0% found this document useful (0 votes)
184 views1 page

Yuasa Technical Data Sheet: The World's Leading Battery Manufacturer

This document is a technical data sheet for the Yuasa SWL2500EFR industrial VRLA battery. It provides specifications for the battery such as its nominal voltage, capacity at various discharge rates, physical dimensions, terminal type, operating temperature range, charge voltages and currents, and certifications. Safety information is also given regarding battery installation, handling, venting, gas release, and recycling.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
184 views1 page

Yuasa Technical Data Sheet: The World's Leading Battery Manufacturer

This document is a technical data sheet for the Yuasa SWL2500EFR industrial VRLA battery. It provides specifications for the battery such as its nominal voltage, capacity at various discharge rates, physical dimensions, terminal type, operating temperature range, charge voltages and currents, and certifications. Safety information is also given regarding battery installation, handling, venting, gas release, and recycling.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Yuasa Technical Data Sheet

Yuasa SWL2500EFR Industrial VRLA Battery

Specifications
Nominal voltage (V) 12
10m rate Constant Power (Typ) to 9.6V at 20°C 2940
(W/Block)
10m rate Constant Power (Typ) to 1.6V/cell at 490
20°C (W/Cell)
20-hr rate Capacity to 10.5V at 20°C (Ah) 93.6
10-hr rate Capacity to 10.8V at 20°C (Ah) 90
Dimensions
Length (mm) 305 (±3)
Width (mm) 168 (±2)
Height (mm) 224.5 (±1)
Mass (kg) 33
Terminal Type
Threaded terminal - (M=Male or F=Female) M6 (F)
Torque (Nm) 4.8
Operating Temperature Range
Storage (in fully charged condition) -20°C to +50°C
Charge -15°C to +50°C Layout
Discharge -20°C to +60°C
Storage
Capacity loss per month at 20°C (% approx.) 3
Case Material
Standard ABS (UL94:V0)
Charge Voltage
Float charge voltage at 20°C (V)/Block 13.65 (±1%)
Float charge voltage at 20°C (V)/Cell 2.275 (±1%)
3rd Party Certifications
Float Chg voltage tmp correction factor from std -3
ISO9001 - Quality Management Systems
20°C (mV)
ISO14001 - Environmental Management Systems
Cyclic (or Boost) charge Voltage at 20°C (V)/Block 14.5 (±3%)
ISO45001 OHSAS Management Systems
Cyclic (or Boost) charge Voltage at 20°C (V)/Cell 2.42 (±3%)
UNDERWRITERS LABORATORIES Inc.
Cyclic Chg voltage tmp correction factor from std -4
20°C (mV)
Charge Current
Float charge current limit (A) No limit
Cyclic (or Boost) charge current limit (A) 22.5
Maximum Discharge Current Safety
1 second (A) 1000
1 minute (A) 500 Installation
Can be installed and operated in any orientation except
Short-Circuit Current & Internal Resistance permanently inverted.
Internal resistance - according to EN IEC 60896-21 6.5 Handles
(mΩ) Batteries must not be suspended by their handles (where
Short-Circuit current - according to EN IEC 2258 fitted).
60896-21 (A) Vent valves
Each cell is fitted with a low pressure release valve to allow
Impedance
gasses to escape and then reseal.
Measured at 1 kHz (mΩ) 4 Gas release
Design Life & Approvals VRLA batteries release hydrogen gas which can form
EUROBAT Classification: Long life 10 to 12 years explosive mixtures in the air. Do not place inside a sealed
Yuasa design life at 20°C (yrs) up to 10 years container.
Recycling
YUASA’s VRLA batteries must be recycled at the end of life in
accordance with local and national laws and regulations.

Data Sheet generated on 09/12/2021 – E&OE

The world's leading battery manufacturer www.yuasaeurope.com