Product Description: SD-VTK Air Velocity Test Kit

The document describes an air velocity test kit used to measure air pressure differential in HVAC ducts. The kit contains tubes and hoses to connect to a duct smoke detector's air inlet and exhaust. The pressure difference must be between 0.005-1.00 inches of water for proper detector operation.

Uploaded by

Isaac Velasquez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
151 views1 page

Product Description: SD-VTK Air Velocity Test Kit

The document describes an air velocity test kit used to measure air pressure differential in HVAC ducts. The kit contains tubes and hoses to connect to a duct smoke detector's air inlet and exhaust. The pressure difference must be between 0.005-1.00 inches of water for proper detector operation.

Uploaded by

Isaac Velasquez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SD-VTK

Air Velocity Test Kit

Product description

Sampling
tube HVAC duct

Air exhaust
tube
Airflow

The SD-VDTK Air Velocity Test Kit is used in conjunction with


a suitable air pressure differential meter (supplied by the
installer) to measure the air pressure differential between the
air sampling tube and the air exhaust tube inside a
SuperDuct™ duct smoke detector. The kit contains two rubber
stoppers, two metal tubes, and two rubber hoses. Air sampling
tube

Measuring air pressure differential


Air pressure
For the duct smoke detector to operate as designed, there differential
must be a sufficient amount of difference in air pressure meter
between the air inlet and the air exhaust to pull smoke
particulate through the sensing chamber.
Figure 1: Duct detector pressure differential test setup
Air pressure differential must be measured when the duct
smoke detector is first installed.
Air pressure differential must measure between 0.005 and 1.00
inches of water. If the air pressure differential does not fall
within this range, check the duct smoke detector for air leaks or
blockages. In addition, check the sampling tube for correct
orientation.
If the required air pressure differential cannot be obtained,
relocate the duct smoke detector and seal all holes in the
HVAC duct.
Note: In order to measure the air pressure differential, air must
be moving through the HVAC system.
To measure air pressure differential:

1. Assemble the rubber stopper, metal tube, and rubber hose


as shown in Figure 1. Connect the rubber hoses to both
openings on the air pressure differential meter.
2. Remove the detector cover.
3. Plug the rubber stoppers into the air sampling tube and
the air exhaust tube as shown in Figure 1.
4. Verify that the reading on the air pressure differential
meter falls between 0.005 and 1.00 inches of water.

Installation Sheet 11MAY04 P/N: 3100692 REV: 1.0


SD-VTK - Air Velocity Test Kit 1/1