN    II Protective insulated
                                            Degree of protection IEC/EN                 IP54
                                            EMC                                         CE according to 2004/108/EC
                                            Low voltage directive                       CE according to 2006/95/EC
                                            Certification IEC/EN                        IEC/EN 60730-1 and IEC/EN 60730-2-14
                                            Mode of operation                           Type 1.B
                                            Rated impulse voltage supply / control      4 kV
                                            Rated impulse voltage auxiliary switch      4 kV
                                            Control pollution degree                    3
                                            Ambient temperature                         -30...50°C
                                            Non-operating temperature                   -40...80°C
                                            Ambient humidity                            95% r.h., non-condensing
                                            Maintenance                                 Maintenance-free
                                Weight      Weight approx.                              1.8 kg
www.belimo.eu                              LF230-S • en-gb • 2015-10-07 • subject to changes                                     1
                                                   Spring-return actuator, Open-close, AC 230 V, 4 Nm, With
LF230-S                                            integrated auxiliary switch
    Safety notes
                                                  •	 The device must not be used outside the specified field of application, especially not
                                         !           in aircraft or in any other airborne means of transport.
                                                  •	 Outdoor application: only possible in case that no (sea)water, snow, ice, insolation
                                                     or aggressive gases interfere directly with the actuator and that is ensured that the
                                                     ambient conditions remain at any time within the thresholds according to the data
                                                     sheet.
                                                  •	 Caution: Power supply voltage!
                                                  •	 Only authorised specialists may carry out installation. All applicable legal or
                                                     institutional installation regulations must be complied during installation.
                                                  •	 The device may only be opened at the manufacturer’s site. It does not contain any
                                                     parts that can be replaced or repaired by the user.
                                                  •	 Cables must not be removed from the device.
                                                  •	 To calculate the torque required, the specifications supplied by the damper
                                                     manufacturers concerning the cross-section, the design, the installation site and the
                                                     ventilation conditions must be observed.
                                                  •	 The device contains electrical and electronic components and must not be disposed
                                                     of as household refuse. All locally valid regulations and requirements must be
                                                     observed.
    Product features
                          Mode of operation       The actuator moves the damper to the operating position at the same time as
                                                  tensioning the return spring. The damper is turned back to the safety position by spring
                                                  energy when the supply voltage is interrupted.
                    Simple direct mounting        Simple direct mounting on the damper spindle with an universal spindle clamp,
                                                  supplied with an anti-rotation device to prevent the actuator from rotating.
                   High functional reliability    The actuator is overload protected, requires no limit switches and automatically stops
                                                  when the end stop is reached.
              Adjustable angle of rotation        Adjustable angle of rotation with mechanical end stops.
                       Flexible signalization     With adjustable auxiliary switch (0 ... 100%)
    Accessories
                                                  Description                                                               Type
                     Electrical accessories       Auxiliary switch, 2 x SPDT                                                S2A-F
                                                  Feedback potentiometer, 200 Ohm, incl. installation accessories           P200A-F
                                                  Feedback potentiometer 1 kOhm, incl. installation accessories             P1000A-F
                                                  Description                                                               Type
                   Mechanical accessories         Shaft extension 170 mm, for damper spindles Ø 6...20 mm                   AV6-20
                                                  Shaft extension 250 mm, for damper spindles Ø 8...25 mm                   AV8-25
                                                  Spindle clamp, for damper spindles Ø 16...20 mm                           K6-1
                                                  Straight ball joint with M8, suitable for damper crank arms KH8           KG10A
                                                  Angled ball joint with M8, suitable for damper crank arms KH8             KG8
                                                  Damper crank arm, for damper spindles                                     KH8
                                                  Actuator arm, for damper spindles Ø 8...16 mm                             KH-LF
                                                  Angle of rotation limiter, for LF with end stop                           ZDB-LF
                                                  Additional shaft adapter 4-kt. 8x8mm for LF                               ZF8-LF
                                                  Mounting kit for linkage operation LF..                                   ZG-LF1
                                                  Mounting kit for linkage operation LF.., suitable for damper spindles Ø   ZG-LF3
                                                  10...18 mm
2                                                LF230-S • en-gb • 2015-10-07 • subject to changes                           www.belimo.eu
                                                     Spring-return actuator, Open-close, AC 230 V, 4 Nm, With
 LF230-S                                             integrated auxiliary switch
 Electrical installation
                                         Notes           •	 Caution: Power supply voltage!
     !                                                   •	 Parallel connection of other actuators possible. Observe the performance data.
Wiring diagrams
AC 230 V, open-close
N    L
                                        Cable colours:
 1   2         S1 S2 S3
                                        1 = blue
                                        2 = brown
                                        S1 = white
                0...100%                S2 = white
                                        S3 = white
 Dimensions [mm]
Spindle length                                       Dimensional drawings
                           Min. 84 
                                                     18.5
         L
                           Min. 20 
                                                                                                                82
                                                     57
Clamping range
                                                     6.5
             8 ...16          8 ...16
                                                     80
                                                                                                                98
                                                                25    18
                                                                                  111
                                                                                  125
                                                                                  130
                                                                                  181