0% found this document useful (0 votes)
296 views2 pages

ADE-1F2 DS - For Non-Armoured Cable: Hazardous Area Cable Glands

This document provides information on the ADE-1F2 DS hazardous area cable gland, including: 1. It is suitable for non-armoured cable, marine shipboard cable, and tray cable. 2. It has double seal protection and certifications for use in hazardous zones and locations including ATEX, IECEx, UL, and other international standards. 3. It provides flame and environmental sealing for cables and has options for additional clamping and materials like nickel-plated brass, stainless steel, bronze, and aluminum.

Uploaded by

Ing Zener
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
296 views2 pages

ADE-1F2 DS - For Non-Armoured Cable: Hazardous Area Cable Glands

This document provides information on the ADE-1F2 DS hazardous area cable gland, including: 1. It is suitable for non-armoured cable, marine shipboard cable, and tray cable. 2. It has double seal protection and certifications for use in hazardous zones and locations including ATEX, IECEx, UL, and other international standards. 3. It provides flame and environmental sealing for cables and has options for additional clamping and materials like nickel-plated brass, stainless steel, bronze, and aluminum.

Uploaded by

Ing Zener
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

ADE-1F2 DS - for non-armoured cable

Hazardous area cable glands

Suitable for the following cable types:


• Non-armoured cable
• Marine shipboard cable; Type P cable
• Tray cable: TC
Double seal provides 100% of cable clamping.

Certifications and compliances


• ATEX No. INERIS 12ATEX0032X
Zones 1 and 2, Groups I, IIA, IIB and IIC
Zones 21 and 22, Groups IIIA, IIIB and IIIC
II2GD / Ex db IIC/ Ex eb IIC / Ex tb IIIC
II3G Ex nRc IIC
IM2 / Ex db I / Ex eb I ; for mining applications
Brass or bronze size 8 to 17; NPT 1" to 4", ISO 32 to 110
Stainless steel size 4 to 17; NPT 3/8" to 4", ISO 16 to 110

• IECEx No. IECEx INE 12.0025X


Zones 1 and 2, Groups I, IIA, IIB and IIC
Zones 21 and 22, Groups IIIA, IIIB and IIIC
Ex db IIC / Ex eb IIC / Ex nRc IIC / Ex tb IIIC
Ex db I / Ex eb I ; for mining applications
Brass or bronze size 8 to 17; NPT 1" to 4", ISO 32 to 110
Stainless steel size 8 to 17; NPT 1" to 4", ISO 32 to 110

• UL: 3DJN E310130 Class I Zone 1*, AEx e II


ADE size 3 to 8, NPT 1/2" to 1 1/4" or ISO 20 to 40 with non-armoured cable
TC-ER-HL up to 1” diameter

• UL: 3DJN E310130 Class I Zone 2*, AEx e II, Ex e II


ADE size 3 to 17, NPT 1/2" to 4" or ISO 20 to 110 with non-armoured cable
2G 2D ITC, MV, PLTC, TC-ER, TC-ER-HL, TC
• UL: 3LRC E314047 Class I Zone 2*, AEx e II, Ex e II
ADE size 3 to 17, NPT 1/2" to 4" or ISO 20 to 110 with non-armoured marine
option cable
IP66 IP68 316L * Can be used in Div.2 provided that the enclosure contains no components that produce arcs or
sparks.

Other certificates: Shipping applications:


CEPEL 05.0558X ABS 14-HS1274083-PDA
CCoE P360379-1 BV 40910/A0 BV
KOSHA 2015-BO-0249 to 0256 DNV TAE000010X
NANIO TC-RU C-FR.ГБ05.B.00858 Lloyds 11/00072
1 2 NEPSI GYJ13.1082X DTS-01:1991

Technical specification
• Nickel-plated brass for superior corrosion resistance. 316L stainless steel, bronze
and aluminum options available. It is recommended that a suitable lubricant is used
on all threads of stainless steel and aluminum versions.
• Temperature range: -60 °C to +140 °C
• IP66 / IP68 according to the method of attachment and the condition of the
equipment area, see page 2.5

Features and benefits


1: Flameproof and sealing on outer sheath of the cable
2: Environmental sealing and controlled pulling resistance on outer sheath of the
cable.
3: Additional clamping for strain relief (optional).

2.8 EATON Cable glands global solutions catalogue


ADE-1F2 DS - for non-armoured cable
Hazardous area cable glands

INTRODUCTION
L E**

* For ‘across corners’

A*
dimensions, multiply
B*

‘across flats’ dimensions


by 1.1

** For ‘E’ see thread


dimension page 5.18

HAZARDOUS AREA CABLE GLANDS


CABLE CODES KIT OPTIONS
THREAD
SERIES SEALING MATERIAL OPTION
SIZE K1 Accessories kit 1 Kit 1 contents:
RANGE
K2 Accessories kit 2 K1 • Locknut
ADE2 M25 3 NPN K3 Accessories kit 3 • Green composite washer
BLANK No option Kit 2 contents:
SELECT • Locknut
K2 • Green composite washer
• Earth tag
0 = XS • Shroud
1=S

HAZARDOUS AREA ACCESSORIES


SELECT
Kit 3 contents:
2=M NPN Nickel-plated brass
SELECT SSN Stainless steel
• Locknut
3=L
BZN Bronze
K3 • Green composite washer
ALN Aluminum (not Group I)
• Earth tag
• Serrated washer

Ordering codes
CABLE SEALING RANGE
THREAD THREAD THREAD CABLE ISO (NPT) ADE CATALOG CATALOG
SIZE SIZE CODE THREAD SIZE CODE SEALING OUTER SHEATH GLAND NUMBER NUMBER
SERIES (ISO) (ISO) SIZE (NPT) (NPT) RANGE MIN - MAX A B L SIZE (ISO) (NPT)

ADE2 12* M12 - - 3 4.5 - 8.0 17 17 42.0 4 ADE2M123NPN -


ADE2 16* M16 - - 2 4.5 - 8.5 17 19 42.0 4 ADE2M162NPN -
ADE2 16* M16 - - 3 7.0 - 12.0 19 19 47.0 5 ADE2M163NPN -
ADE2 20 M20 1/2" N050 0 2.7 - 5.5 15 24 42.0 3 ADE2M200NPN ADE2N0500NPN
ADE2 20 M20 1/2" N050 1 4.5 - 8.5 17 24 42.0 4 ADE2M201NPN ADE2N0501NPN

INDUSTRIAL CABLE GLANDS


ADE2 20 M20 1/2" N050 2 7.0 - 12.0 19 24 47.0 5 ADE2M202NPN ADE2N0502NPN

AND ACCESSORIES
ADE2 20 M20 1/2" N050 3 10.0 - 16.0 (15.5) 24 24 54.0 6 ADE2M203NPN ADE2N0503NPN
ADE2 25 M25 3/4" N075 1 7.0 - 12.0 19 30 47.0 5 ADE2M251NPN ADE2N0751NPN
ADE2 25 M25 3/4" N075 2 10.0 - 16.0 24 30 54.0 6 ADE2M252NPN ADE2N0752NPN
ADE2 25 M25 3/4" N075 3 13.5 - 20.5 30 30 63.0 7 ADE2M253NPN ADE2N0753NPN
ADE2 32 M32 1" N100 3 18.0 - 27.5 (26.0) 41 41 79.0 8 ADE2M323NPN ADE2N1003NPN
ADE2 40 M40 1 1/4" N125 3 23.0 - 34.0 48 48 86.0 9 ADE2M403NPN ADE2N1253NPN
ADE2 50 M50 1 1/2" N150 1 29.0 - 41.0 55 55 90.0 10 ADE2M501NPN ADE2N1501NPN
ADE2 - - 2" N200 2 35.0 - 48.0 64 64 90.0 11 - ADE2N2002NPN
ADE2 50 M50 - - 2 35.0 - 45.0 64 64 99.0 11 ADE2M502NPN -
ADE2 63 M63 2" N200 3 42.0 - 56.0 (53.0) 72 72 106.0 12 ADE2M633NPN ADE2N2003NPN
ADE2 75 M75 2 1/2" N250 3 50.0 - 65.0 (62.5) 85 85 119.0 13 ADE2M753NPN ADE2N2503NPN
ADE2 90 M90 3" N300 2 58.0 - 74.0 95 95 123.0 14 ADE2M902NPN ADE2N3002NPN
ADE2 90 M90 3" N300 3 66.0 - 83.0 (78.0) 110 110 139.0 15 ADE2M903NPN ADE2N3003NPN
ADE2 110 M110 3 1/2" N350 2 75.0 - 93.0 (92.0) 120 120 139.0 16 ADE2M1102NPN ADE2N3502NPN
ADE2 110 M110 4" N400 3 85.0 - 104.0 135 135 156.0 17 ADE2M1103NPN ADE2N4003NPN
TECHNICAL GUIDE

* Not UL certified. Above catalog numbers are for nickel-plated brass; refer to order code diagram for other options.

All dimensions in mm.

EATON Cable glands global solutions catalogue 2.9