Low Voltage Alternator - 4 Pole: 2650 To 3300 kVA - 50 HZ / 3150 To 3900 kVA - 60 HZ Electrical and Mechanical Data
Low Voltage Alternator - 4 Pole: 2650 To 3300 kVA - 50 HZ / 3150 To 3900 kVA - 60 HZ Electrical and Mechanical Data
Standards
Nidec Leroy-Somer LSA 53.2 alternator meets all key international standards and regulations, including IEC 60034,
NEMA MG 1.32-33, ISO 8528-3, CSA C22.2 n°100-14 and UL 1446 (UL 1004 on request). Also compliant with IEC 61000-6-2,
IEC 61000-6-3, IEC 61000-6-4, VDE 0875G, VDE 0875N and EN 55011, group 1 class A for European zone.
Nidec Leroy-Somer LSA 53.2 alternator can be integrated in EC marked generator set, and bears EC, EAC and CMIM markings.
It is designed, manufactured and marketed in an ISO 9001 and ISO 14001 quality assurance environment.
Mechanical construction
● Compact and rigid assembly to better withstand generator vibrations
● Steel frame
● Cast iron flanges and shields
● Two-bearing and single-bearing versions designed to be suitable for engines on the market
● Half-key balancing
● Regreasable bearings
● Clockwise rotation in standard
General characteristics
Insulation class H Excitation system AREP + PMI
Winding pitch 2/3 (wind. 6S) AVR type D550
Number of wires 6 Voltage regulation (*) ± 0.25 %
Protection IP 23 Short-circuit current 300% (3 IN) : 10s
Altitude ≤ 1000 m Total Harmonic Distortion THD (**) in no-load <4%
Overspeed 2250 R.P.M. Waveform: NEMA = TIF (**) < 50
Air flow 2.5 m3/s (50 Hz) - 2.8 m3/s (60 Hz) Waveform: I.E.C. = THF (**) <2%
(*) steady state (**) between phases
LSA 53.2 M7 kVA 2650 2650 2650 2417 2417 2417 2783 2783 2783 2915 2915 2915
kW 2120 2120 2120 1934 1934 1934 2226 2226 2226 2332 2332 2332
LSA 53.2 M9 kVA 3000 3000 3000 2736 2736 2736 3150 3150 3150 3300 3300 3300
kW 2400 2400 2400 2189 2189 2189 2520 2520 2520 2640 2640 2640
LSA 53.2 M12 kVA 3300 3300 3300 3010 3010 3010 3465 3465 3465 3630 3630 3630
kW 2640 2640 2640 2408 2408 2408 2772 2772 2772 2904 2904 2904
LSA 53.2 M7 kVA 2888 3150 2634 2873 3032 3308 3176 3465
LSA 53.2 M9 kVA 3300 3600 3010 3283 3465 3780 3630 3960
LSA 53.2 M12 kVA 3630 3900 3311 3557 3812 4095 3993 4290
97.5 97.5
97.4 97.5 97.4 97.3
97.5 97.3 97.3 97.3
97.0 97.0
96.5 96.5
96.6 96.6 96.6 96.6
95.5 95.5
95.4 95.3
95.0 95.0
25% 50% 75% 100% 25% 50% 75% 100%
97.4 97.3
97.5 97.3
97.2
97.0
96.5
96.5 96.5
96.0 96.3
96.1
95.5 95.6
95.0 95.1
25% 50% 75% 100%
Load - % kWe
0 2000 4000 6000 8000 10000 0 2000 4000 6000 8000 10000
0% 0%
10%
10%
Voltage dip
Voltage dip
20%
20%
30%
30%
40%
M12
M9 M12
40% M7 50%
M7 M9
10%
Voltage dip
20%
30%
40%
M12
M7 M9
50%
40% M7
M9
M12
30%
Voltage rise
20%
10%
0%
0 1000 2000 3000 4000 5000 6000
96.5 96.5
96.6 96.6
96.5 96.4 96.5 96.4
96.0 96.3 96.3
96.0
95.5 95.5
95.4 95.3
95.0 94.9 95.0
94.9
94.5 94.5
25% 50% 75% 100% 25% 50% 75% 100%
96.9
97.0
96.5
96.5
96.3 96.4 96.3
96.0
95.5
95.0 94.9
94.5 94.5
25% 50% 75% 100%
Load - % kWe
0 2000 4000 6000 8000 10000 0 2000 4000 6000 8000 10000
0% 0%
10%
10%
Voltage dip
Voltage dip
20%
20%
30%
30%
40%
M12
M9 M12
40% M7 50%
M7 M9
10%
Voltage dip
20%
30%
40%
M12
M7 M9
50%
40% M7
M9
M12
30%
Voltage rise
20%
10%
0%
0 1000 2000 3000 4000 5000 6000
10
8
LSA 53.2 M7
6
0
0.001 0.01 0.1 1 10 100
Time (seconds)
10
8
LSA 53.2 M9
6
0
0.001 0.01 0.1 1 10 100
Time (seconds)
10
8
LSA 53.2 M12
6
0
0.001 0.01 0.1 1 10 100
Time (seconds)
663
(wall)
AIR
on Ø 850.9
12 x Ø 18
12 Lifting points 16 x Ø 14 on Ø 641.3
(1480)
Rotation
317
Ø 787.4f8
Ø 673.1f7
Ø 150 m6
920x920
Ø 1040
AIR
INLET
-1
0
500
560
2 x M12
AIR
OUTLET
7 Ø 1006
381 220 220 423 +100mm 6.3
(PMG option) 180 940 180
35
491 1200 533
15 1500 383 75 1150 75
2246 1300
55
4 x Ø 14.5
(dowell pin) E
4 x Ø 33
60
(fixation)
4 x M27x2 Ground connection
(jacking screw)
J1 J2 J3
k1 k2 k3
Ø 220
Ø 240
Ø 250
Ø 234
Ø 180
Ø 170
Ø 150
Ø 120
Ø 115
NOTE: Dimensions are for information only and may be subject to modifications. Contractual 2D drawings and 3D drawing files are available
and can be downloaded from the site: www.leroy-somer.com/epg. The torsional analysis of the transmission is the responsability of genset
manufacturer.
670
(wall)
AIR No counter
flange
16 x M12
232 Lifting points on Ø 850.9 Counter flange
(1487)
16 x Ø 14
317
Rotation
Ø 787.4f8
Ø 150 m6
920x920
Ø 880
AIR
AIR INLET
E
-1
0
566.5
500
2 x M12
7
Ø 1006
250 220 220 423 +100mm 6.3
701 1200 533 (PMG option) 180 940 180
35
301 1500
75 1150 75
2184
2434 1300
55
4 x Ø 14.5
(dowell pin) E
4 x Ø 33
60
(fixation)
4 x M27x2 Ground connection
(jacking screw)
J1 J2 J3
k1 k2 k3
Ø 150
Ø 160
Ø 175
Ø 245
Ø 310
Ø 289
Ø 190
Ø 170
Ø 160
Ø 140
Ø 138
NOTE: Dimensions are for information only and may be subject to modifications. Contractual 2D drawings and 3D drawing files are available
and can be downloaded from the site: www.leroy-somer.com/epg. The torsional analysis of the transmission is the responsability of genset
manufacturer.
Linkedin.com/company/leroy-somer
Twitter.com/Leroy_Somer_en
Facebook.com/LeroySomer.Nidec.en
YouTube.com/LeroySomerOfficiel
© Nidec 2020. The information contained in this brochure is for guidance only and does not form part of
any contract. The accuracy cannot be guaranteed as Nidec have an ongoing process of development
and reserve the right to change the specification of their products without notice.
Moteurs Leroy-Somer SAS. Siège : Bd Marcellin Leroy, CS 10015, 16915 Angoulême Cedex 9, France.
Capital social : 38 679 664 €, RCS Angoulême 338 567 258.
5451 en - 2021.03 / j