Medium Voltage RMU Solutions
Medium Voltage RMU Solutions
Tri-MEC
Ring Main Units
Medium Voltage Secondary Distribution
Ring Main Units Up to 24kV, SF6-Insulated
Electric Equipment
Ring Main Units
Technology
Safety
Durability and usefulness
Saving Cost
CONTENTS: Applications 4
Features 5
Configurations 6
Modules 8
SF6-Insulated RPL 13
RVB 14
RBR 15
Cable termination 16
Ring switch / Circuit breaker 16
Fuse-switch 16
Pannel connection 18
Accessories 19
Installation 24
Technical data 25
Quality assurance 26
Ring Main Units
Applications Tri-MEC
Substation
Commercial &
Transmission Industrial
line customers
Power plant
4
Features
Technology
•Metal enclosed unit for indoor installation and type tested.
•Insulated by SF6 Gas
•Independent of climate.
•ON-OFF-EARTH, three position load break switch.
Safety
•Approachable and operable safely in the presence of power in the cables.
•Clear indication of operation status via mimic diagram on front panel.
•Fully automatic interlocking system.
•Voltage detector to check the presence of voltage in the cable.
Saving cost
•Only a little maintenance is required except replacement of HRC Power fuse after installation.
•Compact design that requires minimum space to install and operate locally is
main advantage especially where the space is limited.
•Materials can be recycled after the end of its service life.
5
Ring Main Units
Configurations
General
Tri-MEC RMU is an extensible and non-extensible ring main unit for the secondary distribution
network. Tri-MEC RMU can be supplied in various different configurations suitable for most
switching applications in 24 kV distribution networks.
When combined with the Tri-MEC RMU, they represent a complete solution for 24kV
secondary distribution networks. Tri-MEC RMU is a completely sealed system with a stainless
steel tank, gas tight metal enclosure, containing all the live parts, Switching-disconnector, earth
switch, Fuse switch, the circuit breaker.
A sealed steel tank filled with SF6 gas ensures a high level of reliability as well as safety and a
maintenance-free system. The Tri-MEC RMU offers the user a choice of either a switch-
disconnector combined with fuse or circuit breaker with relay for protection of the transformer.
Tri-MEC RMU can be controlled completely with an feeder remote unit. Most of this switchgear
exists in version that are extensible on the right or on both sides, in order to provide for future
development.
R
RMU L: LBS R: Rising
F: Fuse S: Standard
B: Breaker
Non-Extensible type
RPS
<2 LBS + 1 Fused LBS>
VD Fuse VD
1502
706
Weight: 400kg
RPF(1R1F)
<1 Fused LBS + Bus rising>
* S LBS
1537
Fuse VD
695
SA *
1061 706
880
Extensible type
RPL <LBS Panel>
LBS
1750
VD
0
456 73
Weight: 210kg
* S LBS
1750
Fuse
683
611 730
765
Weight: 275kg
VCB Trip
1750
2×CT OC
*
520 730
Weight: 260kg
VD
456 730
Note) *: Option
7
Ring Main Units
Modules
LBS
VD
< ON position > < OFF position > < EARTH position >
EARTHING
EARTHING LOAD BREAK
LOAD EARTHING
EARTHING LOAD BREAK
LOAD EARTHING
EARTHING LOAD BREAK
LOAD
SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH
Earth
Ear th Close Earth
Ear th Close Earth
Ear th Close
Feature
•Three position load break switch and earthing switch.
•Indicator of switch position for load break switch and earthing switch.
•Voltage indicator lamp on panel makes it possible to check the presence of voltage in the cables.
•Pressure gage indicates status of SF6 gas tank and make it check leakage of gas.
•Intelligent interlock system
: To switch to Earth position, it should pass "OFF" position from "ON" position
•Applied high-speed rotary puffer type for extinction of arc.
•Dead front structure: It prevents an accident of touching because the live part is not exposed.
•Electrical (Remote/Local)operation :
operated by controller which can communicate with FRU (Feeder Remote Unit)
•Busbars, 630A
8
Fuse-switch module (RPF)
A
*
S LBS
B
Fuse
Note) *: Option
< ON position > < OFF position > < EARTH position >
B
B C
Open Earth
Ear th Open Earth
Ear th Open Earth
Ear th
EARTHING
EARTHING SWITCH EARTHING
EARTHING SWITCH EARTHING
EARTHING SWITCH
Feature
•Fuse rating: 24kV, Max 63A HRC power fuse
•Indicator of switch position for load break switch and earthing switch
•The Fuses conforming to DIN 43625 are used.
•Automatically tripped to protect from fault current when a fuse is blown
•Applied high-speed rotary puffer type for extinction of arc.
•Dead front structure: It prevents an accident of touching because the live part is not exposed.
•Busbars 200A
•Option: CTD (Condensor Trip Device)
9
Ring Main Units
Modules
VCB Trip
2×CT OC
*
Note) *: Option
Feature
•200A vacuum circuit breaker
•Rated breaking time: 3cycle
•Latched mechanism - close and open coil
•Protection as specified by customers
•Motor charge type and Manual charge type
•Option:CTD(Capacitor Trip Device), OCR
10
Outer assembly(Non-Extensible)
❶
❾
❿
❸
⑮ ❼
⑯ ⑰
11
Ring Main Units
Outer assembly(Extensible)
RPF (Fuse-switch)
⑲ ❶
❺
⑭
⑫
❹
⑬ ⑪
❽ ❻
12
RPL (Ring switch)
❶
⑭
❽
❾
❿ ❷
❻ ❺
❶ 630A bushing for connector ❻ Earth connection Hole ⑪ Gas pressure gauge
❷ 600A bushing ❼ Upper side cover ⑫ Fixing bolt for cover
LBS
❸ Chamber ❽ Operation mechanism ⑬ Earthing busbar
❹ Elbow connection (option) ❾ Nameplate ⑭ Lift lug
VD
❺ Cable clamp ❿ Voltage detector
13
Ring Main Units
Outer assembly(Extensible)
❽ ❾
❹
❷
❶ 630A bushing for connector ❻ Gas pressure switch (Option) ⑪ Voltage detector
Trip ❷ 630A bushing ❼ Upper side cover ⑫ Gas pressure gauge
VCB
❸ Chamber ❽ Operation mechanism ⑬ CT
OC ❹ Elbow connection (Option) ❾ Gas filling valve
2×CT
* ❺ Cable clamp ❿ Nameplate
Note) *: Option
14
RBR (Bus rising)
⑫ ❻
❼ ❸
❹ ❺
VD
15
Ring Main Units
Cable termination
❽
❻ ❼ ❿ ❸ ❾
❺
Semi-permanent, crimped-bolted connector sized for the ❻ Voltage test point cap ❿ Threaded stud
specific conductor. Crimped on with standard tools and Molded conduction rubber cap fits over the test point and
dies, Also used in the 650Y splice. A removable threaded stud is included with every 655LR
onto the connector housing.
and K655LR.
❸ Molded conductive shield ❼ Voltage test point
Outer jacket of 1/8 think molded conduction peroxide- The 1 hex nut located on the top of the insulation plug
cured EPDM provides a virtually in destructible ground allows the circuit to be tested without disturbing the
shield for true dead-front construction. A patented ELASTI- connection. The nut is fully insulated from the conductor
and pick up capacitance voltage. A torque wrench with a 1
MOLD feature.
hex socket attachment is required during installation.
Fuse-switch
The straight receptacles are fully-shield, fully-submersible and separable insulated connectors. These will accommodate
conductor sizes of No. 4 solid through 4/0 stranded and cable insulation diameters from 0.495" through 0.985".
Molded conductive insert
Conductor contact
Bushing Bail
for load tip
side
Wire
Straight receptacle housing
Grounding eye
Straight
receptacle Bail
Nut
Cable
"A"
Bail plate
16
Cable termination
17
Ring Main Units
Pannel connection
Plug
Clamping bolt
Washer
Spacer Cross connector
Mold cable
End connector
Bushing
18
Accessaries
Fuse
Features
1. The LS HRC Power Fuses belong to the PRIME MEC
series.
It interrupts high currents before the peak value and
therefore cuts down the required withstand capacity of
the associated equipment on the electric system.
2. Though small in size, it has a high breaking capacity and
its enclosed type is suitable for use inside of the panel
board.
3. PRIME-MEC fuses are equipped with striker pins for
trip indicators as well as for inflicting impulse to trip
link of related load break switches.
100A 20
20
75A
Operating time(sec.) →
10 63A 10
8 8
6 50A 6
4 40A 4
30A
2 2
20A
1 10A 1
0.8 0.8
5A 0.6
0.6
0.4 0.4
0.2 0.2
0.1 0.1
0.08 0.08
0.06 0.06
0.04 0.04
0.02 0.02
0.01 0.01
20
40
60
80
400
800
200
600
4000
100
2000
4
6000
8000
2
1000
10000
10
6
0.1
0.2
2
0.02
0.04
0.06
0.08
0.4
0.6
0.8
6
8
10
100
40
4
20
19
Ring Main Units
Accessaries
Vacuum Interrupter
In the closed position, normal current flows
through the interrupter. When a fault occurs
and interruption is required, the contacts are
quickly separated.
Current path
The arc drawn between the surfaces of
contacts is rapidly moved around the slotted
contact surface by self induced magnetic
Driving force
effects, preventing gross contact erosion and
on the high the formation of hot spot on the surface.
current ARC The arc burns in an ionized metal vapor,
which condenses on the surrounding metal
ARC
shield. At current zero the arc extinguishes
and vapor production ceases.
The metal vapor plasma is very rapidly
dispersed, cooled, recombined, and deionized,
and the metal vapor products are quickly
condensed so that the contacts withstand the
Figure 1. Current flow and driving
force on arc for spiral
transient recovery voltage.
contact
Fault
current
Voltage Phenomena
(ⅰ) Arc reignition
(ⅱ) Restrikes
(ⅲ) B. I. L
(ⅳ) AC voltage
withstand
Recovery
voltage
20
Relay
GIPAM
DPR
Devices
Protection/monitoring Code
GIPAM DPR-011S DPR-111S DPR-211S DPR-311S DPR-411S DPR-511S
Three-phase overcurrent 50-51 ○ ○ ○
Zero-sequence overcurrent 50N-51N ○ ○
Selective zero-sequence overcurrent 67G ○ ○
Overvoltage 59 ○ ○ ○
Undervoltage 27 ○ ○ ○
Zero-sequence overvoltage 59N ○ ○
Measuring ○
21
Ring Main Units
Accessaries
Current transformer
Max. system voltage kV 0.6
Secondary current A 5
Rated burden VA 10
Rated frequency Hz 60
Polarity Subtractive
Surge arrester
The 273ESA Elbow Arrester is combined with a loadbreak elbow connector interface.
Bushing
Bushing insert
Probe Spade terminal Shelded elbow
Grounding eye
Cable adapter
Protective characteristics
Note1)
Duty cycle Maximum discharge voltage (kV crest) F.O.W. protective
MCOV
rating ×20 microsecond current wave
8× level
(kVrms)
(kVrms) 1.5kV 3kV 5kV 10kV 20kV (kV crest) Note2)
22
CTD (Condenser trip device)
(For discharge)
AC input DC output
CTD is built as standard in the contactor with
AC control of instantaneous excitation so that
the contactor can be tripped within 30 seconds in
the event of an electricity failure. The automatic
Control circuit diagram
trip circuit in the event of an electricity failure is
to be built by a customer.
Rating Description
Type CTD-100 CTD-200
Rated voltage Rated current (A) Rated voltage Rated current (A)
DC 24V 10 DC 24V 10
DC 110V 2.5 DC 110V 2.5
Note 1) Range of the normal operating voltage: 85~110% Note 1) Range of the normal operating voltage: 70~110%
2) DC 24V is the underdeveloped rating. 2) DC 24V is the underdeveloped rating.
Plug in type
07
08
09
10
11
01
02
03
04
05
06
12
13
14
17
18
19
23
Ring Main Units
Installation
R = 10D
D : Cable diameter
607
626
466
120
61.5
102 327 524 327 102 90.5 377 144 315 144 315
40
70.5 315
61.5
61.5
70.5 315
61.5
70.5 470
24
Technical data
Rated voltage up to kV 24
Electrical life E3
Mechanical life M1
25
Ring Main Units
Quality assurance
Seismic tests
Application standard: JEAG5003-1999
26
Norminals
Test Structural
excitation level(g) Direction Freq.(Hz) Waveforms Duration(S) Operability
category integrity
X/Y/Z
Resonance X
search 0.1/0.1/0.1 Y 0.5-30 Random 328 N/A N/A
test Z
Real Kobe
earthquake 0.3/0.3/0.15 XYZ Earth- 82 OK OK
test quake
0.3/0/0 X OK OK
0.3/0/0.15 XZ OK OK
5
0/0.3/0 Y OK OK
0/0.3/0.15 YZ OK OK
0.3/0/0 X OK OK
Sine 30 0.3/0/0.15 XZ Sine 30 OK OK
waves test 10
0/0.3/0 Y Wave Waves OK OK
0/0.3/0.15 YZ OK OK
0.3/0/0 X OK OK
37.8
0.3/0/0.15 XZ OK OK
0/0.3/0 Y OK OK
12.2
0/0.3/0.15 YZ OK OK
Resonance X
search 0.1/0.1/0.1 Y 0.5-30 Random 328 N/A N/A
test Z
Ordering Information
LGS R M 24 6 12 RT D
27
Leader in Electrics & Automation
� For your safety, please read user's manual thoroughly before operating.
� Contact the nearest authorized service facility for examination, repair, or adjustment.
� Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions � Any maintenance and inspection shall be performed by the personnel having expertise concerned.
www.lsis.biz