Fire Alarm Control Panel BS-60: Operator's Handbook
Fire Alarm Control Panel BS-60: Operator's Handbook
BS-60
Operator's handbook
Program version
P1-BS60-202E-0
116-P-BS60/FEE 2005-06-13 1
BS-60 Operators handbook
Contents
Page
1. Control panel..................................................................................................4
2. Prewarning .....................................................................................................5
2.1 Indications on the control panel at “Prewarning” ..................................5
2.2 Actions to be taken at “Prewarning”:......................................................5
3. Fire alarm ......................................................................................................7
3.1 Indications on the control panel at “Fire alarm” .....................................7
3.2 Actions to be taken at “Fire alarm”:........................................................7
4. More alarms (Multiple alarms) ...................................................................9
4.1 Indications on the control panel at “More alarms”: ................................9
4.2 Actions to be taken at “More alarms”:....................................................9
5. Fault .............................................................................................................11
5.1 Indications on the control panel at “Fault”: ..........................................11
5.2 Actions to be taken at “Fault”:...............................................................11
5.3 Fault signal from internal buzzer at processor fault or fault with the
internal 5V .........................................................................................................12
6. Menu ............................................................................................................13
6.1 Menu structure ......................................................................................13
6.2 Menu operation .....................................................................................15
6.3 “MAIN MENU”....................................................................................15
7. Out-/in-control ............................................................................................16
7.1 Disable ..................................................................................................16
7.1.1 Disablement of address ..................................................................17
7.1.2 Disablement of zone .........................................................................18
7.1.3 Disablement of Fire-Brigade/Fighters (BMA, BMF) ......................19
7.1.4 Disablement of sounder (AK-circuit) ...............................................19
7.1.5 Disablement of controls ....................................................................20
7.1.5.1 Disablement of zone controls...................................................21
7.1.5.2 Disablement of Control-1 ........................................................22
7.1.5.3 Disablement of Control-2 ........................................................22
7.2 Restore ..................................................................................................23
7.2.1 Restoring of address(es)....................................................................23
7.2.2 Restoring of zone ..............................................................................24
7.2.3 Restoring of Fire Brigade/Fighters (BMA/BMF) .........................24
7.2.4 Restoring of sounders .......................................................................25
7.2.5 Restoring of controls.........................................................................25
7.2.5.1 Restoring of zone control.........................................................25
7.2.5.2 Restoring of Control-1 .............................................................26
7.2.5.3 Restoring of Control-2 .............................................................26
7.3 Alarm delay...........................................................................................27
8. Test ...............................................................................................................29
8.1 Test Frontpanel / buzzer........................................................................29
8.2 Test BMA/BMF ....................................................................................30
8.3 Test fault ...............................................................................................30
8.4 Test sounders ........................................................................................31
1. Control panel
The operating panel consists of a text display (information window), indication
lamps, operation buttons and a number key-pad.
With these controls and indication devices, the entire fire alarm system is
controlled.
Fig. no. 1: BS-60 front panel with text display, indication lamps,
operation buttons and a number key-pad.
DISABLE
ALARM
FIRE SONE
Silence&Resound
Sounders
MORE
ALARMS RESET
If there is a slowly developed fire, the PREWARNING lamp will light before the
lamps in the fire sign light up.
A. Follow all precautions described in the local fire instructions step by step.
D. Investigate the scene of fire and carry out the necessary actions.
E. Press “RESET”.
This text will remain for 60 seconds. (The seconds are counted in the display
with one point appearing for every second from 0 to 30 seconds, and then the
following 30 seconds are counted down by the removal of one point every
second from 30 to 0.)
RESET OK
NORMAL CONDITION
DISABLE
ALARM
FIRE SONE
Silence&Resound
Sounders
MORE
ALARMS RESET
This text states that an alarm has been sounded from the detector with address
no. 14 in zone no. 3.
If there is a fire slowly developed, the PREWARNING lamp will light before the
lamps in the fire sign light.
A: Follow the precautions described in the local fire instruction step by step.
When the scene of the fire is investigated and the necessary actions are
carried out, the sounders may be switched off.
All the alarm devices will be stopped, including the internal buzzer. (The panel
buzzer will emit a sound signal every fourth minute as long as the door is open). If
the key is pressed once again the alarm devices will start up again.
See sec. 7.3 “Set alarm delay” for more information.
All the alarm sounder outputs from the control panel will be turned off when the
operation key “SILENCE/RESOUND SOUNDERS” button is pressed the first
time. However, the message to the Fire Brigade/Fighters (BMA-) is not turned off.
When the scene of the fire is investigated and the necessary actions are
carried out, reset the fire alarm control panel to normal condition.
E: Press “RESET”
RESET OK
NORMAL CONDITION
Normal condition means that the door on the control panel is closed and only the
MAINS lamp is lit.
After resetting, an address may still be in an alarm state. This can be due to
mechanical damage, water damage, presence of smoke still in the detector’s
chamber or an technical fault.
If there is any address in an alarm state after resetting, it will be automatically
disabled and isolated from the rest of the system.
Contact Autronica’s service department to repair any fault so that the detector(s)
can return to normal condition.
The red FIRE indication The red MORE ALARMS The upper line in the display
lamps lights with pulsating indication lamp light. indicates the first alarm. The
light. lower line indicates the last
alarm.
DISABLE
ALARM
FIRE SONE
Silence&Resound
Sounders
MORE
ALARMS RESET
1 2 3
FUNCTION 4 5 6
PREWARN. UTKOBLET
7 8 9
FAUL MAIN 0 M
BS 60
The display then indicates the number of the first and last alarm together with the
zone number and the detector address.
When more alarms are registered the text in the display may appear as follows:
NOTE! The last alarm will appear in the lower line in the display.
B: In order to find out which alarms are in between the first and the last
alarm, press the operation key “MORE ALARMS”.
The alarms in between will then appear in the lower line in the text
display, one for each press on the key.
The alarms will appear in order, i.e. alarm no 2 will appear with the first
press on the key (alarm number one will always remain in the top line),
alarm number three with the second press of the key, alarm number four
with the third press etc.
Fault 5. Fault
UTKOBLET
ALARM
BRANN SONE
1 2 3
5 6
The amber (yellow) FAULT FORVARSEL DELER AV ANLEGGET
UTKOBLET
4
7 8 9
FEIL NETT
indication lamp lights with 0 M
BS 60
pulsating light.
C: Press “RESET”.
RESET OK
NORMAL CONDITION
Fault on 5.3 Fault signal from internal buzzer at processor fault or fault
processor or with the internal 5V
internal 5V
• Loss of internal 5V will give continuous signal in the internal buzzer.
• Processor fault will give pulsing- or continuous signal in the internal buzzer.
• At both fault types the display will be dark or the text will be locked.
Menu 6. Menu
2--Test 1--Frontpanel/buzzer
2--BMA, BMF
3--Fault
4--Sounders
5--Controls. 1--Zone-control
6--Alarm 2--Control-1
3--Control-2
3--Show- 1--Prewarning
status 2--Fault
E) 3--Disablements
4--Stored-events
2--Internal 1--Program-version
E) 2--Adjust-clock
E) 3--Show-clock
D) 3--Config. 1--Data
2--Zone 1--Start no.
2--Edit 1--Insert
2--Delete
3--End
3--Automatic
B) 4--Save 3--Renumber
4--Delete
C) 5--Service 1--Alarm-test 5--End
2--Custom-text
3--Watchdog-counter
All information given in this section is closely related to the MENU structure
given in section 6.1.
Please confer this structure when reading the following information.
By pressing the ”MENU” key, the system always returns to the main menu.
Values which are used are default values from the factory. All values can be
changed by using the key-pad. Remember to save the values before closing the
door.
When the control panel door is opened, the following text will appear in the
display:
When the alarm delay is activated, the following text will appear in the display:
(See section 7.3).
H - Hours
MM - Minutes
By pressing the “MENU” key, the following text will appear in the display:
Out-/in-control 7. Out-/in-control
MAIN MENU
When disabling parts of the system, the amber (yellow) lamp “FUNCTION
DISABLED” on the front of the control panel will light as long as the disabling
lasts.
By selecting disable time of 99 hours, the function will be disabled for ever.
To reach this function rapidly, press “1” when the front door is opened.
For the LPC program version the internal buzzer will be activated approx. every 5
sec. while some parts are disabled.
DISABLE ADDRESS(ES)
SELECT ADDRESS (01 - XX): 00
Select the address to be disabled and press ↵. The address will now appear twice.
By pressing ↵ again only the current address will be disabled.
Disablement of To disable a group of addresses, enter start and stop address, and press ↵. When
a group of disabling a group of addresses, no manual call-points will be disabled.
addresses
If all addresses in a zone are disabled, the lamp “DISABLING ZONE” will light
with an amber (yellow) light as long as the disabling lasts.
DISABLEMENT OF ADDRESS(ES) OK
NUMBER: nn, TOTAL: NN, PRESS ‘MENU’
DISABLE ZONE
SELECT ZONE-NUMBER: 000
A amber (yellow) lamp “CUSTOM DESIGNED TEXT” might light (in addition
to the lamp “FUNCTION DISABLED” as long as the disablement lasts.
A amber (yellow) lamp “CUSTOM DESIGNED TEXT” might light (in addition
to the lamp “FUNCTION DISABLED” as long as the disablements lasts.
The following text will appear in the display for the English version:
ENTER PASSWORD:
DISABLE SOUNDER(S)
SELECT SOUNDER-OUTPUT: 00
DISABLEMENT OF 4 SOUNDER-OUTPUTS OK
PRESS ‘MENU’
DISABLEMENT OF SOUNDER-OUTPUT: PP
ENTER DISABLE TIME (HOURS): 02
DISABLEMENT OF SOUNDER-OUTPUT: PP OK
PRESS ‘MENU’
PP is disabled sounder-output.
DISABLE CONTROLS:
1:ZONE-CONTR. 2:CONTROL-1 3:CONTROL-2
DISABLE ZONE-CONTROL(S)
SELECT ZONE-CONTROL: 000
DISABLEMENT OF NN ZONE-CONTROL(S) OK
PRESS ‘MENU’
If an unused zone-control is selected, the following text will appear in the display:
ACCESS OF ZONE-CONTROL ZZZ IS BLOCKED
PRESS ‘MENU’
DISABLEMENT OF CONTROL-1
ENTER DISABLE TIME (HOURS): 02
DISABLEMENT OF CONTROL-1 OK
PRESS ‘MENU’
DISABLEMENT OF CONTROL-2
ENTER DISABLE TIME (HOURS): 02
DISABLEMENT OF CONTROL-2 OK
PRESS ‘MENU’
To reach this function rapidly, press “2” when the front door is opened.
RESTORE ADDRESS(ES)
SELECT ADDRESS (01-XX): 00
Restoring of one Enter the address to be restored and press ↵.The address will now appear twice.
address
By pressing ↵ again only the current address will be restored.
Restoring of a To restore a group of addresses, enter start and stop address and press ↵.
group of
addresses The following text will appear in the display:
RESTORE OF nn ADDRESS(ES) OK
PRESS ‘MENU’
RESTORE ZONE
SELECT ZONE -NUMBER: 000
If an unused zone is selected, the following text will appear in the display:
RESTORE SOUNDER(S)
SELECT SOUNDER-OUTPUT: 00
Restoring of all By pressing ↵ at sounder-output 00, all sounder-outputs will be restored, and the
sounder outputs following text will appear in the display:
RESTORE OF 4 SOUNDER-OUTPUTS OK
PRESS ‘MENU’
RESTORE OF SOUNDER-OUTPUT: PP OK
PRESS ‘MENU’
RESTORE CONTROLS:
1:ZONE-CONTR. 2:CONTROL-1 3:CONTROL-2
RESTORE ZONE-CONTROL(S)
SELECT ZONE-CONTROL: 000
Restoring of all
116-P-BS60/FEE 2005-06-13 25 Autronica Fire and Security AS
zone-controls
BS-60 Operators handbook
By pressing ↵ at zone-control 000, all controls will be restored, and the following
text will appear in the display:
RESTORE OF 16 ZONE-CONTROL(S) OK
PRESS ‘MENU’
If an unused zone is selected, the following text will appear in the display:
RESTORE OF CONTROL-1 OK
PRESS ‘MENU’
RESTORE OF CONTROL-2 OK
PRESS ‘MENU’
ALARM DELAY
ENTER DURATION (HOURS): 08
To reach this function rapidly, press “3” when the front door is opened.
When the alarm delay is activated, a alarm delay (T1) function will hold the
controlling of sounders and BMA-circuit. (Fire Brigade/Fighters).
If the alarm is confirmed within the alarm delay (T1) by operating the
“SILENCE/RESOUND SOUNDERS” button, an additional alarm delay (T2) will
be activated.
Test 8. Test
Main menu
Test Frontpanel/buzzer
BMA/BMF
Fault
Sounders
Controls Zone-control
Alarm Control-1
Control-2
All tests will be terminated by pressing “MENU” or closing the door. If a fire
alarm occurs, the tests will be terminated, and the alarm messages will appear in
the display.
TEST1:FRONTPANEL/BUZZER 2:BMA/BMF
3:FAULT 4:SOUNDERS 5:CONTOLS 6:ALARM
DISPLAY TEST:
All characters used in the display will appear, and all indication lamps on the
control panel front will light. The internal buzzer will be activated approx. every
5. sec.
This function will activate the devices connected to the corresponding outputs.
When the earth failure test sequence is finished, the next sequence automatically
will start.
The test process will take 1 minute. It is indicated by appearing dots in the display
for the first half minute. Then the sequence is reversed the next half minute.
When the address fault active test sequence is finished, the next sequence will
automatically start.
This test sequence (which is a real battery load test) lasts for 10 seconds, and will
normally not give any fault message.
When the test battery active sequence is finished, the main menu will appear.
SOUNDER TEST
WHEN COMPLETED PRESS ’MENU’
During the test sequence all sounder outputs will be activated. The sequence is
interrupted/completed by pressing “MENU”.
TEST CONTROLS:
1:ZONE-CONTR. 2:CONTROL-1 3:CONTROL-2
Testing To test the zone-controls one by one, select the zone-control to be tested. It is
zone-controls possible to test more than one at the time.
one by one
TEST ZONE-CONTR.NO: ZZZ nn OUTP. IN TEST
WHEN COMPLETED PRESS ’MENU’
TEST OF CONTROL-1
WHEN COMPLETED PRESS ‘MENU’
TEST OF CONTROL-2
WHEN COMPLETED PRESS ‘MENU’
The control panel will simulate an automatic alarm without changing the state of
the panel. (The panel can not see the difference between a real alarm and a
simulated alarm.)
The fire indicator lamps, zone indicator lamps, alarm devices and the internal
buzzer will be activated when the test is carried out.
Select “ALARM” by pressing “6” in the “TEST”-menu and the following text will
appear in the display:
Enter address to be tested, press ↵, and the following text will appear in the
display:
Press “SOUNDER SILENCE” and “RESET” and the control panel will return to
normal condition.
or:
If ↵ is not pressed in a few sec. the text always return to the first fault message
which was given.
SHOW-STATUS FAULT
NO EVENTS, PRESS ‘MENU’
SHOW-STATUS DISABLEMENTS
0 DISABLEMENTS IN PANEL
or:
SHOW-STATUS DISABLEMENTS
ZONE NO YYY RESTORE TT HOUR(S)
(If more than one zone is disabled, there will be one message for each.)
SHOW-STATUS DISABLEMENTS
ADDRESS NO XX RESTORE TT HOUR(S)
(If more than one address is disabled, there will be one message for each).
SHOW-STATUS DISABLEMENTS
FIRE BRIG. RESTORE TT HOUR(S)
SHOW-STATUS DISABLEMENTS
SOUNDER OUTPUT PP RESTORE TT HOUR(S)
(If more than one sounder output is disabled, there will be one message for each).
SHOW-STATUS DISABLEMENTS
ZONE-CONTROL: ZZZ RESTORE TT HOUR(S)
(If more than one zone-control is disabled, there will be one message for each).
SHOW-STATUS DISABLEMENTS
CONTROL-1 RESTORE TT HOUR(S)
SHOW-STATUS DISABLEMENTS
CONTROL-2 RESTORE TT HOUR(S)
SHOW-STATUS DISABLEMENTS
NN DISABLEMENTS IN PANEL
If parts of the panel was disabled for 99 hours, the following text will appear in
the display:
SHOW-STATUS DISABLEMENTS
‘part of the system’ RESTORE UNDEF. (LOCAL)
or:
SHOW-STATUS DISABLEMENTS
‘part of the system’ RESTORE UNDEF. (MASTER)
Use the ↵ key to scroll forward. Use the “9” to scroll backward.
Internal Program-version
Adjust-clock
Show-clock
Config. Data
Zone Start no.
Edit Insert
Automatic Delete
Save Renumber End
Delete
End
SYSTEM SENSITIVITY:
1:ADDRESS 2:BEYOND-LIMITS
The “SYSTEM SENSITIVITY” function enables the user to read the analogue
measuring signals from the individual detector (address), or from all addresses
connected to the control panel.
The analogue signal is automatically updated every 7th second.
10.1.1 Addresses
Addresses
Select “1” in the “SYSTEM SENSITIVITY”-menu, and the following text will
appear in the display:
ADDRESS SENSITIVITY:
1:SINGLE-ADDRESSES 2:TOTAL
ADDRESS: 00
Press ↵ and the system will suggest the next following address.
The analogue signal is indicated in milliseconds, and the value might alter slightly
at each update due to minor environmental changes.
Values:
- 32 ms = detector fault
34 - 110 ms = normal value
112 - 126 ms = prewarning
128 - = fire alarm
10.1.1.2 Total
The system will measure all addresses (detectors) connected to the loop one by
one.
Select “2” in “ADDRESS SENSITIVITY”-menu, and the following text will
appear in the display:
Select “2” in “SYSTEM SENSITIVITY”-menu, and the following text will appear
in the display:
The system will measure all addresses (detectors) connected in the loop.
Each detector address beyond limits will be indicated for approx. 5 seconds in the
display:
This sequence will automatically be ended when all detector addresses beyond
limits are listed, or when ↵ is pressed.
10.2.2 Adjust-clock
Select “ADJUST-CLOCK” by pressing “2” in the “SYSTEM INTERNAL”-menu,
and the following text will appear in the display:
Enter the correct day and press ↵, enter the correct month and press ↵ so..
When all corrections are done, the following text will appear in the display:
10.2.3 Show-clock
Select “SHOW-CLOCK” by pressing “3” in the “SYSTEM INTERNAL”-menu,
and the following text will appear in the display: