0% found this document useful (0 votes)
60 views2 pages

Fcu Hidden Ceiling 2 TR Four Pipe

The document provides technical specifications for an air handling unit project including: - Project details such as the date, project ID, and name - Dimensions, weight, and other physical characteristics of the unit - Air flow rate and external pressure drop specifications - Fan details such as power, sound levels, and count - Coil details including area, pitch, and connection sizes - Cooling capacity and performance details like temperatures and humidity - Heating capacity and performance details - A psychrometric chart for reference

Uploaded by

mahmadwasi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views2 pages

Fcu Hidden Ceiling 2 TR Four Pipe

The document provides technical specifications for an air handling unit project including: - Project details such as the date, project ID, and name - Dimensions, weight, and other physical characteristics of the unit - Air flow rate and external pressure drop specifications - Fan details such as power, sound levels, and count - Coil details including area, pitch, and connection sizes - Cooling capacity and performance details like temperatures and humidity - Heating capacity and performance details - A psychrometric chart for reference

Uploaded by

mahmadwasi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

TECHNICAL DATA

Date 18/12/2020 Rev. Date 18/12/2020


Project ID 2074 Tracking Number
Project Name FCU-SHAHZEB
2.2.3.9
FCU Name FNCL-HCT-0-(4)-(4)-173-L-R AHUSEL V. 06/06/2016
FCU Model FOUR PIPE HIDDEN CEILING TYPE Page 1/2
Air Flow 800 ft³/min Speed Medium
External Pressure Drop 0.75 inAq Quantity 1
CONDITIONS
City Altitude 0m
Atmosphere Pressure 407 inAq Air Density 1.1988 kg/m³
FAN
Electrical Power 0 Btu/h Electrical Current 0.00 A
Sound Power Level (H/M/L) 60 / 58 / 56 dB(A) Fan Count 4
COIL
Air Velocity 215.3 ft/min Coil Area 26.89 m²
Row Count 4 Pitch 2.1 mm
Entry Connection Diameter 3/4" DN20 Exit Connection Diameter 3/4" DN20
2. Entry Connection Diameter 1/2" DN15 2. Exit Connection Diameter 1/2" DN15
COOLING
Fluid WATER Fluid Temperature 44.60 °F / 53.60 °F
Inlet Dry Thermometer 80.60 °F Outlet Dry Thermometer 56.74 °F
Inlet Wet Thermometer 67.16 °F Outlet Wet Thermometer 55.32 °F
Inlet Relative Humidity 50.00 % Outlet Relative Humidity 91.69 %
Capacity / Sensible Capacity 28,413 Btu/h / 20,238 Btu/h Pressure Drop 0.07 inAq
Fluid Pressure Drop 18.07 kPa Fluid Flow 0.3968 kg/s
Fluid Volumetric Flow 0.841 ft³/min Tube Inner Volume 3.07 L
HEATING
Fluid WATER Fluid Temperature 176 °F / 140 °F
Inlet Dry Thermometer 68 °F Outlet Dry Thermometer 104.6 °F
Inlet Wet Thermometer 56.81 °F Outlet Wet Thermometer 69.33 °F
Inlet Relative Humidity 50.00 % Outlet Relative Humidity 15.57 %
Capacity 31,774 Btu/h Pressure Drop 0.02 inAq
Fluid Pressure Drop 9.22 kPa Fluid Flow 0.1111 kg/s
Fluid Volumetric Flow 0.2422 ft³/min Tube Inner Volume 1.06 L
SIZE
Size (mm) 1890 x 250 x 550 mm Package Size (mm) 1910 x 260 x 560 mm
Weight 55.00 kg

www.ahuselection.com Office Tel: +90 850 532 26 31 Factory Tel: +90 850 532 26 31
[email protected] Office Fax: +90 850 532 26 31 Factory Fax: +90 850 532 26 31

Designer: Shahzeb Khan 18.12.2020


AHU Selection
TECHNICAL DATA
Date 18/12/2020 Rev. Date 18/12/2020
Project ID 2074 Tracking Number
Project Name FCU-SHAHZEB
2.2.3.9
FCU Name FNCL-HCT-0-(4)-(4)-173-L-R AHUSEL V. 06/06/2016
FCU Model FOUR PIPE HIDDEN CEILING TYPE Page 2/2