Res-5010 en V4
Res-5010 en V4
RES-5010
Operating
instructions
Important features
• Complete control via PROFINET interface („Conformance Class C“, IO/RT and IRT acc. to IEC
61784-2), (2 x RJ-45)
• Automatic zeroing (AUTOCAL)
• Automatic optimisation (AUTOTUNE)
• Automatic configuration of the secondary voltage and current range (AUTORANGE)
• Automatic phase correction (AUTOCOMP)
• Automatic frequency adaptation
• Booster output
• Analogue output 0…10 VDC for ACTUAL temperature
• Alarm function with error diagnosis
• Heating element alloy and temperature range can be selected
• Wide voltage range for the use of 110…480 V1 (as from 02/2021)
• Eight channels for administration of various calibration values
1 Revision list
Version Change
1 • Creation of documentation
• New: Voltage supply range changed to max. 480 VAC1 (as from 02/2021)
section 10 "Technical data" on page 56
1. Standard: 415 VAC, optional and on request: 480 VAC
2 General information
This RESISTRON® temperature controller is manufactured according to EN 61010-1. In the course of its manu-
facture it passed through quality assurance, whereby it was subjected to extensive inspections and tests. As a
result of this, the product left our factory in perfect condition.
Please carefully read through the operating manual before using the RESISTRON® temperature controller. Keep
the operating manual for later reference and make sure that information and functions important for the user are
available.
The recommendations and warning notes contained in these operating instructions must be complied with, in
order to guarantee safe operation.
The device can be operated within the limits indicated in the "Technical Data" without impairing its operational
safety. Installation and maintenance may only be performed by technically trained, skilled persons who are familiar
with the associated risks and warranty provisions.
2.1 Copyright
All contents, in particular texts, photographs and graphics, are protected by copyright. All rights, including to rep-
lication, publication, editing and translation, are reserved.
RESISTRON® temperature controllers may only be used for heating and temperature control of heatsealing bands
which are expressly approved for them, and providing the regulations, notes and warnings contained in these
instructions are observed.
In case of non-observance or use contrary to the intended purpose, there is a risk that safety will be impaired or
that the heatsealing band, electrical wiring, transformer etc. will overheat. This is the personal responsibility of the
user.
The use of suitable heatsealing bands is a basic prerequisite for reliable and safe operation of the system.
The resistance of the heatsealing band which is used must have a positive minimum temperature coefficient in
order to guarantee trouble-free operation of the RESISTRON® temperature controller.
The temperature coefficient must be specified as follows:
–4 –1 –1
TCR = 10x10 K or K or ppm/K
e.g. Alloy A20: TCR = 1100 ppm/K
LEX3500: TCR = 3500 ppm/K
Vacodil: TCR = 1100 ppm/K
®
The RESISTRON temperature controller must be set and coded according to the temperature coefficient of the
heatsealing band.
The temperature coefficient must be taken from the ROPEX application report and must be set accordingly.
The use of incorrect alloys with a too low temperature coefficient and incorrect coding of the
! RESISTRON® temperature controller leads to uncontrolled heating of the heatsealing band, which
will ultimately burn out!
The original heatsealing bands must be clearly identified by means of suitable markings as well as the connector
geometry, length, or other means to ensure that replacement bands are identical.
A suitable impulse transformer is necessary in order to guarantee trouble-free operation of the control loop. This
transformer must be designed according to EN 61558 or UL 5058 (isolating transformer with reinforced insulation)
and have a one section bobbin. When the impulse transformer is installed, suitable touch protection must be pro-
vided in accordance with the national installation regulations for electrical equipment. In addition to this, water,
cleaning solutions and conductive fluids must be prevented from seeping into the transformer.
The current transformer supplied with the RESISTRON® temperature controller is an integral part of the control
system.
Only the original ROPEX PEX-W4 or PEX-W5 current transformer may be used. Other transformers may cause
the equipment to malfunction.
The current transformer may only be operated if it is correctly connected to the RESISTRON® temperature con-
troller (see section "Startup and operation"). The relevant safety instructions contained in section "Power supply",
must be observed. External monitoring modules can be used in order to additionally increase operating safety.
They are not included in the scope of supply of the standard control system and are described in a separate doc-
ument.
ROPEX provides line filters in different power classes. The ROPEX application report lists the suitable line filter
which can be ordered accordingly.
The use of an original ROPEX line filter is mandatory in order to comply with the directives mentioned in
section 2.10 "DECLARATION OF CONFORMITY" on page 7. This device must be installed and connected
according to the instructions contained in section "Power supply" as well as the separate documentation enclosed
with the line filter.
2.7 Maintenance
The controller requires no special maintenance. Regular inspection and / or tightening of the terminals – including
the terminals for the winding connections on the impulse transformer – is recommended. Dust deposits on the con-
troller can be removed with dry compressed air.
Dust deposits and dirt from liquids result in a loss of function. Accordingly, installation in a switch
! cabinet or terminal cabined with IP54 is recommended.
2.8 Transportation
2.9 Disposal
This device is subject to Directive 2012/19/EU concerning the reduction of the increasing amount of
waste electrical and electronic equipment and the disposal of such waste in an environmentally
sound way.
To guarantee proper disposal and / or the recover of reusable material, please take the device to a
designated municipal collection point and observe local regulations.
Careless, uncontrolled disposal can cause damage to the environment and human health. By
ensuring that your product is disposed of or recycled in a responsible way, you can help protect the
environment and human health.
We hereby declare that the following device has been developed and manufactured in conformance with the direc-
tives cited below:
EN 61010-1 Safety requirements for electrical equipment, control, and laboratory use
Note:
This declaration of conformity certifies that the device/electronic itself complies with the above-mentioned direc-
tives. The CE mark on the device/electronic does not relieve the machinery manufacturer of his duty to verify the
conformity of the completely installed, wired and operationally ready system in the machine with the EMC directive.
Comments:
RESISTRON/CIRUS temperature controllers are not independently operable devices. They are used by the
machinery manufacturer to form a sealing system by adding EMC-relevant components such as filters, trans-
formers, heatsealing bands and wiring. The final configuration may vary significantly in terms of performance and
physical dimensions. All information provided by us in connection with the line filter is merely intended as a guide
and is based on a typical measuring setup. It serves to demonstrate that compliance with the EMC directive can
be achieved by using a line filter that is suitable for the overall system. The line filter and current transformer must,
however, be determined on the basis of the respective application. We also wish to point out that the transformer
which is used must be designed in accordance with VDE 0551/EN 61558 or UL 5058 for safety reasons.
3 Use
This RESISTRON® temperature controller is part of the “Series 5000”, whose main characteristic is micropro-
cessor technology. All RESISTRON® temperature controllers provide temperature regulation of heating elements
as are used in a variety of foil sealing processes.
The most common heating elements include:
• ribbon cables (straight and contoured)
• clincher bands
• beaded bands
• cutting wires
• heat-sealing blades
• soldering bows
The main application area is sealing or cutting of thermoplastics using the thermal impulse process.
The most common application areas are:
• vertical and horizontal form-fill-seal machines (VFFS and HFFS)
• bagging, filling and sealing machines
• film-wrapping machines
• bag-production machines
• group packaging machines
• foil sealing devices
• spout and hose sealing
• and much more
4 Functional principle
The resistance of the heating element, which changes with temperature, is measured by means of current and
voltage measurement, displayed and compared with the specified setpoint value. Measurements are made
50 times per second in a 50 Hz network, 60 times per second in a 60 Hz network.
The primary voltage of the impulse transformer is adjusted following the leading edge principle if the measured
values deviate from the setpoint value. The related current change in the heating element results in a rise in tem-
perature and change of resistance. The change in resistance is measured and evaluated by the RESISTRON®
temperature controller. The temperature controller adjusts the control variables according to the change and the
set setpoint.
Even the smallest thermal loads on the heating element are recorded and can be quickly and precisely corrected.
Measurement of pure electric variables, together with the high measurement rate, result in a highly dynamic ther-
moelectric control circuit. The principle of primary-side transformer control proves to be especially advantageous
as it permits a very large secondary current range with low power loss. This permits an optimal adjustment to the
load and thus the desired dynamics with extremely compact device measurements.
5 Device features
The RESISTRON® temperature controller RES-5010 is equipped with a PROFINET interface. Through this inter-
face, all functions and parameters can be parameterised by means of the higher level machine controller. In addi-
tion, important controller information is queried and can be processed accordingly.
The ACTUAL temperature of the heating element is output through the PROFINET interface and through an ana-
logue output 0…10 VDC. The real heating element temperature can be visualised on an external display instru-
ment (e.g. ATR-x) or via the operating unit of the machine controller.
The RES-5010 has an integrated error diagnosis that checks both the external system (heating element, wiring,
etc.) and the internal electronics. A differentiated error message is output through the PROFINET interface in case
of malfunction.
To increase operational security and immunity to interference, all PROFINET signals from the controller and
heating circuit are electrically isolated.
Adjustment for different heating element alloys (alloy A20, Vacodil, etc.) and setting of the temperature range to
be used (0…300 °C or 0…500 °C) can be made through coding switches on the temperature controller itself or
through the PROFINET interface.
The compact design of the RESISTRON® temperature controller RES-5010 as well as the plug-in connecting ter-
minals make mounting and installation easier.
An overview of the most important features and functions:
• Easy calibration of the heating element through AUTOCAL, the automatic zero-point setting
• Eight channels permit switching of the calibration parameters during tool change.
• High control dynamics through AUTOTUNE, automatic adjustment to the controlled system
• High flexibility: The AUTORANGE function covers a secondary voltage range of 0.4 V to 120 V and a current
range of 30 A to 500 A.
• Automatic adjustment to the network frequency in the range of 47 Hz to 63 Hz
• Wide voltage range for flexible use from 110 VAC to 480 VAC1 (as from 02/2021)
• Easy and convenient system diagnosis and process visualisation through the free, downloadable software
ROPEXvisual®
• Comprehensive error diagnosis over the PROFINET interface
• Booster output available for connecting a switching amplifier
• High process security through comprehensive options for evaluating the parameter data (e.g. temperature
diagnosis or heat-up time monitoring)
Mounting, installation and startup may only be performed by authorized persons who have received
! suitable instruction and are familiar with the associated risks and warranty provisions.
The supply voltage to the machine side must lie within the permitted voltage and frequency range
! of the RESISTRON® temperature controller Otherwise, there is the danger of a defect.
The overcurrent protective devices marked (*) should be used in installations conforming to UL standards.
If one such device is not adequate for the heatsealing application, two separate overcurrent protective devices
should be provided – one for the controller and one for the application ( ROPEX Application Report).
The overcurrent protective device must be located directly adjacent to the controller.
The minimum possible specification for this device is indicated in the ROPEX Application Report based on the
calculated currents. If a larger overcurrent protective device is fitted, you must match the current carrying
capacity of the other components accordingly (e.g. cables, impulse transformer etc.).
5. A disconnecting device must be provided when the system is installed; it must be marked as belonging to the
system and fitted in a readily accessible position.
If a miniature circuit breaker is used, it can also perform the function of this device.
6. Connect the RESISTRON® temperature controller to the PROFINET controller using a suitable (standard
compliant) cable.
Check that all system connections – including the terminals for the impulse transformer windings
! – are securely attached.
7. Make sure the wiring conforms to all relevant national and international installation regulations.
Sample depiction
Impulse
transformer
Dimension
transformer correctly
- Secondary voltage
- Power 20 mm clearance if several
- Duty cycle controllers installed on
one top hat rail
LINE
L1 (L1)
N (L2) Line
GND/
Earth
Over-current protection
Double-pole circuit-breaker or fuses,
ON Kc
( ROPEX Application Report)
Short-circuit protection only. RESISTRON® tem-
I> I> ! perature controller not protected.
OFF
3
Ka Relay Ka
For "HEAT ON - OFF" function (all-pole) or
"EMERGENCY STOP".
Line filter
LINE The filter type and size must be determined according to
FILTER
the load, the transformer and the machine wiring
( ROPEX Application Report).
Short wires Do not run the filter supply wires (line side) parallel
3
UR
! to the filter output wires (load side).
ROPEX
temperature RESISTRON® temperature controller
IR controller
Relay Kb
Kb Load break (all-pole), e.g. in combination with the alarm
output of the temp. controller (ROPEX recommendation).
When using a series resistor RV-....-1 the relay Kb
! shall be installed.
U1 3
Impulse Transformer
PRIM.
Designed according to EN 61558 (isolating transformer
with reinforced insulation). Connect core to ground.
Use transformers with a one section bobbin. The
! power, duty cycle and voltage values must be deter-
U2
2 mined individually according to the application ( ROPEX
SEC.
Application Report and "Accessories" leaflet for impulse
1
transformers).
2
Wiring
The wire cross-sections depend on the application
( ROPEX Application Report).
R
Wires must always be twisted (min. 20 turns/meter).
These wires must be twisted (min. 20 turns/meter)
if several control loops are laid together ("crosstalk").
Twisting (min. 20 turns/meter) is recommended to
improve EMC.
To comply with EMC directives – corresponding to EN 50081-1 and EN 50082-2 – RESISTRON control loops
must be operated with line filters.
These filters damp the reaction of the phase-angle control on the line and protect the controller against line distur-
bances.
The use of a suitable line filter is part of the standards conformity and a prerequisite of the CE mark.
!
ROPEX line filters are specially optimized for use in RESISTRON control loops. Providing that they are installed
and wired correctly, they guarantee compliance with the EMC limit values.
You can find the exact specification of the line filter in the ROPEX Application Report calculated for your particular
heatsealing application.
For more technical information: "Line filter" documentation.
It is permissible to supply several RESISTRON control loops with a single line filter, providing the total current does
not exceed the maximum current of the filter.
The wiring instructions contained in section 6.3 "Power supply" on page 12 must be observed.
Example drawing for LF-06480:
Large cross-section
wire to ground
max. 1 m
PE
LINE ROPEX
temperature
controller
The PEX-W4/-W5 current transformer supplied with the RESISTRON® temperature controller is an integral part
of the control system. The current transformer may only be operated if it is connected to the temperature controller
correctly ( section 6.3 "Power supply" on page 12).
6.5.1 PEX-W4
24 75 14
23 28
terminal
wires
60
12
39
26
14
terminal
block
6.5.2 PEX-W5
Line filter
1
Ethernet
RES-5010 LINE
TX+ 1 2
PORT 1 (RJ45)
TX- 2
RX+ 3 15
BOOSTER
OUTPUT
RX- 6 16
4 Ethernet
Termination
module
5 3
7 4
8 U1
prim.
Shield Impulse
Ethernet transformer
PORT 2 (RJ45)
(for assignment U2
see PORT 1) sec.
Ground
Must be grounded 8 Heat-
externally to UR R sealing
prevent 6 9 band
twisted
electrostatic
charging!
V+ 5 10
24 VDC POWER IR
SUPPLY 11
V- 7
Current
transformer
12
ALARM OUTPUT
max. 30 V 13
14
_
18
ATR
°C 17
+
ANALOG OUTPUT
+0...10 VDC
Line filter
1
Ethernet
RES-5010 LINE
TX+ 1 2
PORT 1 (RJ45)
TX- 2 Booster
3 1
RX+ 3 15
IN OUT
RX- 6 16
4 2
4 twisted
Ethernet Max. length 1 m
Termination
module
5 3 NC
7 4 NC
8 U1
prim.
Shield Impulse
Ethernet transformer
PORT 2 (RJ45)
(for assignment U2
see PORT 1) sec.
Ground
Must be grounded 8 Heat-
externally to UR R sealing
prevent 6 9 band
twisted
electrostatic
charging!
V+ 5 10
24 VDC POWER IR
SUPPLY 11
V- 7
Current
transformer
12
ALARM OUTPUT
max. 30 V 13
14
_
18
ATR
°C 17
+
ANALOG OUTPUT
+0...10 VDC
PROFINET
Coding and slide LEDs ports
switches
USB interface
Terminal plan
Nameplate
Connection terminals
The controller must be switched off in order to configure the coding and slide switches.
!
2x
7.2.2 Configuration of the rotary coding switch for the temperature range and alloy
AUX
PC CONFIGURATION 9
8 300°C 3500ppm/K 3500ppm/K
780ppm/K (L)
8
5
300°C
500°C
9 PC-CONFIGURATION 0
1100ppm/K (A20)
780ppm/K (L)
4
1
500°C
300°C
1
67 9
1100ppm/K (A20) 0 300°C
2 34
8
TEMP. COEFFICIENT SWITCH POS. TEMP. RANGE
0
5
1
789
2 34
0 = Factory settings
6
The setting of the rotary coding switch for the temperature range and alloy can be overwritten with
! the parameter data ( section 8.7 "Parameter data" on page 31).
If the switch is set to "9", more temperature ranges and alloys can be selected in the ROPEX visualization software
( section 8.12 "USB interface for visualization software ROPEXvisual®" on page 47).
01…FE RES-5010-01…RES-5010-FE
00 = Factory settings
CD
AB E
23 6
45
F0 1
Device name preset to
CD
0...F
45
CD
CD
F01
By assigning device names using rotary coding switches, you can replace a device in an existing machine without
a programming tool. Simply configure the replacement device with the same switch settings.
If the RES-5010 was named using a suitable PROFINET tool (e.g. Siemens STEP7), the preset device name can
be erased by means of the rotary coding switches. To do this, make sure the controller is de-energized, then set
the switches to 0xFF and switch the controller on again. It is sufficient to supply the controller with 24 VDC. No
connection is required to the PROFINET network. After the device name has been successfully erased, the red
DATA EXCHANGE LED blinks at approx. 4 Hz. The power supply to the controller must then be momentarily inter-
rupted in order for the new switch settings to take effect.
In addition to the device name, restoring the factory settings by setting the rotary coding switch to
! "0xFF" also erases all I&M data in the memory.
In order to assign the device name via the PROFINET interface (e.g. using a programming tool), the
! rotary coding switch must be set to "0x00".
Note: By using a configuring tool (e.g. Siemens STEP7) to specify the PROFINET topology, you can also assign
a name automatically if the controller does not already have a device name when it is switched on. In this case,
the PLC automatically assigns it the name stored in the project.
AUX
closed by alarm.
(factory setting) 0
789
1
2 34
6
If the switch is set to "Alarm relay de-energized at alarm / PC CONFIGURATION", you can select more alarm
output configurations in the ROPEX visualization software ( section 8.12 "USB interface for visualization soft-
ware ROPEXvisual®" on page 47).
An overheated or burned-out heatsealing band must no longer be used because the temperature
! coefficient has been irreversibly altered.
A very important design measure is copper-coating or silver-coating of the heating element ends. The thermal
characteristics change in this range through coating of the heating element ends. As a result, the ends remain
cold, which permits exact temperature control and increases the useful life of the heating element.
The heatsealing band must be replaced in accordance with the instructions provided by the manu-
! facturer.
Each time the heatsealing band is replaced, you must calibrate the zero point with the AUTOCAL function while
the band (and the environment, i.e. silicone, PTFE cover, sealing bar etc.) is still cold in order to compensate pro-
duction-related resistance tolerances.
If a new heating element is used, the above-described procedure for burning in must be performed.
Please also refer to section 2 "General information" on page 3 and section 3 "Use" on page 8.
Mounting, installation and startup may only be performed by authorized persons who have received
! suitable instruction and are familiar with the associated risks and warranty provisions.
If the red "ALARM" LED lights up for 0.3…1.5 seconds when the voltage is switched on in addition
! to the yellow "AUTOCAL" LED, the configuration of this controller has been changed in the visual-
ization software ( section 8.12 "USB interface for visualization software ROPEXvisual®" on page 47). In
order to avoid malfunctions, please check the controller configuration before continuing the startup pro-
cedure.
7. The green "DATA EXCHANGE" LED lights up to indicate an active PROFINET communication.
9. Activate the AUTOCAL function while the heatsealing band is still cold by setting the AC bit (AUTOCAL) in the
PROFINET protocol ( section 8.4 "Communication protocol" on page 25). The yellow "AUTOCAL" LED lights
up for the duration of the calibration process (approx. 10…15 seconds). The AA bit (AUTOCAL active) is addi-
tionally set and a voltage of approximately 0 VDC appears at the actual value output (terminals 17+18). If an
ATR-x is connected, it indicates 0…3 °C.
After the zero point has been calibrated, the "AUTOCAL" LED goes out and a voltage of 0.66 VDC (300 °C
range) or 0.4 VDC (500 °C range) appears at the actual value output. If an ATR-x is connected, it must be set
to "Z".
If the zero point was not calibrated successfully, the AL bit (alarm active) is set and the red "ALARM" LED blinks
slowly (1 Hz). In this case the controller configuration is incorrect ( section 7.2 "Device configuration" on
page 17, ROPEX Application Report). Repeat the calibration after correcting the controller configuration.
10.After the zero point has been successfully calibrated, specify a defined temperature by means of the
PROFINET protocol (set point) and set the ST bit. The RA bit (control active) is then activated and the "HEAT"
LED lights up. The heating and control process can be observed at the actual value output.
The controller is functioning correctly if the temperature (which corresponds to the signal change at the analog
output or the actual value in the PROFINET protocol) is a regular curve, in other words it must not jump
abruptly, fluctuate, or temporarily deviate in the wrong direction. This kind of behavior would indicate that the
UR measurement cable was laid incorrectly.
If an error code is displayed, proceed as described in section 8.19 "Error messages" on page 50.
11. Burn in the heatsealing band ( section 7.3 "Replacing and burning in the heatsealing band" on page 19) and
run the AUTOCAL function again.
Always use a heatsealing band with the correct alloy, dimensions, and copper plating in order to
! avoid malfunctions and overheating.
8 Device functions
See also section 6.6 "Wiring diagram (standard)" on page 15.
Vi s u a l
BUS FAILURE Lit or blinking if no connection
(red/green exists to PROFINET.
LED)
DATA EXCH Lit (green) while data exchange
(red/green with PROFINET controller.
LED) 5 6 7 8 9 10 11
In addition to the functions shown above, the LEDs also indicate various controller operating states. These states
are described in detail in the table below:
OUTPUT
In control mode, luminous intensity is proportional to heating current.
(green)
Green: Communication
Rotary coding switches for with PROFINET controller
DATA EXCHANGE
— device name set to 0xFF is active
(red / green)
(factory setting restored) Red: Internal error in
PROFINET module
RX / TX PORT 1, 2
Device is transmitting / receiving Ethernet frames
(yellow)
The following sections only describe controller-specific functions. For general information on the PROFINET inter-
face and the system configuration, please refer to the description of your PLC.
The PROFINET interface of the RES-5010 supports "Conformance Class C" with IO/RT and IRT according to IEC
61784-2.
The controller can communicate via the PROFINET interface provided the 24 VDC supply voltage (terminals 5+7)
is present.
If no line voltage is present however (e.g. if it is switched off in order to open a door), error code 901 or 201 (error
group 7, no line voltage / sync signal) appears on the controller and the alarm relay is switched. This happens due
to the absence of line voltage. The error message can be reset by switching on the line voltage again and setting
the RS bit ( section 8.5.3 "Reset (RS)" on page 27).
You can easily process the error code that appears if the line voltage is switched off – or suppress switching of
the alarm relay – in the PLC program.
The configuring tools for the PROFINET controller interpret the content of the device master files (GSDML) and
use this information to create a parameter set for the PROFINET controller which controls user data traffic. The
GSDML-V2.4-ROPEX-0150-RES-5010-20200921.XML file of the RES-5010 contains all essential controller infor-
mation for the configuration, e.g. the I/O data description, parameter descriptions, error messages etc. The device
master files and the associated image files (.BMP) for visualization in the configuring tool can be requested by e-
mail ([email protected]) or downloaded from our website (https://ropex.de). If the controller already has an IP
address, the device master file can also be downloaded from the integrated web server.
After linking the required device master file into the configuring tool, you must assign a unique name to the con-
troller (device initialization). The controller is shipped without a name. You must also select the desired parameter
values.
The communication protocol consists of 2x16 bit input words and 3x16 bit output words (from the point of view of
the controller). This protocol separates the set point and the actual value of the RES-5010 from the status infor-
mation and the control functions, to simplify decoding by the PROFINET controller.
Bits 0…7 form the low byte and bits 8…15 the high byte ("INTEL format").
The 2 x 16-bit input data contains the set point in word and the control functions in word :
Name: 0 0 0 0 0 0 0
Bit no.: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
The 3 x 16-bit output data contains the actual value in word , the status information in word , and the error
code in word :
Name:
Bit no.: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Error code
Name: 0 0 0 0 0 0 A9 A8 A7 A6 A5 A4 A3 A2 A1 A0
Bit no.: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
If the optional "Temperatures" submodule has been configured, the controller returns another 16-bit output word
with the start temperature:
Name:
Bit no.: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
The term "input data" refers to the data that is transferred from the PROFINET controller to the RES-5010. It con-
tains the set point as well as the control functions such as START or AUTOCAL for the RES-5010. These functions
are explained in the following.
If the PROFINET controller marks its output data with the IOPS "bad" or does not transmit any data at all, all bits
are set to 0 (inactive). An active heatsealing process is interrupted.
1. An AUTOCAL request cannot be accepted until 10 seconds after the controller is switched on. During this time
the controller shows "AUTOCAL blocked" (AG bit = 1) in the output data.
2. The AUTOCAL function is not activated if the heatsealing band cools down at a rate of more than 0.1 K/s. If
the AC bit is set, the function is automatically executed when the cooling rate falls below the specified value.
3. If the START bit is set (ST bit = 1), the AUTOCAL function is not executed ("HEAT" LED lit).
4. If the RESET bit is set (RS bit = 1), the AUTOCAL function is not executed.
5. The AUTOCAL function cannot be activated if error codes 101…103, 201…203 or 9xx appear as soon as the
controller is switched on ( section 8.19 "Error messages" on page 50). It also cannot be activated if error
codes 201…203 or 9xx appear and the controller has operated correctly at least once since being switched on.
If the AUTOCAL function is blocked (AG bit = 1), an AUTOCAL request (AC bit = 1) causes the "AUTOCAL" LED
to blink fast (4 Hz).
The "HEAT" LED on the front panel of the RES-5010 lights up continuously for the duration of the heating time.
A start request is not processed as long as the AUTOCAL function is active, a fault is present on the controller,
the set point is less than 20 °C higher than the calibration temperature, or the RS bit is set. In this case, the "HEAT"
LED blinks.
The heatup process is terminated if the ST bit is reset or if a communication error occurs.
The ST bit is only accepted if the AUTOCAL function is deactivated and there are no faults.
The alarm relay is switched if the ST bit is set while a warning with error code 104…106, 111…114, 211, 302, or
303 is indicated ( section 8.19 "Error messages" on page 50). The heating element is not heated.
Large output values lead to a very rapid temperature rise of the heatsealing band and possibly to
! overheating. Temperature diagnostics should be activated to detect a temperature overshoot and
trigger an error.
The power output level must be specified in the setpoint as a percentage of the maximum power at the time the
KS bit is activated. The permissible value range is 0…100%. For larger values, a limitation to 100% takes place.
The power setting level must be determined by sealing tests. The machine must operate under real conditions.
When determining the output level, it is recommended to start with 10% and to increase the value in small steps.
The term "output data" refers to the data that is transferred from the RES-5010 to the PROFINET controller. It con-
tains the current actual value as well as all important information on the current status of the controller. If a fault is
signaled, it can be diagnosed accurately with the help of the error code.
Actual value
Set+ Δϑ high
Set
Set+ Δϑ low
Time
TO bit
1
0
Time
Unlike the "Temperature achieved" status bit (TE bit), the actual temperature is evaluated independently of the
control mode.
3. "Active when Tact = Tset" with latch function
A heatsealing cycle starts when the ST bit is set. The TO bit is set when the actual temperature reaches the
temperature tolerance band for the first time during a heatsealing cycle. If the actual temperature leaves the
tolerance band again while the ST bit is still set, the TO bit is reset (Fig. a.). If the actual temperature does not
leave the tolerance band while the ST bit is still set, the TO bit is not reset until the start of the next heatsealing
cycle (latch function, Fig. b.). The switching state of the TO bit can thus be queried after the ST bit has been
reset and before the start of the next heatsealing cycle.
Setpoint Setpoint
Time Time
ST bit 1 ST bit 1
0 0
Time Time
TO bit 1 TO bit 1
0 0
Time Time
The parameter data contains values for selecting the heatsealing band alloy, the temperature range, the high and
low tolerance limits for temperature monitoring, the calibration temperature, and the optional heating time limit. It
is transferred from the PROFINET controller to the RES-5010 each time the system is started up. The parameters
can also be queried by the PROFINET controller or transmitted by it to the RES-5010 controller at any time using
asynchronous read / write services. They are not stored in the RES-5010. The parameter data can be addressed
at slot 1, subslot 1, starting at index 4. It has the following structure:
The date, time, operating hours counter, and counters for the individual calibration channels can be read out at
slot 1, subslot 2. Apart from the operating hours counter (index 4…7) and the non-clearable total cycle counter
(index 8…11), these counters can also be reset by means of a write access.
A plausibility check which takes account of leap years is performed after writing the date or time. If the transferred
values do not contain any valid date or time information, the RES-5010 responds with an access error: 0xb7
"Invalid Range". To prevent inconsistencies, the individual date or time values should be changed together with a
single write access, in other words index 0…3 and 4…7.
The start temperature ( section 8.6.12 "Start temperature" on page 31) and the internal device temperature are
available at slot 1, subslot 3. They are read-only values which cannot be written,
The channel-specific deviations from the calibration data are available at slot 1, subslot 4 ( section 8.5.5 "Master
AUTOCAL (MA)" on page 27). They are read-only values which cannot be changed. The absolute calibration
resistances are available from index 17. At index 16 the value of the passes through the current transformer is
available. This value can also be written and will be stored retentively in the controllers memory with every change.
The correct calculation of the absolute calibration resistances is only possible if the real count of wire passes
through the current transformer is given in this parameter.
Slot 1, subslot 5 contains the elements required for the TCR Calculator ( section 8.7.2 "TCR Calculator" on
page 35). The external measured temperature is writable, the calculated temperature coefficient is read-only.
11 Variable: Parameter index 15 is used Variable: Parameter index 13/14 as well as the
channel-specific temperature coefficients at
index 26/27, 29/30, 32/33, 35/36, 38/39, 41/42,
44/45 are used
You must always execute the AUTOCAL function after changing the "Temperature range / alloy", "Temperature
range", or "Temperature coefficient" parameter.
Errors in the calculation of the temperature coefficient are reported with the value 0 (calculated temperature coef-
ficient too low or no active control operation) or 65535 (calculated temperature coefficient too high).
To use the calculated TCR value, it must be set for the corresponding channel as temperature coefficient in param-
eter index 13/14, 26/27, 29/30, 32/33, 35/36, 38/39, 41/42 or 44/45 (temperature coefficient). In addition, the
value 11 (variable) must be used in parameter index 4 (alloy / temperature range).
AC bit <2.0 s
1
0
t
Function
AUTOCOMP
AUTOCAL
0
t
"AUTOCAL"
LED
Lit
Off
t
"OUTPUT"
LED
Lit
Off
t
The "OUTPUT" LED blinks several times when the AUTOCOMP function is executed and the actual value
output (terminals 17+18) changes to 0…3 °C (corresponds to approx. 0 VDC).
3. "AUTO"
This setting causes the AUTOCOMP function to be automatically activated after the AUTOCAL function has
been successfully executed.
AC bit
0
t
Function
AUTOCOMP
AUTOCAL
0
t
"AUTOCAL"
LED
Lit
Off
t
"OUTPUT"
LED
Lit
Off
t
The "OUTPUT" LED blinks several times when the AUTOCOMP function is executed and the actual value
output (terminals 17+18) changes to 0…3 °C (corresponds to approx. 0 VDC).
The AUTOCOMP function must be activated in the parameter data ( section 8.7 "Parameter data" on page 31)
(default setting: AUTOCOMP off).
ACTUAL temperature
Set+ Δϑ high
Set
Set+ Δϑ low
Time
Error code
307
If the temperature diagnosis is not activated by the time the START signal is deactivated (i.e. if the ACTUAL tem-
perature does not exceed the high or low tolerance band limit), the corresponding error code (309, 310) appears
and the alarm relay is switched.
An additional delay time (0..9.9 s) can be set in the parameter data (GSDML file). The first time the low tolerance
limit is exceeded, the temperature diagnosis is not activated until the configured delay time has elapsed. The tem-
perature diagnosis function can thus be selectively deactivated, e.g. if the temperature drops temporarily owing to
the closure of the sealing jaws.
The high and low tolerance limits cannot be set in the ROPEX visualization software. The same limits apply as
with the TO bit. They can only be set in the parameter data ( section 8.7 "Parameter data" on page 31).
ACTUAL temperature
Set
95% of set
Time-
out
Time
Heatup time Error code
304
The "Heatup timeout" function must be enabled for use in the parameter data ( section 8.7 "Parameter data" on
page 31) (default setting: heatup timeout off).
ST bit
0
ACTUAL t
temperature
T
0
t
ACTUAL indication
Hold off
T
0
t
Hold on Hold Hold
T
0
t
Hold 2 s Hold Hold
T
0
t
2s 2s
End of
heatsealing phase
The "Hold mode" function must be activated in the parameter data ( section 8.7 "Parameter data" on page 31)
(default setting: hold mode off).
A measuring pause that is set too small can lead to an increased temperature if the system is incor-
! rectly dimensioned (secondary voltage of the impulse transformer is too large) or if the sealing tem-
peratures are low.
The integrated web server enables quick and easy access to status information and parameter values of the tem-
perature controller via the existing Ethernet connection. The device protocol can additionally be read out and dis-
played. A graph showing the last 5 seconds of a heating impulse allows a rapid qualitative evaluation of the con-
trolled system.
The latest version of the operating instructions can be downloaded from the ROPEX website by clicking on the
picture of the device on any page. To make sure this latest version is always available in any selectable language,
the instructions are not stored in the device; you must therefore have an Internet connection in order to access the
operating instructions.
You can go direct to the official ROPEX website by clicking on the ROPEX logo in the top right-hand corner.
The web server uses JavaScript and has been successfully tested with Internet Explorer 9, 10, and 11 as well as
with Microsoft Edge. It also works with the latest version of the Safari and Firefox browsers.
device description file for your product here ( section 8.3 "Device master file (GSDML)" on page 24). No Internet
connection is necessary to do this because the file is already stored in the device’s internal memory.
Under "Counters" you see a list of all cycle and operating hours counters, which are useful for statistical purposes.
The download may take a few seconds, depending on the number of entries which are stored here. The newest
events appear at the top of the list.
If any new events occur while this page is displayed, you do not see them until you refresh the list by clicking on
the "Protocol" menu again.
The vertical lines mark the beginning of a new heatsealing impulse (ST bit set). A negative set point indicates the
start of a new impulse in the exported data. Cooling processes are not normally visible because they take place
when the ST bit is reset.
These initial calibration resistances are the basis for the calculation of the calibration deviation. Each execution of
the AUTOCAL function will calculate both, the absolute calibration resistance and likewise the percentual calibra-
tion deviation towards the initial calibration resistance.
The calculation of the absolute resistance values is liable to variation and imprecision due to toler-
! ances in production, to application dimensioning, to quality of cabling, to fluctuations in the power
supply, etc.
Trouble-free operation of the temperature controller is guaranteed within the line voltage and 24 VDC supply
voltage tolerances specified in section 10 "Technical data" on page 56.
If the 24 VDC supply voltage drops below the permitted lower limit, the controller is switched to standby mode. No
more heatsealing processes take place and no more measuring impulses are generated. Normal operation is
resumed when the input voltage returns to the specified tolerance range again.
Standby mode is indicated by 0…3 °C (i.e. approx. 0 V) at the analogue output. In addition, the SA bit is set in the
status word for the cyclic output data.
Trouble-free operation of the controller is only guaranteed within the specified tolerance range of
! the input voltage. An external voltage monitor must be connected to prevent low line or 24 VDC
supply voltage from resulting in defective heatseals.
The RES-5010 supplies an analog 0…10 VDC signal, which is proportional to the real ACTUAL temperature, at
terminals 17+18.
RES-5010
0V 18
0…10 VDC
Temperature
meter
e.g. ATR-3
Voltage values:
0 VDC 0 °C
10 VDC 300 °C or 500 °C, depending on the device configuration
The relationship between the change in the output voltage and the ACTUAL temperature is linear.
Temperature T
270 450
240 400
210 350
180 300
150 250
120 200
90 150
60 100
20 ºC 20 ºC
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
0.66 V Voltage U VDC 0 .4 V Voltage U VDC
“ZERO“ “ZERO“
An indicating instrument can be connected to this output in order to visualize the temperature of the heatsealing
band.
The ROPEX ATR-x temperature meter is optimally adapted to this application in every respect (size, scale,
dynamic behavior) and can be used for this, if needed ( section 6 "Mounting and installation" on page 9).
The meter not only facilitates SET-ACTUAL comparisons but also enables other criteria such as the heating rate,
set point achieved within the specified time, cooling of the heatsealing band etc. to be evaluated.
The temperature meter additionally permits disturbances in the control loop (loose connections, contacting or
wiring problems) as well as any line disturbances to be observed extremely efficiently and interpreted accordingly.
The same applies if several neighbouring control loops interfere with one another.
If a fault is signalled, this analog output is used to display a selective error message ( section 8.19 "Error mes-
sages" on page 50).
The RES-5010 controller has a connection for an external switching amplifier (booster) as standard. This connec-
tion (at terminals 15+16) is necessary for high primary currents (continuous current > 5 A, pulsed current > 25 A).
The booster should be connected as described in section 6.7 "Wiring diagram with booster connection" on
page 16.
The connecting cable to the booster must not be longer than 1 m; it must also be twisted in order to
! reduce EMC interference to a minimum.
A USB interface (type: Micro USB) is provided for system diagnostics and process visualization. This USB inter-
face enables a data connection to be set up to ROPEXvisual®, the ROPEX visualization software.
12 13 14 15 16 17 18
Vis u al
5 6 7 8 9 10 11
PROCESS CONTROL
EQUIPMENT
E464680
www.ROPEX .de
1 2 3 4 Made in Germany
The ROPEX visualization software is described in a separate document. The software and the documentation are
available in the download area (search term: “Visual”).
Internal interface for diagnostics and maintenance. This interface is not currently available.
0
78 9
1
2 34
6
The number of heatsealing cycles executed since the controller was shipped is stored in the internal memory
(ST bit = 1). This is a read-only counter which cannot be reset. It can be displayed in the ROPEX visualization soft-
ware ( section 8.12 "USB interface for visualization software ROPEXvisual®" on page 47), via the integrated
web server, or using the acyclic services of the PROFINET interface.
The number of operating hours since the controller was shipped is stored in the internal memory. This counter
works with a resolution of six minutes. It is a read-only counter which cannot be reset. It can be displayed in the
ROPEX visualization software ( section 8.12 "USB interface for visualization software ROPEXvisual®" on
page 47), via the integrated web server, or using the acyclic services of the PROFINET interface.
To simplify error diagnoses during operation, the RES-5010 controller has a data memory for error messages
( section 8.19 "Error messages" on page 50) and executed AUTOCAL functions ( section 8.5.1 "Automatic
zero calibration AUTOCAL (AC)" on page 26).
The 400 most recent messages are stored. They can be read out and displayed in the ROPEX visualization soft-
ware ( section 8.12 "USB interface for visualization software ROPEXvisual®" on page 47) or via the integrated
web server.
The RES-5010 also features a built-in clock ( section 8.17 "Built-in clock (date and time)" on page 48). All mes-
sages are saved in the data memory together with their date and time of occurrence (timestamp).
The stored messages can be exported as a csv-file. If needed, ROPEX can evaluate the exported file
! and create an error diagnosis.
The RES-5010 has a built-in clock. All messages are saved in the data memory ( section 8.16 "Data memory
for error messages and AUTOCAL" on page 48) together with their date and time of occurrence (timestamp). Error
messages can thus be interpreted more accurately whenever a problem needs to be analyzed.
The built-in clock can be set and read out in the ROPEX visualization software ( section 8.12 "USB interface for
visualization software ROPEXvisual®" on page 47) or using the acyclic services of the PROFINET interface. The
date and time can be read out but not set via the integrated server.
A maintenance-free capacitor is used to operate the clock. There is no battery that has to be replaced every now
and then.
The controller must remain switched on for at least three hours to make sure the clock’s capacitor is fully charged.
When the controller is switched off, the fully charged capacitor can keep the clock running for approximately 2…4
weeks. If the controller is switched off for longer, the date and time will have to be set again. You can do this in
the ROPEX visualization software ( section 8.12 "USB interface for visualization software ROPEXvisual®" on
page 47) or using the acyclic services of the PROFINET interface.
The capacitor is not charged when it leaves the factory. When the controller is started up, you must set the clock
if you want error messages to be saved in the data memory ( section 8.16 "Data memory for error messages
and AUTOCAL" on page 48) together with their date and time of occurrence.
The controller can also be operated without the clock. In this case, the dates and times that are saved in the data
memory will be invalid ( section 8.16 "Data memory for error messages and AUTOCAL" on page 48) . However,
this has no effect on the temperature control functions.
To increase operational safety and avoid faulty heatsealing, this controller incorporates special hardware and soft-
ware features to facilitate selective error detection and diagnosis. Both the external wiring and the internal system
are monitored.
These features significantly assist the operator in identifying the cause of abnormal situations.
A system fault is reported or differentiated by means of the following indications.
If the alarm relay has the opposite configuration to the factory setting ( section 7.2.3 "Configura-
! tion of the rotary coding switches for device names" on page 18), these states are reversed.
D.) Error code indicated via the actual value output 0…10 VDC (terminals 17+18):
Since a temperature indication is no longer necessary if a fault occurs, the actual value output is used to display
error messages whenever a fault is signaled.
Thirteen voltage levels are available for this purpose in the 0…10 VDC range, each of which is assigned an error
code ( section 8.19 "Error messages" on page 50).
For statuses that require AUTOCAL, or if the device configuration is incorrect (error codes 104…106, 111…114,
211, 302, 303), the signal at the actual value output jumps back and forth at 1 Hz between the voltage value cor-
responding to the error and the end of the scale (10 VDC, i.e. 300 °C or 500 °C). If the START signal is present in
one of these states, the voltage value does not change any more.
If a ROPEX temperature meter (e.g. an ATR-x) is connected to the controller’s analog output, the temperature
indication can be directly assigned to the error codes if an alarm is signaled.
An error message can be reset by setting the RS bit or by momentarily interrupting the power to the controller
(24 VDC supply voltage).
If an error message is reset with the RS bit, it is not actually reset until the RS bit is reset.
Invalid error messages may appear when the controller is switched off owing to the undefined operating state. This
must be taken into account when they are evaluated by the higher-level controller (e.g. a PLC) in order to avoid
false alarms.
In addition to the error codes diagnosed in the event protocol, you can also access the PROFINET diagnosis func-
tion (extended device diagnosis). The error codes appear in the configuring tool in plain text because they are
stored in the device master file (GSDML).
The table below shows the meaning of the error codes. It includes a description of each error as well as the
required corrective action.
The block diagram in section 8.20 "Fault areas and causes" on page 54 helps you clear a particular error quickly
and efficiently.
Thirteen voltage levels for diagnosing errors appear at the RESISTRON® temperature controller’s actual value
output. The error messages are even more finely differentiated internally. The 3-digit error codes described below
can be displayed via the PROFINET interface or in the ROPEX visualization software ( section 8.12 "USB inter-
face for visualization software ROPEXvisual®" on page 47) to facilitate troubleshooting).
If the actual value output is evaluated in order to identify an error message – in the higher-level con-
! troller, for instance – the tolerance window must be adjusted to prevent incorrect interpretations.
Please note the tolerances of the actual value output ( section 10 "Technical data" on page 56).
NOTE: The error messages shown here are output as faults (constant error voltage at actual value output,
alarm LED lit continuously, alarm relay energized).
Act. val.
Action if machine
Error output Action if machine
Cause already operated, HS
code voltage started for first time
band not changed
[V]
107 Temperature step, down Fault areas Fault areas
108 Temperature step, up ("loose contact") ("loose contact")
307
2.66
308 Temperature too high / low
- -
309 ( section 8.7.11)
310
914
915 4.66 Internal fault, device defective Replace device Replace device
916
NOTE: The specified error messages are initially output as warnings (actual value output jumps back and forth
between two values, alarm LED blinks, alarm relay de-energized). When the START signal is activated, the
warning changes to a fault (actual value output no longer jumps back and forth, see bold italic values, alarm
LED lit continuously, alarm relay energized).
Act. val.
Action if machine
Error output Action if machine
Cause already operated, HS
code voltage started for first time
band not changed
[V]
6.00
211 Data error Perform AUTOCAL Perform AUTOCAL
10
NOTE: The specified error messages are initially output as warnings (actual value output jumps back and forth
between two values, alarm LED blinks, alarm relay de-energized). When the START signal is activated, the
warning changes to a fault (actual value output no longer jumps back and forth, see bold italic values, alarm
LED lit continuously, alarm relay energized).
Act. val.
Action if machine
Error output Action if machine
Cause already operated, HS
code voltage started for first time
band not changed
[V]
Ext. calibration temp. fluctu- Perform AUTOCAL with Perform AUTOCAL with
116 ates, stable ext. calibration stable ext. calibration
no calibration possible temperature temperature
5 1 2 2 9
6 3
Temperature
4 controller
HARDWARE
9
8
UR
7
1
IR
8
9 Factory settings
The RESISTRON® temperature controller RES-5010 is configured at the factory as follows:
AUX
PC CONFIGURATION 9
temperature range
3500ppm/K 8 300°C
780ppm/K (L) 5 500°C
1100ppm/K (A20) 4 500°C
0 780ppm/K (L) 1 300°C
789
12
1100ppm/K (A20) 0 300°C
34
TEMP. COEFFICIENT SWITCH POS. TEMP. RANGE
6 5
0
1
789
2 34
6
10 Technical data
Operation of the temperature controller outside of these technical specifications results in loss of
! warranty and can cause defects.
Line voltage Connected between neutral conductor and one line conductor:
110 VAC -15%…300 VAC +10%
or
Connected between two line conductors:
until 01/2021: 110 VAC -15%…415 VAC +10%
as from 02/2021: 110 VAC -15%…480 VAC1 +10%
The voltage between the line conductor and ground must not be more
! than 300 VAC.
PROFINET interface "Conformance Class C", IO / RT and IRT acc. to IEC 61784-2
2 Ethernet switch ports RJ45
Wiring: IEC 61784-5-3
Data transfer rate: 100 Mbit/s
Data transport layer: Ethernet II, IEEE 802.3
Topology discovery: LLDP, SNMP V1, MIB2, physical device
Addressing: DCP or selectable with rotary coding switch
FSU (Fast Startup) support: Yes, but startup time approx. 2.5 s.
Heatsealing band The temperature range and temperature coefficient settings can also be specified
type and temperature in the ROPEX visualization software ( section 8.12 "USB interface for visualiza-
range tion software ROPEXvisual®" on page 47) in addition to using the rotary coding
switch or via the PROFINET interface (see below):
Temperature range: 200 °C, 300 °C, 400 °C, or 500 °C
Temperature coefficient: 400…4000 ppm/K (variable setting range)
Five different ranges can be set using the rotary coding switch or via the
PROFINET interface:
Temperature coefficient 1100 ppm/K, 0…300 °C (e.g. Alloy A20)
Temperature coefficient 780 ppm/K, 0…300 °C (e.g. Alloy L)
Temperature coefficient 1100 ppm/K, 0…500 °C (e.g. Alloy A20)
Temperature coefficient 780 ppm/K, 0…500 °C (e.g. Alloy L)
Temperature coefficient 3500 ppm/K, 0…300 °C (e.g. LEX3500)
Please take the necessary setting from the ROPEX application report
UL file E464680
End holders to mechanically fix the controller must be fitted at both ends for
mounting on a vertical top hat rail.
Connecting cable Rigid or flexible; 0.2…2.5 mm² (AWG 24…12) plug-in connectors
Type / cross-sections
Plug-in connectors: Tightening torque: 0.5…0.6 Nm
(screwdriver: SZS 0.6x3.5 mm)
11 Dimensions
135.0
113.0
75.0 90.0
12 Modifications
Owing to its universal design, the RESISTRON® temperature controller RES-5010 is suitable for a very wide range
of heatsealing applications.
One modification (MOD) is available for the RESISTRON® temperature controller RES-5010 for implementing
special applications.
The modifications must be ordered separately.
MOD 01
Booster for low secondary voltages (UR = 0.2…60 VAC). This modification is necessary, for example, for very
short or low-resistance heatsealing bands.
13 How to order
Images exemplary
Controller RES-5010
Art. no. 7501000
Scope of supply: Controller includes connector plug-in parts
(without current transformer)
Please indicate the article numbers of the controller and the required modifications
(optional) in all orders,
e.g. RES-5010 + MOD 01 (controller with booster for low voltage)
Order of art no. 7501000 + 800001
Impulse transformer
For design and order specifications, see ROPEX applica-
tion report
Design in accordance with EN 61558
Available with UL certifications and thermal switch, if nec-
essary.
In addition, we can individually design and offer you an
upstream transformer.
Booster B- . . .
075415: Impulse loaded 75 A, 415 VAC, art. no. 885302
100400: Impulse loaded 100 A, 400 VAC, art. no. 885304
Lines
For design and order specifications, see ROPEX applica-
tion report
14 Index
Numbers F
24VDC supply voltage 57 Factory settings 56
Fault 29
A Fault areas 54
AA bit 29 Fuse 12
Actual value 31
Actual value output 46 H
AC bit 26 Heatsealing band type 57
AG bit 29 Heatup timeout 39
Alarm output 49
Alarm relay 19, 58 I
Alloy 18, 21 Impulse transformer 12, 60
Altitude 58 Input data 26
AL bit 21, 29 Installation 9, 58
Ambient conditions 58 Installation procedure 9
Ambient temperature 58 Installation regulations 10
Application Report 10, 13
AUTOCAL 9, 21
Active 29 L
Blocked 26, 29 Line filter 5, 12, 13
Starting 26 Line frequency 57
AUTOCOMP 37 Line voltage 57
Automatic phase angle compensation 37
Automatic zero calibration 21, 26 M
Automatic zeroing 9 Maintenance 5, 56
AUTOTUNE 9 Master AUTOCAL (MA) 27
AUX interface 48 Measurement interruption 25, 30
Measurement pause 27
B Measuring impulse duration 36
Booster 16, 61 Measuring range 57
Booster connection 47 Modification MOD 59, 60
Burning in (heatsealing band) 19, 21 Monitoring current transformer 60
MP bit 27
MSW-2 60
C MU bit 30
Circuit-breaker 12
Control active 30
Current transformer 13, 60 N
Network filter 60
Network frequency 9
D
Data format 36
Data memory 48 O
Date 48 Output data 28
Degree of protection 58 Over-current protection 12
Device master file (GSDML) 24
Dimensions 59 P
Disposal 5 PEX-W4/-W5 5, 13
PEX-W5 60
E Phase angle compensation 37
Error code format 37 Power loss 58
Error diagnosis 9 Power supply 12
Error messages 50 Power supply system 57
External module/channel errors 36 PROFINET interface 57
External switching amplifier 16
R Temperature regulation 8
RA bit 21, 30 TE bit 29
Relative humidity 58 Thermal impulse process 8
Replacement (heatsealing band) 20, 21 Time 48
Reset 27 Timestamp 48
ROPEXvisual 47 TO bit 29
RS bit 27 Transformer 4, 12, 60
Transportation 5
Type of construction 56
S
Set point 28
Standby mode 45 U
Start 26 UL file 58
Startup 17 Undervoltage detection 45
ST bit 21 USB interface 47
System diagnosis 47 Use 8
System monitoring 49
V
T View of the device 17
TCR 4, 19 Visualization software 47
TCR Calculator 35
Temperature achieved 29 W
Temperature coefficient 4, 19 WA bit 29
Temperature diagnosis 38, 39 Web server 41
Temperature meter 47, 60 Wiring 10, 12
Temperature OK 29 Wiring diagram 15, 16
Temperature range 18, 57