0% found this document useful (0 votes)
2K views76 pages

Schneider EasyPact EXE - DATASHEET

Manual Disjuntor Média Tensão Schneider
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views76 pages

Schneider EasyPact EXE - DATASHEET

Manual Disjuntor Média Tensão Schneider
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 76

EasyPact EXE

Medium Voltage Distribution


Catalog 2021
Vacuum circuit breaker up to 17.5 kV
Fixed and withdrawable versions

EasyPactExe.se.com
General contents

Overview 6

Range description 26

Function and modules description 36

Product references 48

L-Frame cradle 64

se.com EasyPact EXE Catalog | 3


4 | EasyPact EXE Catalog se.com
Your needs EasyPact EXE answers

Designed for greater safety,


for both the operator and end user
Safety applications.

Simple to use, with fast delivery,


easy online ordering, and
Simply to use personalized technical support.

Flexible, with modular kits offering


more options for later customization
than other circuits breakers in its
Flexibility class.

se.com EasyPact EXE Catalog | 5


Overview

6 | EasyPact EXE Catalog se.com


Overview

Field of applications 8

Designed for greater safety 10

Simple to use 12

Flexible 15

EcoStruxureTM ready solutions 16

A comprehensive solution 17

Schneider Electric Services 21

Quality - Environment 24

se.com EasyPact EXE Catalog | 7


Overview Field of applications

EasyPact EXE is a range of vacuum circuit Description


breakers designed to connect building
infrastructure (heating, ventilation, lighting, Energy Buildings - Industry - MMM - O&G
etc.) and industrial plant processes (MV Primary substation (> 20 MVA) Heavy industry primary substation
(10-50 MVA)
motors, MV/LV substations, furnaces, etc.)
to the power grid, and to protect people
and equipment.

Large switching substation (> 4 MVA) Large MV consumer site (10-50 MVA)
DM104289

MV/LV substation (<4 MVA) MV consumer site (1-5 MVA)

EasyPact EXE is available in 2 versions: fixed and


withdrawable.

The fixed version comprises:


PM106400

• 3 poles equipped with vacuum interrupters for medium voltage systems up to


17.5 kV / 31.5 kA / 2 500 A
• 6 primary contacts to connect the vacuum interrupters to the switchgear
busbars section on one side and to cables or to another busbars section on the
other side
• A spring-operated mechanism to give the device an opening and closing speed
that is independent of the operator
• A set of terminal blocks to connect the circuit breaker auxiliaries to the
switchgear control circuit and protection relay
• A front cover with pushbuttons, status indicators, and a lever to charge the
closing spring in case of lack of auxiliary supply voltage
PM106461

The withdrawable version comprises:


• 6 arms mounted on the switching device to adapt the position of the primary
contacts to engage into the switchgear
• A racking trolley to move the circuit breaker from the disconnected position to
the service position and vice versa, either by rotating a lever on the front of the
switchgear with the door closed, or remotely by activating an electrical order
from the control room
• A removable LV plug with flexible ducting to maintain the circuit breaker auxiliary
circuits connected to the switchgear control circuit and the protection relay in
any circuit breaker position: disconnected or service

8 | EasyPact EXE Catalog se.com


Overview Field of applications

Applications
PM105370

Infrastructure
• Airports
• Hospitals

Large commercial buildings


• High rise buldings
PM105359

• Mails
• Shopping centres,
• Office buildings

Industrial plants
• Batch processes plants
• Cement plants
• Food and beverage plants
PM105369

Power grid
• Distribution substations

Switchgear room SCADA


Control and monitoring
DM104282
PM105368

EasyPact EXE circuit breaker enables the Panel Builder to design switchgear
solutions with enhanced safety features, which can be fully controlled from a
separate room.

se.com EasyPact EXE Catalog | 9


Overview Designed for greater safety

The IEC (1) standard stipulates: Operating mechanism


"Select equipment that minimizes the risks
The operating mechanism gives the device an opening and closing speed that
to personnel from improper operation (for
is independent of the operator whether the order is electrical or manual.
example, fast acting ground switches on lines,
It carries out reclosing cycles and it is automatically recharged by a geared motor
motor operators to allow remote operation)".
after each closing.
The right choice of components, such as The opening order has priority over closing order. In the event of permanent and
racking trolley, vacuum interrupter and simultaneous opening and closing orders, it has to maintain the circuit breaker in
operating mechanism, is crucial to fulfil this the "open" position. Once the opening order has been canceled, the closing order
IEC recommendation. has to be interrupted then reactivated to enable closing of the circuit breaker.

(1)
Chapter 12.3 of the IEC 62271-1 edition 2017
The EasyPact EXE operating mechanism comprises:
• A mechanism that stores in the springs the energy required to open, close,
and open the device
• A mechanical antipumping system to prevent reclosing after a close-open
PE56600

operation as long as the closing order is maintained


• A vertical lever to manually charge the closing spring of the mechanism
• Two pushbuttons on the front for manual opening and closing orders,
which can be equipped with keylocking and padlocking accessories
• A device indicating the closing spring "charged" and "discharged" status by
means of a mechanical indicator on the front
• A mechanical position indicator on the front to indicate whether the device
is open or closed
• A gear motor (MCH) for automatically charging the closing spring.
The gear motor is equipped as standard with an electrical contact to signal the
Operating mechanism "charged" position of the mechanism (springs charged)
• An electrical closing release for remote closing order (XF)
• An electrical opening release for remote opening order (MX1) and optionally,
a second electrical opening release that can be either shunt opening type (MX2)
or undervoltage type (MN)
• A ready to close contact (PF) indicating that the circuit breaker fulfills
the following conditions:
- the circuit-breaker contacts are opened
- the closing spring is charged
- the opening push button is not activated by a keylock device or manually
- the opening shunt release is not energized
- the undervoltage release, if present, is energized
• One, two or three blocks of 4 auxiliary contacts for remote indication of the open
or closed position of the circuit breaker
• An operation counter (CDM)

The materials used to manufacture operating mechanism sub-assemblies have


been selected and designed to operate 10 000 cycles with preventive maintenance
under the conditions defined by the IEC standard.

10 | EasyPact EXE Catalog se.com


Overview Designed for greater safety

Rotary closing spring charging system


PM108930

As an alternative option to the integrated spring charging system, we can provide a


manual rotary system that uses a removable rotary crank. This rotary system allows
charging of the closing spring when auxiliary power is not available and when the
MV compartment door is closed.
A decoupling device helps operator safety should the auxiliary power supply be
reestablished during manual charging.

Please contact your local Schneider Electric representative.

Vacuum interrupter
PE55694

The vacuum interrupter has to convey and break the rated normal current, and has
to convey and break the rated short-circuit current a number of times, in line with
the manufacturer’s specification.
It consists of two electrical contacts, one fixed and the other mobile, inside
a sealed enclosure. The level of pressure inside the enclosure has to be very low
(less than 10-1 Pa) to reach the value specified for the dielectric withstand between
the open contacts. In order to maintain the pressure level inside the interrupter
throughout its expected operating life, the enclosure has to be perfectly sealed,
and the various components have to be fully degassed. This is achieved by:
• Using materials that are specifically selected for this application
Vacuum interrupter
(metals and ceramics)
• Using an appropriate assembly process (vacuum, high temperature brazing)
• The use of a "getter" material to absorb the residual gas inside the enclosure.
EasyPact EXE vacuum interrupters are designed to operate 10 000 cycles, under
the conditions defined by the IEC standard.

Racking device
PM106402

The racking device moves the circuit breaker from the disconnected position to the
service position and vice versa. The racking operation can be done either manually,
by rotating a lever on the front of the switchgear with the door closed, or remotely
by activating an electrical order. Remote operation is recommended as it allows
Racking device convenient operation from beyond any arc flash boundary.
The EasyPact EXE racking device has a robust interlocking system with the
switchgear door, the circuit-breaker and the earthing switch. It can be equipped
with an electric motor for remote racking from the control room.
The materials used to manufacture EasyPact EXE racking trolley sub-assemblies
have been selected and designed to operate 2 000 cycles under the conditions
defined by the IEC standard.

se.com EasyPact EXE Catalog | 11


Overview Simple to use

Customer support EasyPact EXE on SE.com web page


A QR code on the front of the EasyPact EXE
enables Specifier, Panelbuilders and End-Users Specifier, Panelbuilders and End-Users have access to:
to access easily to Information and support. • Catalogue and Brochure
• Certificate of Conformity for each Basic Function
PM106407

• 3D models
• User Guide, Receipt Guide
• Instruction sheet
PM106408

EasyPact EXE on Safe Repository


https://saferepository.schneider-electric.com/login
Product QR code
"FLASH ME"
Panelbuilders and End-Users owner of EasyPact EXE device have access,
according to Reference number and Serial number to:
• Routine test
• Nameplate information
• Assembly sheet with the list of Kits assembled on the Device
• Certificate of dispatch of the Device from Schneider Electric
PM106465

• Maintenance information

Customer Care Center


Specifiers, Panelbuilders and End-Users have access to on line Customer Care
Center to request information on EasyPact EXE.Schneider Electric has set up call
centers and e-mail contacts in more than 190 countries to provide a rapid response
to customer inquiries.
PM105387

Personnel in the country using EasyPact EXE are trained to provide qualified
answers to customer questions.

Technical and commercial support


Schneider Electric offers extensive technical and commercial support to Panel
Builders, including expert advice on
• How to customize EasyPact EXE
PM105365

• How to integrate EasyPact EXE in switchgear


• How to prepare switchgear for testing in the laboratory
• How to analyze the results from type tests to improve switchgear design
• How to verify the technical performance of EasyPact EXE in assembled
switchgear

Training documents and other support material can be provided to Panel Buiders.

Please contact your Schneider Electric sales representative for more information.

12 | EasyPact EXE Catalog se.com


Overview Simple to use

Robust design controls


PM105367

EasyPact EXE has been designed in accordance with rigorous verification


checks that include:
• A product design quality system certified ISO 9001 compliant by AFNOR
(an independent certification organization based in France)
• Recognized simulation software to verify the dielectric, thermal, and
electrodynamic behavior of the circuit breaker components in various
switchgear models
• Extensive type tests in laboratories accredited according to ISO/IEC standard
17025
DM104281

Every type of EasyPact EXE circuit breaker has been subjected


to the following type tests, as defined by the IEC standard
62271-100: 2017-06
• Dielectric tests
Proven compliance • Measurement of the resistance of the main circuit
with IEC standard • Temperature rise tests
• Short-time withstand current and peak withstand current tests
• Additional tests on auxiliary and control circuits
• Mechanical operating test at ambient temperature
• Short-circuit making and breaking tests
PM106410

• Extended mechanical endurance tests for M2 class


• Electrical endurance tests for E2 class
Certificat de conformité / Certificate of conformity • Capacitive current switching tests:
N° 01-42-327-02
- Line-charging current switching test
Délivré à / Issued to: Schneider Electric Industries SAS
89, Boulevard Franklin Roosevelt
92500 RUEIL MALMAISON - FRANCE - Cable-charging current switching test
Pour le produit / For the product: Disjoncteur haute tension / High-voltage circuit-breaker
Référence(s) / Reference(s): EXE122006A1B version fixe / fixed version - Single capacitor bank switching tests
EasyPact EXE 12kV 20kA 630A (145mm distance d'entrephase / 145mm phase distance)
Selon dossier dʼidentification / According to Identification File: NVE6726500 Rev 01
• Out-of-phase making and current switching tests
Marque commerciale / Trademark: Schneider Electric
Fabricant / Manufacturer: Schneider Electric Industries SAS
Site de fabrication / Place of manufacture: Schneider Electric, SEA plant - Aubenas - FRANCE
All type tests are witnessed by a third party, ASEFA, which has the authority to issue
Informations complémentaires / Additional information: sans objet / none
a certificate of conformity according to ISO/IEC standard 17065.
Document(s) de référence / Reference document(s):
IEC 62271-100 Ed 2.1 (2012-09): liste des essais en Annexe 1 / list of tests in Annex 1

Caractéristiques certifiées / Certified ratings: voir Annexe 2 / refer to Annex 2


The certificates of conformity issued by ASEFA indicate
Document(s) pris en compte (s) / Relevant document(s):
Rapport(s) dʼessai / Test report(s): voir Annexe 1 / refer to Annex 1
(émis par F11 en tant que laboratoire homologue ASEFA, et DNV-GL/KEMA / issued by F11 as ASEFA approved laboratory,
and DNV-GL/KEMA)
the following on the front page:
Ce certificat ne sʼapplique quʼà lʼéchantillon soumis à lʼessai de type / This certificate applies only to the sample submitted to the type test.
Ce certificat a été émis selon les dispositions des Règles de certification ASEFA en vigueur / This certificate has been issued under the provisions
of the current ASEFA Certification Rules. • The apparatus type defined as fixed or withdrawable and the phase distance
Fontenay-aux-Roses, Le Président de l'ASEFA / The Chairman of ASEFA, • The circuit breaker reference defined by the main rated characteristics: rated
Le / On : 08/07/2016

voltage, rated short-circuit breaking current, rated normal current


Marie-Elisabeth DʼORNANO po. Vincent SCHUHL • The list of relevant type test reports used by ASEFA to certify EasyPact EXE
conformity with the IEC standard
La reproduction de ce certificat de conformité n'est autorisée que sous la forme de fac-similé photographique intégral / This certificate of conformity shall only be reproduced in the form of a complete photographic fac simile.

33, av du général Leclerc


92260 Fontenay-aux-Roses – France Accréditation
tél. 01 40 95 61 02 n° 5-0037
e-mail : [email protected] Portée disponible sur /
Scope available on
www.cofrac.fr
Maquette Certificat ASEFA HT, version K / Form of ASEFA HT Certificate, version K

se.com EasyPact EXE Catalog | 13


Overview Simple to use

Robust manufacturing controls


PM105366

EasyPact EXE is manufactured in factories certified compliant to ISO 9001 for


product quality by third party.
The following quality controls are implemented to ensure that each product
delivered to Panel Builder has the same performance as the unit type tested:
• Regular inspection of critical components and processes using a coordinate
measuring machine
• Regular measure of residual gas inside the vacuum interrupter by mass
spectrometry
• Regular mechanical tests on circuit breaker samples
• Routine tests on all products:
- Dielectric tests on the main circuit
- Tests on auxiliary and control circuit
- Measurement of the resistance of the main circuit
- Design and visual checks
- Mechanical operating tests
- Tightness test of each individual vacuum interrupter

14 | EasyPact EXE Catalog se.com


Overview Flexible

Schneider Electric delivers products with Customization flexibility


assembly instruction sheets available on
website at www.schneider-electric.com. Arms & LV
Locking
clusters connector
The Panel Builder customizes the circuit
breaker by following these instructions. Keylocking

PM105388
This enables the Panel Builder to be very
flexible when ordering products references.

Push button

PM105389
PM106461

padlock

Auxiliaries

PM105390
Position contacts (OC)

PM105392

PM105391

PM105391

PM105391
Racking device MCH XF MN
MX

Simple online ordering On-the-shelf availability


With MySE, the Schneider Electric online EasyPact EXE benefits from Schneider Electric's well-established supply chain with
application, registered Panel Builders can local distribution centers that can deliver high demand products in few days (5 days
access order management and logistics
ex-works usually).
information securely and immediately
(24/7).
This app provides the real-time price and
lead time for any EasyPact EXE reference
Broad range of dimensions
and offers additional benefits such as online
ordering, delivery status follow-up, invoice The wide range of dimensions available in this catalog enables Panel Builders to
reprinting, etc. build compact cubicles starting at 600 mm/800 mm wide for ratings up to 1 250 A
and 800 mm/900 mm wide for ratings up to 2 500 A. In addition, the availability of
Registered Panel Builders can also versions with phase distances of 150 mm, 210 mm, and 275 mm means that circuit
access Power Build Medium Voltage, breakers of various brands can be replaced in existing cubicles with minor
EasyPact EXE product selector, which modifications to the cubicle architecture.
allows to easily generate the list of product
references needed for a given switchgear
configuration, and to upload it into MySE
and Panelbuilder ERP. Cost saving
The features listed above help to reduce costs and give Panel Builders more time to
do what really matters: Take care of customers.

se.com EasyPact EXE Catalog | 15


Overview EcoStruxure ready solutions

Scalability with fit-for-purpose solutions


For customers who would like a digital approach, we propose an efficient and
cost-effective alternative to breaker, cable and busbar thermo scanning using
temperature wireless sensors and a smart phone app.

Easergy TH110
DM107694

Wireless Thermal Sensor


A battery-less sensor, helping ensure continuous thermal monitoring to
detect potential loose connections of:
• Cable connections
• Busbar connections
• Circuit breaker arms
DM107695-m

Local, on demand connectivity enables:


• Nearby thermal monitoring on your smartphone up to 10 m from your switchgear
• Fast access to documentation via QR code
NFC
To connect
place here

Enhanced for modern MV distribution


The connected switchgear is the perfect choice for intelligent distribution, helping
to secure both new and existing operations. Thanks to its innovative tools and IoT
capabilities, your switchgear can start to become future-ready.
DM107696

DM105004

c
PM108893

16 | EasyPact EXE Catalog se.com


Overview A comprehensive solution
The EasyPact family: Build your complete
MV & LV distribution network
DM104280

EasyPact EXE
VCBs

EasyPact MVS
ACBs

EasyPact CVS
MCCBs

EasyPact TVS
Motor starters

EasyPact EZC
MCCBs
PM105393

PM105395
Medium voltage
General specification EasyPact EXE
Rated voltage (kV) 7,2 / 12 - 17,5
Rated lightning impulse withstand (kV) 60 / 75 - 95
Rated short circuit breaking current (kA) 20 - 25 - 31.5
PM105394

Rated duration of short circuit (s) 3


630 - 800 - 1 250
Rated normal current (A)
1 600 - 2 000 - 2 500
Target application Building, industry, and power grid

Low voltage
General specification EasyPact MVS EasyPact CVS EasyPact TVS EasyPact EZC
Rated insulation voltage (V) Ui 1 000 690 690 690
Impulse withstand voltage (kV) Uimp 12 8 6 6
Rated operational voltage
690 440 690 550
(V AC 50/60 Hz) Ue
Target application Buildings and industry Commercial and Buildings and simple Commercial and
industrial buildings industry residential buildings

se.com EasyPact EXE Catalog | 17


Overview A comprehensive solution
The EasyPact family: Build your complete
MV & LV distribution network

EasyPact MVS
SEA10FD0180911EN-01

The easy choice for reliable performance

Application
Power circuit breakers, ideal for the "head end" of electrical distribution panels in
medium to large office buildings and factories.

Performance
Reliable performance for the entire range with a rating:
• Ics = Icu = Icw (1 s) = 50 and 65 kA at 440 V

Flexibility
Covers a broader range of applications than competing offers:
• Suitable for applications up to 690 V
• Operates across a wide temperature range before requiring derating
• Compatible with copper and aluminium connections
• Includes a complete range of switch disconnectors

EasyPact CVS
PB106445-05_3P_QRCODE

The easy choice for quality and value

Application
Moulded-case circuit breakers, an excellent choice for feeders and sub-feeders
in small and medium-sized industrial and commercial buildings.

Performance
• Ics = 100% Icu
• Suitable for reverse feeding applications
• Adjustable thermal protection
• Optional insulation fault protection
• IEC 60947-2 isolation and highly visible contact position ensures the downstream
circuit is safe.

Flexibility
• Compatible with copper and aluminium connections
• Includes a complete range of switch disconnectors

18 | EasyPact EXE Catalog se.com


Overview A comprehensive solution
The EasyPact family: Build your complete
MV & LV distribution network

EasyPact EZC
CPB100604-01_QR

The easy choice for simplicity

Application
Moulded-case circuit breakers, ideal for feeders and sub-feeders in residential,
commercial, and marine applications.

Performance
Three sizes, fixed settings, and an attractive price point make this range well
suited for simple protection in small and medium-sized buildings.

Flexibility
Multiple connection options:
• Fixed front mounting, plug-in mounting, front connections, bare cables
connected through cable lugs, screwed inside the breaker
• Unique "fish bone" connection, space saving especially for marine applications

EasyPact TVS
CPB100404-38
PM105363

CPB100405-45

The easy choice for simplicity and flexibility

Application
Motor starter solutions, ideal for HVAC, textile, material handling, and manufacturing
environments.

Performance
PM105364

CPB100402-20

Optimized range of features, performance, and quality at their price point.

Flexibility
Complete range of products covers wide range of applications:
• Basic motor protection circuit breaker
• Contactors
• Thermal overload relays
• Control relays

se.com EasyPact EXE Catalog | 19


Overview A comprehensive solution

Schneider Electric product portfolios Protection and control relays


include a wide choice of multi-function
Protection and control relays provide all the necessary functions:
relays to be used together with
• Effective fault diagnosis and protection planning
EasyPact EXE to build a consistent
• Accurate measurements and detailed diagnosis
solution for protection, control,
• Integral equipment control
and monitoring.
• Local or remote indication and operation

Easergy P3
PM106336

The Easergy P3 range of relays is suitable for all common applications as well as
some specific applications including advanced metering functions. Easergy P3
relays are to protect applications, from overhead line feeders and substations to
power plants and industrial power systems.
Easergy P3
Sepam
PE60300

Sepam series 20, series 40, series 60 and series 80 protection relays take full
advantage of Schneider Electric’s experience in electrical network protection.

Sepam allows easy upgrading: addition of communication, digital I/O’s, analog


output, or temperature acquisition systems can be added due to its modular
design.

Sepam range MiCOM


MiCOM protection provides the user with a choice of optimised solutions for
PM102898

specific protection requirements within the distribution network.

The MiCOM relay series offers comprehensive protective function solutions for
all power supply systems as well as for various functional and hardware project
stages.

PowerMeter and circuit monitors


MiCOM range
The PowerLogic PowerMeter replaces a whole set of basic analogue meters.
PM105362

This cost-effective, high-performance meter provides a full range of accurate


PE57123

true-rms metering values.

The PowerLogic series 3000/4000 Circuit Monitor is designed for critical power
users and large energy consumers, to provide the information needed to confidently
enter the evolving world of deregulation.
PowerLogic
range It can be adapted to meter almost any time-of-use or real-time rate.
PM106411

VAMP arc fault protection relay


The VAMP arc protection unit detects an arc flash in an installation and trips the
feeding breaker. The unique arc fault protection functionality enhances the safety
of both people and property and has made VAMP a leading brand in arc protection
VAMP 125 relays worldwide.

20 | EasyPact EXE Catalog se.com


Overview Schneider Electric services
Peace of mind throughout your
installation life cycle

How can you cut costs and Plan


improve performance at the Schneider Electric helps you plan the full design and execution of your solution,
same time? looking at how to secure your process and optimize your time:
• Technical feasibility studies: Design a solution in your environment
When it comes to your electrical distribution • Preliminary design: Accelerate turnaround time to reach a final solution design
infrastructure, the answer is straightforward:
get professional expertise.

Install
Life Cycle Services
Life Cycle Services Schneider Electric will help you to install efficient, reliable and secured solutions
based on your plans.
DB408843

• Project management: Complete your projects on time and within budget


Plan
What are my options? • Commissioning: Ensure your actual performance matches the design, through
on-site testing and commissioning, and tools and procedures

Install
How do I install and commission? Operate
Schneider Electric helps you maximize your installation uptime and control your
capital expenditure through its service offer.
Operate
How do I operate and maintain? • Asset operation solutions: Provide the information you need to enhance
installation performance, and optimize asset maintenance and investment
• Advantage service plans: Customize service plans that cover preventive,
Optimize predictive and corrective maintenance
How do I optimize? • On-site maintenance services: Deliver extensive knowledge and experience
in electrical distribution maintenance
• Spare parts management: Ensure spare parts availability and an optimized
maintenance budget of your spare parts
Renew
• Technical training: Build the necessary skills and competencies to properly
How do I renew my solution?
and efficiently operate your installations

When it comes to your electrical Optimize


distribution installation, Schneider Electric can make recommendations for improved availability, reliability
we secure help you: and quality.
• MP4 electrical assessment of customer installations:
• Increase productivity and reliability Define an improvement and risk management program
• Mitigate risk and limit downtime
• Keep equipment up to date and
extend lifespan Renew
• Cut costs and increase savings
• Improve your return on investment Schneider Electric extends the life of your system while providing upgrades.

We can offer an end of life processing of old electrical equipment.


CONTACT US! • ECOFIT™: Keep up to date and improve the performance of your electrical
installations (LV, MV, protection relays, etc.)
www.schneider-electric.com/b2b/ • MV product end of life: Recycle and recover outdated equipment with end of
en/services/ life services

se.com EasyPact EXE Catalog | 21


Overview Schneider Electric Services
Peace of mind throughout your
installation life cycle

Frequency of maintenance intervention


Schneider Electric recommends implementing a schedule for maintenance
activities to extend electrical distribution equipment performance over time.

Frequencies under normal/healthy operation (minor equipment criticality and


optimal environmental conditions) can be generally defined as described in the
table below:

Maintenance Min. freq.(1) Who


Manufacturer Certified End user
Partner
Exclusive every 5 years
Advanced every 2 years
Light every 1 year

(1) Recommended minimum frequency under normal operating conditions (minor equipment
criticality and favourable environmental conditions).

However, for Eclusive Maintenance, the frequency could be increased according to


Electrical-Room Environment conditions and Equipment Criticality, as described in
the table below:

Electrical-Room Equipment CRITICALITY


The Electrical-Room ENVIRONMENTAL
ENVIRONMENTAL conditions Minor Major Critical
conditions (favorable,normal, severe)
(i.e.corrosive, naval, offshore) are following Favourable 5 5 4

recommendations of Manufacturer’s services. Normal 5 4 3


Severe 4 3 2
Equipment Criticality is the combination
Recommended PERIODICITY in YEARS
of device stress level and its impact on the
reliability of the installation; the level of
criticality are (minor, major, critical). Spare parts
Under Schneider Electric’s spare parts management policy, EasyPact EXE parts will
For more details about how to categorize
be available for 10 years after end of commercialization of the product.
your Electrical-Room Environment conditions
and Equipment Criticality contact your Sales
representative. Services Contract
A service contract for the switchgear room can be offered by the local
Schneider service team with packages such as predictive maintenance, preventive
maintenance, 24/7 hotline, emergency on-site intervention, and emergency spare
part delivery. The availability of the service plan offers varies in different countries.

22 | EasyPact EXE Catalog se.com


Overview Schneider Electric Services
The main advantages of modernization
solutions using EasyPact EXE

Asset optimization
PM105360

The life of existing electrical equipment is extended thereby increasing the return
on investment.

Reduced production stoppage


A retrofit full panel replacement can take anywhere from only a few minutes
up to an hour. When considering whether to maintain equipment or replace it,
facility managers should take into account the initial capital cost, along with
potential disruption to the facility’s processes and workflow during the course of
changing out the equipment. Unless process loads can be rerouted temporarily
during the demolition of old equipment and installation of the new switchgear,
the cost of lost production can be substantial.

Improved cash flow


A full retrofit of an industrial site could be spread over several years. Often, when
new equipment is purchased, the on-site physical plant also needs to be modified
to accommodate the new equipment, which adds to the cost.

Reduced risk
Installing new switchgear involves more cabling (which requires that existing
cabling above and below the equipment be moved). In some cases, cabling may
need to be replaced or spliced, which introduces a higher element of risk.

Peace of mind
Pre-tested solutions from established manufacturers provide a high degree
confidence in a retrofit solution. Schneider Electric have managed thousands
of switchgear retrofit projects and have an extensive library of lessons learned.
Qualified personnel and up-to-date tools reduce the risk of accidents and delays.
Accompanying safety improvements and updated warranties also contribute to
overall power network peace of mind.

Digitization
Retrofit solutions also open the door to enhanced equipment connectivity.
This then allows access to more detailed levels of energy management date, which
enables better monitoring of energy consumption.

Lower environmental impact


Since a retrofit solution replaces only a portion of the existing electrical equipment,
fewer waste materials need to be processed than if a complete replacement were
to occur.

se.com EasyPact EXE Catalog | 23


Overview Quality - Environment

Quality assurance
PM105359

Schneider Electric incorporates a functional organization into each of its business


units and manufacturing plants, the purpose of which is to provide a means of
checking quality and monitoring compliance with standards.
This procedure is:
• Uniform throughout all departments
• Recognized by many customers and approved organizations
But above all, its strict application has allowed us to obtain the recognition of
AFNOR certification, an independant organisation delivering AFAQ quality mark.
The quality system for the design and manufacture of circuit breakers has been
PM105396

PM105397

certified in conformity with the requirements of the ISO 9001:2015 quality


assurance model.

Environmental performance
Schneider Electric is committed to a long-term environmental approach.
All necessary measures have been taken in conjunction with our services, suppliers,
and subcontractors so that the materials used in the composition of the equipment
comply with acceptable content levels of regulated substances as defined by
regulations and directives. The production site is certified to ISO 14001.
In addition, the materials used in EasyPact EXE, insulators and conductors, are
identified and can easily be separated and recycled, as detailed in the "Product
Environment Profile" file. An end-of-service-life manual details procedures for
dismantling and processing components.

24 | EasyPact EXE Catalog se.com


Green Premium
TM

An industry leading portfolio of offers delivering sustainable value

The Green Premium program stands for our commitment to deliver


customer valued sustainable performance. It has been upgraded
with recognized environmental claims and extended to cover all
offers including Products, Services and Solutions.
CO2 and P&L impact through… Resource Performance
More than 75% of our Green Premium brings improved resource efficiency throughout an asset’s
product sales offer superior lifecycle. This includes efficient use of energy and natural resources, along
transparency on the material with the minimization of CO2 emissions.
content, regulatory information
and environmental impact of Cost of ownership optimization through… Circular Performance
our products: We’re helping our customers optimize the total cost of ownership of their
assets. To do this, we provide IoT-enabled solutions, as well as upgrade,
• RoHS compliance repair, retrofit, and remanufacture services.
• REACh substance information
• Industry leading # of PEP’s* Peace of mind through… Well-being Performance
• Circularity instructions Green Premium products are RoHS and REACh compliant. We’re going
beyond regulatory compliance with step-by-step substitution of certain
materials and substances from our products.

Improved sales through… Differentiation


Green Premium delivers strong value propositions through third-party
labels and services. By collaborating with third-party organizations we can
support our customers in meeting their sustainability goals such as green
Discover what we building certifications.
mean by green
Check your products!
*PEP: Product Environmental Profile (i.e. Environmental Product Declaration)
Range description

26 | EasyPact EXE Catalog se.com


Range description

Fixed Circuit Breaker (CB) 28


Main characterisitcs 28
Dimensions 29

Withdrawable Circuit Breaker (CB)


30
Tulip Contact
Main characterisitcs 30
Dimensions 31

Withdrawable Disconnecting Device (DD)


32
Tulip Contact
Main characterisitcs 32
Dimensions 33

General Characteristics 34
Service and storage conditions 34
Electrical characteristics (CB) 35

se.com EasyPact EXE Catalog | 27


Range description Fixed Circuit Breaker (CB)
Main characteristics

According to IEC 62271-100: 2012


PM106400

Designation Dimensions and electrical characteristics


Phase distance (mm) 145 150 185 185 210 210 240 275
Rated voltage Ur kV 12 p p p p p p p p

17.5 p p p p p p p p

Rated frequency fr Hz 50/60 p p p p p p p p

Rated short duration power Ud kV 28 p p p p p p p p


PM106412

frequency withstand voltage (1) p p p p p p p p


38
Rated lightning impulse Up kV 75 p p p p p p p p
withstand voltage p p p p p p p p
95
Rated short-circuit breaking Isc kA 20 p p p p
current p p p p p p
25
31.5 p p p p p p p p

Rated duration of short- tk s 3 p p p p p p p p


circuit

Rated normal current Ir A 630 p p p p

800 p p p p

1 250 p p p p

1 600 p p

2 000 p p

2 500 p p p

Additional characteristics according to IEC 62271-100 are listed in the common characteristics section.
(1) Contact us for 42 kV - 5 min.©

The EasyPact EXE fixed version is equipped with threaded copper connection terminals at the top and bottom.
The shape and dimensions of conductors should be determined by the Panel Builder according to the dielectric
withstand and temperature rise characteristics of the whole connection system.
Field deflectors on lower connection up to 1250 A may be required to achieve 95 kV BIL dielectric withstand
depending on the switchgear architecture.
Please contact your sales representative to receive EasyPact EXE integration guide with more information.
PM105376
PM105377

Connection terminal Connection terminal


without field deflector with field deflector

28 | EasyPact EXE Catalog se.com


Range description Fixed Circuit Breaker (CB)
Dimensions

Phase distance 145 mm Phase distance 150 mm


Up to 17.5 kV / 31.5 kA / 1 250 A DM104268
Up to 17.5 kV / 31.5 kA / 1 250 A

DM104269
DM104267

150 150

DM104270
145 145

270 270
527 527

175 175

300 85
300 85
470
470

Phase distance 185 mm Phase distance 210 mm


Up to 17.5 kV / 31.5 kA / 2 000 A Up to 17.5 kV / 31.5 kA / 2 500 A
185 185 210 210
DM104273

DM104274
DM104271

DM104271

270 527 270


527

H H
300 125 300 147
429 594 429
550

H • 175 mm up to 1 250 A H • 175 mm up to 1 250 A


• 158 mm for 1 600 A and 2 000 A • 158 mm for 1 600 A, 2 000 A and 2 500 A

Phase distance 240 mm Phase distance 275 mm


Up to 17.5 kV / 31.5 kA / 2 500 A Up to 17.5 kV / 31.5 kA / 2 500 A

240 240 275 275


DM104275

DM104276

DM104276

DM104276

527 270 527 270

158 158

300 180 429 300 212


429
660 724
PM106414

The full set of 3D models is available at:


www.schneider-electric.com/en/product-range-download/63374-easypact-exe#tabs-top

se.com EasyPact EXE Catalog | 29


Range description Withdrawable Circuit Breaker
(CB) - Tulip Contact
Main characteristics

According to IEC 62271-100: 2012


PM106461

Designation Dimensions and electrical characteristics


Phase distance (mm) 150 210 210 275
Rated voltage Ur kV 12 p p p p

17.5 p p p p

Rated frequency fr Hz 50/60 p p p p

Rated short duration Ud kV 28 p p p p


power frequency p p p p
38
PM106412

withstand voltage (1)


Rated lightning impulse Up kV 75 p p p p
withstand voltage p p p p
95
Rated short-circuit Isc kA 20 p p
breaking current p p p p
25
31.5 p p p p

Rated duration of tk s 3 p p p p
short-circuit
Rated normal current Ir A 630 p p

800 p p

1 250 p p

1 600 p

2 000 p

2 500 p

Additional characteristics according to IEC 62271-100 are listed in the common characteristics section.
(1) Contact us for 42 kV - 5 min.

Tulip-type contacts
PM106425

The shape of EasyPact EXE contact is tulip-type. The size depends on the rated
current to provide a maximum contact surface optimizing heat dissipation and
offering good compensation characteristics for electrodynamic forces. The Panel
PM108894

Builder should provide fixed type contacts with the correct shape, tolerance,
and material characteristics compatible with the EasyPact EXE tulip-type contacts.

Arms
PM106426

The shape and size of EasyPact EXE arm depend on the rated lightning impulse
voltage, the rated normal current, and the racking trolley stroke.

Racking device
PM106402

EasyPact EXE racking device enables Panel Builder to design switchgear solutions
with enhanced safety features. It has a robust interlocking system with the
switchgear door, the circuit-breaker and the earthing switch. It can be equipped
with an electric motor for remote racking from the control room.

30 | EasyPact EXE Catalog se.com


Range description Withdrawable Circuit Breaker
(CB) - Tulip Contact
Dimensions

Phase distance 150 mm Phase distance 210 mm


Up to 17.5 kV / 31.5 kA / 1 250 A Up to 17.5 kV / 31.5 kA / 1 250 A
DM104264

DM104288

205

577
579
260
14 13.5 13.5 382 200
502 653 438

Phase distance 210 mm


205 ±3

Up to 17.5 kV / 31.5 kA / 2 000 A


DM104265
260

382 200
438 310
652

651
280

13.5 13.5 359 200


653 382

Phase distance 275 mm


Up to 17.5 kV / 31.5 kA / 2 500 A
DM104266

310
652

650
280

13.5 13.5 359 200


853 382
414
PM106414

The full set of 3D models is available at:


www.schneider-electric.com/en/product-range-download/63374-easypact-exe#tabs-top

se.com EasyPact EXE Catalog | 31


Range description Withdrawable Disconnecting
Device (DD) - Tulip Contact
Main characteristics

This device allows disconnection of the upstream and downstream circuits in


PM108901

the cubicle. It is installed in the same location as the withdrawable circuit beaker
in the switchgear compartment, with the option to rack the device remotely.

It includes a device to lock it in the service position.

According to IEC 62271-102: 2011


Designation Dimensions and electrical characteristics
Phase distance (mm) 150 210 210 275
PM108895

Rated voltage Ur kV 12 p p p p

17.5 p p p p

Rated frequency fr Hz 50/60 p p p p

Rated short duration Ud kV 28 p p p p


power frequency p p p p
38
withstand voltage (1)
Rated lightning impulse Up kV 75 p p p p
withstand voltage p p p p
95
Rated short-time lk kA 31.5 p p p p
withstand current
Rated peak withstand Ip kA 82 p p p p
current
Rated duration of tk s 3 p p p p
short-circuit
Rated normal current Ir A 1 250 p p

2 000 p

2 500 p

(1) Contact us for 42 kV - 5 min.

32 | EasyPact EXE Catalog se.com


Range description Withdrawable Disconnecting
Device (DD) - Tulip Contact
Dimensions

Phase distance 150 mm Phase distance 210 mm


Up to 17.5 kV / 31.5 kA / 1 250 A Up to 17.5 kV / 31.5 kA / 1 250 A
DM105651

DM105652

205

577
579
260
14 13.5 13.5 382 200
502 653 438

Phase distance 210 mm


205 ±3

Up to 17.5 kV / 31.5 kA / 2 000 A


DM105653
260

382 200
438 310
652

651
280

13.5 13.5 359 200


653 382

Phase distance 275 mm


Up to 17.5 kV / 31.5 kA / 2 500 A
DM105654

310
652

650
280

13.5 13.5 359 200


853 382
414
PM106414

The full set of 3D models is available at:


www.schneider-electric.com/en/product-range-download/63374-easypact-exe#tabs-top

se.com EasyPact EXE Catalog | 33


Range description General characteristics
Service and storage conditions

Normal service conditions


According to IEC 62271-1: 2017

EasyPact EXE has been designed to operate in the following


conditions
Ambient air temperature • Minimum value: -25°C
• Maximum value: 40°C
• Average measured over 24 hours period ≤ 35°C
Altitude Less than or equal to 1 000 m above sea level
(derating coefficient to be applied for altitudes
higher than 1 000 m)
Atmosphere No dust, smoke, salt, corrosive or flammable gas or
vapor
Humidity • Average relative humidity over 24 hours ≤ 95%
• Average relative humidity over 1 month ≤ 90%
• Average vapor pressure over 24 hours ≤ 2.2 kPa
• Average vapor pressure over 1 month ≤ 1.8 kPa

Other service conditions


If operated beyond the normal service conditions, the circuit breaker is submitted
to accelerated aging.

The circuit breaker may only be used under conditions other than the normal
service conditions with express written permission from Schneider Electric.

Storage
In order to preserve all of the device’s characteristics when stored for prolonged
DM104151

periods, we recommend to store the device in its original packaging, in dry


conditions, and sheltered from the sun and rain at a temperature between -25°C
and +55°C.

The maximum storage period is 12 months.


55 °C
If the device was stored:
25 °C • Between 6 and 12 months: perform basic preventive maintenance to ensure a
correct device operation
• Beyond 12 month: contact your Schneider Electric Service local representative
for device check-up.

34 | EasyPact EXE Catalog se.com


Range description General characteristics
Electrical characteristics (CB)

According to IEC 62271-100: 2012


PM1053882

Common characteristics 12 kV 17.5 kV

Rated short-time withstand kA/3s (50/60 Hz) = Isc = Isc


current (Ik/tk)
Rated operating sequence O-3 min - CO-3 min - CO p p

O-0.3 s - CO-3 min - CO p p

O-0.3 s - CO-15 s - CO p p

Operating times Opening < 50 ms < 50 ms


Breaking < 66 ms < 66 ms
Closing < 71 ms < 71 ms
Electrical endurance E2 E2
Rated line-charging 10-C2 10-C1
breaking current
Rated cable-charging 25-C2 31.5-C1
breaking current
Rated single capacitor A-class at 1 250 A 25 kA 400-C2 400-C1(1)
bank breaking current A-class at 1 250 A 31.5 kA 400-C1 400-C1(1)

(1) Contact your Schneider Electric sales representative for more information.

Mechanical endurance
EasyPact EXE installed in normal service condition and with preventive maintenance
program is designed up to:

Mechanical endurance
Circuit breaker M2 (IEC 62271-100: 2012) 10 000 operating cycles
Racking trolley M1 ( IEC 62271-102: 2018) 2 000 operating cycles
(disconnecting functions)
MCH motor 10 000 charging operations
MX/XF, MN releases 10 000 operations

se.com EasyPact EXE Catalog | 35


Function and
modules description

36 | EasyPact EXE Catalog se.com


Function and
modules description
Overview 38
Fixed Circuit Breaker 38
Withdrawable Circuit Breaker 39

Remote control auxiliaries 40


Mandatory auxiliaries 40
Optional auxiliaries 41
Indication 42

Withdrawability 43
Racking Device 43

Locking 44
Fixed Circuit Breaker 44

LV connection 45
Fixed circuit Breaker 45
Withdrawable Circuit Breaker 46

Racking Device interlocking 47

se.com EasyPact EXE Catalog | 37


Function and Overview
modules description
Fixed Circuit Breaker

Indication Remote control Remote control Mandatory


Optional
4 terminal
blocks
PM105391
DM104291

PM105391

PM105392

PM106415
Position
contacts (OC) MX2/MN MX1/XF MCH

c b a

PM106416
LV connection elbow left

LV connection elbow right

PM106417
Top cover
LV connector
male
PM106418

c
LV connector female
b a

Pushbutton
padlock

Keylock
Padlocking
Basic device
function

Front cover
PM106420

Pushbuttons and indicators


PM106421

PM106422

Opening pushbutton Closing pushbutton


PM106423

PM106424

Main contact Spring charged and


position indicator ready-to-close indicator

Operating counter Nameplate

38 | EasyPact EXE Catalog se.com


Function and Overview
modules description
Withdrawable Circuit Breaker

Indication Remote control Remote control Mandatory


Optional
4 terminal
blocks

PM105391
DM104291

PM105391

PM105392
Position
contacts (OC) MX2/MN MX1/XF MCH

c b a

Tulip-type contacts
PM106419

PM106417
Basic
function
LV connection Top cover
c elbow left
b
Arms a

LV connector female
Tripping

Shutter
ramp
Locking
magnet

Side earthing Front cover

Bottom earthing

Motorized racking trolley


Manual racking trolley
PM106461

Locking handles

Locking tabs
Door interlock
Locking handles

se.com EasyPact EXE Catalog | 39


Function and Remote control auxiliaries
modules description
Mandatory auxiliaries

Shunt opening Shunt closing The remote control auxiliaries comprises an electric motor (MCH) a shunt closing
release MX1 release XF release (XF), and a shunt opening release (MX1)

Electric motor (MCH)


PM106427

The electric motor operates to charge the closing spring as soon as it is connected
to the auxiliary power supply. This allows the circuit breaker to close after opening
according to the rated operating sequence.
A lever is located on the front of the circuit breaker that enables the closing spring
to be charged manually if the auxiliary power supply is unavailable.
The electric motor is equipped with an electrical contact to indicate the "spring
charged" status of the mechanism.
The electric motor includes a gear reducer.

Characteristics
Power supply • DC: 24-30 V, 48-60 V, 110-130 V, 200-250 V
• AC (50 Hz / 60 Hz): 48-60 V, 100-130 V, 200-240 V
Operating range 0.85 to 1.1 Ua
Consumption (VA or W) 180
Motor overcurrent 2 to 3 In for 0.1 s
Electric
motor MCH Charging time ≤7 s
MCH contact 10 A / 240 V
PM106428

Shunt closing release (XF)


A shunt closing release operates to close the circuit breaker when the voltage at the
terminals of the release is between 85% and 110% of its rated voltage. The closing
release is designed to withstand permanent power supply.
Electric
motor MCH Characteristics
Power supply • DC: 24-30 V, 48-60 V, 100-130 V, 200-250 V
• AC (50Hz / 60Hz): 24 V, 48 V, 100-130 V, 200-250 V
PM105391

Operating range 0.85 to 1.1 Ua


Consumption (VA or W) Triggering 200 (for 200 ms)
Latched 4.5

Shunt closing
release XF
Shunt opening release (MX1)
A shunt opening release operates to open the circuit breaker when the voltage
at the terminals of the release is between 70% and 110% (in the case of direct
current)- or between 85% and 110% (in the case of alternative current)- of its
PM105391

rated voltage. The opening release is designed to withstand permanent power


supply and to lock the circuit breaker in the "open" position as long as the voltage is
maintained at its terminals.

Shunt opening Characteristics


release MX1 Power supply • DC: 24-30 V, 48-60 V, 100-130 V, 200-250 V
• AC (50 Hz / 60 Hz): 24 V, 48 V, 100-130 V, 200-250 V
Operating range • DC: 0.7 to 1.1 Ua
• AC: 0.85 to 1.1 Ua
Consumption (VA or W) Triggering 200 (for 200 ms)
Latched 4.5

40 | EasyPact EXE Catalog se.com


Function and Remote control auxiliaries
modules description
Optional auxiliaries

EasyPact EXE can be equipped with a second Second shunt opening release (MX2)
opening release that can be either a shunt
The second shunt opening release operates to open the circuit breaker when the
opening release or an undervoltage release.
voltage at the terminals of the release is between 70% and 110% (in the case of
direct current)- or between 85% and 110% (in the case of alternative current)- of its
rated voltage.
PM106427

The opening release is designed to withstand permanent power supply and to lock
the circuit breaker in the "open" position as long as the voltage is maintained
at its terminals.

Characteristics
Power supply • DC: 24-30 V, 48-60V, 100-130 V, 200-250 V
• AC (50Hz / 60Hz): 24 V, 48 V, 100-130 V, 200-250 V
Operating range • DC: 0.7 to 1.1 Ua
• AC: 0.85 to 1.1 Ua
Consumption (VA or W) Triggering 200 (for 200 ms)
Latched 4.5

Undervoltage release (MN)


The undervoltage release operates to open the circuit breaker when the voltage
at the terminals of the release falls below 35% of its rated voltage, even if the fall
Shunt opening is slow and gradual.
release MX2 or
Under voltage The undervoltage release does not operate the circuit breaker when the voltage at
release MN its terminals exceeds 70% of its rated supply voltage. The area between 35% and
70% is uncertain, and the undervoltage release might operate to open the circuit
breaker.
The closing of the circuit breaker is possible when the voltage at the terminals of
the release is equal to or exceeds 85% of its rated voltage. On the other hand,
PM105391

the closing of the circuit breaker is impossible as long as the voltage at the
terminals is below 35% of the rated supply voltage.

Shunt opening Characteristics


release MX2
Power supply • DC: 24-30 V, 48-60 V, 100-130 V, 200-250 V
• AC (50Hz / 60Hz): 24 V, 48 V, 100-130 V, 200-250 V
Operating range Opening 0.35 to 0.7 Ua
Closing 0.85 Ua
Consumption (VA or W) Triggering 200 (for 200 ms)
PM105391

Latched 4.5

Undervoltage
Release combination table
release MN
MCH p p p
XF p p p
MX1 p p p
MX2 p
MN p

se.com EasyPact EXE Catalog | 41


Function and Remote control auxiliaries
modules description
Indication

Position contacts (OC)


PM106429

EasyPact EXE is equipped with one block of four position contacts as standard,
and the Panel Builder may add one or two additional blocks of four contacts.
Rotary type The maximum number of position contacts is twelve.
contacts (OC)
Characteristics
Standard delivery 1 (1 block of 4 contacts)
Maximum quantity 3 (3 blocks of 4 contacts)
Breaking capacity (A) Standard Min. load: 100 mA / 24 V
Cos : 0.3 V AC 240 / 380 10 / 6
V DC 24 / 48 10 / 6 *
125 10 / 6
250 3
* standard contacts: 10 A; optional contacts: 6 A (temperature derating)

"Ready to close" contact (PF)


PM106430

A "ready to close" contact (PF) indicates that the circuit breaker is ready to close
in the following conditions:
• The circuit breaker contacts are open
• The operating mechanism closing spring is charged
"Ready to close"
• The opening pushbutton is not activated (by a keylock or manually)
PF contact
• The opening shunt release is not energized
• The undervoltage release, if present, is energized

EasyPact EXE is always equipped with 1 "ready to close" contact (PF)


for remote control.

Characteristics
Standard delivery 1
Maximum quantity 1
Breaking capacity (A) Standard Min. load: 100 mA / 24 V
Cos : 0.3 V AC 240 / 380 5
V DC 24 / 48 3
125 0.3
250 0.15

Operation counter (CDM)


PM106431

An operation counter counts the number of operating cycles (close-open) that


Operation counter
the device has carried out.
(CDM)
EasyPact EXE is always delivered with an operation counter showing the number
of close-open cycles that have been performed for the factory routine test.

42 | EasyPact EXE Catalog se.com


Function and Withdrawability
modules description
Racking Device

The EasyPact EXE withdrawable version EasyPact EXE racking function


requires a racking device, arms, and tulip-
type contacts for connection to the switchgear EasyPact EXE racking device enables Panel Builder to design switchgear solutions
with enhanced safety features. It has a robust interlocking system with the
power circuit, and a removable LV plug to
switchgear door, the circuit-breaker and the earthing switch.
connect auxiliary circuits.
It can be equipped with an electric motor for remote racking from the control room.

The Racking Device is composed of 3 elements:


PM106402

• Racking Trolley
• Shutter Ramp
• Tripping

Racking Trolley
The EasyPact EXE racking function comprises:
PM106405

• A racking trolley equipped with 4 wheels for moving on the rails located at the
bottom of the circuit breaker compartment, and with shutter ramps to operate
the shutter mechanism according to the racking trolley position
• A system to attach the racking trolley to the switchgear frame
• A racking trolley with a threaded shaft that rotates to move the circuit breaker
inside the circuit breaker compartment
• 2 sets of 4 contacts to indicate electrically if the circuit breaker is in service
position, intermediate position or in disconnected position
Shutter ramps • A set of mechanical parts, called Tripping fixed on the mechanical support, to
interlock the racking trolley with the following equipment:
PM106406

- Earthing switch
- Circuit breaker
• An optional motor drive that rotates to move the circuit breaker inside the circuit
breaker compartment.

Tripping
PM108896

PM108897

Earthing
The racking device is earthed using bar earthing or through side earthing.

Bottom earthing Side earthing


PM108900-m

Motor controller
The motor controller is required for the remote operation of racking device,
it have also have the feature of over-current protection.

Motor controller

se.com EasyPact EXE Catalog | 43


Function and Locking
modules description
Fixed Circuit Breaker

PM106432
Easypact EXE can be equipped with locking
in permanent position either by padlock or by
keylock and with pushbutton padlock.

PM106433
Locking the circuit breaker
in the open position

Screen for pushbutton padlocking


An optional transparent screen can prevent
access to the opening and/or closing pushbuttons
Screen for

PM106434
on the circuit breaker.
pushbutton
Locking is achieved by means of one of the
padlocking
following:

• By 2 screws

Locking in permanent open position by padlock


DM103574_LG

The circuit breaker is locked


PM106435
PM106464

in the "open" position by


maintaining the opening
pushbutton in the engaged
• By 3 padlocks
position with a padlock
(not supplied with the circuit breaker)
holder for 1 to 3 padlocks
Padlocking of the (not supplied).
circuit breaker in the
DM103572_LG

"open" position

Locking in permanent open position by keylock


The circuit breaker is locked in the "open" position by maintaining the opening
• By a lead seal pushbutton in the engaged position with a keylock device with the following options:
(not supplied with the circuit breaker)
• 1 single keylock supplied with 2 identical keys
• 1 single keylock for the circuit breaker supplied with 1 key, plus 1 identical
keylock delivered separately to be mounted on the device to be interlocked with
DM103573_LG

the circuit breaker, using the key supplied for the circuit breaker.
PM106432

Keylocking of the circuit breaker


in the "open" position
DM103773
DM103771

Flat key Cylindrical key

The key is free after locking. The key can be used to operate or give access to
remote devices (Earthing switch, Transformer ...).

44 | EasyPact EXE Catalog se.com


Function and LV connection
modules description
Fixed Circuit Breaker

EasyPact EXE is equipped with a set of terminal blocks to connect LV wiring to the
PM105399

circuit breaker auxiliary circuit. An elbow enables the wiring to pass through the
circuit breaker front cover on either the right or the left side.

Elbow on the right An optional flexible LV connector enables connection of the circuit breaker
auxiliary circuits to the switchgear control cabinet in any circuit breaker positions:
disconnected or service. It consists of a 58 pin male connector with flexible
duct mounted on circuit breaker and a 58 pin female connector mounted on the
PM106463

switchgear frame to be connected to the LV cabinet.

Fixed version wiring diagram example


DM104256

-X01-F 36 33 32 29 -X01-F 11 13 28 6 -X01-F 8 5 9 7

-X01-M 36 33 32 29 -X01-M 11 13 28 6 -X01-M 8 5 9 7

-Q1 -X02 -X02 -X02


Elbow on the left
242 244 232 234 222 224 212 214 142 144 132 134 122 124 112 114 42 44 32 34 22 24 12 14

MV Circuit breaker
-Q1 -Q1 -Q1 -Q1 -Q1 -Q1 -Q1 -Q1 -Q1 -Q1 -Q1 -Q1
/3.0:C /3.0:C /3.0:C /3.0:C /3.0:C /3.0:C /3.0:C /3.0:C /3.0:C /3.0:C /3.0:C /3.0:C
14
11 /3.8:C
OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11 OF4 OF3 OF2 OF1
12
24
21 /3.8:C
22 -X02 241 -X02 231 -X02 221 -X02 211 -X02 141 -X02 131 -X02 121 -X02 111 -X02 41 -X02 31 -X02 21 -X02 11
34
31 /3.7:C
32
44
41 /3.7:C
42
114
111 /3.6:C
112 -X01-M 44 43 42 39 -X01-M 12 23 38 16 -X01-M 18 15 19 17
124
121 /3.5:C
122
134 -X01-F 44 43 42 39 -X01-F 12 23 38 16 -X01-F 18 15 19 17
PM105398

131 /3.5:C
132
144
141 /3.4:C

2nd additionnal block of contact 1st additionnal block of contact


142
214
211 /3.4:C
212
224
221 /3.3:C
222
234
232
244
231 /3.3:C
Circuit breaker is shown in open position.
241 /3.2:C
242

Undervoltage trip coil


OR
2nd shunt trip coil

-X01-F 4 -X01-F 31 -X01-F 3 -X01-F 3 -X01-F 26 24 25

-X01-M 4 -X01-M 31 -X01-M 3 -X01-M 3 -X01-M 26 24 25

-X02 A2 C2 D2 C12 -X02 254 252 B3 B2

Q1 -MCH

254 252
M
-PF
PF 251
PF contact shown MCH contact
-XF -MX1 -MN -MX2 in position spring in position -MCH
not loaded. spring not /4.8:C
loaded

-X02 A1 -X02 C1 -X02 D1 -X02 C11 -X02 251 -X02 B1


PE PE

-X01-M 14 -X01-M 30 -X01-M 2 -X01-M 2 -X01-M 1 -X01-M 40 -X01-M 34 -X01-M 35

-X01-F 14 -X01-F 30 -X01-F 2 -X01-F 2 -X01-F 1 -X01-F 40 -X01-F 34 -X01-F 35

PE PE

LV terminal
Circuit breaker is shown in open position.
Auxiliary supply off and control spring discharged.
The circuit diagram shows all possible equipments.

Note: please refer to the detail of drawing NNZ7536800.


PM106461

58 pin male connector

se.com EasyPact EXE Catalog | 45


Function and LV connection
modules description
Withdrawable Circuit Breaker

The LV connector collects electrical orders and status information from the circuit
PM106463

breaker terminal blocks and from the racking trolley terminal blocks. The number
of pins in the LV connector (maximum 58 pins) may limit the number of available
position contacts for the switchgear LV cabinet.

Withdrawable version wiring diagram example


DM103696
Circuit breaker truck position contacts actuation:
-X01-F 48 -X01-F 52 -X01-F 20 -X01-F 49 10 -X01-F 57 -X01-F 55 -X01-F 27

Service position
-X01-M 48 -X01-M 52 -X01-M 20 -X01-M 49 10 -X01-M 57 -X01-M 55 -X01-M 27
Test position Service position Q2
Test position

S9 contacts 1
1 -X04-M 4 -X04-M 2 13 -X04-M 9 12 -X04-M 7 -X04-M 17 -X04-M 19 Q1 Q1 (ex: 13 / 14 NO contact) 0
-X04-M Q2 Q2
S10 contacts 1
-X04-F 1 -X04-F 4 -X04-F 2 13 -X04-F 9 12 -X04-F 7 -X04-F 17 -X04-F 19 (ex:13 / 14 NC contact) 0

-Q2
S9-S10 actuation details
MV Racking truck 13 23 33 43 53
-S9 -S9 -S9 -S9 -S9 1 Test position Intermediate Service position
/3.0:B /3.0:B /3.0:B /3.0:B /5.4:B
14 24 34 44 54
-M2 M S10 14 S10 14 S10 14
-S9
13 13 13
13 23 33 43 53
-S10 -S10 -S10 -S10 -S10
13 14 /3.2:B /3.0:C /3.0:C /3.0:C /3.0:C /5.4:B
14 24 34 44 54 2
23 24 /3.3:B
33 34 /3.4:B
43 44 /3.4:B 6 16 5 15 3 14 11 8 18 20
53 54 /3.5:B -X04-F -X04-F -X04-F -X04-F -X04-F -X04-F -X04-F
-X04-M 6 16 -X04-M 5 15 -X04-M 3 14 -X04-M 11 -X04-M 8 -X04-M 18 -X04-M 20

-S10
13 14 /3.2:B 14 13 14 13 14 13
23 24 /3.3:B
-X01-M 50 51 -X01-M 53 54 -X01-M 21 22 -X01-M 47 -X01-M 58 -X01-M 56 -X01-M 37 S9 S9 S9
33 34 /3.4:B
43 44 /3.5:B -X01-F 50 51 -X01-F 53 54 -X01-F 21 22 -X01-F 47 -X01-F 58 -X01-F 56 -X01-F 37
53 54 /3.6:B

If motorized trolley option


refer to page n°5 for connection

-X01-F 36 33 32 -X01-F 29 -X01-F 11 13 28 6 -X01-F 8 5 9 7

-X01-M 36 33 32 -X01-M 29 -X01-M 11 13 28 6 -X01-M 8 5 9 7

-Q1
MV Circuit breaker -X02 242 244 232 234 222 224 212 214 -X02 142 144 132 134 122 124 112 114 -X02 42 44 32 34 22 24 12 14

-Q1 -Q1 -Q1 -Q1 -Q1 -Q1 -Q1 -Q1 -Q1 -Q1 -Q1 -Q1
/3.0:D /3.0:D /3.0:D /3.0:D /3.0:D /3.0:D /3.0:D /3.0:D /3.0:D /3.0:D /3.0:D /3.0:D
14
11 /3.8:E
OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11 OF4 OF3 OF2 OF1
12
24
21 /3.8:E
22 -X02 241 -X02 231 -X02 221 -X02 211 -X02 141 -X02 131 -X02 121 -X02 111 -X02 41 -X02 31 -X02 21 -X02 11
34
31 /3.7:E
32
44
41 /3.7:E
42
114
111 /3.6:E
112 -X01-M 44 43 42 -X01-M 39 -X01-M 12 23 38 16 -X01-M 18 15 19 17
124
121 /3.5:E
122
134 -X01-F 44 43 42 -X01-F 39 -X01-F 12 23 38 16 -X01-F 18 15 19 17
131 /3.5:E
132
144
141 /3.4:E

2nd additionnal block of contact 1st additionnal block of contact


142
214
211 /3.4:E
212
224
221 /3.3:E
222
234
232
231 /3.3:E Circuit breaker is shown in open and rack-out (test) position.
244
241 /3.2:E
242

Undervoltage trip coil


OR
2nd shunt trip coil

-X01-F 45 -X01-F 4 -X01-F 31 -X01-F 3 -X01-F 3 -X01-F 26 24 25

Q2 -X01-M 45 -X01-M 4 -X01-M 31 -X01-M 3 -X01-M 3 -X01-M 26 24 25

-X03-F 1

-X02 A2 C2 D2 C12 -X02 254 252 B3 B2


-X03-M 1
-LM
PF contact shown -MCH
in position spring M
Q1 not loaded.
-PF
254 252

PF 251
MCH contact
-XF -MX1 -MN -MX2 in position -MCH
spring not /4.9:C
loaded
-X03-M 2

-X02 A1 -X02 C1 -X02 D1 -X02 C11 -X02 251 -X02 B1


-X03-F 2
PE PE

-X01-M 46 -X01-M 14 -X01-M 30 -X01-M 2 -X01-M 2 -X01-M 1 -X01-M 40 -X01-M 34 -X01-M 35

-X01-F 46 -X01-F 14 -X01-F 30 -X01-F 2 -X01-F 2 -X01-F 1 -X01-F 40 -X01-F 34 -X01-F 35

PE PE
LM Electromagnet locks the trolley in
RACK-OUT position when LM is not activated

Circuit breaker is shown in open and rack-out (test) position.


Auxiliary supply off and control spring discharged.
The circuit diagram shows all possible equipments.

-Q3
1 2

-X 16
-X 1 -X 2 -X 3 -X 4 -X 5 -X 6 -X 7 -X 8

13 13 13
-SW3 -SW4 -SW1 -X01-F 57 -X01-F 55 -X01-F 27
14 14 14
-X01-M 57 -X01-M 55 -X01-M 27

-X04-M 7 -X04-M 17
11 -X04-M 19
EC
-X 1 -X 6 -X 7 -SW2 -X04-F 7 -X04-F 17
12 53 -X04-F 19
-S9 1
Remote control commands /3.5:B
54 53
-S10 -M2 M
-X 2 -X 3 -X 4 -X 5
/3.6:B
54
2
8 18 20
-X04-F -X04-F -X04-F
-X04-M 8 -X04-M 18 -X04-M 20

-X01-M 58 -X01-M 56 -X01-M 37

-X01-F 58 -X01-F 56 -X01-F 37

-X 9 -X 10 -X 11 -X 12 -X 13 -X 14 -X 15 -X 17

-TRC13
1 9 10 11 12 13 15 14 4 3
Power + Remote Rack-in Remote Rack-out Remote Remote/Local Ready Test position Work position Motor - Motor +
command command reset

5 7
-TRC13 -TRC13
Power - COM Allow Fault
6 8
2 16 operation

-X 18 -X 19 -X 20 -X 21 -X 22
-Q3
3 4

Wiring diagram and connection for the optional motorization of the racking trolley.

Note: please refer to the detail of drawing NNZ7536700.

46 | EasyPact EXE Catalog se.com


Function and Racking Device interlocking
modules description

The following table describes the interlocking functions available on the


withdrawable version of EasyPact EXE.

How to use the table


Each box describes the possible status of parts interlocked with the circuit breaker
at a given status.

• Removed: The circuit breaker is extracted from the switchgear

• Disconnected/test: The circuit breaker is inside the switchgear compartment;


its power connections are separated from the switchgear contacts by shutters
and the LV auxiliary circuits are connected

• Intermediate: The circuit breaker is moving from the disconnected position


to the service position or vice versa

• Service: The circuit breaker power connections are connected to the switchgear
contacts, the LV auxiliary circuits are connected, and the switchgear door is
closed and locked

Withdrawable circuit breaker positions


DM103941

DM103940

DM103939

DM103938
Racking-in

Racking-out

Parts Service Intermediate Disconnected/test Removed

Locking tabs Locked Locked Locked / Unlocked

LV connection plug Connected Connected Connected / Disconnected Disconnected

Compartment door Closed and Locked Closed and Locked Unlocked Unlocked

Circuit Breaker OPEN / CLOSED OPEN OPEN / CLOSED OPEN / CLOSED


main contacts position

Earthing switch Earthing Switch OPEN


mechanical link Earthing Switch OPEN Earthing Switch OPEN
position Earthing Switch CLOSED

Shutters OPEN OPERATING CLOSED CLOSED

se.com EasyPact EXE Catalog | 47


Product references

48 | EasyPact EXE Catalog se.com


Product references

Commercial reference numbering system 50

Basic function Circuit Breaker (CB) 51


12 kV and 17.5 kV - 20 kA 51
12 kV and 17.5 kV - 25 kA 52
12 kV and 17.5 kV - 31.5 kA 53

Basic function Disconnecting Device (DD) 54


12 kV and 17.5 kV - up to 31.5 kA 54

Remote control and 55


thermal monitoring auxiliaries
Mandatory 55
Optional 55
Indication 55
Racking Device motor control 55
Thermal Sensor with Spring Charging motor 56
Consumable Kits 56

Withdrawability 57
MV connection - Tulip contact 57
Racking Device 58

LV connection 59
Fixed 59
Withdrawable 59

Locking 60

Accessories 61
Labels 61
Rack-in / rack-out crank 61

Spare parts 62

se.com EasyPact EXE Catalog | 49


Product references Commercial reference
numbering system

Commercial number composition


For circuit breaker, disconnecting device, and earthing device.

Example:
Basic function for VCB
12 kV - 25 kA - 630A - pd = 145 mm - IEC - Basic function Circuit Breaker

EXE - 12 - 25 - 06 - A - 1 - B
The commercial number composition is: EXE122506A1B

Please contact us for other versions such as GOST, etc.

EXE - - - - - 1 -
Function
Range Code Value Code
EasyPact EXE EXE Basic function B
circuit breaker
Rated voltage Basic function D
Value Code disconnecting device

12 kV 12
Standard Code
17.5 kV 17
IEC 1
Rated short-circuit
breaking current Phase-to-phase distance
Value Code Value Code
20 kA 20 Rated normal current 145 mm A
25 kA 25 Value Code 150 mm K
31.5 kA 31 185 mm B
630 A 06
800 A 08 210 mm L

1 250 A 12 240 mm C

1 600 A 16 275 mm M

2 000 A 20
2 500 A 25

50 | EasyPact EXE Catalog se.com


Product references Basic function
Circuit Breaker (CB)
12 kV and 17.5 kV - 20 kA
PM106400

An EasyPact EXE Basic function Circuit Breaker (CB) consists of:


• The basic function circuit breaker
• 1 ready to close contact PF with 1 terminal block
• 1 block of 4 auxiliary contacts with 4 terminal blocks
• 4 additional terminal blocks
• 1 operating counter
• 1 receipt guide
Additional options may be added, using the catalog product references.

Basic function
Phase distance (mm) 145 185 240 150 210 275
630 A EXE122006A1B EXE122006B1B - EXE122006K1B EXE122006L1B -
800 A EXE122008A1B EXE122008B1B - EXE122008K1B EXE122008L1B -
1 250 A EXE122012A1B EXE122012B1B - EXE122012K1B EXE122012L1B -
12 kV
1 600 A - - - - - -
2 000 A - - - - - -
2 500 A - - - - - -
630 A EXE172006A1B EXE172006B1B - EXE172006K1B EXE172006L1B -
800 A EXE172008A1B EXE172008B1B - EXE172008K1B EXE172008L1B -
1 250 A EXE172012A1B EXE172012B1B - EXE172012K1B EXE172012L1B -
17.5 kV
1 600 A - - - - - -
2 000 A - - - - - -
2 500 A - - - - - -
Notes:
• The 12 kV basic function may be used for 7.2 kV rated voltage

Check your commercial number:

EXE - - 20 - - - 1 - B
Function
Range Code Value Code
EasyPact EXE EXE Basic function B
circuit breaker
Rated voltage
Value Code Standard Code
12 kV 12 IEC 1
17.5 kV 17
Phase-to-phase distance
Rated short-circuit
breaking current Value Code

Value Code 145 mm A


150 mm K
20 kA 20 Rated normal current
185 mm B
Value Code
210 mm L
630 A 06
800 A 08
1 250 A 12

se.com EasyPact EXE Catalog | 51


Product references Basic function
Circuit Breaker (CB)
12 kV and 17.5 kV - 25 kA
PM106400

An EasyPact EXE Basic function Circuit Breaker (CB) consists of:


• The basic function circuit breaker
• 1 ready to close contact PF with 1 terminal block
• 1 block of 4 auxiliary contacts with 4 terminal blocks
• 4 additional terminal blocks
• 1 operating counter
• 1 receipt guide
Additional options may be added, using the catalog product references.

Basic function
Phase distance (mm) 145 185 240 150 210 275
630 A EXE122506A1B EXE122506B1B - EXE122506K1B EXE122506L1B -
800 A EXE122508A1B EXE122508B1B - EXE122508K1B EXE122508L1B -
1 250 A EXE122512A1B EXE122512B1B - EXE122512K1B EXE122512L1B -
12 kV
1 600 A - EXE122516B1B - - EXE122516L1B -
2 000 A - EXE122520B1B - - EXE122520L1B -
2 500 A - - EXE122525C1B - EXE122525L1B EXE122525M1B
630 A EXE172506A1B EXE172506B1B - EXE172506K1B EXE172506L1B -
800 A EXE172508A1B EXE172508B1B - EXE172508K1B EXE172508L1B -
1 250 A EXE172512A1B EXE172512B1B - EXE172512K1B EXE172512L1B -
17.5 kV
1 600 A - EXE172516B1B - - EXE172516L1B -
2 000 A - EXE172520B1B - - EXE172520L1B -
2 500 A - - EXE172525C1B - EXE172525L1B EXE172525M1B
Notes:
• The 12 kV basic function may be used for 7.2 kV rated voltage

Check your commercial number:

EXE - - 25 - - - 1 - B
Function
Range Code Value Code
EasyPact EXE EXE Basic function B
circuit breaker
Rated voltage
Value Code Standard Code
12 kV 12 IEC 1
17.5 kV 17 Phase-to-phase distance

Rated short-circuit Value Code


breaking current Rated normal current 145 mm A
Value Code Value Code 150 mm K
25 kA 25 630 A 06 185 mm B
800 A 08 210 mm L
1 250 A 12 240 mm C
1 600 A 16 275 mm M
2 000 A 20
2 500 A 25

52 | EasyPact EXE Catalog se.com


Product references Basic function
Circuit Breaker (CB)
12 kV and 17.5 kV - 31.5 kA
PM106400

An EasyPact EXE Basic function Circuit Breaker (CB) consists of:


• The basic function circuit breaker
• 1 ready to close contact PF with 1 terminal block
• 1 block of 4 auxiliary contacts with 4 terminal blocks
• 4 additional terminal blocks
• 1 operating counter
• 1 receipt guide
Additional options may be added, using the catalog product references.

Basic function
Phase distance (mm) 145 185 240 150 210 275
630 A EXE123106A1B EXE123106B1B - EXE123106K1B EXE123106L1B -
800 A EXE123108A1B EXE123108B1B - EXE123108K1B EXE123108L1B -
1 250 A EXE123112A1B EXE123112B1B - EXE123112K1B EXE123112L1B -
12 kV
1 600 A - EXE123116B1B - - EXE123116L1B -
2 000 A - EXE123120B1B - - EXE123120L1B -
2 500 A - - EXE123125C1B - EXE123125L1B EXE123125M1B
630 A EXE173106A1B EXE173106B1B - EXE173106K1B EXE173106L1B -
800 A EXE173108A1B EXE173108B1B - EXE173108K1B EXE173108L1B -
1 250 A EXE173112A1B EXE173112B1B - EXE173112K1B EXE173112L1B -
17.5 kV
1 600 A - EXE173116B1B - - EXE173116L1B -
2 000 A - EXE173120B1B - - EXE173120L1B -
2 500 A - - EXE173125C1B - EXE173125L1B EXE173125M1B
Notes:
• The 12 kV basic function may be used for 7.2 kV rated voltage

Check your commercial number:

EXE - - 31 - - - 1 - B
Function
Range Code Value Code
EasyPact EXE EXE Basic function B
circuit breaker
Rated voltage
Value Code Standard Code
12 kV 12 IEC 1
17.5 kV 17
Phase-to-phase distance
Rated short-circuit Value Code
breaking current
Rated normal current 145 mm A
Value Code
Value Code 150 mm K
31.5 kA 31
630 A 06 185 mm B
800 A 08 210 mm L
1 250 A 12 240 mm C
1 600 A 16 275 mm M
2 000 A 20
2 500 A 25

se.com EasyPact EXE Catalog | 53


Product references Basic function
Disconnecting Device (DD)
12 kV and 17.5 kV - up to 31.5 kA

An EasyPact EXE Basic function Disconnecting Device (DD) consists of:


PM108901

• The basic function Disconnecting Device


• An interlocking cam
• 1 receipt guide

Additional options may be added, using the catalog product references.

Basic function
Phase distance (mm) 150 210 275
630 A - - -
800 A - - -
1 250 A EXE123112K1D EXE123112L1D -
12 kV
1 600 A - - -
2 000 A - EXE123120L1D -
2 500 A - - EXE123125M1D
630 A - - -
800 A - - -
1 250 A EXE173112K1D EXE173112L1D -
17.5 kV
1 600 A - - -
2 000 A - EXE173120L1D -
2 500 A - - EXE173125M1D
Notes:
• The 12 kV basic function may be used for 7.2 kV rated voltage

Check your commercial number:

EXE - - 31 - - - 1 - D
Function
Range Code Value Code
EasyPact EXE EXE Basic function D
disconnecting device
Rated voltage
Value Code Standard Code

12 kV 12 IEC 1
17.5 kV 17
Phase-to-phase distance
Rated short-circuit Value Code
breaking current
145 mm A
Value Code
150 mm K
31.5 kA 31 Rated normal current
185 mm B
value Code 210 mm L
1 250 A 12 240 mm C
1 600 A 16 275 mm M
2 000 A 20
2 500 A 25

54 | EasyPact EXE Catalog se.com


Product references Remote control and thermal
monitoring auxiliaries

Mandatory auxiliaries Voltage References


PM106428

Electric motor MCH DC 24-30 V EXECH02D


48-60 V EXECH04
100-125 V EXECH10D
200-250 V EXECH20D
Electric motor MCH AC (50/60 Hz) 48-60 V EXECH04
100-130 V EXECH10A
200-240 V EXECH20A
Opening release MX & DC 24-30 V DC/24 V AC 59284
PB116264

closing release XF AC (50/60 Hz) 48-60 V DC/48 V AC 59285


100-130 V DC/100-130 V AC 59286
200-250 V DC/200-250 V AC 59287

Optional auxiliaries Voltage References


Opening release MX (2nd) DC 24-30 V DC/24 V AC 59284
PB116264

AC (50/60 Hz) 48-60 V DC/48 V AC 59285


100-130 V DC/100-130 V AC 59286
200-250 V DC/200-250 V AC 59287
Undervoltage release MN DC 24-30 V DC/24 V AC 59288
PB116264

AC (50/60 Hz) 48-60 V DC/48 V AC 59289


110-130 V DC/100-130 V AC 59290
200-250 V DC/200-250 V AC 59291

Indication Description References


Additional position contacts 4 NO/NC auxiliary contact 5 A - 240 V EXE47887
PM108927

OC (1 or 2 blocks of 4 NO/ Auxiliary Terminal Block 3-Wire 4x EXE47074


NC maximum)
PM108928

Racking Device motor controller Description References


(Installed in LV cabinet)
Racking device Low voltage motor controller 110 V AC/DC EXETRLMC10
PM108900-m

Racking device Low voltage motor controller 220 V AC/DC EXETRLMC20

se.com EasyPact EXE Catalog | 55


Product references Remote control and thermal
monitoring auxiliaries

Thermal Sensor with electric motor MCH Description References


Remote Control Motor 24-30 V DC with 1 set TH110 EXECH02DTH1
PM108929

Remote Control Motor 48-60 V DC/V AC with 1 set TH110 EXECH04TH1


Remote Control Motor 100-125 V DC with 1 set TH110 EXECH10DTH1
Remote Control Motor 200-250 V DC with 1 set TH110 EXECH20DTH1
Remote Control Motor 100-125 V AC with 1 set TH110 EXECH10ATH1
Remote Control Motor 200-250 V AC with 1 set TH110 EXECH20ATH1
Remote Control Motor 24-30 V DC with 2 set TH110 EXECH02DTH2
Remote Control Motor 48-60 V DC/V AC with 2 set TH110 EXECH04TH2
Remote Control Motor 100-125 V DC with 2 set TH110 EXECH10DTH2
Remote Control Motor 200-250 V DC with 2 set TH110 EXECH20DTH2
Remote Control Motor 100-125 V AC with 2 set TH110 EXECH10ATH2
Remote Control Motor 200-250 V AC with 2 set TH110 EXECH20ATH2
Remote Control Motor 24-30 V DC with 3 set TH110 EXECH02DTH3
Remote Control Motor 48-60 V DC/V AC with 3 set TH110 EXECH04TH3
Remote Control Motor 100-125 V DC with 3 set TH110 EXECH10DTH3
Remote Control Motor 200-250 V DC with 3 set TH110 EXECH20DTH3
Remote Control Motor 100-125 V AC with 3 set TH110 EXECH10ATH3
Remote Control Motor 200-250 V AC with 3. set TH110 EXECH20ATH3
Remote Control Motor 24-30 V DC with 4 set TH110 EXECH02DTH4
Remote Control Motor 48-60 V DC/V AC with 4 set TH110 EXECH04TH4
Remote Control Motor 100-125 V DC with 4 set TH110 EXECH10DTH4
Remote Control Motor 200-250 V DC with 4 set TH110 EXECH20DTH4
Remote Control Motor 100-125 V AC with 4 set TH110 EXECH10ATH4
Remote Control Motor 200-250 V AC with 4 set TH110 EXECH20ATH4

Consumable Kits Description References


Zigbee Dongle + Adaptor REL52867
PM108913

Ferromagnetic ribbon (62M min) EMS59441


PM108914

NFC Tag (50 units min) REL52862


PM108915

56 | EasyPact EXE Catalog se.com


Product references Withdrawability
MV connection - Tulip contact

Caption: Only identical colour shapes can be associated.

Arms for Tulip cluster Description References


Phase distance (mm)
150 210 275
Set of 3 Arms non Insulated
MV Arms 630 A EXEARM06B
PM106426

Not Insulated for Tulip cluster

MV Arms 800 A - 1 250 A EXEARM12B


Not Insulated for Tulip cluster

Set of 3 Arms non Insulated MV Arms 1600 A - 2 000 A EXEARM20B


PM106495

Not Insulated for Tulip cluster

MV Arms 2500 A EXEARM25B


Not Insulated for Tulip cluster

Set of 3 Arms Insulated MV Arms 630 A EXEARM06B1


Insulated for Tulip cluster with Up = 95 kV
PM106497

MV Arms 800 A - 1250 A EXEARM12B1


Insulated for Tulip cluster with Up = 95 kV

Note: Each Circuit Breaker requires two sets.

Field deflector Description References


Phase distance (mm)
Set of 3 Field Deflectors
150 210 275
PM108916

Field Deflectors Coated-95KV BIL EXEFLDFBE


PM108917

Field Deflectors up to 1 250 A (optional for fix version) EXEFLDF

Tulip cluster Description References


Phase distance (mm)
Set of 6 Tulip cluster
150 210 275
PM106496

MV Tulip cluster 630 A - 800 A- 1 250 A EXECLU12B

MV Tulip cluster 1 600 A - 2 000 A EXECLU20B

MV Tulip cluster 2 500 A EXECLU25B

se.com EasyPact EXE Catalog | 57


Product references Withdrawability
Racking device

Caption: Only identical colour shapes can be associated.

Manual Racking Trolley for 200 mm stroke Description References


Phase distance (mm)
PM108899

150 210 275


Racking trolley 150 mm stroke 200 mm manual EXETRKKB2
Racking trolley 210 mm stroke 200 mm manual EXETRKLB2
Racking trolley 275 mm stroke 200 mm manual EXETRKMB2

Motorized Racking Trolley for 200 mm stroke Description References


Phase distance (mm)
150 210 275
Racking trolley 150 mm stroke 200 mm motorized 110 V AC/V DC EXETRKKB2M10
PM108898

Racking trolley 210 mm stroke 200 mm motorized 110 V AC/V DC EXETRKLB2M10


Racking trolley 275 mm stroke 200 mm motorized 110 V AC/V DC EXETRKMB2M10
Racking trolley 150 mm stroke 200 mm motorized 220 V AC/V DC EXETRKKB2M20
Racking trolley 210 mm stroke 200 mm motorized 220 V AC/V DC EXETRKLB2M20
Racking trolley 275 mm stroke 200 mm motorized 220 V AC/V DC EXETRKMB2M20

Racking Trolley Earthing Description References


Phase distance (mm)
PM108896

150 210 275

Racking trolley bottom earthing EXETRECB2


PM108897

Racking trolley side earthing EXETRECB1

Racking Trolley Base Description References


Phase distance (mm)
PM108918

150 210 275


Racking trolley base phase distance 210 mm stroke 200 mm CD 310 mm EXETRPBL
Racking trolley base phase distance 275 mm stroke 200 mm CD 310 mm EXETRPBM

Shutter Ramp Description References


Phase distance (mm)
PM106405

150 210 275


Shutter ramp CD 205 mm 1250 A EXESHRP5
Shutter ramp CD 310 ≥ 1600 A EXESHRP2

Tripping chain for Withdrawable VCB Description References


Phase distance (mm)
PM106406

150 210 275


Trolley Tripping Component ≤1250 A EXETRIP5
PM108919

Trolley Tripping Component ≥1250 A EXETRIP6

58 | EasyPact EXE Catalog se.com


Product references LV connection

Fixed type LV connection


LV 58 pins connector (M&F) Description References
For fixed VCB LV 58 pins connector (Male & Female) EXPLWB
PM108920

Elbow for LV connection

Elbow LV connection elbow right EXEELR


PM105399

LV connection elbow left EXEELL


PM106463

Withdrawable type LV connection


LV 58 pins connector (M&F) Description References
For withdrawable LV 58 pins connector (Male & Female) EXPLWB
PM108920

VCB

se.com EasyPact EXE Catalog | 59


Product references Locking

Locking accessories for Fixed type Description References


Padlocking Locking of the circuit breaker in the open position by padlock EXE48541
PM108921

device (key locks not supplied)

Locking of the circuit Flat key 1 key lock + 2 flat keys 41940
PM108922

breaker in the open


position by keylocks 2 key locks + 1 flat key (1) 41950

Locking of the circuit Cylindrical 1 key lock + 2 cylindrical keys 42888


PM108923

breaker in the open key


position by keylocks 2 key locks + 1 cylindrical key (1) 42878

Push button padlock Disabling of O/C circuit breaker pushbutton 48536


PM106434

(padlock not supplied)

(1)
One keylock mounted on the breaker, + one identical keylock supplied separately for interlocking with another device.

Locking accessories for withdrawable type Description References


Racking device locking magnet 24 V DC - V AC EXETR2LKMA02
PM108924

Racking device locking magnet 48 V DC - V AC EXETR2LKMA04


Racking device locking magnet 110 V DC - V AC EXETR2LKMA10
Racking device locking magnet 220 V DC - V AC EXETR2LKMA20

60 | EasyPact EXE Catalog se.com


Product references Accessories

Rack-in / rack-out crank Description Reference


Truck operating shaft EXESHFT2
PM108925

se.com EasyPact EXE Catalog | 61


Product references Spare parts

• Only end users (level 2) are allowed to replace the components listed below. These kit components should only be assembled, installed,
used, tested, repaired or maintained by qualified personnal
• To order spare parts, please contact your Schneider Electric representative or your equipment manufacturer
• For any modification or upgrade of the circuit breaker, contact your equipment manufacturer or Schneider Electric

Basic function circuit breaker Description References


PM106431

Operating counter Counter 48535


PM106430

Ready to close Ready to close contact 51-240 V 47080


contact PF

Device covers Description References


PM106458

Removable top cover Removable top cover with screw EXECOTO


PM106459

Main front cover for CB Circuit Breaker main front cover with screw (1) EXECOFRCB
PM106499

Main front cover for DD Disconnecting Device main front cover with screw (1) EXECOFRDD

(1)
Please contact Schneider Electric sales representative for more information to obtain nameplate of the Device.

62 | EasyPact EXE Catalog se.com


Product references

se.com EasyPact EXE Catalog | 63


L-Frame cradle

64 | EasyPact EXE Catalog se.com


L-Frame cradle

Introduction 66

L-Frame cradle references 68

Dimensions 69

se.com EasyPact EXE Catalog | 65


L-Frame cradle Introduction

The L-Frame cradle is supplied as a self-supporting frame, including all interlocks and racking features, and help provide a reliable
and cost-effective solution for integration in a wide range of indoor Air Insulated Switchgear.
The L-Frame cradle brings the benefits of Schneider Electric proven technology to the design and manufacture of withdrawable
switchgear cubicles.
It provides to our Partners a complete solution with connection of the circuit breaker to the contacts in the bushings and allows the
Partners to focus and shorten the design of the switchgear.

Cradle for integration of switching devices


PM105644

The L-Frame cradle is delivered fully assembled and ready for integration of
EasyPact EXE circuit breakers and consists of:
• A left and a right sides frames
• Shutters with their shutter mechanisms
• Rails for guiding the circuit breaker from test to service position
• Bushings with fixed contacts
• Copper bars for connection to the main Busbar of the switchgear
• Two holes on the front of the L-Frame cradle for guiding and aligning the
extraction table
• A self-supporting frame
EasyPact EXE
and L-frame cradle
As an option, it includes a fully rated and interlocked earthing switch. It can give
to the Partners the advantage of a type tested solution for the earthing switch.

The earthing switch is assembled and set by the Schneider Electric


PM105645

manufacturing plant. For 12 kV/17.5 kV, only the fixed contacts (quantity 3 delivered
with the L-Frame cradle as loose components) will have to be assembled and
adjusted on the main circuit of the switchgear.
The earthing switch includes:
• An operating mechanism mounted on the right side of the L-Frame cradle
• A power circuit unit with a fast-acting closing mechanism independent of the
operator
• A mechanical interlocking with the circuit breaker and prevents:
Earthing switch - racking in the circuit breaker if the earthing switch is closed
- closing the earthing switch if the circuit breaker is not opened and fully racked out

66 | EasyPact EXE Catalog se.com


L-Frame cradle Introduction

According to IEC 62271-200: 2011-10


Designation Dimensions and electrical characteristics
Phase distance (mm) 150 210 275
12 p p p
Rated Voltage Ur kV
17.5 p p p
PM105644

Rated frequency fr Hz 50 / 60 p p p
(1)
Rated short duration power 28 p p p
Ud kV
frequency withstand voltage 38 p p p

Rated lightning impulse 75 p p p


Up kV
withstand voltage 95 p p p

Rated short-time 25 p p p
Ik kA
withstand current 31.5 p p p

Rated duration of
tk s 3 p p p
short-circuit
630 / 800 p p

1 250 p p
Rated normal current Ir A
1 600 / 2 000 p

2 500 p

Preferred cubicle width mm 650 800 1000


(1) In accordance with GOST standard: 42 kV 5 min

se.com EasyPact EXE Catalog | 67


L-Frame cradle L-Frame cradle references

Cradle without earthing switch


Phase distance (mm) 150 210 275
Up to Up to
PM105646

AVXN10478-16 AVXN10478-17 -
1 250 A 31.5 kA

12 / 1 600 A / Up to
- AVXN10478-18 -
17.5 kV 2 000 A 31.5 kA

Up to
2 500 A - - AVXN10478-19
31.5 kA

Cradle with earthing switch


Phase distance (mm) 150 210 275
Up to Up to
PM105647

AVXN10478-01 AVXN10478-12 -
1 250 A 31.5 kA

12 / 1 600 A / Up to
- AVXN10478-13 -
17.5 kV 2 000 A 31.5 kA

Up to
2 500 A - - AVXN10478-14
31.5 kA

Earthing Switch handle Description Reference


PM105648

Earthing switch operating handle CHD1000063P0005

Note: The 12 kV cradle may be used for 7.2 kV rated voltage / Please contact your Schneider Electric sales representative for more information

68 | EasyPact EXE Catalog se.com


L-Frame cradle Dimensions
Without earthing switch

Up to 17.5 kV

Up to 31.5 kA / Up to 1 250 A

Phase distance 150 mm Phase distance 210 mm


DM108501

150 150

DM108502
210 210

205 205

1094 260
1077 260

359.5
359.5
800 1071
650 1054

31.5 kA / Up to 1 250 A, Up to 31.5 kA / 2 500 A


up to 31.5 kA / 1 600 A - 2 000 A
Phase distance 210 mm Phase distance 275 mm
DM108503

DM108504

210 210 275 275

310 310
1249 1229
280 280

359.5 359.5

800 1101 1000 1126

se.com EasyPact EXE Catalog | 69


L-Frame cradle Dimensions
With earthing switch

Up to 17.5 kV

Up to 31.5 kA / Up to 1 250 A

Phase distance 150 mm Phase distance 210 mm


DM108505

150 150

DM108506
210 210

205 205

1077 1094
260 260

359.5 359.5

650 1054 800 1071

31.5 kA / Up to 1 250 A, Up to 31.5 kA / 2 500 A


up to 31.5 kA / 1 600 A - 2 000 A,
Phase distance 210 mm Phase distance 275 mm
DM108507

DM108508

210 210 275 275

310
310
1229
1249
280
280

359.5
359.5
1000 1126
800 1101

70 | EasyPact EXE Catalog se.com


L-Frame cradle

se.com EasyPact EXE Catalog | 71


TOOLS

se.com

This international web site allows you to access all the


Schneider Electric solutions and product information via:
• Comprehensive descriptions
• Range datasheets
• A download area
• Product selectors

You can also access information dedicated to your


business and contact your Schneider Electric country
support.
PM103687

72 | EasyPact EXE Catalog se.com


How can digital
bring more value at work?
Simplify your life at all steps of your business

Connect Panel Builder Portal


You'll get:
The Schneider Electric™ Panel Builder Portal can help you find what you need • Productivity tools
to create better, more efficient Low Voltage or Medium Voltage Switchboards, • Personalized resources
in less time. • Collaborative sales support
panel builders web page • Trainings

Get support anytime


• 24/7 self-service, mobile catalog and access With
to expert help
• Off-line and on-line catalog Schneider Electric
• Manage and track your orders
Partner Program,
PM107043

• Advanced support

MySchneider App

Discover, select and define get more


PM107044

done!
Experience our advanced WEB
functionalities that help to:
• Select and compare components
• Build easily and automatically your
technical documentation with ready to
use tools Think big.
www.se.com
Partner up!
Visit our page and get more:

Order and check ordering information


panel builders web page
A self-service ordering platform to access
PM108872

detailed information:
• Check real-time price and availability
information
• Order online
• Check order status and tracking information
• Get financial documentation

mySE

se.com EasyPact EXE Catalog | 73


Notes

74 | EasyPact EXE Catalog se.com


Schneider Electric Industries SAS

35, rue Joseph Monier


CS 30323
92506 Rueil Malmaison Cedex
France

RCS Nanterre 954 503 439


Capital social 896 313 776 €
www.se.com

03-2021

© 2021 - Schneider Electric. All Rights Reserved.


All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. This document has been
Document reference: NRJED316708EN printed on recycled paper