Bluebox Tetris - 2 80-900
Bluebox Tetris - 2 80-900
84 to 913 kW
General Strengths
A generation of customised high energy efficiency chillers,
with scroll compressors, designed to meet requirements in ►► Unit in Eurovent class A
the commercial and industrial sectors
►► A and A+ units with Night Shift function
Configurations ►► Hydraulic modules also integrated with buffer tank
A and A+: High efficiency unit ►► Three types of pumps: standard, oversize and for high
LN: Low noise unit percentages of glycol (up to 50% e.g.)
SLN: Super low noise unit ►► User-side pumps with inverter available
HP: Reversible heat pump ►► Multilogic
DS: Unit with desuperheater ►► Integrated web server
DC: Unit with total recovery
Unit with hydraulic module
TETRIS 2
CONTENTS
SPECIFICATIONS3
VERSIONS4
TECHNICAL SPECIFICATIONS - TETRIS 2 16
TECHNICAL SPECIFICATIONS - TETRIS 2A 18
TECHNICAL SPECIFICATIONS - TETRIS 2SLN 19
TECHNICAL SPECIFICATIONS - TETRIS 2A+ 20
TECHNICAL SPECIFICATIONS - TETRIS 2A SLN 21
ELECTRICAL SPECIFICATIONS - TETRIS 2 22
ELECTRICAL SPECIFICATIONS - TETRIS 2A TETRIS 2 SLN 22
ELECTRICAL SPECIFICATIONS - TETRIS 2A+ TETRIS 2A SLN 22
TECHNICAL SPECIFICATIONS FOR PUMPS 23
OPERATING LIMITS - TETRIS 2 24
COOLING24
RECOVERY24
HEATING24
OPERATING LIMITS - TETRIS 2A - TETRIS 2 SLN 25
COOLING25
RECOVERY25
HEATING25
OPERATING LIMITS - TETRIS 2A+ - TETRIS 2A SLN 26
COOLING26
RECOVERY26
HEATING26
ALLOWED FLOW RATE RANGE 27
VERSIONS THAT ARE NOT POSSIBLE - TETRIS 2 28
VERSIONS THAT ARE NOT POSSIBLE - TETRIS 2A - TETRIS 2 SLN 29
VERSIONS THAT ARE NOT POSSIBLE - TETRIS 2A+ - TETRIS 2A SLN 29
NOISE LEVELS - TETRIS 2 30
NOISE LEVELS - TETRIS 2 /LN 31
NOISE LEVELS - TETRIS 2 A 32
NOISE LEVELS - TETRIS 2 A /LN 32
NOISE LEVELS - TETRIS 2 SLN 32
NOISE LEVELS - TETRIS 2 A+ 33
NOISE LEVELS - TETRIS 2 A+ /LN 33
NOISE LEVELS - TETRIS 2 A SLN 33
DIMENSIONAL DIAGRAMS 34
2
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
3
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
4
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
• temperature probe at the inlet of each recovery exchanger. • modules /1PM, /2PM, /3PM, /1PMS, /2PMS and /3PMS that
have pumps with increased available discharge head
For multi-circuit units, the probe is supplied with the unit and
is to be positioned on the exchanger inlet manifold (by the • modules /1PG, /2PG, /3PG, /1PGS, /2PGS and /3PGS that
customer). have pumps suitable for operating with glycol up to 50%
Hydraulic modules with one pump have:
• liquid receiver for each refrigerant circuit with system for
emptying the refrigerant from the condensing coil • one pump
• potential free contact in the electrical control panel for ac- • a gate valve on the delivery side of the pump
tivation of recovery. • an expansion vessel
When required by the system, through the closing of a con- Hydraulic modules with two pumps have:
tact, the control automatically manages activation of recovery.
• two pumps
Recovery management is carried out through a control on the
temperature of the return water. • a check valve on the delivery side of each pump
The control also automatically manages safety deactivation of • a gate valve on the outlet of the delivery manifold
recovery if the condensing pressure becomes too high, and • an expansion vessel
changes to using the condensing coils. Hydraulic modules with three pumps have:
This option is not available for /HP units. • three pumps
/DS: unit with desuperheater • a check valve on the delivery side of each pump
In addition to the basic set-up, /DS units comprise (for each • a gate valve on the outlet of the delivery manifold
refrigerant circuit) an exchanger for condensation heat reco- • an expansion vessel
very of up to 20% (depending on size, version and operating In the version with 2 pumps, these are always with one on
conditions), placed in series with the condensing coil. The standby while the other is working. Switching over between
exchanger is a braze-welded plate heat exchanger. the pumps is automatic and is done by time (to balance the
For multi-circuit units, the exchangers are to be manifolded hours of operation of each one) or in the event of failure.
outside the unit (by the customer). In the version with 3 pumps (each sized to 33% of the flow
To maximize the use of the accessory and optimize machine rate), the 3 pumps operate at the same time; if one of them
operation, combination with the speed adjuster of the fans or fails, up to 78% of refrigeration capacity will in any case be
5
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
guaranteed.
Also, for hydraulic modules with 3 pumps, during summer
starting of units provided with three pumps, when the water
temperature is higher than the maximum allowed limit, the
control automatically starts the unit with only two pumps. In
this way, by reducing the water flow rate, the evaporating
pressure, and consequently the delivery pressure, is also re-
duced, so preventing the unit from shutting down. The third
pump begins working automatically when the temperature of
the reference water returns within the set limits.
Hydraulic modules with tank also have:
• a gate valve at the inlet of the pump or the suction manifold
• a tank with drain valve and air valve
Refer to the table of configurations that are not possible to
check for availability of specific set-ups.
6
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
7
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DESCRIPTION OF ACCESSORIES
CODE Accessory Operation and advantages
Compressor suction and The valves situated on the suction side and on the delivery side of the manifold of the compressors allow the
RUB delivery valves
compressor unit ((tandem or trio) to be isolated from the rest of the refrigerant circuit, so making the mainte-
nance operations quicker and less invasive.
With this accessory, instead of each individual safety valve per circuit, there is a "candelabrum" with two safety
DVS Double safety valve valves and a diverter valve for choosing the valve in operation. This allows the safety valves to be replaced
without having to drain the machine and without having to stop it.
When the compressors stop, the controller always closes the electronic expansion valve to prevent dangerous
Capacitive backup battery refrigerant migration. The presence of the backup battery ensures that the electronic valve is kept in closed
BC for electronic expansion position even when there is no power supply
valve This accessory uses a condenser, and not an ordinary battery, as energy storage: this allows it to be unaffected
by the memory effect of normal batteries and eliminates its need for maintenance.
Application of this accessory is compulsory if the unit has to produce water with temperature lower than +3°C
(if the unit is provided with double set point or variable set point, the lower set point is considered).
BK Brine Kit The accessory consists of adopting an increased insulation and a suitable sizing and calibration of some com-
ponents.
This accessory compulsorily requires the insertion of the condensing control with speed adjuster or the EC fans.
With this accessory, a refrigerant leak detector is placed inside each compressor compartment. Detection of a
refrigerant leak is managed by the control through a specific alarm and display of a specific icon on the display
RPR Refrigerant leak detector of the control. This alarm does not stop the unit.
The accessory can be applied only to units in LN or SLN set-up.
With this accessory, a refrigerant leak detector is placed inside each compressor compartment. Detection of a
refrigerant leak is managed by the control through a specific alarm and display of a specific icon on the display
Refrigerant leak detector of the control. For all the circuits of the unit, the alarm also starts the machine stopping procedure with pump
RPP with automatic pump down
down, confining all the refrigerant in the coils.
The accessory includes the capacitive backup battery.
The accessory can be applied only to units in LN or SLN set-up.
FAN ACCESSORIES
With this accessory, EC fans, with electronically commutated brushless motor, are used for the ventilating
section. These guarantee very high efficiency levels for all working conditions and allow a 15% saving on the
power absorbed by each fan working at full capacity.
VEC EC fans
Also, through a 0-10V analogue signal sent to each fan, the microprocessor carries out condensing/evaporating
control by continuous adjustment of the air flow rate as the external air temperature changes, with a further
reduction in electrical absorption and noise emission.
With this accessory, EC fans, with electronically commutated brushless motor, are used for the ventilating sec-
tion. These guarantee very high efficiency levels for all working conditions. Through a 0-10V analogue signal
sent to each fan, the microprocessor carries out condensing/evaporating control by continuous adjustment of
VEM Oversize EC fans the air flow rate as the external air temperature changes, with a further reduction in electrical absorption and
noise emission.
Oversize EC fans make it possible to have an available residual pressure of about 70Pa for standard units and
about 100Pa for SLN units.
8
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
Pressure recuperator
RECP
Normally, the air ejected by the fan has a high speed and this manifests itself as kinetic energy that is dissipated
into the environment.
The pressure recuperator is a passive element situated on the ejection duct of each individual fan designed
to allow better conversion of kinetic energy into static pressure, which manifests itself as a higher pressure
generated by the fan.
This higher pressure can have at least two possible applications:
• For the same fan speed, the pressure recuperator allows an increase of about 50Pa in the available dis-
charge head of the ventilating section to be obtained. This can be useful for overcoming the head losses
that may be present in specific installations. The increase in available discharge head is to be considered
in addition to the increase that can already be obtained with the application of oversize EC fans.
• For the same pressure differential on the air, the pressure recuperator allows the same air flow rate to be
obtained with a lower number of revolutions of the fan. This automatically produces a reduction of up to
3 dB(A) in the noise emission of the unit and a reduction in the absorption of the fan, with an immediate
increase in the overall efficiency of the unit.
To allow optimization of the performance of the accessory, combination with the speed adjuster or EC fans
is necessary. In this last case, the higher efficiency of the EC fans (especially when operating at low speed) is
added to the performance improvement generated by the pressure recuperator.
The accessory is supplied separately from the unit on one or more pallets and it must compulsorily be installed
(by the customer) before the first start-up of the machine.
9
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
Circuit braker
that has a constant flow pump on the primary circuit (P1) and a variable
flow pump on the secondary circuit (P2). P1
This diagram shows the use of the hydraulic uncoupling pipe (circuit
breaker) between primary and secondary circuit that is sized at 100%
of the flow rate: if the points of use require only a percentage of the
rated power, the uncoupling pipe recirculates the excess flow rate with
consequent waste of pumping energy.
In the solution with the “Inverter for pump on user side” accessory, there is a single variable flow pumping unit
(P1), already integrated in the chiller, which feeds both the primary and secondary circuits. Instead of a simple
separation pipe, a bypass valve (VBP) is inserted and this guarantees that the minimum water flow rate to the
evaporator is maintained even when demand from the points of use is well below nominal demand.
This system also allows the separation pipe and the bypass valve to be sized for a much lower water flow rate
than the rated flow rate, to therefore obtain a net reduction in energy losses due to water recirculation.
The benefits obtained with the use of this accessory are therefore:
• insertion of a single set of pumps in the system, with consequent reduction in investment and pumping
costs
• reduction in the space necessary inside the technical compartment of the building
• simplification of the hydraulic circuit
• greater pumping energy efficiency 22%
Also, by assessing the ESEER level of the unit, also counting the
improvement
To understand more clearly how the accessory works, we refer to the following layout:
VBP
Δp1 Δp2
P1 VFW
The whole system is controlled by a dedicated controller (provided with its display) that, through pressure
transducers, detects the head losses on the evaporator (∆p1) and the head losses on the system side (∆p2).
When all the points of use are in operation, the pump of the unit works at the rated flow rate. The decrease in
heat load of the system causes the shut-off valves of the points of use to close, with a consequent increase in
head losses on the system side because of the increase in flow rate in the lines left open.
The control therefore detects the variation of ∆p2 and, by also assessing the water outlet temperature from the
exchanger (varied with respect to the decrease in head), implements a procedure of adjustment of the speed
of the pump P1 in order to return the head losses to nominal conditions.
10
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
Again considering the water outlet temperature and the variation of ∆p1, the control checks that there is always
the minimum flow rate to the exchanger needed to ensure correct heat exchange. If the flow rate required by
the system is too low to have the correct flow rate to the exchanger, the control modulates the bypass valve
VBP until the correct operating conditions for both the system and the exchanger are restored.
To ensure correct operation of this system in all conditions, it is necessary to assess the volumes of water present
in the system and their position: when the system has most of the shut-off valves closed and therefore with
IPU Inverter for pump on user
heat load near zero, even if the machine is working in conditions of maximum capacity reduction, conditions
side that trigger the antifreeze alarm could occur. To avoid this problem, it is necessary to have a “thermal wheel
minimum” in the section between the exchanger of the unit and the bypass valve (represented in the figure
with the VFW tank). The required volume can be determined with the following formula:
For /DC or /DS version units with more than one refrigerant circuit, there will be a recovery exchanger for each
circuit, which must be manifolded by the customer.
COL Water manifolds for DS/DC
For some models, the supply of manifolds with the machine can be requested as an accessory. They are to be
installed on site by the customer.
These are electric heaters inserted on the user-side heat exchanger, on the pumps and in the tank (depending
on the configuration of the machine) to prevent damage to the hydraulic components due to ice formation
during periods when the machine is stopped.
Based on normal operating conditions and the percentage of glycol in the system, an appropriate “antifreeze
RA Anti-freeze heater alarm” temperature is set in the control. When a temperature that is 1°C higher than the antifreeze alarm
threshold is detected at the outlet from the exchanger, the pump (if present) and the antifreeze heaters are
switched on. If the temperature of the outgoing water reaches the antifreeze alarm threshold, the compres-
sors are stopped, keeping the heaters and the pumps active, and the general alarm contact of the machine is
activated.
With this accessory, a safety valve is inserted in the hydraulic circuit of the unit: when the calibration pressure
is reached, the valve opens and, by discharging (to be routed by the customer), prevents the system pressure
VSIW Water-side safety valve from reaching limits that are dangerous for the components present in the system. The valves have positive
action, that is, performance is guaranteed even if the diaphragm deteriorates or breaks.
11
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
ELECTRICAL ACCESSORIES
Compared to the parametric control, the advanced control adds the following functionalities
• recording of all the variables and parameters of the unit with sampling for 15 seconds - this allows a log
CA Advanced control to be kept with FIFO logic that covers about 20 days, depending on the size of machine
• an Ethernet serial port with TCP/IP protocol and Modbus over IP
• an integrated WEB server with display pages and management of preloaded pages
The control is set for using the BACnet protocol (instead of Modbus) on the Ethernet port.
BACnet protocol over IP
PBA (Ethernet) By default, the programming gives read-only access to the control of the unit. Enabling of read/write access
should be requested when ordering.
With this accessory, a RS485/Lon gateway is installed inside the electrical control panel.
GLO Lon Gateway By default, the programming gives read-only access to the control of the unit. Enabling of read/write access
should be requested when ordering.
Multilogic function for With this accessory, the unit is programmed as master of a system of machines in Multilogic network (for
further details, refer to the control manual). Also, a network gateway with 4 ports is installed in the electrical
FM2 Master unit for managing control panel of the unit to allow the unit to be connected to an external LAN network and up to 2 slave units
up to 2 Slaves to be managed.
Multilogic function for With this accessory, the unit is programmed as master of a system of machines in Multilogic network (for
further details, refer to the control manual). Also, a network gateway with 8 ports is installed in the electrical
FM6 Master unit for managing control panel of the unit to allow the unit to be connected to an external LAN network and up to 6 slave units
up to 6 Slaves to be managed.
Multilogic function for With this accessory, the unit is programmed as slave of a system of machines in Multilogic network (for further
FM0 Slave unit details, refer to the control manual).
With this accessory, an electrical control panel, containing power factor correction condensers to bring the
cosφ of the unit to being greater than 0.9, is supplied with the unit. The condensers should be connected
Power factor correction to (by the customer) to the electrical control panel of the unit in the specially prepared terminal board.
RIF cosφ≥ 0.9
Besides reducing the absorbed reactive power, the use of this accessory also allows the maximum ab-
sorbed current to be lowered.
For units fitted with this accessory, it is possible to preset two different operating set points and manage the
Double set point from change from one to the other through a digital signal.
SETD digital input
The set point temperatures must be specified when ordering.
Variable set point with
For units fitted with this accessory, the set point can be varied continuously between two preset values, a
SETV remote signal (0-1V, 0-10V, maximum and a minimum, depending on an external signal that can be of the 0-1V, 0-10V or 4-20mA type.
4-20mA)
When this accessory is requested, the unit is set to use the water outlet temperature (instead of the inlet tem-
Outgoing water tempera- perature) as reference for thermoregulation.
COTW ture control This system requires the management of a neutral zone to the control; the lower the number of compressors
of the unit, the wider this zone will be.
For units fitted with this accessory, the set point of the unit is set so that it can vary between two values, a maxi-
mum and a minimum, depending on the external air temperature. The compensation ramp and the maximum
and minimum values of the set point can be changed by the user.
Unless otherwise specified in the order, the control will be set to implement a negative compensation logic
according to the temperatures
Summer shown
positive
Summer in compensation
positive the following diagrams:
compensation Summer negative
Summer negative
compensation
compensation
SET SET
POINT 2 17/12°C
POINT 2 17/12°C SET SET
POINT 2 17/12°C
POINT 2 17/12°C
Negative compensation Positive compensation
Summer
Summer positive
positive compensation
compensation Summer
Summer negative
negative compensation
compensation
SET SET POINT
POINT 2 17/12°C
2 17/12°C SET SET POINT
POINT 2 17/12°C
2 17/12°C
SET SET
POINT 1 12/7°C
POINT 1 12/7°C SET SET
POINT 1 12/7°C
POINT 1 12/7°C
Chiller
temperature 25°C
25°C 35°C
35°C 25°C
25°C 35°C
35°C
External
External air temperature
air temperature External
External air temperature
air temperature
Winter
Winter
positive
positive
compensation
compensation Winter
Winter
negative
negative
compensation
compensation
SET SET
POINT 2 40/45°C
POINT 2 40/45°C SET SET
POINT 2 40/45°C
POINT 2 40/45°C
Heat pump
Winter
Winter positive
positive compensation
compensation Winter
Winter negative
negative compensation
compensation
SET SET POINT
POINT 2 40/45°C
2 40/45°C SET SET POINT
POINT 2 40/45°C
2 40/45°C
SET SET
POINT 1 35/40°C
POINT 1 35/40°C SET SET
POINT 1 35/40°C
POINT 1 35/40°C
0°C0°C 15°C
15°C 0°C0°C 15°C
15°C
SET SET POINT
POINT 1 35/40°C
1 35/40°C External
External
air temperature
air temperature SET SET POINT
POINT 1 35/40°C
1 35/40°C External
External
air temperature
air temperature
0°C0°C 15°C
15°C 0°C0°C 15°C
15°C
External
External air temperature
air temperature External
External air temperature
air temperature
Relay for management of 1 This accessory can be requested for units without pumps and allows a pump outside the machine to be con-
RE1P external pump trolled.
Relay for management of 2 This accessory can be requested for units without pumps and allows two pumps outside the machine to be
RE2P external pumps controlled with a running/stand-by logic by implementing a rotation on the hours of operation.
12
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
The scroll compressors have DOL (Direct On Line) starting and their torque (T) and current (I) characteristics are
shown in the following diagrams:
T [Nm] I [A]
ISC
T [Nm] I [A]
ISC
IN
rpm rpm
IN
For an individual compressor, the normal starting current I will be 4-5 times its rated current IN.
SC
SOFT Electronic soft-starter If the unit is equipped with the electronic
rpm soft-starter accessory, the starting
rpm of each compressor is done with
anT acceleration
[Nm] ramp that allows the effective
I [A] value (rms value) of the inrush current of the individual compres-
sor to be lowered.
T [Nm] I [A]
ISC
IN
rpm ISC rpm
IN
rpm rpm
Remote-controlled user
This accessory consists of a replica of the control that can be remotely operated up to 150m, from which it
terminal is possible to work completely on the configuration of the unit and display all its parameters on the display.
This terminal is suitable for insertion in an ordinary electrical enclosure box (box 503) and does not need an
TERM external power supply unit because it takes its power directly from the control of the unit.
The terminal is also fitted with an NTC temperature probe and can therefore work as a room thermostat (for
LE or LE/HP units combined with air handling units).
The parameters are accessed by entering passwords that enable the various modification levels.
Remote-controlled user
terminal (unit with advanced
control)
This accessory allows the terminal normally situated on the machine to be replicated on a support situated at a
distance. It is particularly suitable when the unit is placed in an area that is not easily accessible.
TERM
The accessory is supplied with the unit and is to be installed by the customer at a maximum distance of 120m
from the unit.
A manual switch to which to connect two separate power supply lines (for example, one from the mains power
Double power supply with line and one from the uninterruptible power supply unit) is installed in the electrical control panel of the unit.
DAM manual switching
The switching from one line to another is manual and compulsorily requires passing through the OFF position.
A motor-driven automatic switch to which to connect two separate power supply lines (for example, one from
Double power supply with the mains power line and one from the uninterruptible power supply unit) is installed in the electrical control
DAA automatic switching panel of the unit.
The switching from one line to another is automatic and compulsorily requires passing through the OFF position.
Maximum and minimum This accessory constantly monitors the voltage value and the unit's power supply phase sequence. If the supply
RMMT voltage relay
voltage does not fall within the set parameters or there is a phase reversal, an alarm is generated that stops the
machine to prevent damage to its main parts.
With this accessory, automatic circuit breakers are installed for the protection of auxiliary loads and fans.
IA Automatic circuit breakers Also, this accessory uses automatic circuit breakers with adjustable thermal overload protection to protect the
compressors.
13
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
With this accessory, it is possible to set the unit so that the controller switches off the compressors when the
unit is operating in heat pump mode and the external air temperature falls below a minimum set limit: this
will prevent the unit from going into low pressure alarm, so avoiding having to manually restart the machine.
At the same time, the control will enable a digital output that can be used for activating an auxiliary heat source.
When the external air temperature returns above the set threshold temperature, the unit will automatically
resume operation without it being necessary to do anything.
Stopping of the unit due
For units equipped with integrated pump, the pump will always be kept running so as to prevent ice formation
ARU to temperatures below the
and ensure correct reading of the temperature and antifreeze safety probes at all times.
operating limit
The stopping temperature must be set based on the set point temperature and in accordance with what is al-
lowed by the operating limits of the machine.
With the default programming, the limit that considers a production of outgoing water at 45°C is set, therefore
-7°C for standard units and -10°C for A, A+, SLN and A/SLN units.
The same function can be used to set an external air temperature below which to use an alternative heat source
because it is more efficient or economically more advantageous.
Night Shift System This accessory is applied to high efficiency /LN version units with speed adjuster or to SLN units.
In the day time band, which is normally the one with the highest heat load, priority is given to efficiency and
therefore the machine works with a fan control curve that maximises the EER. In this time band, therefore, the
unit is a high efficiency low noise machine (equivalent to A/LN or A+/LN)
NSS
In the night time band, priority goes to keeping down the noise of the machine and therefore the control
implements a reduction of the air flow rate using a specific speed adjuster control curve. So in this time band,
the unit is a super low noise machine (equivalent to SLN).
The time bands can be set from the control depending on installation requirements.
Heater for electrical control Electric heaters are positioned inside the electrical control panel and these prevent the formation of ice or
SQE panel condensation inside it.
OTHER ACCESSORIES
Rubber anti-vibration These allow you to reduce the vibrations transmitted from the unit to the surface it is standing on. Accessory
AG mounts supplied with the unit.
Spring anti-vibration These allow you to reduce the vibrations transmitted from the unit to the surface it is standing on. Accessory
AM mounts supplied with the unit.
The e-coated microchannel coils are treated by immersion of the whole exchanger in an emulsion of organic
resins, solvents, ionic stabilisers and deionised water. This is all subjected to a suitable electric field that causes
the formation of a solid, uniform deposit on the exchanger. The function of this deposit will be to protect the
aluminium from corrosion without penalising its thermophysical properties.
The choice of whether or not to treat the exchanger should be made with regard to the environment in which
the unit is to be installed and through observation of other structures and machinery with exposed metal sur-
faces present in the destination environment.
The cross observation criterion is the most valid method of selection currently available without having to carry
out preliminary tests or measurements with instruments. The identified reference environments are:
• marine coastal
• industrial
• urban with a high housing density
• rural
Please note that in cases where different conditions co-exist, even for short periods, the choice must be suit-
MCHE E-coated microchannel coil able for preserving the exchanger in the harsher environmental conditions and not in conditions between the
worst and best situation.
Particular attention must be given to cases where an environment that is not particularly aggressive becomes
aggressive as a consequence of a local and/or temporal concomitant cause such as, for example, due to the
presence of a heating flue outlet or an industrial kitchen or a solvent extraction fan in a small craft business.
Protective treatment of the exchanger is strongly recommended if at least one of the points below is verified:
• there are obvious signs of corrosion of the exposed metal surfaces in the installation area
• the distance from the coast is less than 20 km
• the prevailing winds come from the sea towards the unit
• the environment is industrial with a significant concentration of pollutants
• the environment is urban with a high population density
• the environment is rural with the presence of organic discharges and effluents.
For installations within a kilometre of the coast, the use of Cu/Al coils with anti-corrosion treatment is strongly
recommended for cooling only units too. This accessory is not available for HP version units.
RAAL Cu/Al coils This accessory uses finned pack coils with copper tubes and aluminium fins instead of microchannel coils.
This accessory uses finned pack coils with copper tubes and aluminium fins pre-painted with an anti-corrosion
ALPR Pre-painted aluminium coil treatment. This accessory is available only for HP version units.
14
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
The treatment is applied exclusively to finned pack coils with copper tubes and aluminium fins and consists of
aluminium passivation and coating with a polyurethane base; a double layer of paint, of which the first pas-
sivates the aluminium and acts as primer and the second is a polyurethane based surface coating. The product
has high resistance to corrosion and all environmental conditions.
The choice of whether or not to treat the exchanger should be made with regard to the environment in which
the unit is to be installed and through observation of other structures and machinery with exposed metal sur-
faces present in the destination environment.
The cross observation criterion is the most valid method of selection currently available without having to carry
out preliminary tests or measurements with instruments. The identified reference environments are:
• marine coastal
• industrial
• urban with a high housing density
• rural
Coil treated with anti-cor- Please note that in cases where different conditions co-exist, even for short periods, the choice must be suit-
ANTC rosion paints able for preserving the exchanger in the harsher environmental conditions and not in conditions between the
worst and best situation.
Particular attention must be given to cases where an environment that is not particularly aggressive becomes
aggressive as a consequence of a local and/or temporal concomitant cause such as, for example, due to the
presence of a heating flue outlet or an industrial kitchen or a solvent extraction fan in a small craft business.
Protective treatment of the exchanger is strongly recommended if at least one of the points below is verified:
• there are obvious signs of corrosion of the exposed metal surfaces in the installation area
• the distance from the coast is less than 20 km
• the prevailing winds come from the sea towards the unit
• the environment is industrial with a significant concentration of pollutants
• the environment is urban with a high population density
• the environment is rural with the presence of organic discharges and effluents.
For chiller units, this accessory also includes the “Cu/Al coil” accessory.
The unit is delivered so that it can be disassembled easily on site if this makes the installation operations easier.
A unit requested with this option is supplied:
• screwed instead of riveted
Partially assembled con-
PREA struction
• with plugged and not welded pipes
• without refrigerant charge
• untested
• covered by the warranty only if reassembled and screwed together by personnel authorized by the factory
Special pallet/skid for con- The unit is placed on a skid that makes the container loading and unloading operations easier. The accessory
SLIT tainer shipment is mandatory if shipping by container is required
Steel sections for container With this accessory, steel sections are fitted on the machine for loading into container.
PRAC shipment If this accessory is requested, loading is only into container and must compulsorily be carried out at the factory.
To protect the elements of the hydraulic circuit (in particular, the exchangers), there are Y filters that can stop
and settle the particles that are normally present in the water flow and would otherwise settle in the more
delicate parts of the hydraulic circuit and damage its heat exchange capacity.
FW Water filter
Installation of the water filter is mandatory even when it is not supplied as an accessory.
Accessory supplied with the unit.
15
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
1. External air temperature 35°C; user-side heat exchanger inlet-outlet water temperature 12-7°C. Values compliant with standard EN 14511
2. External air temperature 7°C DB, 6°C WB; user-side heat exchanger inlet-outlet water temperature 40-45°C. Values compliant with standard EN 14511
3. Sound power levels calculated according to ISO 3744
4. Sound pressure levels measured at a distance of 10 metres from the unit in free field and directivity factor Q=2
5. The reading refers to the basic unit with microchannel coils
6. The reading refers to the basic unit with Cu/Al coils
7. The reading refers to the unit without pumps, tank or recovery Refer to the specific dimensional drawing if the unit is configured
16
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
1. External air temperature 35°C; user-side heat exchanger inlet-outlet water temperature 12-7°C. Values compliant with standard EN 14511
2. External air temperature 7°C DB, 6°C WB; user-side heat exchanger inlet-outlet water temperature 40-45°C. Values compliant with standard EN 14511
3. Sound power levels calculated according to ISO 3744
4. Sound pressure levels measured at a distance of 10 metres from the unit in free field and directivity factor Q=2
5. The reading refers to the basic unit with microchannel coils
6. The reading refers to the basic unit with Cu/Al coils
7. The reading refers to the unit without pumps, tank or recovery Refer to the specific dimensional drawing if the unit is configured
17
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
1. External air temperature 35°C; user-side heat exchanger inlet-outlet water temperature 12-7°C. Values compliant with standard EN 14511
2. External air temperature 7°C DB, 6°C WB; user-side heat exchanger inlet-outlet water temperature 40-45°C. Values compliant with standard EN 14511
3. Sound power levels calculated according to ISO 3744
4. Sound pressure levels measured at a distance of 10 metres from the unit in free field and directivity factor Q=2
5. The reading refers to the basic unit with microchannel coils
6. The reading refers to the basic unit with Cu/Al coils
7. The reading refers to the unit without pumps, tank or recovery Refer to the specific dimensional drawing if the unit is configured
18
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
1. External air temperature 35°C; user-side heat exchanger inlet-outlet water temperature 12-7°C. Values compliant with standard EN 14511
2. External air temperature 7°C DB, 6°C WB; user-side heat exchanger inlet-outlet water temperature 40-45°C. Values compliant with standard EN 14511
3. Sound power levels calculated according to ISO 3744
4. Sound pressure levels measured at a distance of 10 metres from the unit in free field and directivity factor Q=2
5. The reading refers to the basic unit with microchannel coils
6. The reading refers to the basic unit with Cu/Al coils
7. The reading refers to the unit without pumps, tank or recovery Refer to the specific dimensional drawing if the unit is configured
19
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
1. External air temperature 35°C; user-side heat exchanger inlet-outlet water temperature 12-7°C. Values compliant with standard EN 14511
2. External air temperature 7°C DB, 6°C WB; user-side heat exchanger inlet-outlet water temperature 40-45°C. Values compliant with standard EN 14511
3. Sound power levels calculated according to ISO 3744
4. Sound pressure levels measured at a distance of 10 metres from the unit in free field and directivity factor Q=2
5. The reading refers to the basic unit with microchannel coils
6. The reading refers to the basic unit with Cu/Al coils
7. The reading refers to the unit without pumps, tank or recovery Refer to the specific dimensional drawing if the unit is configured
20
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
1. External air temperature 35°C; user-side heat exchanger inlet-outlet water temperature 12-7°C. Values compliant with standard EN 14511
2. External air temperature 7°C DB, 6°C WB; user-side heat exchanger inlet-outlet water temperature 40-45°C. Values compliant with standard EN 14511
3. Sound power levels calculated according to ISO 3744
4. Sound pressure levels measured at a distance of 10 metres from the unit in free field and directivity factor Q=2
5. The reading refers to the basic unit with microchannel coils
6. The reading refers to the basic unit with Cu/Al coils
7. The reading refers to the unit without pumps, tank or recovery Refer to the specific dimensional drawing if the unit is configured
21
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
Unit Size 43.6 47.6 50.7 53.8 58.8 62.8 67.9 70.9 74.10 78.10 80.12 87.12 93.12
TETRIS 2
Max. absorbed power kW 218,1 240,0 250,8 261,6 290,8 320,0 338,1 360,0 370,8 400,0 392,4 436,2 480,0
Max. absorbed current A 337,5 381,6 386,4 391,2 450,0 508,8 528,3 572,4 577,2 636,0 586,8 675,0 763,2
Max. inrush current A 588 632 637 619 701 760 779 823 828 887 814 926 1.014
Max. inrush current with soft-starter A 464 508 513 510 577 636 655 699 704 763 705 802 890
Rated power of standard fan n° x kW 6 x 2,0 6 x 2,0 7 x 2,0 8 x 2,0 8 x 2,0 8 x 2,0 9 x 2,0 9 x 2,0 10 x 2,0 10 x 2,0 12 x 2,0 12 x 2,0 12 x 2,0
Rated current of standard fan n° x A 6 x 4,3 6 x 4,3 7 x 4,3 8 x 4,3 8 x 4,3 8 x 4,3 9 x 4,3 9 x 4,3 10 x 4,3 10 x 4,3 12 x 4,3 12 x 4,3 12 x 4,3
Rated power of EC fan n° x kW 6 x 1,9 6 x 1,9 7 x 1,9 8 x 1,9 8 x 1,9 8 x 1,9 9 x 1,9 9 x 1,9 10 x 1,9 10 x 1,9 12 x 1,9 12 x 1,9 12 x 1,9
Rated current of EC fan n° x A 6 x 2,9 6 x 2,9 7 x 2,9 8 x 2,9 8 x 2,9 8 x 2,9 9 x 2,9 9 x 2,9 10 x 2,9 10 x 2,9 12 x 2,9 12 x 2,9 12 x 2,9
Rated power of EC OVS fan n° x kW 6 x 3,0 6 x 3,0 7 x 3,0 8 x 3,0 8 x 3,0 8 x 3,0 9 x 3,0 9 x 3,0 10 x 3,0 10 x 3,0 12 x 3,0 12 x 3,0 12 x 3,0
Rated current of EC OVS fan n° x A 6 x 4,5 6 x 4,5 7 x 4,5 8 x 4,5 8 x 4,5 8 x 4,5 9 x 4,5 9 x 4,5 10 x 4,5 10 x 4,5 12 x 4,5 12 x 4,5 12 x 4,5
Power supply V/ph/Hz 400/3~/50
Power supply for auxiliary circuits V/ph/Hz 230-24/1~/50
22
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
23
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
COOLING HEATING
valid for sizes
10.2, 16.2, 24.3, 32.4, 33.4, 37.4, 41.4, 47.6, 62.8, 70.9, 78.10, 93.12
LW FSA FU FSA
20 60
user-side water outlet temperature (°C)
INV GLY
45
5
40
BK
0
35
-5 30
-10 25
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45
external air temperature (°C) external air temperature (°C)
15 55
50
10 FU (HP)
45
5
40
GLY
0
BK
35
-5 30
-10 25
25 30 35 40 45 50 55 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45
recovery water outlet temperature (°C) external air temperature (°C)
FSA (Fan Speed Adjuster): in the area indicated by the arrow, it is mandatory to include the ”Fan speed adjuster” or ”EC fans” accessory.
LW (Less Wind): in the area indicated by the arrow, the unit can work only if there is no wind.
FU (Forced Unloading): in the indicated area, the control could actuate a forced capacity reduction of the compressors so as to prevent tripping of the safety devices.
FU (HP) (Forced Unloading): in the indicated area, the control could actuate a forced capacity reduction of the compressors so as to prevent tripping of the safety
devices. To operate in this area the unit has to be equipped with the advanced controller.
INV (INVerter pump on user side): the use of the ”Inverter pump on user side” accessory is allowed only in the area indicated by the arrow. For different conditions,
please contact our sales department.
GLY (GLYcol): for SET point temperatures below 5°C, it is mandatory to use suitable percentages of antifreeze additives (glycols) to prevent ice formation in the
exchanger.
BK (Brine Kit): for SET point temperatures below 3°C, it is mandatory to use the ”Brine Kit” accessory.
24
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
COOLING HEATING
valid for sizes
23.2
LW FSA HAT FSA
60
user-side water outlet temperature (°C)
INV GLY
45
5
40
BK
0
35
-5
30
-10
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 25
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45
external air temperature (°C) external air temperature (°C)
FSA
20 60
user-side water outlet temperature (°C)
15 55
50
10 FU
45
5
40
GLY
0
BK
35
-5 30
-10 25
25 30 35 40 45 50 55 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45
recovery water outlet temperature (°C) external air temperature (°C)
FSA
60
user-side water outlet temperature (°C)
55
50
FU
45
40
35
30
25
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45
external air temperature (°C)
FSA (Fan Speed Adjuster): in the area indicated by the arrow, it is mandatory to include the ”Fan speed adjuster” or ”EC fans” accessory.
LW (Less Wind): in the area indicated by the arrow, the unit can work only if there is no wind.
FU (Forced Unloading): in the indicated area, the control could actuate a forced capacity reduction of the compressors so as to prevent tripping of the safety devices.
INV (INVerter pump on user side): the use of the ”Inverter pump on user side” accessory is allowed only in the area indicated by the arrow. For different conditions,
please contact our sales department.
GLY (GLYcol): for SET point temperatures below 5°C, it is mandatory to use suitable percentages of antifreeze additives (glycols) to prevent ice formation in the
exchanger.
BK (Brine Kit): for SET point temperatures below 3°C, it is mandatory to use the ”Brine Kit” accessory.
25
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
COOLING HEATING
valid for sizes
8.2, 13.3, 18.4, 23.5, 27.6
LW FSA HAT FSA
60
user-side water outlet temperature (°C)
INV GLY
45
5
40
BK
0
35
-5 FU
30
-10
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 25
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45
external air temperature (°C) external air temperature (°C)
FSA
20 60
user-side water outlet temperature (°C)
15 55
50 FU
10
45
5
40
GLY
0
BK
35
-5 30
-10 25
25 30 35 40 45 50 55 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45
recovery water outlet temperature (°C) external air temperature (°C)
FSA
60
user-side water outlet temperature (°C)
55
50
45 FU
40
35
30
25
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45
external air temperature (°C)
FSA (Fan Speed Adjuster): in the area indicated by the arrow, it is mandatory to include the ”Fan speed adjuster” or ”EC fans” accessory.
LW (Less Wind): in the area indicated by the arrow, the unit can work only if there is no wind.
FU (Forced Unloading): in the indicated area, the control could actuate a forced capacity reduction of the compressors so as to prevent tripping of the safety devices.
INV (INVerter pump on user side): the use of the ”Inverter pump on user side” accessory is allowed only in the area indicated by the arrow. For different conditions,
please contact our sales department.
GLY (GLYcol): for SET point temperatures below 5°C, it is mandatory to use suitable percentages of antifreeze additives (glycols) to prevent ice formation in the
exchanger.
BK (Brine Kit): for SET point temperatures below 3°C, it is mandatory to use the ”Brine Kit” accessory.
26
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
(1) Rated flow rate with 35°C air and 12/7°C water conditions
27
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
HP /DS /ST 1P
HP /DS /ST 2P
HP /DS /ST 3P
/DC /ST 1PS
/DC /ST 2PS
/DC /ST 3PS
/DS /ST 1P
/DS /ST 2P
/DS /ST 3P
HP /DS
HP /DC
BASIC
/DC
/DS
HP
10.2 ! ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! " ! ! - ! " - ! " -
12.2 ! ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! " ! ! - ! " - ! " -
1 13.2 ! ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! " ! ! - ! " - ! " -
15.2 ! ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! " ! ! - ! " - ! " -
16.2 ! ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! " ! ! - ! " - ! " -
20.3 ! ! ! ! ! - ! ! - " " - ! ! - " " - ! ! " ! ! - ! ! - " " -
24.3 ! ! ! ! ! - ! ! - " " - ! ! - " " - ! ! " ! ! - ! ! - " " -
2 27.4 ! ! ! ! - ! ! - ! " - " ! - ! " - " ! ! " ! - ! ! - ! " - "
29.4 ! ! ! ! - ! ! - ! " - " ! - ! " - " ! ! " ! - ! ! - ! " - "
32.4 ! ! ! ! - ! ! - ! " - " ! - ! " - " ! ! " ! - ! ! - ! " - "
33.4 ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! ! " ! - ! ! - ! ! - !
37.4 ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! ! " ! - ! ! - ! ! - !
3 41.4 ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! ! " ! - ! ! - ! ! - !
43.6 ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! ! " ! - ! ! - ! ! - !
47.6 ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! ! " ! - ! ! - ! ! - !
50.7 ! ! ! ! - ! " - " " - " " - " " - " ! ! " ! - ! " - " " - "
53.8 ! ! ! ! - ! " - " " - " " - " " - " ! ! " ! - ! " - " " - "
4 - - - - - - - -
58.8 ! ! ! ! ! " " " " " " " " ! ! " ! ! " " " "
62.8 ! ! ! ! - ! " - " " - " " - " " - " ! ! " ! - ! " - " " - "
67.9 ! ! ! ! - ! " - " " - " " - " " - " ! ! " ! - ! " - " " - "
70.9 ! ! ! ! - ! " - " " - " " - " " - " ! ! " ! - ! " - " " - "
5 - - - - - - - -
74,10 ! ! ! ! ! " " " " " " " " ! ! " ! ! " " " "
78,10 ! ! ! ! - ! " - " " - " " - " " - " ! ! " ! - ! " - " " - "
80.12 ! ! ! ! - ! " - " " - " " - " " - " ! ! " ! - ! " - " " - "
6 87.12 ! ! ! ! - ! " - " " - " " - " " - " ! ! " ! - ! " - " " - "
93.12 ! ! ! ! - ! " - " " - " " - " " - " ! ! " ! - ! " - " " - "
! = Version possible
" = Version not possible
28
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
/DS /ST 1P
/DS /ST 2P
/DS /ST 3P
HP /DC
HP /DS
BASIC
/DC
/DS
HP
1 11.2 ! ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! " ! ! - ! " - ! " -
17,2 ! ! ! ! ! - ! ! - " " - ! ! - " " - ! ! " ! ! - ! ! - " " -
2 - - - - - - - -
23,2 ! ! ! ! ! ! ! " " ! ! " " ! ! " ! ! ! ! " "
28,4 ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! ! " ! - ! ! - ! ! - !
3 34,4 ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! ! " ! - ! ! - ! ! - !
38,4 ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! ! " ! - ! ! - ! ! - !
43,4 ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! ! " ! - ! ! - ! ! - !
4 - - - - - - - -
47,4 ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! " ! ! ! ! ! !
50,6 ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! ! " ! - ! ! - ! ! - !
5 - - - - - - - -
57,6 ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! " ! ! ! ! ! !
64.6 ! ! ! ! - ! ! - ! ! - ! ! - ! ! - ! ! ! " ! - ! ! - ! ! - !
6 - - - - - - - -
70.6 ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! " ! ! ! ! ! !
/DS /ST 1P
/DS /ST 2P
/DS /ST 3P
HP /DC
HP /DS
BASIC
/DC
/DS
HP
! = Version possible
" = Version not possible
29
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
10.2 87 55 86 54 85 53 84 52 85 53 82 50 73 41 66 34 89 57
12.2 87 55 86 54 85 53 84 52 85 53 82 50 73 41 66 34 89 57
13.2 87 55 86 54 85 53 84 52 85 53 82 50 73 41 66 34 89 57
15.2 88 56 87 55 86 54 85 53 85 53 83 51 74 42 67 35 89 57
16.2 88 56 87 55 86 54 85 53 85 53 83 51 74 42 67 35 89 57
20.3 91 59 90 58 89 57 88 56 88 56 85 53 77 45 70 38 92 60
24.3 91 59 90 58 89 57 88 56 88 56 85 53 77 45 70 38 92 60
27.3 94 62 93 61 92 60 91 59 91 59 88 56 80 48 73 41 95 63
29.4 94 62 93 61 92 60 91 59 91 59 88 56 80 48 73 41 95 63
32.4 95 63 94 62 93 61 92 60 92 60 89 57 81 49 74 42 96 64
33.4 96 64 95 63 94 62 93 61 93 61 90 58 82 50 75 43 97 65
37.4 96 64 95 63 94 62 93 61 93 61 90 58 82 50 75 43 97 65
41.4 96 64 95 63 94 62 93 61 93 61 90 58 82 50 75 43 97 65
43.6 96 64 95 63 94 62 93 61 93 61 90 58 82 50 75 43 97 65
47.6 96 64 95 63 94 62 93 61 93 61 90 58 82 50 75 43 97 65
50.7 97 65 96 64 95 63 94 62 94 62 91 59 83 51 76 44 98 66
53.8 99 67 98 66 97 65 96 64 95 63 93 61 85 53 77 45 100 68
58.8 99 67 98 66 97 65 96 64 95 63 93 61 85 53 77 45 100 68
62.8 99 67 98 66 97 65 96 64 95 63 93 61 85 53 77 45 100 68
67.9 99 66 98 65 97 64 96 63 95 62 93 60 85 52 77 44 100 67
70.9 99 66 98 65 97 64 96 63 95 62 93 60 85 52 77 44 100 67
74.10 100 67 99 66 98 65 97 64 96 63 94 61 86 53 78 45 101 68
78.10 100 67 99 66 98 65 97 64 96 63 94 61 86 53 78 45 101 68
80.12 101 68 100 67 99 66 98 65 97 64 95 62 87 54 79 46 102 69
87.12 101 68 100 67 99 66 98 65 97 64 95 62 87 54 79 46 102 69
93.12 101 68 100 67 99 66 98 65 97 64 95 62 87 54 79 46 102 69
Declared data with 35°C air and 12/7°C water inlet/outlet conditions
Lw: sound power value based on measurements made in accordance with ISO 3744 and the Eurovent certification programme. This certification refers specifically to the sound power
level in dB(A). This is therefore the only acoustic reading to be considered binding.
Lp: mean sound pressure level, measured at 10 metres from the unit, in free field on a reflecting surface. Non binding value obtained from the sound power level
30
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
10.2 86 54 82 50 84 52 84 52 82 50 74 42 66 34 59 27 86 54
12.2 86 54 82 50 84 52 84 52 82 50 74 42 66 34 59 27 86 54
13.2 86 54 82 50 84 52 84 52 82 50 74 42 66 34 59 27 86 54
15.2 87 55 83 51 85 53 85 53 82 50 75 43 67 35 60 28 86 54
16.2 87 55 83 51 85 53 85 53 82 50 75 43 67 35 60 28 86 54
20.3 88 56 85 53 86 54 86 54 83 51 76 44 69 37 62 30 87 55
24.3 89 57 87 55 87 55 87 55 84 52 76 44 69 37 62 30 88 56
27.3 90 58 87 55 88 56 88 56 85 53 77 45 70 38 63 31 89 57
29.4 91 59 87 55 89 57 88 56 86 54 77 45 70 38 63 31 90 58
32.4 92 60 88 56 90 58 90 58 87 55 79 47 72 40 65 33 91 59
33.4 93 61 89 57 91 59 91 59 88 56 80 48 73 41 66 34 92 60
37.4 93 61 89 57 91 59 91 59 88 56 80 48 73 41 66 34 92 60
41.4 94 62 90 58 92 60 92 60 89 57 81 49 74 42 67 35 93 61
43.6 94 62 90 58 92 60 92 60 89 57 81 49 74 42 67 35 93 61
47.6 94 62 90 58 92 60 92 60 89 57 81 49 74 42 67 35 93 61
50.7 95 63 91 59 93 61 93 61 90 58 82 50 75 43 68 36 94 62
53.8 96 64 92 60 94 62 94 62 91 59 83 51 76 44 69 37 95 63
58.8 96 64 92 60 94 62 94 62 91 59 83 51 76 44 69 37 95 63
62.8 96 64 92 60 94 62 94 62 91 59 83 51 76 44 69 37 95 63
67.9 97 64 93 60 95 62 95 62 93 60 84 51 77 44 70 37 96 63
70.9 97 64 93 60 95 62 95 62 93 60 84 51 77 44 70 37 96 63
74.10 98 65 94 61 96 63 96 63 92 59 85 52 78 45 70 37 97 64
78.10 99 66 95 62 97 64 97 64 93 60 86 53 79 46 71 38 98 65
80.12 100 67 96 63 98 65 98 65 94 61 87 54 80 47 72 39 99 66
87.12 100 67 96 63 98 65 98 65 94 61 87 54 80 47 72 39 99 66
93.12 100 67 96 63 98 65 98 65 94 61 87 54 80 47 72 39 99 66
Declared data with 35°C air and 12/7°C water inlet/outlet conditions
Lw: sound power value based on measurements made in accordance with ISO 3744 and the Eurovent certification programme. This certification refers specifically to the sound power
level in dB(A). This is therefore the only acoustic reading to be considered binding.
Lp: mean sound pressure level, measured at 10 metres from the unit, in free field on a reflecting surface. Non binding value obtained from the sound power level
31
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
11.2 76 44 66 34 77 45 79 47 79 47 83 51 75 43 65 33 86 54
17.2 71 39 62 30 77 45 79 47 83 51 84 52 78 46 71 39 88 56
23.2 68 36 68 36 82 50 86 54 86 54 81 49 76 44 72 40 89 57
28.4 77 45 67 35 80 48 82 50 84 52 86 54 79 47 72 40 90 58
34.4 74 42 65 33 80 48 82 50 86 54 87 55 81 49 74 42 91 59
38.4 73 41 64 32 80 47 83 51 87 54 87 54 81 48 73 41 91 59
43.4 77 45 72 39 82 50 87 55 87 55 84 51 79 47 76 44 91 58
47.4 71 38 71 38 85 52 89 56 89 56 84 51 79 47 75 43 92 59
50.6 76 43 66 34 82 49 84 52 88 56 89 56 83 50 76 43 93 61
57.6 75 43 66 34 82 49 85 52 89 56 88 56 82 50 75 43 93 61
64.6 79 47 74 41 84 52 89 57 89 57 86 54 81 49 79 46 93 61
70.6 72 40 72 40 86 54 90 58 90 58 85 53 81 48 77 44 93 61
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
11.2 73 41 63 31 74 42 75 43 75 43 79 47 71 39 62 30 82 50
17.2 67 35 59 27 73 41 75 43 79 47 80 48 74 42 68 36 84 52
23.2 65 33 65 33 78 46 82 50 82 50 77 45 73 41 69 37 85 53
28.4 73 41 64 32 76 44 78 46 80 48 82 50 76 44 69 37 86 54
34.4 70 38 62 30 76 44 79 47 82 50 83 51 77 45 71 39 87 55
38.4 70 37 61 29 76 44 79 47 83 50 83 50 77 44 70 37 87 55
43.4 74 41 68 36 78 46 83 51 83 51 80 48 75 43 73 40 87 54
47.4 68 35 67 35 81 48 84 52 85 52 80 48 76 43 72 39 88 55
50.6 72 40 63 31 78 46 80 48 84 52 85 52 79 46 72 40 89 57
57.6 72 39 63 31 78 45 81 48 85 52 84 52 79 46 72 39 89 57
64.6 76 43 70 38 80 48 85 53 85 53 82 50 78 45 75 42 89 57
70.6 69 37 69 37 82 50 86 53 86 54 82 49 77 45 73 41 89 57
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
11.2 70 38 61 29 71 39 72 40 72 40 76 44 69 37 60 28 79 47
17.2 66 34 57 25 71 39 74 42 77 45 78 46 72 40 66 34 82 50
23.2 63 31 62 30 75 43 79 47 79 47 75 43 70 38 67 35 82 50
28.4 71 39 62 30 74 42 76 44 78 46 80 48 74 42 67 35 84 52
34.4 69 37 60 28 74 42 77 45 80 48 81 49 75 43 69 37 85 53
38.4 68 36 60 27 74 42 77 45 81 48 81 48 75 42 68 36 85 53
43.4 72 39 66 34 76 44 81 48 81 48 78 45 73 41 71 38 85 52
47.4 65 33 65 33 78 46 82 49 82 49 78 45 73 41 70 37 85 53
50.6 70 38 62 29 76 44 78 46 82 50 83 50 77 44 71 38 87 55
57.6 70 38 62 29 76 44 79 46 83 50 82 50 77 44 70 37 87 55
64.6 74 41 68 36 78 45 83 50 83 50 80 47 75 43 73 40 87 54
70.6 67 35 67 35 80 47 84 51 84 51 79 47 75 42 71 39 87 55
Declared data with 35°C air and 12/7°C water inlet/outlet conditions
Lw: sound power value based on measurements made in accordance with ISO 3744 and the Eurovent certification programme. This certification refers specifically to the sound power
level in dB(A). This is therefore the only acoustic reading to be considered binding.
Lp: mean sound pressure level, measured at 10 metres from the unit, in free field on a reflecting surface. Non binding value obtained from the sound power level
32
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
8.2 62 30 60 28 75 43 75 43 80 48 74 42 72 40 66 34 83 51
13.3 62 30 60 28 76 44 77 45 83 51 76 44 73 41 66 34 85 53
18.4 76 44 66 34 77 45 79 47 79 47 83 51 75 43 65 33 86 54
23.5 66 34 64 32 79 47 79 47 84 52 78 46 76 44 71 39 87 55
27.6 71 39 62 30 77 45 79 47 83 51 84 52 78 46 71 39 88 56
31.4 76 43 66 34 82 49 84 52 88 56 89 56 83 50 76 43 93 61
36.4 76 43 66 34 82 49 84 52 88 56 89 56 83 50 76 43 93 61
41.5 95 63 91 59 93 61 93 61 90 58 82 50 75 43 68 36 94 62
44.6 96 64 92 60 94 62 94 62 91 59 83 51 76 44 69 37 95 63
49.6 96 64 92 60 94 62 94 62 91 59 83 51 76 44 69 37 95 63
54.6 96 64 92 60 94 62 94 62 91 59 83 51 76 44 69 37 95 63
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
8.2 61 29 56 24 74 42 75 43 77 45 66 34 65 33 59 27 79 47
13.3 61 29 56 24 75 43 77 45 79 47 68 36 66 34 59 27 81 49
18.4 64 32 59 27 77 45 79 47 80 48 69 37 68 36 63 31 82 50
23.5 65 33 60 28 78 46 79 47 81 49 70 38 69 37 64 32 83 51
27.6 65 33 60 28 79 47 80 48 82 50 72 40 70 38 64 32 84 52
31.4 68 36 68 36 82 50 86 54 86 54 81 49 76 44 72 40 89 57
36.4 68 36 68 36 82 50 86 54 86 54 81 49 76 44 72 40 89 57
41.5 77 45 67 35 80 48 82 50 84 52 86 54 79 47 72 40 90 58
44.6 74 42 65 33 80 48 82 50 86 54 87 55 81 49 74 42 91 59
49.6 73 41 64 32 80 47 83 51 87 54 87 54 81 48 73 41 91 59
54.6 73 41 64 32 80 47 83 51 87 54 87 54 81 48 73 41 91 59
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
8.2 60 28 52 20 73 41 74 42 73 41 57 25 57 25 51 19 76 44
13.3 60 28 52 20 74 42 76 44 75 43 60 28 58 26 51 19 78 46
18.4 63 31 55 23 76 44 78 46 76 44 60 28 60 28 55 23 79 47
23.5 64 32 56 24 77 45 78 46 77 45 61 29 61 29 56 24 80 48
27.6 64 32 56 24 78 46 79 47 78 46 63 31 62 30 56 24 81 49
31.4 73 41 64 32 76 44 78 46 80 48 82 50 76 44 69 37 86 54
36.4 73 41 64 32 76 44 78 46 80 48 82 50 76 44 69 37 86 54
41.5 70 38 62 30 76 44 79 47 82 50 83 51 77 45 71 39 87 55
44.6 89 57 87 55 87 55 87 55 84 52 76 44 69 37 62 30 88 56
49.6 89 57 87 55 87 55 87 55 84 52 76 44 69 37 62 30 88 56
54.6 89 57 87 55 87 55 87 55 84 52 76 44 69 37 62 30 88 56
Declared data with 35°C air and 12/7°C water inlet/outlet conditions
Lw: sound power value based on measurements made in accordance with ISO 3744 and the Eurovent certification programme. This certification refers specifically to the sound power
level in dB(A). This is therefore the only acoustic reading to be considered binding.
Lp: mean sound pressure level, measured at 10 metres from the unit, in free field on a reflecting surface. Non binding value obtained from the sound power level
33
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 10.2,12.2,13.2,15.2,16.2 CH-HP-LN (ST)-1P-2P A4F849-A
34
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 10.2,12.2,13.2,15.2,16.2 CH-HP-LN -1PS-2PS A4F850-A
35
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 20.3,24.3,27.4,29.4,32.4 CH-HP-LN -(ST)-1P-2P-3P-1PS-2PS-3PS A4F851-A
36
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 33.4,37.4,41.4,43.6,47.6 CH-HP-LN -(ST)-1P-2P-3P-1PS-2PS-3PS A4F852-A
37
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 50.7 - 93.12 CH- HP- LN- (ST) A4F853-A
38
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 50.7 - 93.12 CH- HP- LN- ST 1P-3P A4F854-A
39
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 50.7 - 93.12 CH- HP- LN- ST 1PS-3PS A4F855-A
40
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 A / TETRIS 2 SLN 11.2 CH-HP-LN (ST)-1P-2P A4F860-A
41
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 A / TETRIS 2 SLN 11.2 CH-HP-LN -1PS-2PS A4F861-A
42
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 A / TETRIS 2 SLN 17.2,23.2 CH-HP-LN -(ST)-1P-2P-3P-1PS-2PS-3PS A4F862-A
43
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 A / TETRIS 2 SLN 28.4 - 70.6 CH-HP-LN -(ST)-1P-3P-1PS-3PS A4F863-A
44
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 A+ / TETRIS 2A SLN 8.2 - 70.6 CH-HP-LN (ST)-1P-2P A4F173 - A
45
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 A+ / TETRIS 2A SLN 8.2 - 70.6 CH-HP-LN -1PS-2PS A4F174 - A
46
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 A+ / TETRIS 2A SLN 13.3,18.4 CH-HP-LN -(ST)-1P-3P-1PS-3PS A4F175 - A
47
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
DIMENSIONAL DIAGRAMS
TETRIS 2 A+ / TETRIS 2A SLN 23.5 - 54.6 CH-HP-LN -(ST)-1P-3P-1PS-3PS A4F176 - A
48
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
TETRIS 2
49
Blue Box reserves the right to alter specifications. www.blueboxgroup.com
10214100902_Tetris 2_28-08-2015