Aegis Panel Datasheet K-84-100
Aegis Panel Datasheet K-84-100
Conventional Fire Alarm-Suppression Control Unit A UTC Fire & Security Company
Effective: March 2007
84-100
FEATURES
• Agency Approvals • Input and Output
• FM Approved • 3 Detection Circuits
• FM Approved to ANSI/UL 864, 9th edition • 2 Supervisory Circuits
• FM Approved to ULC-S527-99 • 1 Manual Release Circuit
• Other domestic U.S. approvals/listings pending/ • 1 Abort Input Circuit
in-process • 3 Notification Appliance Circuits
• Suppression focused Control Unit • 2 Release Circuits
• Listed for a Wide Range of Suppression Systems • 4 Form-C Relays
• Kidde FM-200®, FE13TM, CO2, 3MTM Novec 1230 • Programmable Relays
Fire Protection Fluid, ArgoniteTM, and Halon
• Robust Power Supply
Clean Agents
• Elegant User-Interface
• Kidde IND™ Dry Chemical & WHDR™ Wet
Chemical Systems • Simple Configuration
• Sprinkler Supervisory Service • Password Protected
• Deluge, Preaction, Foam, Foam-Water Systems • Digital Release Countdown
• Combination Clean Agent plus Pre-Action System • Battery Voltage and Charging Current Display
• Built-in Class-A and Class-B Circuitry • Extensive Diagnostics
• Sophisticated Programmable Notification Appliance • Backwards Compatible
Circuits • Improved and Enlarged Cabinet Design
• Independently Programmable Agent Releasing Circuits • 5-Year Warranty
with Triple-R Protection
DESCRIPTION
The Kidde AEGIS is the technologically most advanced Con-
ventional Single Hazard Agent Releasing Unit available to
the Fire-Alarm Suppression industry today. It combines the
high quality, system reliability, and flexibility required by
modern commercial, high-tech and industrial applications
in an aesthetically pleasing and physically robust package.
RELAY 2 TB10
RELAY 1 TB11
TB13
2
BUILT-IN CLASS A AND B CIRCUITRY POWER-LIMITED CIRCUITRY
For the input and NAC circuits, the choice of Class A or All circuits, excluding ARCs are inherently power-limited.
Class B supervision is made at site on the board itself by Agent Release Circuits, except when firing Initiators, can
selecting the terminals used for wiring. Neither conversion also be made power-limited by a field located inline releas-
boards nor additional hardware nor jumper selection is re- ing diode device thereby allowing cost effective installation
quired for this purpose. with all wiring in the same conduit.
AGENT RELEASE CIRCUITS (ARC) ROBUST POWER SUPPLY UNIT (PSU)
The two circuits can be programmed for activation by dif- The AEGIS features a universal 120/240 V, 50/60 Hz AC
ferent inputs, with independent time delays and abort modes Power Supply Unit with a robust 5.4 Amps of 24 VDC power.
to fire combinations of two of the following releasing de- Input voltage selection is via a slider switch with no jumper
vices: cutting required. The on-board battery charger is able to
• 1 or 2 Kidde Continuous and Momentary Solenoid charge 24 VDC (2 x 12) batteries of capacity up to 68 AH
Control Heads thereby allowing from 24 hours of supervision plus 5 min-
utes of alarm to 90 hours of supervision plus 10 minutes of
• 1 Kidde Initiator alarm required by some jurisdictions.
• 1 Factory Mutual Group A, B, D, E, F, G, I, J, or K AUXILIARY POWER SUPPLY
Solenoid
Up to 1 Amp of auxiliary power at 24 VDC is available to
In other words, operating in tandem, the two circuits can power external 4-wire devices such as Flame Detectors,
release: AlarmLine modules, Duct Detectors, etc.
• 1 or 2 Control Heads on ARC1 and 1 or 2 Control ELEGANT USER-INTERFACE
Heads on ARC2
The user-interface consists of an array of LED Indicators,
• 1 or 2 Control Heads on ARC1 and 1 Initiator on ARC2 Control Switches, a Digital Display, and Buzzer. Over and
or vice-versa above the System, Power Supply status, Input circuit Fire
• 1 or 2 Control Heads on ARC1 and 1 FM Sprinkler and Trouble and Output circuit Trouble LEDs, the AEGIS
Solenoid on ARC2 or vice-versa annunciates its suppression state-of-alarm via three addi-
tional Pre-Release, Releasing and Post Release LEDs. Four
• 1 Initiator on ARC1 and 1 Initiator on ARC2 switches are provided, one each for Acknowledge, Signal
• 1 FM Solenoid on ARC1 and 1 FM Solenoid on ARC2 Silence, System Reset and Output Disable. The 3-digit dis-
This configurability is useful for those jurisdictions where play provides a countdown of impending agent release. On
the gaseous suppression agent is required to be supple- command from the user-interface switches, it also indicates
mented with a pre-action system. the battery open circuit voltage and charging current.
3
BACKWARDS COMPATIBILITY TECHNICAL SPECIFICATIONS (CONT’D)
Consistent with previous generation Kidde control equip- • One (1) Abort Circuit
ment, the AEGIS is listed to be backwards compatible with
- Compatible with normally open contact-closure type
the full range of Kidde-Fenwal conventional detectors, alarm
devices
devices and suppression accessories. Going forward, this
will allow older generation panels to be replaced with rela- - Configurable as Class A/Style D or Class B/Style B
tive ease. - Supervised for ground faults and open circuits
IMPROVED AND ENLARGED CABINET DESIGN - Power-limited
The cabinet design allows for easy installation by fitting be- • Two (2) Supervisory Circuits
tween the studs of a standard 16 inch studded wall. It is - Compatible with normally open contact-closure type
large enough to house two 12 VDC, 12 AH Batteries and devices
provides up to 2 inches (51 mm) of wiring and finger space - Configurable as Class A/Style D or Class B/Style B
between the circuit board and the cabinet wall.
- Supervised for ground faults and open circuits
An optional door design features a factory installed Manual
- Power-limited
Release and Abort switch for applications with space con-
straints. Both switches incorporate guards that prevent their • Three (3) Notification Appliance Circuits (NACs)
inadvertent activation. - Compatible with polarized 24 VDC Audio-Visual de-
Other cabinet options include a flush mounting trim-ring and vices
a dead-front plate required for Canadian applications. - Rated at 1.5 Amps each
- Configurable as Class A/Style Z or Class B/Style Y
TECHNICAL SPECIFICATIONS - Supervised for ground faults, shorts, and open cir-
• Hazards Protected cuits
- One - Power-limited
• Power Supply - First Alarm operates NAC 1, Pre-Release operates
- 120/240 Vac, 50/60 Hz (90 to 264 Vrms, 47 to 63 Hz) NAC 2, Releasing operates NAC 3
AC Main Input - Common NAC/ARC output disconnect switch
- 5.4 Amps at 27 Vdc Output • Two (2) Agent Release Circuits
- Battery capacity up to 68 AH @ 24 Vdc - Each compatible with 1 or 2 control heads, or 1 initia-
- Auxiliary power output rated at 1 Amp at 18.8 - 27.6 tor, or 1 FM sprinkler solenoid
Vdc (resettable) - Circuits electrically capable of simultaneously releas-
• Three (3) Detection Circuits ing any combination of two of the above devices
- Compatible with up to 25 CPD-705x, PSD-715x, and - Factory configured as Class B/Style Y
THD-705x detectors and normally open contact-clo- - Supervised for ground faults and open circuits
sure type devices - Non-power-limited. May be power-limited (except with
- Configurable as Class A/Style D or Class B/Style B initiators) and supervised for short circuit using inline
- Supervised for ground faults and open circuits releasing resistor-diode device
- Power limited - Common NAC/ARC output disconnect switch
- DET 1 and DET 2 used for suppression • Four (4) Relays
- DET3/WF configurable for detection or waterflow - 3 independently programmable, normally de-energized
Form-C
• One (1) Manual Release Circuit
- Compatible with normally open contact-closure type - 1 dedicated normally energized Form-C Trouble Re-
devices lay
- Configurable as Class A/Style D or Class B/Style B - Relay contacts rated 3 Amps at 30 Vdc/120 Vac (re-
sistive)
- Supervised for ground faults and open circuits
- Power limited
4
TECHNICAL SPECIFICATIONS (CONT’D) ORDERING INFORMATION
• Enclosure
PART
- NEMA 1 rated 18 gauge sheet steel with door DESCRIPTION
NUMBER
- Red color
- Suitable for wall and surface mounting Kidde AEGIS Control Unit 84-732001-001
- Optional Trim Ring Kidde AEGIS Control Unit with
84-732001-201
- Optional Dead-Front Panel Switches
- Optional door with Manual Release and Abort switches
In-Line Releasing Diode (10K) Kit 06-220023-001
- Dimensions:
- with Standard Door: Trim Ring 76-600000-007
14-1/4 in. W x 5 in. D x 19 in. H Dead-Front Panel* 06-236725-001
(362 mm x 127 mm x 483 mm)
Battery Enclosure 76-100010-001
- with Switch Door
14-1/4 in. W x 6 in. D x 19 in. H Kidde AEGIS Conventional Fire
(362 mm x 152 mm x 483 mm) Alarm-Suppression Control Unit IOM 06-236716-001
Manual
• Environmental Criteria
- Indoor/Dry use only Kidde AEGIS User's CD 06-236727-001
- Operating temperature range: 32°F to 120°F (0°C to *For Canadian applications, order Control Unit and
49°C) Dead-Front Panel separately.
- Humidity: 93 ± 2% RH at 90 ± 3°F (32 ± 2°C )
• Packaging/Shipping
- Enclosure, PCB, and PSU packaged in individual car-
tons
- Accessories shipped include mounting hardware, bat-
tery leads, IOM manual on CD-ROM, operating in-
struction sheet, and EOL resistor kit
- Order inline releasing resistor-diode device (if required)
and batteries separately
5
Kidde is a registered trademark of Kidde-Fenwal, Inc.
AEGIS and Gemini are trademarks of Kidde-Fenwal, Inc. For detailed installation, operation, and configuration infor-
FM-200 is a registered trademark of Chemtura. mation, refer to the Kidde AEGIS Conventional Fire Alarm-
FE-13 is a registered trademark of DuPont.
3MTM NovecTM 1230 Fire Protection Fluid is a trademark of 3M. Suppression Conventional Unit Installation, Operation, and
Argonite is a registered trademark of Ginge Kerr. Maintenance Manual P/N 06-236716-001.