0% found this document useful (0 votes)
151 views

1.eastron SDM230-2T Smart Meter Modbus Protocol Implementation V1.1

The document describes a Modbus protocol for interfacing with an Eastron SDM230-2T smart meter. It provides an overview of the Modbus protocol and details the electrical interface, data formats, register addresses, and meter parameters that can be accessed via Modbus functions including voltage, current, power, energy and demand values. Up to 30 values can be transferred in a single transaction via the RS485 port using Modbus RTU mode with a maximum network length of 1200 meters and 32 nodes.

Uploaded by

Ronald N Meza C
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
151 views

1.eastron SDM230-2T Smart Meter Modbus Protocol Implementation V1.1

The document describes a Modbus protocol for interfacing with an Eastron SDM230-2T smart meter. It provides an overview of the Modbus protocol and details the electrical interface, data formats, register addresses, and meter parameters that can be accessed via Modbus functions including voltage, current, power, energy and demand values. Up to 30 values can be transferred in a single transaction via the RS485 port using Modbus RTU mode with a maximum network length of 1200 meters and 32 nodes.

Uploaded by

Ronald N Meza C
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

Eastron SDM230Modbus Protocol V1.

1.Eastron SDM230-2T Smart Meter Modbus Protocol Implementation V1.1

1.1 Modbus Protocol Overview

This section provides basic information for interfacing the Eastron Smart meter to a
Modbus Protocol network. If background information or more details of the Eastron
implementation is required, please refer to section 2 and 3 of this document.

Eastron offers the option of an RS485 communication facility for direct connection to
SCADA or other communications systems using the Modbus Protocol RTU salve protocol.
The Modbus Protocol establishes the format for the master’s query by placing into it the
device address, a function code defining the requested action, any data to be sent, and an
error checking field. The slave’s response message is also constructed using Modbus
Protocol. It contains fields confirming the action taken, any data to be returned, and an
error-checking field. If an error occurs in receipt of the message, SDM230-2T will make no
response. If the SDM230Modbus is unable to perform the requested action, it will
construct an error message and send it as the response.

The electrical interface is 2-wire RS485, via 2 screw terminals. Connection should be
made using twisted pair screened cable (Typically 22 gauge Belden 8761 or equivalent).
All "A" and "B" connections are daisy chained together. Line topology may or may not
require terminating loads depending on the type and length of cable used. Loop (ring)
topology does not require any termination load. The impedance of the termination load
should match the impedance of the cable and be at both ends of the line. The cable
should be terminated at each end with a 120 ohm (0.25 Watt min.) resistor. A total
maximum length of 1200 meters is allowed for the RS485 network. A maximum of 32
electrical nodes can be connected, including the controller. The address of each Eastron
can be set to any value between 1 and 247. Broadcast mode (address 0) is supported.

The format for each byte in RTU mode is:


Coding System: 8-bit per byte
Data Format: 4 bytes (2 registers) per parameter.
Floating point format ( to IEEE 754)
Most significant register first (Default). The default may be changed if
required -See Holding Register "Register Order" parameter.
Error Check Field: 2 byte Cyclical Redundancy Check (CRC)
Framing: 1 start bit
8 data bits, least significant bit sent first
1 bit for even/odd parity (or no parity)
1 stop bit if parity is used; 1 or 2 bits if no parity
Data Coding
All data values in the SDM230-2T smart meter are transferred as 32 bit IEEE754 floating

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

point numbers, (input and output) therefore each SDM230-2T meter value is transferred
using two Modbus Protocol registers. All register read requests and data write requests
must specify an even number of registers. Attempts to read/write an odd number of
registers prompt the SDM230-2T smart meter to return a Modbus Protocol exception
message. However, for compatibility with some SCADA systems, SDM230-2T Smart
meter will response to any single input or holding register read with an instrument type
specific value.

The SDM230-2T can transfer a maximum of 30 values in a single transaction; therefore


the maximum number of registers requestable is 60. Exceeding this limit prompts the
SDM230-2T to generate an exception response.

Data transmission speed is selectable between 1200,2400, 4800, 9600

1.2 Input register


Input registers are used to indicate the present values of the measured and calculated
electrical quantities. Each parameter is held in two consecutive16 bit register. The
following table details the 3X register address, and the values of the address bytes within
the message. A (*) in the column indicates that the parameter is valid for the particular
wiring system. Any parameter with a cross(X) will return the value zero. Each parameter is
held in the 3X registers. Modbus Protocol function code 04 is used to access all
parameters.
For example, to request: Amps 1 Start address=0006
No. of registers =0002
Amps 2 Start address=0008
No. of registers=0002
Each request for data must be restricted to 40 parameters or less. Exceeding the 40
parameter limit will cause a Modbus Protocol exception code to be returned.
Modbus
Protocol
Input Register
Address Start
Parameter
(Register) Address
Hex
Length Data Hi Lo
Description Units
(bytes) Format Byte Byte
30001 Phase 1 line to neutral volts. 4 Float V 00 00
30007 Phase 1 current. 4 Float A 00 06
30013 Phase 1 power. 4 Float W 00 0C
30019 Phase 1 apparent power. 4 Float VA 00 12
30025 Phase 1 reactive power. 4 Float VAr 00 18
30031 Phase 1 power factor 4 Float None 00 1E
30037 Phase 1 phase angle. 4 Float Degrees 00 24

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

30071 Frequency of supply voltages. 4 Float Hz 00 46


30073 Import active energy since last Float kWh 00 48
4
reset
30075 Export active energy since last Float kWh 00 4A
4
reset
30077 Import reactive energy since last Float kVArh 00 4C
4
reset
30079 Export reactive energy since last Float kVArh 00 4E
4
reset
30085 当前有功功率需量 4 Float W 00 54
30087 有功功率最大需量 4 Float W 00 56
30089 当前正向有功功率需量 4 Float W 00 58
30091 正向有功功率最大需量 4 Float W 00 5A
30093 当前反向有功功率需量 4 Float W 00 5C
30095 反向有功功率最大需量 4 Float W 00 5E
30259 当前电流需量 4 Float A 01 02
30265 电流最大需量 4 Float A 01 08
30343 Total active energy 4 Float kWh 01 56
30345 Total reactive energy 4 Float kVArh 01 58
30385 Current resettable total active 4 Float kWh 01 80
energy
30387 Current resettable total reactive 4 Float kWh 01 82
energy
34877 Total active Energy Rate 1 4 Float kWh 13 0C
34879 Total active Energy Rate 2 4 Float kWh 13 0E
34885 Import active Energy Rate 1 4 Float kWh 13 14
34887 Import active Energy Rate 2 4 Float kWh 13 16
34893 Export active Energy Rate 1 4 Float kWh 13 1C
34895 Export active Energy Rate 2 4 Float kWh 13 1E
34901 Total reactive Energy Rate 1 4 Float kVArh 13 24
34903 Total reactive Energy Rate 2 4 Float kVArh 13 26
34909 Import reactive Energy Rate 1 4 Float kVArh 13 2C
34911 Import reactive Energy Rate 2 4 Float kVArh 13 2E
34917 Export reactive Energy Rate 1 4 Float kVArh 13 34
34919 Export reactive Energy Rate 2 4 Float kVArh 13 36
35075 Maximum system positive active 4 Float kW
13 D2
power demand of Tarrif 1
35077 Maximum system positive active 4 Float kW
13 D4
power demand of Tarrif 2
35205 Maximum system reverse active 4 Float kW 14 54
power demand of Tarrif 1

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

35207 Maximum system reverse active 4 Float kW 14 56


power demand of Tarrif 2
Tariff1 total active Maximum
35473 4 Float W 15 60
Power Demand
35479 Tariff 1 L1 Maximum Current Float
4 A 15 66
Demand
35487 Tariff 2 total active Maximum
4 Float W 15 6E
Power Demand
35493 Tariff 2 L1 Maximum Current Float
4 A 15 74
Demand

1.3 Modbus Protocol Holding Registers and Digital meter set up

Holding registers are used to store and display instrument configuration settings. All holding
registers not listed in the table below should be considered as reserved for manufacturer use
and no attempt should be made to modify their values.
The holding register parameters may be viewed or changed using the Modbus Protocol. Each
parameter is held in two consecutive 4X registers. Modbus Protocol Function Code 03 is used
to read the parameter and Function Code 16 is used to write. Write to only one parameter per
message.
Modbus
Protocol
Address Parameter Start
Register Address Valid range Mode
Hex
High Low
Byte Byte
Write pulse on period in
milliseconds: 60, 100 or 200, default
Pulse output 1 100.
40013 00 OC r/w
Width
Length : 4 byte
Data Format : Float
Write the network port parity/stop bits
for MODBUS Protocol, where: 0 = One
stop bit and no parity, default. 1 = One
stop bit and even parity. 2 = One stop bit
Network Parity
40019 00 12 and odd parity.3 = Two stop bits and no r/w
Stop
parity.

Length : 4 byte
Data Format : Float

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

Write the network port node


address: 1 to 247 for MODBUS
Protocol, default 1.
40021 Network Node 00 14 r/w

Length : 4 byte
Data Format : Float
Write the network port baud rate for
MODBUS Protocol, where:
0 = 2400 baud. 1 = 4800 baud.
Network Baud 2 = 9600 baud, default.
40029 00 1C r/w
Rate 5=1200 baud .

Length : 4 byte
Data Format : Float
Write MODBUS Protocol input
parameter for pulse out 1:
1: import active energy
2: total active energy
4: export active energy, default
Pulse 1
40087 00 56 5: import reactive energy r/w
Energy Type
6: total reactive energy
8: export reactive energy

Length : 4 byte
Data Format : Float
00 00 :清除最大需量
461457 清除历史数据 F0 10 Length : 2 byte wo
Data Format:Hex
数据格式:需量时间-滑差时间-轮显时
间 - 背 光 点 亮 时 间 , 单 位 是
Demand min-min-s-min,默认 15-01-00-60
interval , slide Note:
time, automatic Demand interval =0:需量不更新
462721 scroll display F5 00 scroll time=0:the display does not scroll r/w
interval(scroll automatically.
Time), Backlight time=0 Backlight always on
Backlight time
Length : 4 byte
Data Format : BCD
Write pulse divisor index: n = 0 to 3
463761 Pulse 1 Divisor F9 10 r/w
00 00:0.001 kWh(KVArh)/imp,default

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

00 01:0.01 kWh(KVArh)/imp
00 02:0.1 kWh(KVArh)/imp
00 03:1 kWh(KVArh)/imp

Length : 2 byte
Data Format : Hex
00 01:total = import
00 02:total = import + export
Measurement 00 03:total = import – export
463777 F9 20 r/w
mode
Length : 2 byte
Data Format : Hex
Continuous working period--hour

463793 Running time F9 30 r/w


Length : 4 byte
Data Format : Float

Note:
Mode 1: Measure imported energy, Total energy=Imported energy.
Mode 2: Measure imported energy and exported energy, Total energy=Import
energy + export energy(default).
Mode 3: Measure imported energy and exported energy, Total energy=Imported
energy- exported energy.

2 RS485 General Information


Some of the information in this section relates to other Eastron Digital meter product families,
and is included to assist where a mixed network is implemented.RS485 or EIA (Electronic
Industries Association) RS485 is a balanced line, half-duplex transmission system allowing
transmission distances of up to 1.2 km. The following table summarizes the RS-485 Standard:

PARAMETER
Mode of Operation Differential
Number of Drivers and Receivers 32 Drivers, 32 Receivers
Maximum Cable Length 1200 m
Maximum Data Rate 10 M baud
Maximum Common Mode Voltage 12 V to –7 V
Minimum Driver Output Levels (Loaded) +/– 1.5 V
Minimum Driver Output Levels (Unloaded) +/– 6 V
Drive Load Minimum 60 ohms
Driver Output Short Circuit Current Limit 150 mA to Gnd,
250 mA to 12 V

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

250 mA to –7 V
Minimum Receiver Input Resistance 12 kohms
Receiver Sensitivity +/– 200 mV

Further information relating to RS485 may be obtained from either the EIA or the various
RS485 device manufacturers, for example Texas Instruments or Maxim Semiconductors. This
list is not exhaustive.

2.1 Half Duplex

Half duplex is a system in which one or more transmitters (talkers) can communicate with one
or more receivers (listeners) with only one transmitter being active at any one time. For
example, a “conversation” is started by asking a question, the person who has asked the
question will then listen until he gets an answer or until he decides that the individual who was
asked the question is not going to reply.
In a 485 network the “master” will start the “conversation” with a “query” addressed to a
specific “slave”, the “master” will then listen for the “slave’s” response. If the “slave” does not
respond within a pre-defined period, (set by control software in the “master”), the “master” will
abandon the “conversation”.

2.2 Connecting the Instruments

If connecting an RS485 network to a PC use caution if contemplating the use of an RS232 to


485 converter together with a USB to RS485 adapter. Consider either an RS232 to RS485
converter, connected directly to a suitable RS232 jack on the PC, or use a USB to RS485
converter or, for desktop PCs a suitable plug in RS485 card. (Many 232:485 converters draw
power from the RS232 socket. If using a USB to RS232 adapter, the adapter may not have
enough power available to run the 232:485 converter.)
Screened twisted pair cable should be used. For longer cable runs or noisier environments,
use of a cable specifically designed for RS485 may be necessary to achieve optimum
performance. All “A” terminals should be connected together using one conductor of the
twisted pair cable, all “B” terminals should be connected together using the other conductor in
the pair. The cable screen should be connected to the “Gnd” terminals.
A Belden 9841 (Single pair) or 9842 (Two pair) or similar cable with a characteristic impedance
of 120 ohms is recommended. The cable should be terminated at each end with a 120 ohm,
quarter watt (or greater) resistor. Note: Diagram shows wiring topology only. Always follow
terminal identification on Eastron Digital meter product label.

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

There must be no more than two wires connected to each terminal, this ensures that a “Daisy
Chain or “straight line” configuration is used. A “Star” or a network with “Stubs (Tees)” is not
recommended as reflections within the cable may result in data corruption.

2.3 A and B terminals

The A and B connections to the Eastron Digital meter products can be identified by the signals
present on them whilst there is activity on the RS485 bus:

2.4 Troubleshooting

·Start with a simple network, one master and one slave. With Eastron Digital meter products
this is easily achieved as the network can be left intact whilst individual instruments are

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

disconnected by removing the RS485 connection from the rear of the instrument.
·Check that the network is connected together correctly. That is all of the “A’s” are connected
together, and all of the “B’s” are connected together, and also that all of the “Gnd’s” are
connected together.
·Confirm that the data “transmitted” onto the RS485 is not echoed back to the PC on the
RS232 lines.(This facility is sometimes a link option within the converter). Many PC based
packages seem to not perform well when they receive an echo of the message they are
transmitting. SpecView and PCView (PC software) with a RS232 to RS485 converter are
believed to include this feature.
·Confirm that the Address of the instrument is the same as the “master” is expecting.
·If the “network” operates with one instrument but not more than one check that each
instrument has a unique address.
· Each request for data must be restricted to 40 parameters or less. Violating this requirement
will impact the performance of the instrument and may result in a response time in excess of
the specification.
·Check that the MODBUS Protocol mode (RTU or ASCII) and serial parameters (baud rate,
number of data bits, number of stop bits and parity) are the same for all devices on the
network.
·Check that the “master” is requesting floating-point variables (pairs of registers placed on
floating point boundaries) and is not “splitting” floating point variables.
·Check that the floating-point byte order expected by the “master” is the same as that used by
Eastron Digital meter products.
·If possible obtain a second RS232 to RS485 converter and connect it between the RS485
bus and an additional PC equipped with a software package, which can display the data on the
bus. Check for the existence of valid requests.
3 MODBUS Protocol General Information
Communication on a MODBUS Protocol Network is initiated (started) by a “Master” sending a
query to a “Slave”. The “Slave“, which is constantly monitoring the network for queries
addressed to it, will respond by performing the requested action and sending a response back
to the ”Master”. Only the “Master” can initiate a query.

In the MODBUS Protocol the master can address individual slaves, or, using a special
“Broadcast” address, can initiate a broadcast message to all slaves. The Eastron Digital meter
do not support the broadcast address.

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

3.1 MODBUS Protocol Message Format


The MODBUS Protocol defines the format for the master’s query and the slave’s response.
The query contains the device (or broadcast) address, a function code defining the requested
action, any data to be sent, and an error-checking field.
The response contains fields confirming the action taken, any data to be returned, and an
error-checking field. If an error occurred in receipt of the message then the message is ignored,
if the slave is unable to perform the requested action, then it will construct an error message
and send it as its response. The MODBUS Protocol functions used by the Eastron Digital
meters copy 16 bit register values between master and slaves. However, the data used by the
Eastron Digital meter is in 32 bit IEEE 754 floating point format. Thus each instrument
parameter is conceptually held in two adjacent MODBUS Protocol registers. Query
The following example illustrates a request for a single floating point parameter i.e. two 16-bit
Modbus Protocol Registers.

First Byte Last Byte


Number Number
Start Start Error Error
Slave Function of of
Address Address Check Check
Address Code Points Points
(Hi) (Lo) (Lo) (Hi)
(Hi) (Lo)

Slave Address: 8-bit value representing the slave being addressed (1 to 247), 0 is reserved for
the broadcast address. The Eastron Digital meters do not support the broadcast address.
Function Code: 8-bit value telling the addressed slave what action is to be performed. (3, 4, 8
or 16 are valid for Eastron Digital meter)
Start Address (Hi): The top (most significant) eight bits of a 16-bit number specifying the start
address of the data being requested.
Start Address (Lo): The bottom (least significant) eight bits of a 16-bit number specifying the
start address of the data being requested. As registers are used in pairs and start at zero, then
this must be an even number.
Number of Points (Hi): The top (most significant) eight bits of a 16-bit number specifying the
number of registers being requested.
Number of Points (Lo): The bottom (least significant) eight bits of a 16-bit number specifying
the number of registers being requested. As registers are used in pairs, then this must be an
even number.
Error Check (Lo): The bottom (least significant) eight bits of a 16-bit number representing the
error check value.
Error Check (Hi): The top (most significant) eight bits of a 16-bit number representing the error
check value.

Response
The example illustrates the normal response to a request for a single floating point parameter
i.e. two 16-bit Modbus Protocol Registers.

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

First Byte Last Byte


First First Second Second Error Error
Slave Function Byte
Register Register Register Register Check Check
Address Code Count
(Hi) (Lo) (Hi) (Lo) (Lo) (Hi)

Slave Address: 8-bit value representing the address of slave that is responding.
Function Code: 8-bit value which, when a copy of the function code in the query, indicates that
the slave recognised the query and has responded. (See also Exception Response).
Byte Count: 8-bit value indicating the number of data bytes contained within this response
First Register (Hi)*: The top (most significant) eight bits of a 16-bit number representing the
first register requested in the query.
First Register (Lo)*: The bottom (least significant) eight bits of a 16-bit number representing
the first register requested in the query.
Second Register (Hi)*: The top (most significant) eight bits of a 16-bit number representing the
second register requested in the query.
Second Register (Lo)*: The bottom (least significant) eight bits of a 16-bit number representing
the second register requested in the query.
Error Check (Lo): The bottom (least significant) eight bits of a 16-bit number representing the
error check value.
Error Check (Hi): The top (most significant) eight bits of a 16-bit number representing the error
check value.
*These four bytes together give the value of the floating point parameter requested.

Exception Response
If an error is detected in the content of the query (excluding parity errors and Error Check
mismatch), then an error response (called an exception response), will be sent to the master.
The exception response is identified by the function code being a copy of the query function
code but with the most-significant bit set. The data contained in an exception response is a
single byte error code.

First Byte Last Byte


Error Error
Slave Function Error
Check Check
Address Code Code
(Lo) (Hi)

Slave Address: 8-bit value representing the address of slave that is responding.
Function Code: 8 bit value which is the function code in the query OR'ed with 80 hex,
indicating that the slave either does not recognise the query or could not carry out the action
requested.
Error Code: 8-bit value indicating the nature of the exception detected. (See “Table Of
Exception Codes“ later).

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

Error Check (Lo): The bottom (least significant) eight bits of a 16-bit number representing the
error check value.
Error Check (Hi): The top (most significant) eight bits of a 16-bit number representing the error
check value.

3.2 Serial Transmission Modes


There are two MODBUS Protocol serial transmission modes, ASCII and RTU. Eastron Digital
meters do not support the ASCII mode.
In RTU (Remote Terminal Unit) mode, each 8-bit byte is used in the full binary range and is not
limited to ASCII characters as in ASCII Mode. The greater data density allows better data
throughput for the same baud rate, however each message must be transmitted in a
continuous stream. This is very unlikely to be a problem for modern communications
equipment.

Coding System: Full 8-bit binary per byte. In this document, the value of each byte will be
shown as two hexadecimal characters each in the range 0-9 or A-F.
Line Protocol: 1 start bit, followed by the 8 data bits. The 8 data bits are sent with least
significant bit first.
User Option Of Parity No Parity and 2 Stop Bits
And Stop Bits: No Parity and 1 Stop Bit
Even Parity and 1 Stop Bit
Odd Parity and 1 Stop Bit.
User Option of Baud 1200,2400,4800 ,9600

The baud rate, parity and stop bits must be selected to match the master’s settings.

3.3 MODBUS Protocol Message Timing (RTU Mode)


A MODBUS Protocol message has defined beginning and ending points. The receiving
devices recognizes the start of the message, reads the “Slave Address” to determine if they
are being addressed and knowing when the message is completed they can use the Error
Check bytes and parity bits to confirm the integrity of the message. If the Error Check or parity
fails then the message is discarded.
In RTU mode, messages starts with a silent interval of at least 3.5 character times.
The first byte of a message is then transmitted, the device address.
Master and slave devices monitor the network continuously, including during the ‘silent’
intervals. When the first byte (the address byte) is received, each device checks it to find out if
it is the addressed device. If the device determines that it is the one being addressed it records
the whole message and acts accordingly, if it is not being addressed it continues monitoring for
the next message.
Following the last transmitted byte, a silent interval of at least 3.5 character times marks the
end of the message. A new message can begin after this interval.
The entire message must be transmitted as a continuous stream. If a silent interval of more

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

than 1.5 character times occurs before completion of the message, the receiving device
flushes the incomplete message and assumes that the next byte will be the address byte of a
new message.
Similarly, if a new message begins earlier than 3.5 character times following a previous
message, the receiving device may consider it a continuation of the previous message. This
will result in an error, as the value in the final CRC field will not be valid for the combined
messages.

3.4 How Characters are Transmitted Serially


When messages are transmitted on standard MODBUS Protocol serial networks each byte is
sent in this order (left to right):
Transmit Character = Start Bit + Data Byte + Parity Bit + 1 Stop Bit (11 bits total):
Least Significant Bit (LSB) Most Significant Bit (MSB)

Start 1 2 3 4 5 6 7 8 Party Stop

Transmit Character = Start Bit + Data Byte + 2 Stop Bits (11 bits total):
Start 1 2 3 4 5 6 7 8 Stop Stop

Eastron Digital meters additionally support No parity, 1 stop bit.


Transmit Character = Start Bit + Data Byte + 1 Stop Bit (10 bits total):
Start 1 2 3 4 5 6 7 8 Stop

The master is configured by the user to wait for a predetermined timeout interval. The master
will wait for this period of time before deciding that the slave is not going to respond and that
the transaction should be aborted. Care must be taken when determining the timeout period
from both the master and the slaves’ specifications. The slave may define the ‘response time’
as being the period from the receipt of the last bit of the query to the transmission of the first bit
of the response. The master may define the ‘response time’ as period between transmitting the
first bit of the query to the receipt of the last bit of the response. It can be seen that message
transmission time, which is a function of the baud rate, must be included in the timeout
calculation.

3.5 Error Checking Methods

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

Standard MODBUS Protocol serial networks use two error checking processes, the error
check bytes mentioned above check message integrity whilst Parity checking (even or odd)
can be applied to each byte in the message.

3.5.1 Parity Checking


If parity checking is enabled – by selecting either Even or Odd Parity - the quantity of “1’s” will
be counted in the data portion of each transmit character. The parity bit will then be set to a 0
or 1 to result in an Even or Odd total of “1’s”.
Note that parity checking can only detect an error if an odd number of bits are picked up or
dropped in a transmit character during transmission, if for example two 1’s are corrupted to 0’s
the parity check will not find the error.
If No Parity checking is specified, no parity bit is transmitted and no parity check can be made.
Also, if No Parity checking is specified and one stop bit is selected the transmit character is
effectively shortened by one bit.

3.5.2 CRC Checking


The error check bytes of the MODBUS Protocol messages contain a Cyclical Redundancy
Check (CRC) value that is used to check the content of the entire message. The error check
bytes must always be present to comply with the MODBUS Protocol, there is no option to
disable it.
The error check bytes represent a 16-bit binary value, calculated by the transmitting device.
The receiving device must recalculate the CRC during receipt of the message and compare
the calculated value to the value received in the error check bytes. If the two values are not
equal, the message should be discarded.
The error check calculation is started by first pre-loading a 16-bit register to all 1’s (i.e. Hex
(FFFF)) each successive 8-bit byte of the message is applied to the current contents of the
register. Note: only the eight bits of data in each transmit character are used for generating the
CRC, start bits, stop bits and the parity bit, if one is used, are not included in the error check
bytes.
During generation of the error check bytes, each 8-bit message byte is exclusive OR'ed with
the lower half of the 16 bit register. The register is then shifted eight times in the direction of
the least significant bit (LSB), with a zero filled into the most significant bit (MSB) position. After
each shift the LSB prior to the shift is extracted and examined. If the LSB was a 1, the register
is then exclusive OR'ed with a pre-set, fixed value. If the LSB was a 0, no exclusive OR takes
place.
This process is repeated until all eight shifts have been performed. After the last shift, the next
8-bit message byte is exclusive OR'ed with the lower half of the 16 bit register, and the process
repeated. The final contents of the register, after all the bytes of the message have been
applied, is the error check value. In the following pseudo code “Error Word” is a 16-bit value
representing the error check values.

BEGIN

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

Error Word = Hex (FFFF)


FOR Each byte in message
Error Word = Error Word XOR byte in message
FOR Each bit in byte
LSB = Error Word AND Hex (0001)
IF LSB = 1 THEN Error Word = Error Word – 1
Error Word = Error Word / 2
IF LSB = 1 THEN Error Word = Error Word XOR Hex (A001)
NEXT bit in byte
NEXT Byte in message
END

3.6 Function Codes


The function code part of a MODBUS Protocol message defines the action to be taken by the
slave. Eastron Digital meters support the following function codes:
MODBUS Protocol
Code Description
name
Read Holding Read the contents of read/write
03
Registers location(4X references)
Read the contents of read only
04 Read Input Registers
location(3X references)

3.7 IEEE floating point format


The MODBUS Protocol defines 16 bit “Registers” for the data variables. A 16-bit number would
prove too restrictive, for energy parameters for example, as the maximum range of a 16-bit
number is 65535.
However, there are a number of approaches that have been adopted to overcome this
restriction. Eastron Digital meters use two consecutive registers to represent a floating-point
number, effectively expanding the range to +/- 1x1037.
The values produced by Eastron Digital meters can be used directly without any requirement
to “scale” the values, for example, the units for the voltage parameters are volts, the units for
the power parameters are watts etc.
What is a floating point Number?
A floating-point number is a number with two parts, a mantissa and an exponent and is written
in the form 1.234 x 105. The mantissa (1.234 in this example) must have the decimal point
moved to the right with the number of places determined by the exponent (5 places in this
example) i.e. 1.234x 105 = 123400. If the exponent is negative the decimal point is moved to
the left.
What is an IEEE 754 format floating-point number?
An IEEE 754 floating point number is the binary equivalent of the decimal floating-point
number shown above. The major difference being that the most significant bit of the mantissa
is always arranged to be 1 and is thus not needed in the representation of the number. The

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

process by which the most significant bit is arranged to be 1 is called normalization, the
mantissa is thus referred to as a “normal mantissa”. During normalization the bits in the
mantissa are shifted to the left whilst the exponent is decremented until the most significant bit
of the mantissa is one. In the special case where the number is zero both mantissa and
exponent are zero.

The bits in an IEEE 754 format have the following significance:


Data Hi Reg, Data Hi Reg, Data Lo Reg, Data Lo Reg,
Hi Byte. Lo Byte. Hi Byte. Lo Byte.
SEEE EMMM MMMM MMMM
EEEE MMMM MMMM MMMM

Where:
S represents the sign bit where 1 is negative and 0 is positive
E is the 8-bit exponent with an offset of 127 i.e. an exponent of zero is represented by 127, an
exponent of 1 by 128 etc.
M is the 23-bit normal mantissa. The 24th bit is always 1 and, therefore, is not stored.

Using the above format the floating point number 240.5 is represented as 43708000 hex:
Data Hi Reg, Data Hi Reg, Data Lo Reg, Data Lo Reg,
Hi Byte Lo Byte Hi Byte Lo Byte
43 70 80 00

The following example demonstrates how to convert IEEE 754 floating-point numbers from
their hexadecimal form to decimal form. For this example, we will use the value for 240.5
shown above
Note that the floating-point storage representation is not an intuitive format. To convert this
value to decimal, the bits should be separated as specified in the floating-point number storage
format table shown above.

For example:
Data Hi Reg, Data Hi Reg, Data Lo Reg, Data Lo Reg,
Hi Byte Lo Byte Hi Byte Lo Byte
0100 0011 0111 0000 1000 0000 0000 0000

From this you can determine the following information.


·The sign bit is 0, indicating a positive number.
·The exponent value is 10000110 binary or 134 decimal. Subtracting 127 from 134 leaves 7,
which is the actual exponent.
·The mantissa appears as the binary number 11100001000000000000000
There is an implied binary point at the left of the mantissa that is always preceded by a 1. This
bit is not stored in the hexadecimal representation of the floating-point number. Adding 1 and

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

the binary point to the beginning of the mantissa gives the following:
1.11100001000000000000000
Now, we adjust the mantissa for the exponent. A negative exponent moves the binary point to
the left. A positive exponent moves the binary point to the right. Because the exponent is 7, the
mantissa is adjusted as follows:
11110000.1000000000000000
Finally, we have a binary floating-point number. Binary bits that are to the left of the binary
point represent
the power of two corresponding to their position. For example, 11110000 represents (1 x 2 7) +
(1 x 26) + (1x 25) + (1 x 24) + (0 x 23)+ (0 x 22) + (0 x 21)+ (0 x 20) = 240.
Binary bits that are to the right of the binary point also represent a power of 2 corresponding to
their position. As the digits are to the right of the binary point the powers are negative. For
example: .100 represents (1 x 2-1) + (0 x 2-2)+ (0 x 2-3) + … which equals 0.5.
Adding these two numbers together and making reference to the sign bit produces the number
+240.5.

For each floating point value requested two MODBUS Protocol registers (four bytes) must be
requested. The received order and significance of these four bytes for Eastron Digital meters is
shown below:
Data Hi Reg, Data Hi Reg, Data Lo Reg, Data Lo Reg,
Hi Byte Lo Byte Hi Byte Lo Byte

3.8 MODBUS Protocol Commands supported


All Eastron Digital meters support the “Read Input Register” (3X registers), the “Read Holding
Register” (4X registers) and the “Pre-set Multiple Registers” (write 4X registers) commands of
the MODBUS Protocol RTU protocol. All values stored and returned are in floating point format
to IEEE 754 with the most significant register first.

3.8.1 Read Input Registers


MODBUS Protocol code 04 reads the contents of the 3X registers.

Example
The following query will request ‘Volts 1’ from an instrument with node address 1:
Field Name Example(Hex)
Slave Address 01
Function 04
Starting Address High 00
Starting Address Low 00
Number of Points High 00
Number of Points Low 02
Error Check Low 71
Error Check High CB
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

Note: Data must be requested in register pairs i.e. the “Starting Address“ and the “Number of
Points” must be even numbers to request a floating point variable. If the “Starting Address” or
the “Number of points” is odd then the query will fall in the middle of a floating point variable
the product will return an error message.
The following response returns the contents of Volts 1 as 230.2. But see also “Exception
Response” later.
Field Name Example (Hex)
Slave Address 01
Function 04
Byte Count 04
Data, High Reg, High Byte 43
Data, High Reg, Low Byte 66
Data, Low Reg, High Byte 33
Data, Low Reg, Low Byte 34
Error Check Low 1B
Error Check High 38

3.9 Holding Registers


3.9.1 Read Holding Registers
MODBUS Protocol code 03 reads the contents of the 4X registers.
Example
The following query will request the prevailing ‘Pulse output 1 Width’:
Field Name Example (Hex)
Slave Address 01
Function 03
Starting Address High 00
Starting Address Low 0C
Number of Points High 00
Number of Points Low 02
Error Check Low 04
Error Check High 08
Note: Data must be requested in register pairs i.e. the “Starting Address“ and the “Number of
Points” must be even numbers to request a floating point variable. If the “Starting Address” or
the “Number of points” is odd then the query will fall in the middle of a floating point variable
the product will return an error message.

The following response returns the contents of Demand Time as 1, But see also “Exception
Response” later.
Field Name Example (Hex)
Slave Address 01
Function 03
Byte Count 04
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

Data, High Reg, High Byte 42


Data, High Reg, Low Byte C8
Data, Low Reg, High Byte 00
Data, Low Reg, Low Byte 00
Error Check Low 6F
Error Check High B5

3.9.2 Write Holding Registers


MODBUS Protocol code 10 (16 decimal) writes the contents of the 4X registers.
Example
The following query will set the Pulse output 1 Width to 60 ms, which effectively resets the
Demand Time:
Field Name Example (Hex)
Slave Address 01
Function 10
Starting Address High 00
Starting Address Low 0C
Number of Registers High 00
Number of Registers Low 02
Byte Count 04
Data, High Reg, High Byte 42
Data, High Reg, Low Byte 70
Data, Low Reg, High Byte 00
Data, Low Reg, Low Byte 00
Error Check Low E6
Error Check High 59

Note: Data must be written in register pairs i.e. the “Starting Address“ and the “Number of
Points” must be even numbers to write a floating point variable. If the “Starting Address” or the
“Number of points” is odd then the query will fall in the middle of a floating point variable the
product will return an error message. In general only one floating point value can be written per
query

The following response indicates that the write has been successful. But see also “Exception
Response”later.
Field Name Example (Hex)
Slave Address 01
Function 10
Starting Address High 00
Starting Address Low 02
Number of Registers High 00

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]
Eastron SDM230Modbus Protocol V1.1

Number of Registers Low 02


Error Check Low E0
Error Check High 08

Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Web: www.eastron.com.cn E-Mail: [email protected]

You might also like