Service Manual: BMS Option For Daikin Water Chillers Gateway Address Card
Service Manual: BMS Option For Daikin Water Chillers Gateway Address Card
BMS
Gateway
t 1 2
ou m m t
int e ar ar se
pr lin al al rx tx re
Serial module
µchiller compact
4899
Service Manual
BMS option for Daikin water chillers
Gateway Address card
EKBMSMBA EKAC10A/30A/60A/120A
EKBMSBNA
ESIE99–03
Table of Contents
1
1 Introduction
Part 1
System Outline
3
1 System Outline
Table of Contents i
ESIE99–03
Part 2
1 Installation
2 Configuration
4
2.1 What Is in This Chapter? .........................................................................................2-13
2.2 Gateway Hardware Configuration............................................................................2-14
2.3 Gateway Software Configuration (MS–DOS program) ............................................2-17
2.4 How to Read or Adjust BMS Parameter Settings with the Small Daikin Controller .2-19
2.5 Settings: Direct and User Parameters in the Small Daikin Controller ......................2-20
5 2.6 How to Read or Adjust BMS Parameter Settings with the Large Daikin Controller .2-22
2.7 e User Settings Menu in the Large Daikin Controller ............................................2-23
ii Table of Contents
ESIE99–03
Part 3
Functional Description 1
1 General
4
3 Database
Part 4
1 Troubleshooting
1 Troubleshooting
3 Appendix A
Drawings
4 Index
iv Table of Contents
ESIE99–03 Introduction
1 Introduction
Introduction The purpose of the Daikin Gateway and address cards is to connect the Daikin water chillers to a larger
Building Management System (BMS).
Before starting up the system for the first time, ensure it has been properly installed.
You will find the following tools at the back of the manual:
■
■
A list of drawings. Refer to Appendix A Drawings.
An index. Refer to Index.
5
Usage of the The present manual gives you all the information you need to do the set up and the troubleshooting
manual related to the BMS option for Daikin water chillers. It is intended for and should only be used by
qualified engineers. It is not intended to replace technical know-how acquired through training and
experience.
Using icons Icons are used to attract the attention of the reader to specific information. The meaning of each icon
is described in the table below:
Type of
Icon Description
information
Caution A ‘caution’ is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, loose data, get an
unexpected result or has to restart (part of) a procedure.
Reference A ‘reference’ guides the reader to other places in this binder or in this
manual, where he/she will find additional information on a specific
topic.
v
Introduction ESIE99–03
In general, control of lights, elevators, water supply, air conditioning, power consumption, etc. can be
controlled by one control system.
Communication To implement correct communication between the connected subsystems and the control system, the
same communication protocol must be used.
3 Daikin BMS option The Daikin BMS option makes it possible to connect the Daikin chillers to a larger control system. The
tools necessary for this communication are the Gateway and the address cards.
After installing address cards and Gateway, the BMS must be programmed to be able to control and
monitor the chillers through the Gateway. To enable this configuration, individual parameters and
relative addresses of the chillers are described in this manual.
4 Illustration The illustration below gives an example of a centralized building control by a BMS.
pr
int
ou
t
lin
e
alar
m
1
alar
m
2
rx tx re
se
t Gateway
Serial module
µchiller compact
Daikin chiller
Daikin chiller
Daikin chiller
vi
ESIE99–03
1
Part 1
System Outline
Introduction The purpose of this part is to describe the communication network outline and the outline of the
individual parts.
3
Overview This part contains the following chapter:
11
Part 1
1
1 System Outline
Introduction The purpose of this chapter is to display a communication network example, to display the Gateway
and address card outline and to display the applicable Daikin chillers’ software versions.
3
Overview This chapter covers the following topics:
1.7 – Outline of the Address Cards in the EKAC30A/60A/120A kits page 1-11 5
The chillers, address cards and the Gateway are Daikin parts. The other equipment must be field
supplied.
Modbus-Jbus or
Field supplied equipment BACnet protocol
Daikin supplied equipment Gateway
Gateway
t 1 2
ou t
nt rm rm
4
e se
pri lin ala ala rx tx re
Serial module
µchiller compact
Address card
EKAC30A/60A Carel protocol
EUWA35HDZW1 or
EUW*100KXY1 or
EUWAT50KAY1 or ...
Address card
EUWA200KX or EKAC120A
EUW(*)120KX or ...
Parts and
description
The table below gives a description of the different parts of the communication outline:
1
Part Description
BMS The Building Management System is the customer’s control unit. Refer to
‘Building Management System (BMS)’ on page vi.
Gateway The Gateway is necessary as an interface between the chillers and the BMS.
It translates the Carel protocol, which is used by the address cards to the
Modbus-Jbus or BACnet protocol, used by the BMS. Refer to ‘Outline of the
Gateway’ on page 1-8.
Address Card The EKAC10A is a small module that should be clicked on a DIN-rail of the
EKAC10A chiller. It enables the chiller to communicate with the Gateway. Refer to ‘Out-
line of the Address Card in kit EKAC10A’ on page 1-10.
Address card
EKAC30A/60A
The EKAC30A/60A is a small electronic board that must be attached to the
main electronic board of the chiller. It enables the chiller to communicate with
3
the Gateway. Refer to ‘Outline of the Address Cards in the
EKAC30A/60A/120A kits’ on page 1-11.
Address Card The EKAC120A are two small electronic boards that must be attached to the
EKAC120A two electronic boards of the chiller. It enables the chiller to communicate with
the Gateway. Refer to ‘Outline of the Address Cards in the
EKAC30A/60A/120A kits’ on page 1-11. 4
Configuration PC The configuration PC is only necessary for configurating the Gateway. Once
this is done, it must be removed. Refer to ‘Connecting the Gateway to the
Configuration Computer’ on page 2-10.
To make it possible to connect 5–12HP chillers to a BMS system, a complete redesign of the switchbox
and the controller had to be done. This means that not on all chillers 5–12HP BMS is applicable.
The only changes for the larger chillers were made in the software. During the first year of production,
the chillers were not equipped with BMS-applied software. To ensure that the chiller is usable for the
BMS the software version must be checked first.
To change the EPROM for the correct software, refer to "Procedure for the Changing of the PCB" in
the relevant Daikin chiller service manual.
3 Address cards The table below displays the product range of the address cards:
Number of
Address card kit
Applicable chillers Software version addresses
name
per chiller
EKAC10A EUWA5-12H(C/D)(Z) – 1
4 EUWY5-10H(C/D)
EUW*40-100KX EPDAIECHWA
V2.012 or later
EUWA*160-200KX EPDAIECHZA
V2.012 or later
EUW*120-200KX
Communication is possible
Gateway name Supported protocol
with maximum ... addresses.
EKBMSMBA Modbus-Jbus 16
EKBMSBNA BACnet 8
BACnet and There are two major differences between the BACnet system and the Modbus-Jbus system:
Modbus-Jbus
differences BACnet system Modbus-Jbus system
The Gateway uses a standard RS-232 The Gateway uses a standard RS-232
(Point-to-Point) to communicate with the super-
visory BMS.
(Point-to-Point) or RS-485 (multidrop) to com-
municate with the supervisory BMS. 3
The Carel standard permits up to eight address The Carel standard permits up to 16 address
card connections to the Gateway. card connections to the Gateway.
Address of the The Gateway can be identified by the supervisor through the assignment of a univocal address within
Gateway the Modbus-Jbus and the BACnet network. The address of the Gateway is programmable during the
configuration.
4
Refer to ‘Gateway Software Configuration (MS–DOS program)’ on page 2-17.
Master-slave The management of the communication occurs in accordance with a master-slave structure in polling,
where the Gateway is the master and the address cards are the slaves. 5
The variable For each address card it is possible to manage up to:
database of each
■ 128 analog variables
address card
■ 128 integer variables
■ 200 digital variables.
The chillers’ variable databases are used as the point of reference for the supplier of the supervisory
BMS to assign a suitable meaning to the variables.
The variables can be read and/or written by the supervisory BMS according to the connected chiller
and/or the application program being used.
The supervisory BMS can’t assign a value to a variable in real mode. The command would be
ineffective.
The variables requested from the supervisory BMS, but not available in the chiller with installed
address card, are sent from the Gateway to the supervisory BMS with the value 0. The supervisory
BMS will have to manage them properly.
3 Illustration The illustrations below display a general overview of the Gateway and its dimensions.
DIMENSIONS
130
Gatew 226
4 ay
52
t
y
se
ewa
re
Gat 18
tx
m
1
rx
ar
m
al
ar
ut
al
e
to
lin
in
pr
20
20
5 105.4
7
166
Gateway
t 1 2
ou m m t modem config.
int e ar ar se cod.
pr lin al al rx tx re
Front view buttons The table below shows the different front view buttons:
Button Function
reset It will reset the Gateway and restart the internal configuration
and external inquiry process of the address cards.
Carel Net. 9-pin Address cards with RS-485 ‘Connecting an Address Card
female standard in the Serial Line’ on page 2-4
Illustration The illustration below shows the dimensions of the address card EKAC10A.
3
Serial module
88 44
µchiller
4 compact
70 64
5 Connections on the The address card, installed on the chiller’s DIN rail (1), has to be connected to:
address card
■ the chiller’s transfo for power supply (2)
■ the Gateway or another address card in the serial line (3)
■ the chiller’s controller (4).
(2) Refer to ‘Connecting the Address Card EKAC10A to the Transfo’ on page 2-7.
(3) Refer to ‘Connecting an Address Card in the Serial Line’ on page 2-4.
(4) Refer to ‘Connecting the Address Card EKAC10A to the Controller’ on page 2-6.
Address card kits The table below gives the address card kits and the applicable chillers:
and applicable
chillers The address card kit ... consist of ... Applicable chillers
M1
5
GROUND
RX+/TX+
RX-/TX-
43
JS2
5 70 5
Connections into To connect the address card into the serial line the following connections have to be made:
the serial line
■ from the address card to the chiller’s field rail (1)
■ from the field rail to the Gateway or another address card in the serial line (2).
(1) Refer to ‘Connecting the Address Card EKAC30A/60A/120A to the Field Rail’ on page 2-9.
(2) Refer to ‘Connecting an Address Card in the Serial Line’ on page 2-4.
11
4
Part 2
Installation
2
Introduction The purpose of this part is to tell you how to install, connect and configurate the system. The chillers’
set up may differ slightly depending on the model.
3
Refer to the relevant Daikin chiller service manual if the screens described in this manual differ too
much from the screens on the chiller’s controller.
Part 2
1
1 Installing and Connecting the System
2
1.1 What Is in This Chapter?
Introduction The purpose of this chapter is to tell you how to set up the system. The troubleshooting chapter refers
to this chapter to check correct installation and wiring.
3
Precautions
■
Strictly follow the instructions on the use of the relevant program during the configuration phase.
Keep the communication cables to link the chillers away from power cables to avoid interference.
5
Before installing Before installing the Gateway ensure you have installed the address cards correctly. Follow the
the Gateway instructions in the installation manuals of the address cards or use the pages listed in the table below.
1.4 – Connecting the Address Card EKAC10A to the Controller page 2-6
1.5 – Connecting the Address Card EKAC10A to the Transfo page 2-7
1.7 – Connecting the Address Card EKAC30A/60A/120A to the Field Rail page 2-9
Example The illustration below shows you a possible serial line connection to the Gateway.
3 GROUND
to serial line
GND TX+RX+ TX-RX-
EKAC10A Gateway
RX+/TX+
RX-/TX-
1 2 3
Serial module
µchiller compact
modem config.
45
1
EKAC30A
4 screw connector
197198199
9-pole male
197 198 199
field rail connection
5
Connecting an The table below shows where address cards must be connected in the serial line:
address card in the
serial line then connect the address card (EKAC10A) or the field
If the chiller is…
rail of the address card (EKAC30A/60A/120A) to ...
not the sole connection and is not another address card or another field rail.
the first in line,
If you have to connect two address cards or field rails, use AWG20 or AWG22 shielded couple type
cables.
Connections The table below shows you which connections must be made:
Installing the The illustration below shows you how to install the address card EKAC10A.
address card
2
module
Serial
µchiller compa
ct
Installation Follow the steps in the table below to install the address card:
procedure
Step Action
4
1 Turn the power off.
2 Place the address card on the upper side of the omega rail.
3 Push the bottom side of the address card until you hear it click into place.
The address card is now locked onto the omega rail.
5
Removing the Follow the steps in the table below should you wish to remove the address card:
address card
Step Action
2 Release the grey clip at the bottom of the address card using a screwdriver.
Installation Follow the steps in the table below to connect the address card to the controller:
procedure
2 Step Action Illustration
4
3 Insert the crimp terminal into the 7-pin socket
as indicated in the illustration.
Illustration The illustration below shows you how to connect the address card to the transfo.
2
12 11
G G0
power supply
Serial module
µchiller compact
3
50 51
fuse
50 51 4
Installation Follow the steps in the table below to connect the address card to the transfo:
procedure
Step Action
5
1 Connect screw connection 11 G0 on the address card to terminal 50 on the main rail. Use
the supplied unfused connection wire.
2 Connect screw connection 12 G on the address card to terminal 51 on the main rail. Use
the supplied fused connection wire.
Installing the The illustration below shows you how to install the address card EKAC30A/60A/120A.
address card
2
4 Installation Follow the steps in the table below to install the address card:
procedure for
EKAC30A/60A Step Action
2 Handle the address card by its edges as indicated in the illustration above.
5 3 Carefully place the address card with the socket into the 7-pin PCB header.
Installation Units with two circuits have two PCBs. You have to install an address card on each PCB.
procedure for
EKAC120A Follow the steps in the table below to install the address card:
Step Action
2 Handle the address card by its edges as indicated in the illustration above.
3 Carefully place the address card with the socket into the 7-pin PCB header (PCB A).
5 Connect the address card of PCB A to the address card of PCB B as listed below. Always
use the same screw connectors.
Connections PCB A and PCB B of the chillers with 2 circuits must be connected as listed below:
between PCB A and
PCB B (EKAC120A) PCB A wire colour PCB B
EKAC30A/60A to The figure below shows you how to connect the address card EKAC30A/60A to the field rail.
the field rail
2
GROUND
RX+/TX+
RX-/TX-
3
197198199 4
197 198 199 field rail terminal
EKAC120A of
PCB B to the field
The figure below shows you how to connect the address card EKAC120A of PCB B to the field rail. 5
rail PCB A PCB B
GROUND
RX+/TX+
RX-/TX-
197198199
Illustration The illustration below shows you how to connect the Gateway to the configuration computer.
2 Configuration PC 25-pin
female
73
2 Gateway
modem config.
9-pin 52 35
3 2
3 female
4 Different cables The configuration computer connection to the Gateway is made via the 9-pin male connector at the
back of the Gateway labelled ‘config.’. Two different cables can achieve connection:
■ a cable with a 9-pin female connector at both ends
■ a cable with one 9-pin female connector (to the Gateway) and one 25-pin female connector (to the
computer).
5 A program on a disk delivered with the kit can start the initial configuration once the cable connects
the Gateway to the computer.
2. TX 2. RX
3. RX 3. TX
7. GND 5. GND
3. TX 2. RX
2. RX 3. TX
5. GND 5. GND
Illustration RS-232 The illustration below shows you how to connect with RS-232.
2
25-pin 73
BMS
2 Gateway
female
modem config.
9-pin
female
52
3 2
35
rs422/485 Carel Net. relay fuse
2. TX 2. RX
3. RX 3. TX
7. GND 5. GND
2. RX 3. TX
3. TX 2. RX
5. GND 5. GND
1 Illustration RS-485 The illustration below shows you how to connect with RS-485.
BMS Gateway
modem config.
45
1 9-pin
2 male
3 RS-485 connection
(only for
For connection between Gateway and BMS using the Modbus-Jbus protocol the possible connections
are listed below:
Modbus-Jbus)
Gateway (connector labelled
’RS-422/RS-485’)
Supervisory BMS
9-pin male cable end
5. TX-/RX-
2 Configuration
1
2.1 What Is in This Chapter?
Introduction The purpose of this chapter is to tell you how to configure the Gateway and how to address the chillers
2
with the controller.
2.4 – How to Read or Adjust BMS Parameter Settings with the Small Daikin Control- page 2-19
ler
2.5 – Settings: Direct and User Parameters in the Small Daikin Controller page 2-20 4
2.6 – How to Read or Adjust BMS Parameter Settings with the Large Daikin Con- page 2-22
troller
2.7 – e User Settings Menu in the Large Daikin Controller page 2-23
2 Enabling the used To enable the connections that you want the Gateway to use, you have to set the jumpers A, B, C and
connections D on the Gateway PCB according to the table below:
4 output communica-
tion RS-485 at the
B 1–2 Modbus-Jbus You can only enable output
communication RS-485 when
‘RS-422/485’ port jumper A is in position 2-3.
from the Gateway to
the BMS
Other jumper positions will lead to error codes and communication malfunction.
Locating the The illustration below shows the Gateway PCB with the 4 jumpers.
jumpers
1
2
jumper A 3
1
A
jumper B B 23
1
jumper C 2
3 C
NO NC
jumper D D
Possible power
supply
The Gateway can run off one of the following voltages:
■ 24 VAC
1
■ 120 VAC
■ 240 VAC.
2
Changing the The illustration below shows the power supply on the PCB of the Gateway.
power supply
3
transformer
240V~
120V~
fuse
power
supply 24V~
unit
4
Changing to 24 or
120 VAC
5
Follow the instruction given below to change the 240 VAC to 24 or 120 VAC:
Step Action
3 Disconnect the cable end coming from the power supply and located at the position
marked with ’240 V~’.
5 Connect the cable end, which you’ve disconnected in step 3, with the connection marked
with:
■ ’24 V~’ when you want to change to 24 VAC power supply
■ ’120 V~’ when you want to change to 120 VAC power supply.
Step Action
1 6 240 VAC and 120 VAC use the same fuse (on the Gateway PCB):
■ type T time-delay
■ nominal current 250 mA
■ nominal voltage 250 V
2 ■ sizes 5 x 20.
When you change the power supply to 24 VAC then replace the fuse with a fuse with the
following specifications:
■ type T time-delay
■ nominal current 315 mA
3 ■
■
nominal voltage 250 V
sizes 5 x 20.
7 Tighten the nuts of the cover and ensure the chassis is grounded again.
Installation To configure the Gateway from the PC follow the steps in the table below:
procedure
Step Action
3
1 Insert the disk.
4 When the configuration is successful the following message appears ***GATEWAY PRO-
GRAMMED*** on the display. 4
5 Restart the Gateway by pressing the Gateway reset button.
Gateway
t 1 2
ou m m t
int
5
e ar ar se
pr lin al al rx tx re
Parameter list means the sequence of parameter selection with the following syntax:
parameter list = <com> <net_address> <n_of_slaves> <Carel_baud> <Gateway_baud> <stop>
<parity>
The PC screen displays the present Gateway configuration in which the parameters depend on the
software version.
1 Parameter
selections
The table below shows the possible parameter selections:
If you only digitize wrbaccnf (for BACnet) or writemb0 (for Modbus-Jbus) without parameters or if
certain parameters are not defined, the DOS program will display the correct syntax to be used.
Parameter values must be separated from the next by means of a blank space.
5 These parameters are chosen in consultation with the supervisory BMS supplier.
Error messages
Refer to ‘Troubleshooting’ on page 4-1 should one of the following error messages appear on-screen:
■ ***ERROR READING GATEWAY CONFIGURATION***
■ ***ERROR SENDING GATEWAY CONFIGURATION***
Example
The example below is a possible configuration command for the site on page 3-14:
2.4 How to Read or Adjust BMS Parameter Settings with the Small Daikin Controller
1
Addressing To address the chillers using the address card EKAC10A, proceed as follows:
procedure
START
2
Press p for five seconds.
Do you want to
adjust the value?
NO 5
YES
STOP
■ After 5 seconds the display starts flashing when no buttons are pressed.
■ You can exit at every step by leaving the buttons untouched for 1 minute. The modifications will
not be saved.
Refer to ‘Settings: Direct and User Parameters in the Small Daikin Controller’ on page 2-20 for an
overview of the parameters.
2.5 Settings: Direct and User Parameters in the Small Daikin Controller
1
Introduction The grey-filled boxes relate to the chillers’ addressing procedure with address card EKAC10A.
Refer to ‘How to Read or Adjust BMS Parameter Settings with the Small Daikin Controller’ on
page 2-19.
2 Direct and user The digital controller provides direct and user parameters:
parameters
■ direct parameters are used for the every day usage of the unit (for example to set the cooling and
heating temperature point and to read operational information)
■ user parameters provide advanced features (for example remote control).
Parameter overview In the table below you will find the description, the type, the code and the values of all of the
5 parameters:
Default Step
Description Type Code Limit values
Value value
not used — c4 10 — —
not used — c5 00 — —
not used — c6 0 — —
time delay between the unit user c8 20 min 0 to 150 min 1 min
shutdown and the pump shut-
down
Default Step
Description Type Code
Value
Limit values
value 1
not used — ca — — —
timer threshold for mainte- user cb 0 hours 0 to 10 000 hours 100 hours
nance warning (disabled)
not used — hb — — —
5
(1) Never lock the keyboard. Unlocking is not possible with the same password. Refer to "Unlocking
the Keyboard" in the service manual for small Daikin chillers ESIE98–06.
The following advanced functions are unavailable when you lock the keyboard:
■ Modifying direct and user parameters (parameters can be displayed but not modified).
■ Selecting cooling or heating mode.
■ Forcing a defrost cycle.
■ Resetting the timers.
Refer to the service manual for small Daikin chillers ESIE98–06 for more information how to change
the parameters.
2.6 How to Read or Adjust BMS Parameter Settings with the Large Daikin Controller
1
Addressing To address the chillers using the address card EKAC30A/60A/120A, proceed as follows:
procedure
START (1)
3
Select screen 2 (see page 2-23) using the h button.
Do you
want to save the NO
modifications?
5 YES
Press j until the cursor stands in the left upper corner.
Select screen 5 (see page 2-24) and 6 (see page 2-25) using the h button.
Adjust the parameters in screen 5 (see page 2-24) and 6 (see page 2-25).
STOP
You need the password to enter this menu. The units leave the factory with password 1914. You can
also create your own password (2).
(1) Refer to ‘How to Read or Adjust BMS Parameter Settings with the Large Daikin Controller’ on
2
page 2-22.
Menu description This menu allows a full customizing of the units and displays the following nine screens:
3
Screen No. Display Description
Screen 1 You need to enter the correct password before you can consult the screens in this menu:
Screen 2 This screen allows you to activate the remote control by BMS:
Possible set-
Line No. Display Description
tings
4 F1/F2 OFF/LOW/MED/HIGH
Lower Upper
Line No. Display Description Step Default
limit limit
5 Screen 5 This screen allows you to activate the PC control mode and to modify the BMS settings:
Possible
Line No. Display Description
settings
This screen will only be displayed if you mentioned that the optional BMS card is installed. You can do
this in screen 2.
Screen 6 This screen allows you to adjust the BMS board settings:
1
Line No. Display Description Possible settings
3 LEAD-LAG HOURS time after which the other circuit should start 100-1000 H
at next start-up
Screen 8 This screen allows you to force the pump via the chiller’s controller and to adjust the pump lead and
lag time:
Possible
Line No. Display Description
settings
2 PUMP LEAD TIME time to run the water pump before starting 0-180 S
up the chiller
3 PUMP LAG TIME time to keep the pump on, after stopping the 0-180 S
chiller
1 Screen 9 This screen allows you to assign password protection to the set point menu:
Possible
Line No. Display Description
settings
4
Part 3
Functional Description
Introduction The purpose of this part is to give some general and some more specific information about the used
protocols, the implemented commands and the databases.
33
Overview This part contains the following chapters:
33
Part 3
1
1 General
Introduction The purpose of this chapter is to give some general information and some references on the used
protocols.
33
Overview This chapter covers the following topics:
Modbus-Jbus The Modicon Modbus protocol implemented in the Gateway complies with the content of the
conformities document:
■ Modicon Modbus Protocol
33 ■
■
Reference Guide
March 1992, PI-MBUS-300 Rev. D
The implemented Modbus-Jbus protocol is of the RTU type based on times. The configuration is of the
multi-drop in RS-485 or point-to-point RS-232. The address sent into the Modbus packet addresses
the Gateway.
4 BACnet The communication parameters between the supervisory system using the BACnet protocol and the
communication Gateway, selectable by the user, are listed below:
parameters
Parameter Selectable value
Modbus-Jbus The communication parameters between the supervisory system using the Modbus-Jbus protocol and
communication Gateway, selectable by the user, are listed below:
parameters
Parameter Selectable value
Chapter Page
Characteristics of The Gateway ”Conformity Class, Object and Service” characteristics are listed in the table below:
the Gateway
Chapter Page
4
Error codes page 313-317
Chapter Page
33
Part 3
1
2 Implemented Commands in the Gateway
Introduction The purpose of this chapter is to provide further information concerning the implemented commands
in the Gateway.
33
Overview This chapter covers the following topics:
2.2 Protocol
1
BACnet Implemented BACnet protocol commands correspond to the Conformity Classes 1 and 2, namely
ReadProperty and WriteProperty. With these functions, it is possible to read and write a single value
at a time.
Modbus-Jbus The software commands of the Modbus-Jbus protocol, ensure the compatibility between Modbus and
Jbus.
33
Digital data Data is coded by a single digit:
Modbus-Jbus
■ '0' for OFF
■ '1' for ON.
All the digital variables are assigned to bit of consecutive registers, each one having:
4 ■ the lower-address variable assigned to the less significant bit
■ the higher-address variable assigned to the most significant bit.
Analogue data An analogue value is represented by a 16-bit register in binary notation in complement on two with:
Modbus-Jbus
■ the most significant part on the byte of higher address
5 ■ the less significant part on the byte of lower address.
The Gateway operates on registers where one register must be considered at 16-bit.
■ Due to the variety of chillers with installed address cards no distinction is made between input
variables (read only) and output variables (read/write) so that the knowledge of the database and
its management depends on the part present on the supervisory system.
5
■ Due to the generality of the system, the Gateway answers in the same way to various Modbus
commands.
33
Part 3
1
3 Database
Introduction The purpose of this chapter is to give further information about on database creation.
page 3-18
4
3.5 – The Address Card EKAC60A Database page 3-21
From the address The variables from each address card database can be digital, analogue or integer. The maximum
card to the Gateway number of transferable variables from an address card to the Gateway is given below:
33 Variable type
digital
Maximum number
200
analogue 128
integer 128
5 The maximum number of transferable variables from the Gateway to the supervisory BMS is given
below:
Corresponding BACnet
Variable type Maximum number
object
If requested by the supervisory BMS, the Gateway sends out the variables that are not present on the
machine with the value 0.
This way, extra inline traffic is created, but the generality of the application is saved. The database is
dimensioned for the address card with the largest number of variables.
Example EKAC10A The table below shows an example of a digital, an analogue and an integer variable for the address
database card EKAC10A:
Parameter
Variable Address Read/
Comment
type number write Direct/
Name Description
user
Gateway database
creation
To create a database that can be implemented in a Modbus-Jbus or a BACnet supervisor proceed as
follows: 1
■ The digital variables are transferred with their addresses to the Gateway (Modbus-Jbus or BACnet)
database. In the Modbus-Jbus database they are read using the commands 1 or 2 (1).
■ The analogue variables are transferred with their addresses to the Gateway (Modbus-Jbus or
BACnet database). In the Modbus-Jbus database they are read using the commands 3 or 4 (1).
■ The integer variables are transferred with their addresses on top of the analogue variables to the
Gateway (Modbus-Jbus or the BACnet) database. In the Modbus-Jbus database they are read
using the commands 3 or 4 (1).
Gateway database
diagram
The creation of a Gateway database from address card databases (slave n databases) is given below.
33
Slave n database (for each PCB address) Gateway database
Digital variables
1 1
Digital variables
200
1
128 Analog variables
200
400
4
...
1 (n-1)*200
128 Integer variables
Analogue variables 5
1
256
512
...
(n-1)*256
(n-1)*256+128
Modbus supervisor In the Modbus supervisor, the operator must reserve 25 bytes for the digitals (200 digital variables)
and 512 bytes for the analogues (128 analogue variables and 128 integer variables) for a total of 456
variables for each address card.
1 Address list
creation illustration
The illustration below shows the Daikin chillers and the BMS.
BMS
Gateway
t 1 2
ou m m t
int e ar ar se
pr lin al al rx tx re
Serial module
µchiller compact
33 Address 1
EUWY10HCW1
4
Address 2
EUWAT50KAY1
PCB A: Address 3
Gateway database The Gateway database creation for the digital variables in the illustration above is herewith given:
creation: digital
variables Address towards Assigned address in the Gateway database
Unit
the Gateway (digital variables)
EUWT200KXY1
PCB A 3 401 → 600
PCB B 4 601 → 800
Gateway database
creation: analogue
The Gateway database creation for the analogue variables in the illustration above is herewith given:
1
variables Assigned address in
Address towards Variable type in the
Unit the Gateway database
the BMS address card database
(analogue variables)
EUWT200KXY1
PCB A 3 513 → 640 Analogue
641 → 768 Integer 33
PCB B 4 769 → 896 Analogue
897 → 1025 Integer
5 21
22
25
r
r
r
EO
EU
Alarm: supply voltage is high
Alarm: supply voltage is low
Output of pump
1= alarm 0=no alarm
1= alarm 0=no alarm
1=on 0=off
26 r Output of compressor 1=on 0=off
28 r Output of reversing valve - 1=on 0=off
29 r Output of alarm 1=on 0=off
30 r Output of fan 1=on 0=off
31 r Input of high pressure or discharge protector or 1= closed 0=open
overcurrent alarm
32 r Input of evaporating temperature thermostat alarm 1= closed 0=open
33 r Input of remote on/off 1= closed 0=open
40 r/w U /d Measurement unit of temperature
47 r/w U H7 Enable/disable “remote on/off” digital input 1=enable 0=disable
39 r U HA Serial address
1= keyboard enabled 33
Address Read
/write Direct/ user Name
Parameter
Description
Comments
EUWA5-10HB(Z) EUWY5-10HB 4
1 r Analogue input 1
2 r Analogue input 2
3 r Analogue input 3 Ambient temperature Coil temperature
10 r/w D r1 Cooling setpoint
11
12
r/w
r/w
D
D
r2
r3
Cooling difference
Heating setpoint
5
13 r/w D r4 Heating difference
2. For all possible values of user settings, refer to the chiller’s operation manual.
33
Digital variables
Address Read
The table below shows the digital variables:
Description Comments
1
/write
EUWA15-30HB(Z) EUWY15-30HB
1 r Digital input 1 Safety circuit 1/1
2 r Digital input 2 Safety circuit -/2
3 r Digital input 3 Safety circuit 2/3
4 r Digital input 4 - Remote cooling/heating
selection
5 r Digital input 5 Flow switch
6 r Digital input 6 - Defrost circuit 1/1
7 r Digital input 7 - Defrost circuit -/2
8 r Digital input 8 - Defrost circuit 2/3
9 r Digital input 9 Dual setpoint
10 r Digital input 10 Remote on/off
11 r Digital input 11 Reverse phase protector
12
13
r
r
Digital output 1
Digital output 2
Compressor 1/1
Compressor -/2
33
14 r Digital output 3 Compressor 2/3
15 r Digital output 4 LP bypass circuit 1/1
16 r Digital output 5 LP bypass circuit -/2
17 r Digital output 6 Pump
18 r Digital output 7 General Alarm
19 r Digital output 8 System on
20
21
r
r
Digital output 9
Digital output 10
Fanspeed 1 (ry1)
Fanspeed 2 (ry2)
4
22 r Digital output 11 Fanspeed 3 (ry3)
23 r Digital output 12 Lp bypass circuit 2/3
24 r Digital output 13 Evaporator heater Reversing valve
25 r Cooling/heating mode - 0=heating 1=cooling
26 r Unit status 1=on 0=off
27
28
29
r
r
r
Freeze up circuit 1/1 active
Freeze up circuit -/2 active
Freeze up circuit 2/3 active
1=yes 0=no
1=yes 0=no
1=yes 0=no
5
30 r Circuit 1/1 safety active 1=yes 0=no
31 r Circuit -/2 safety active 1=yes 0=no
32 r Circuit 2/3 safety active 1=yes 0=no
33 r Manual mode active 1=yes 0=no
37 r Load up timer active 1=not zero 0=zero
38 r Load down timer active 1=not zero 0=zero
39 r Start timer active 1=not zero 0=zero
40 r Flow start timer 1=not zero 0=zero
41 r Flow stop timer 1=not zero 0=zero
42 r Guard timer compressor 1/1 active 1=not zero 0=zero
43 r Guard timer compressor -/2 active 1=not zero 0=zero
44 r Guard timer compressor 2/3 active 1=not zero 0=zero
45 r Anti-recycling time compressor 1/1 active 1=not zero 0=zero
46 r Anti-recycling time compressor -/2 active 1=not zero 0=zero
47 r Anti-recycling time compressor 2/3 active 1=not zero 0=zero
48 r Defrost busy compressor 1/1 - 1=yes 0=no
49 r Defrost busy compressor -/2 - 1=yes 0=no
50 r Defrost busy compressor 2/3 - 1=yes 0=no
51 r Compressor 1/1 off for defrost of other circuit - 1=yes 0=no
52 r Compressor -/2 off for defrost of other circuit - 1=yes 0=no
53 r Compressor 2/3 off for defrost of other circuit - 1=yes 0=no
54 w On-off command If 1 is written, then toggle status of the unit.
After this action the controller resets this parameter
55 w Cool-heat selection command - If 1 is written, then toggle
status of the unit. After this
action the controller resets this
parameter
4 16
17
18
r/w
r/w
r/w
Manual setting of compressor -/2
Manual setting of compressor 2/3
Manual setting of fans
User setting in manual mode
User setting in manual mode
0=very high, 1=high, 2=medium , 3=low
19 r/w Load up time User setting
20 r/w Load down time User setting
21 r/w Running mode 0=auto, 1=manual
27 r Water/air-cooled unit 0=air-cooled unit
1=water-cooled unit
5 28
29
r
r
Cooling only/heat pump unit
2. For all possible values of user settings, refer to the chiller’s operation manual.
Address Read/
write
Description Comments 33
EUWA*40-60KA(X) EUW*40-100KX
1 r Unit status 1=On 0=Off
2 r Enable remote on/off 1=Yes 0=No
3 r Unit safety active 1=Yes 0=No
4 r Digital input 1 Low pressure switch
5 r Digital input 2 High pressure switch
6
7
r
r
Digital input 3
Digital input 4
Reverse phase protector
Overcurrent
4
8 r Digital input 5 Discharge thermal protector
9 r Digital input 6 Compressor thermal protector
10 r Digital input 7 Flow switch
11 r Digital input 8 Bypass
12 r Digital input 9 Dual setpoint
13
14
r
r
Digital input 10
Digital input 11
Digital input remote on/off
Emergency 5
15 r Digital output 1 Star
16 r Digital output 2 Delta
17 r Digital output 3 Compressor status
18 r Digital output 4 Pump
19 r Digital output 5 Alarm status
20 r Digital output 6 12%
21 r Digital output 7 25%
22 r Digital output 8 40%
23 r Digital output 9 Fan 1 -
24 r Digital output 10 Fan 2 -
25 r Digital output 11 Fan 3 -
26 r Digital output 12 Evaporator heater -
27 r Digital output 13 70%
28 r Circuit safety active 1=yes 0=no
29 r Guard timer active 1=not zero 0=zero
30 r Start timer active 1=not zero 0=zero
31 r Anti-recycling timer active 1=not zero 0=zero
32 r Load up timer active 1=not zero 0=zero
33 r Load down timer active 1=not zero 0=zero
34 w On/off command If 1 is written, then toggle status unit. After this action the controller resets this parameter
36 r High pressure setback active 0=not active 1=active
37 r Digital input 12 - Enable/disable limitation
38 r 25% installed 0=no 1=yes
39 r V-A meter installed 0=no 1=yes
33 6 r Status of compressor (if off) for readout in mask 0= OFF Can startup
1= OFF Timers busy
2= OFF Disabled (contact)
0= OFF Can startup
1= OFF Timers busy
2= OFF 0% (Limit contact)
3= OFF safety active 3= OFF safety active
4= OFF bypass mode 4= OFF bypass mode
7 r Unit type 0=EUWA*40J* 1=EUWA*50J* 0=EUW*40K* 1=EUW*60K*
2=EUWA*60J* 3=EUWA*40K* 2=EUW*80K* 3=EUW*100K*
4=EUWA*50K* 5=EUWA*60K*
8 r Refrigeration type 0=R134a 1=R22
4 9
10
r
r
Manufacturer number 1
Manufacturer number 2
First digit
Second digit
11 r Manufacturer number 3 Third digit
12 r Manufacturer number 4 Fourth digit
13 r Manufacturer number 5 Fifth digit
14 r Manufacturer number 6 Sixth digit
15 r Manufacturer number 7 Seventh digit
16 r Actual thermostat step 0,1,2,3,4
5 17
18
r
r/w
Maximum number of thermostat step
Manual setting of compressor
3,4
User settings manual mode:
If 25% is installed: If 25% not installed:
0=0%, 1=25%,2=40%, 0=0%,1=40%,
3=70%,4=100% 2=70%,3=100%
19 r/w Manual setting of fans User settings manual mode -
0=off,1=low,2=med,3=high
20 r/w Load up time in outlet control User setting (thermostat)
21 r/w Load down time in outlet control User setting (thermostat)
22 r/w Load up time in inlet control User setting (thermostat)
23 r/w Load down time in inlet control User setting (thermostat)
24 r/w Running mode 0=inlet, 1=outlet, 2=manual 0=cooling inlet, 1=cooling outlet,
2=cooling manually, 3= heating
inlet, 4=heating manually, 5=double
thermostat inlet, 6=double
thermostat manually
27 r Water/air-cooled unit 0=air-cooled unit
1=water-cooled unit
28 r Cooling only/heat pump 0=cooling only
1=heat pump
29 r Unique eprom parameter 0= EUWA/Y15-30HB
1= EUWA*40-60KA(X)
2= EUWA*80-120KA(X)
3= EUW*40-100KX
4= EUW*120-200KX
5= EUWA*160-200KX
30 r Eprom version (higher part) 1=V1 (V1.012)
31 r Eprom version (lower part) Example 12 (V1.012)
If a parameter is marked with X in column of PBC A or B, then the parameter is present on the marked
PCB.
33
4 2=EUWA*120J
3=EUWA*80K
4=EUWA*100K
7=EUWA*200K 2=EUW*160K
3=EUW*180K
4=EUW*200K
5=EUWA*120K
8 r X Refrigeration type 1=R22 0=R134a
9 r X Manufacturer number 1 First digit
10 r X Manufacturer number 2 Second digit
11 r X Manufacturer number 3 Third digit
5 12
13
r
r
X
X
Manufacturer number 4
Manufacturer number 5
Fourth digit
Fifth digit
14 r X Manufacturer number 6 Sixth digit
15 r X Manufacturer number 7 Seventh digit
16 r X Actual thermostat step 0,1,2,3,4,5,6,7,8
17 r X Maximum number of 7,8
thermostat step
18 r/w X X Manual setting of compressor User settings manual mode
If 25% is installed If 25% not installed
0=0%, 1=25%,2=40%, 0=0%,1=40%,
3=70%,4=100% 2=70%,3=100%
19 r/w X X Manual setting of fans User settings manual mode
0=off,1=low,2=med,3=high
20 r/w X Load up time in outlet control User setting (thermostat)
21 r/w X Load down time in outlet User setting (thermostat)
control
22 r/w X Load up time in inlet control User setting (thermostat)
23 r/w X Load down time in inlet control User setting (thermostat)
24 r/w X Running mode 0=inlet 1=outlet 2=manual
27 r X Water/air cooled unit 0=aircooled unit
1=watercooled unit
28 r X Cooling only/heat pump 0=cooling only
1= heat pump
29 r X Unique eprom parameter 0= EUWA/Y15-30HB(Z)
1= EUWA*40-60KA(X)
2= EUWA*80-120KA(X)
3= EUW*40-100KX
4= EUW*120-200KX
5= EUWA*160-200KX
30 r X Eprom version (higher part) 1=V1 (V1.012)
31 r X Eprom version (lower part) Example 12 (V1.012)
33
Part 4
Troubleshooting
Introduction The purpose of this part is to help you to find the malfunction causes of the system.
Part 4
1 Troubleshooting
Introduction The purpose of this chapter is to help you to identify malfunctions or problems. Before checking the
Daikin BMS option, first check whether the chiller itself is working properly.
The BMS-option enables communication between the Daikin chillers and the BMS. Should a
3
malfunction in the BMS option occur, it is most likely a communication problem.
Gateway front panel The illustration below shows the LED indicators on the Gateway front panel.
Gateway
t 1 2
ou m m t
int e ar ar se
pr lin al al rx tx re
3 Normal Gateway The table below displays the normal LED indicators:
indicators
When the LED ... with colour ... is ..., then the Gateway functions normally.
line yellow on
4 alarm 1
alarm 2
–
–
off
off
rx green flashing
tx green flashing
Normal chiller PCB The table below displays the normal LED indicators:
indicators
When the LED
with colour ... is ..., then the chiller functions normally.
on the ...
orange flashing
green on
(1) This is only for units with two circuits or sites with a DICN.
Chiller malfunction
indicators
1.3 Troubleshooting
1
Introduction This section tells you where or what to check when there is a LED fault indication on the Gateway front
panel.
Refer to the relevant Daikin water chiller service manual for more information about the chiller’s PCB
LED fault indications.
Gateway LED "line" The table below displays the possible causes and the items that must be checked:
is off
Possible causes Check ...
Gateway LED The table below displays the possible causes and the items that must be checked:
"alarm 1" is on
4 Possible causes Action
Refer to ...
5 No Gateway software
configuration
Configurate the software ‘Gateway Software Con-
figuration (MS–DOS pro-
gram)’ on page 2-17.
Gateway LED The table below displays the possible causes and the items that must be checked:
"alarm 2" is on
Possible causes Check ...
Refer to ...
One or more chillers are ■ the power supply to the chiller’s PCB.
switched off
■ the BMS connection mentioned in the ‘e User Settings Menu
chillers’ user settings menu. in the Large Daikin
Controller’ on
page 2-23.
■ the EPROM in the chillers. ■ ‘Software version’
on page 1-6.
Wrong settings in the "e the controller configuration. ‘e User Settings Menu
User Settings Menu" in the Large Daikin
Controller’ on
page 2-23.
Cross-wiring in the serial the wires on every unit and on the pins of ‘Installing and Connect-
line the 9-pin male connector. ing the System’ on
page 2-3.
Appendix A
Drawings
Introduction In order to quickly find the drawings inserted in this manual, appendix A offers a list with all the
drawings.
Overview The table below shows the page and description of all the drawings:
Connecting the address card EKAC30A/60A to the field rail page 2-9
Connecting the address card EKAC120A of PCB B to the field rail page 2-9
A–1
ESIE99–03
A–2
ESIE99–03
Index
1
A
address cards
data transfer to the Gateway. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-12
EKAC10A connecting to the controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-6
EKAC10A connecting to the transfo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-7
EKAC10A database variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-16
3
EKAC10A dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
EKAC10A installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-5
EKAC10A kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
EKAC120A database variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-24
EKAC30A database variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-18
EKAC30A/60A/120A connecting to the field rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
EKAC30A/60A/120A dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
EKAC30A/60A/120A installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-8
4
EKAC30A/60A/120A kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
EKAC60A database variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-21
product range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-6
serial line example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
alarms
Gateway LED alarm 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-6
Gateway LED alarm 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-6
analogue
5
database creation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-12
EKAC10A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-17
EKAC120A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-27
EKAC30A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-20
EKAC60A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-23
Modbus-Jbus representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-8
ASHRAE
references of the BACnet protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-5
B
BACnet
ASHRAE references . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-5
communication parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
BMS
centralized building control example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k vi
connecting to the Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-11
enabling communication with the Gateway. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-14
parameter settings with the large controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-22
parameter settings with the small controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-19
C
communication
outline example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-4
configuration
Gateway hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-14
Gateway software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
Index i
ESIE99–03
1
connecting
address card in the serial line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
EKAC10A to the controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-6
EKAC10A to the transfo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-7
EKAC30A/60A/120A to the field rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
Gateway to the BMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-11
Gateway to the configuration PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-10
D
databases
creation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-12
5 E
EKAC10A
connecting to the controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-6
connecting to the transfo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-7
database variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-16
dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-5
kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
EKAC120A
connecting to the field rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
database variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-24
dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-8
kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
EKAC30A
connecting to the field rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
database variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-18
dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-8
kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
EKAC60A
connecting to the field rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
database variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-21
dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-8
kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
ii Index
ESIE99–03
1
G
Gateway
buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-8
configuration PC installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
connecting to the BMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-11
connecting to the configuration computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-10
connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-9
data transfer to the BMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-12
database creation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-13
enabling communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-14
hardware configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-14
implemented commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-9
kit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-8
LED indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-9, 4-4
parameter descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-18
3
power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-15
precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-3
product range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-6
serial line example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
software configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-9
4
I
integer
database creation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-12
EKAC10A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-17
EKAC120A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EKAC30A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EKAC60A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
k
k
k
3-26
3-20
3-22
5
J
jumpers
enabling address cards-Gateway-BMS communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-14
locating on the Gateway PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-14
L
LED indicators
chiller’s PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-5
Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-4
M
master-slave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-7
Modbus-Jbus
communication parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
conformities. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
data representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-8
MS-DOS
Gateway software configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
O
outline
communication example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-4
EKAC10A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
EKAC30A/60A/120A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
Index iii
ESIE99–03
1
P
parameters
BACnet communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
BMS settings with the large controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-22
BMS settings with the small controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-19
direct and user settings in the small controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-20
Modbus-Jbus communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
user settings in the large controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-23
PC
connecting to the Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-10
Gateway configuration requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
precautions
4 R
RS-232
enabling Gateway serial port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-14
Gateway-BMS connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-11
RS-485
enabling Gateway serial port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-14
Gateway-BMS connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-12
5
S
serial line
communication outline example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-4
connections example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
software
configuration Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
EPROM versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-6
T
troubleshooting
chiller’s PCB LED indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-5
Gateway LED indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-4
iv Index
SERVICE MANUAL
Zandvoordestraat 300
B-8400 Oostende
Belgium