XV105D Fan Speed Controller: General Warning 1.1 Please Read Before Using This Manual 5 Direct and Inverse Action

This document provides instructions for a fan speed controller. It can control fan speed based on temperature, voltage, or current inputs. The minimum and cut-off fan speeds can be adjusted. It has direct or inverse control modes which increase or decrease the fan speed as the input increases.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views2 pages

XV105D Fan Speed Controller: General Warning 1.1 Please Read Before Using This Manual 5 Direct and Inverse Action

This document provides instructions for a fan speed controller. It can control fan speed based on temperature, voltage, or current inputs. The minimum and cut-off fan speeds can be adjusted. It has direct or inverse control modes which increase or decrease the fan speed as the input increases.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Trimmer V min: by turning clockwise this trimmer, the minimum

XV105D fan speed can be changed from 0 to 50% of the


maximum voltage output.
FAN SPEED CONTROLLER Trimmer Cut Off: by turning clockwise this trimmer, the fan cut-
off can be changed from 10 to 30% of the maximum
voltage output.
GENERAL WARNING
Green LED: this LED signals when the load is being controlled.
1.1 Please read before using this manual 5 DIRECT AND INVERSE ACTION
 This manual is part of the product and should be kept near the Direct action: if the input signal increases, the voltage output
instrument for easy and quick reference. proportionally increases (condensing or cooling applications).
 The instrument shall not be used for purposes different from
those described hereunder. It cannot be used as a safety device.
 Check the application limits before proceeding.
 Dixell Srl reserves the right to change the composition of its
products, even without notice, ensuring the same and unchanged
functionality.

1.2 Safety Precautions


 Check the supply voltage is correct before connecting the
instrument.
 Do not expose to water or moisture: use the controller only within
the operating limits avoiding sudden temperature changes with
high atmospheric humidity to prevent formation of condensation If the input signal is higher than the Set, the output signal is 230
 Warning: disconnect all electrical connections before any kind of Volt (fans are running at the maximum speed). When the signal
maintenance. decreases and enters the range between the Set and Set-Diff the
 The instrument must not be opened. output signal follows the temperature variation. Below the Set-diff
 In case of failure or faulty operation send the instrument back to value the output signal is always 0V (if no Vmin has been set).
the distributor or to “Dixell S..r.l.” (see address) with a detailed
description of the fault. Inverse action: if the input signal increases, the voltage output
 Consider the maximum power of the load (see Technical Data). proportionally decreases (evaporating or heating applications).
 Ensure that the wires for probes, loads and the power supply are
separated and far enough from each other, without crossing or
intertwining.
 Fit the instrument away from heater sources and be sure to have
sufficient air flow to allow a good thermal exchange.
2 GENERAL DESCRIPTION
Models XV105D, din rail format, are speed controllers suitable for
industrial and refrigeration applications in particular to control the air
flow in condensing and evaporating processes. By closing an external
jumper it is possible start the fan at the maximum speed for 10
seconds. The input signal can be ordered choosing among
temperature probe NTC, 4/20mA or 0/1Vdc and 0/10Vdc signals.
If the input signal is lower than the Set, the output signal is 230
3 OPERATING
Volt (fans are running at the maximum speed). When the signal
Example of functioning with a condensing unit (direct): the probe must increases and enters the range between the Set and Set+Diff the
be fit where the sensor detects the most critic place of the condenser. output signal follows the temperature variation. Above the
Calibrate the Set trimmer to the temperature (or pressure) at which Set+diff value the output signal is always 0 Volt (if no Vmin has
the fan runs at the maximum speed. Then calibrate the Diff trimmer to been set).
set the temperature (or pressure) differential at which the fan is 6 CONTROLS
stopped. E.g. if the Set is 40°C and the Diff is 10°C, when the
temperature is above 40° the fan runs at maximum speed, if the 6.1 Minimum fan speed
temperature is between 30° and 40° the fan speed is controlled, and To avoid that the fan can be damaged with low voltage output, it
below 30°C the fan is stopped. is possible set a minimum voltage (minimum speed). The range
is selectable from 0 to 50% of the power supply.
4 COMMANDS ON FRONT PANEL
6.2 Cut-off function
Trimmer SET: by turning clockwise this trimmer, the set is changed
from the minimum to the maximum value. See the default The Cut-off function drastically reduces the output to 0V, when
value table for the range. the voltage on the load is lower than a percentage set with this
trimmer. The range is selectable from 10 to 30% of the power
Trimmer differential: by turning clockwise this trimmer, the
supply. Example: if set to the middle position (15%), when the
differential is changed from the minimum to the maximum
value. See the default value table for the range.

1592005000 XV105D GB R1.0 22.06.2012 XV105D 1/2


voltage on the load is lower than 15% of 230V, the fan immediately
are stopped.
6.3 MAXIMUM FAN SPEED AT START UP
By closing the external jumper at terminals 13 and 14, each time the
fan restarts, for 10 seconds it will run at maximum speed.
6.4 Trigger signal
To control loads having more than 500W an external power module
can be connected at terminals 15 and 16.
6.5 Changing the action type with current or
voltage input models
All the instruments with 4/20mA or 0/1Vdc and 0/10Vdc inputs can be
changed from direct to inverse actions. By removing completely the
front panel, an available jumper is fit on the back of the panel circuit.
Jumper closed = direct action, jumper open = reverse action.
7 INSTALLING AND MOUNTING 12 DEFAULT VALUES
The instrument shall be mounted on an omega DIN rail. The Code Input Action Range Diff
temperature range allowed for correct operation is 0 - 60 °C. Avoid XV105D – 50DNO NTC Direct 060°C 130°C
places subject to strong vibrations, corrosive gases, excessive dirt or XV105D – 50RNO NTC Inverse -40+10°C 130°C
humidity. The same recommendations apply to probes. Let air XV105D – 50DAO 4/20mA Direct 420mA 10mA
circulate nearby the instrument.
XV105D – 50RAO 4/20mA Inverse 420mA 110mA
8 ELECTRICAL WIRES XV105D – 50DVO 0/1Vdc Direct 01Vdc 00,5V
The instruments are provided with screw terminal block to connect XV105D – 50RVO 0/1Vdc Inverse 01Vdc 00,5V
cables with a cross section up to 2,5 mm2. Before connecting cables XV105D – 50DWO 0/10Vdc Direct 010Vdc 05V
make sure the power supply complies with the instrument’s XV105D – 50RWO 0/10Vdc Inverse 010Vdc 05V
requirements. Separate the input signal cable from the power supply
cables, from the outputs and the power connections. Do not exceed
the maximum current allowed on the output terminals.
9 OUTPUT STATUS FOR FAULTY PROBE
Open probe (direct action) 0 Volt
Short circuited probe (direct action) 0 Volt
Open probe (inverse action) 230 Volt
Short circuited probe (inverse action) 230 Volt
10 TECHNICAL DATA
Housing: self extinguishing ABS.
Case: 4 DIN modules 70x85 mm; depth 61mm.
Mounting: DIN RAIL mounted in a omega (3) din rail .
Frontal protection: IP40
Connections: Screw terminal block  2,5 mm2 wiring.
Power supply: 230Vac,  10% 50/60Hz.
Power absorption: 1VA max.
Maximum load: 500W.
Input: NTC or 4/20mA or 0/1 and 0/10Vdc.
Range: depending on the probe.
Operating temperature: 060 °C.
Storage temperature: -3085 °C.
Relative humidity: 2085% (not condensing).

11 CONNECTIONS

1592005000 XV105D GB R1.0 22.06.2012 XV105D 2/2