MGate 5103 Series
1-port Modbus RTU/ASCII/TCP/EtherNet/IP-to-PROFINET gateways
Features and Benefits
• Converts Modbus, or EtherNet/IP to PROFINET
• Supports PROFINET IO device
• Supports Modbus RTU/ASCII/TCP master/client and slave/server
• Supports EtherNet/IP Adapter
• Effortless configuration via web-based wizard
• Built-in Ethernet cascading for easy wiring
• Embedded traffic monitoring/diagnostic information for easy troubleshooting
• microSD card for configuration backup/duplication and event logs
• Status monitoring and fault protection for easy maintenance
• Serial port with 2 kV isolation protection
• -40 to 75°C wide operating temperature models available
• Supports redundant dual DC power inputs and 1 relay output
• Security features based on IEC 62443
Certifications
Introduction
The MGate 5103 is an industrial Ethernet gateway for converting Modbus RTU/ASCII/TCP or EtherNet/IP to PROFINET-based network
communications. To integrate existing Modbus devices onto a PROFINET network, use the MGate 5103 as a Modbus master/slave or EtherNet/IP
adapter to collect data and exchange data with PROFINET devices. The latest exchange data will be stored in the gateway. The gateway will
convert stored Modbus or EtherNet/IP data into PROFINET packets so the PROFINET IO Controller can control or monitor field devices.
Easy Configuration via Web Console
The MGate 5103 Series comes with an illustrated Quick Setup guide designed to make configuration easy. With Quick Setup, you can easily access
protocol conversion modes and finish the configuration in a few steps. The MGate 5103 Series also supports a GSDML export function. GSDML
files can be imported into PROFINET PLCs to save time on PLC configuration.
Modbus RTU/ASCII/TCP Protocol Traffic Monitor
MGate 5103 gateways support Modbus RTU/ASCII/TCP Protocol Traffic Monitor for easy troubleshooting, especially during the installation stage.
Communication issues could be caused by incorrect software parameters, such as slave IDs and register addresses, that were entered incorrectly,
or an incorrect command configuration. With Modbus RTU/ASCII/TCP Protocol Traffic Monitor, you can check the captured data and easily identify
the root cause.
Maintenance Functions
MGate 5103 gateways support a system log function that records events in the MGate; users can easily review log data remotely through the web
console. The gateways also support status monitoring and fault protection functions. The status monitoring function notifies a PLC/DCS/SCADA
system when a Modbus device gets disconnected or does not respond, in which case the process PLC/DCS gets the status of each end device
and then issues alarms to notify operators.
Specifications
Ethernet Interface
10/100BaseT(X) Ports (RJ45 connector) 2
Auto MDI/MDI-X connection
Magnetic Isolation Protection 1.5 kV (built-in)
1 www.moxa.com
Ethernet Software Features
Industrial Protocols PROFINET IO Device, Modbus TCP Client (Master), Modbus TCP Server (Slave),
EtherNet/IP Adapter
Configuration Options Web Console (HTTP/HTTPS), Device Search Utility (DSU), Telnet Console
Management ARP, DHCP Client, DNS, HTTP, HTTPS, SMTP, SNMP Trap, SNMPv1/v2c/v3, TCP/IP,
Telnet, SSH, UDP, NTP Client
MIB RFC1213, RFC1317
Time Management NTP Client
Serial Interface
Console Port RS-232 (TxD, RxD, GND), 8-pin RJ45 (115200, n, 8, 1)
No. of Ports 1
Connector DB9 male
Serial Standards RS-232/422/485
Baudrate 50 bps to 921.6 kbps
Data Bits 7, 8
Parity None, Even, Odd, Space, Mark
Stop Bits 1, 2
Flow Control RTS Toggle (RS-232 only), RTS/CTS
RS-485 Data Direction Control ADDC® (automatic data direction control)
Pull High/Low Resistor for RS-485 1 kilo-ohm, 150 kilo-ohms
Terminator for RS-485 120 ohms
Isolation 2 kV (built-in)
Serial Signals
RS-232 TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422 Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w Data+, Data-, GND
RS-485-4w Tx+, Tx-, Rx+, Rx-, GND
Serial Software Features
Configuration Options Serial Console
Industrial Protocols Modbus RTU/ASCII Master, Modbus RTU/ASCII Slave
Modbus RTU/ASCII
Mode Master, Slave
Functions Supported 1, 2, 3, 4, 5, 6, 15, 16, 23
Max. No. of Commands 128
Input Data Size 512 bytes
Output Data Size 512 bytes
2 www.moxa.com
Modbus TCP
Mode Client (Master), Server (Slave)
Client (Master), Server (Slave)
Functions Supported 1, 2, 3, 4, 5, 6, 15, 16, 23
Max. No. of Client Connections 16
Max. No. of Server Connections 32
Max. No. of Commands 128
Input Data Size 512 bytes
Output Data Size 512 bytes
PROFINET
Mode IO Device
IO Device
Max. No. of IO Controller Connections 1 (for read/write)
Input Data Size 512 bytes
Output Data Size 512 bytes
EtherNet/IP
Mode Adapter
CIP Objects Supported Identity, Message Router, Assembly, Connection Manager, TCP/IP interface, Ethernet
link, Port
Max. No. of Scanner Connections 1 (for read-only), 1 (for read/write)
Input Data Size 496 bytes
Output Data Size 496 bytes
Memory
microSD Slot Up to 32 GB (SD 2.0 compatible)
Power Parameters
Input Voltage 12 to 48 VDC
Input Current 455 mA @ 12 VDC
Power Connector Screw-fastened Euroblock terminal
Relays
Contact Current Rating Resistive load: 2 A @ 30 VDC
Physical Characteristics
Housing Metal
IP Rating IP30
Dimensions 36 x 105 x 140 mm (1.42 x 4.14 x 5.51 in)
Weight 507 g (1.12 lb)
3 www.moxa.com
Environmental Limits
Operating Temperature MGate 5103: 0 to 60°C (32 to 140°F)
MGate 5103-T: -40 to 75°C (-40 to 167°F)
Storage Temperature (package included) -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Standards and Certifications
Safety EN 60950-1, UL 508
EMC EN 55032/24
EMI CISPR 32, FCC Part 15B Class B
EMS IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
IEC 61000-4-4 EFT: Power: 4 kV; Signal: 2 kV
IEC 61000-4-5 Surge: Power: 2 kV; Signal: 2 kV
IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m; Signal: 10 V/m
IEC 61000-4-8 PFMF
Hazardous Locations ATEX, Class I Division 2, IECEx
Freefall IEC 60068-2-32
Shock IEC 60068-2-27
Vibration IEC 60068-2-6, IEC 60068-2-64
MTBF
Time 859,422 hrs
Standards Telcordia SR332
Warranty
Warranty Period 5 years
Details See www.moxa.com/warranty
Package Contents
Device 1 x MGate 5103 Series gateway
Cable 1 x RJ45-to-DB9 console cable
Installation Kit 1 x DIN-rail kit
Documentation 1 x quick installation guide
1 x warranty card
4 www.moxa.com
Dimensions
Ordering Information
Model Name Operating Temp.
MGate 5103 0 to 60°C
MGate 5103-T -40 to 75°C
Accessories (sold separately)
Cables
CBL-F9M9-150 DB9 female to DB9 male serial cable, 1.5 m
CBL-F9M9-20 DB9 female to DB9 male serial cable, 20 cm
CBL-RJ45F9-150 RJ45 to DB9 female serial cable, 1.5 m
CBL-RJ45SF9-150 RJ45 to DB9 female serial shielded cable, 1.5 m
Connectors
Mini DB9F-to-TB DB9 female to terminal block connector
DIN-Rail Mounting Kits
DK-25-01 DIN-rail mounting kit, 2 screws
Wall-Mounting Kits
WK-36-02 Wall-mounting kit, 2 plates, 6 screws, 36 x 67 x 2 mm
Power Cords
CBL-PJTB-10 Non-locking barrel plug to bare-wire cable
5 www.moxa.com
© Moxa Inc. All rights reserved. Updated Nov 10, 2019.
This document and any portion thereof may not be reproduced or used in any manner whatsoever without the express written permission of
Moxa Inc. Product specifications subject to change without notice. Visit our website for the most up-to-date product information.
6 www.moxa.com