TROVIS 6400 Automation System

TROVIS 6493 Compact Controller

For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch)

Application
Digital controller to automate industrial and process plants for
general and more complex control tasks. Suitable for control
of continuous, on/off or pulsing final control elements (pneu-
matic actuators with i/p positioners, additional electric actua-
tors, electric heating systems, refrigerating machines etc.)

By setting the functions and parameters, the controller can be


adapted to a control task quickly.
The controller settings are saved in a non-volatile memory, ®

even when the power supply fails.


Electronics from SAMSON
Special features
•• Configuration using the controller keys or the TROVIS-
VIEW 4 software
•• Two analog inputs with filtering, root extraction, function
generation and signal monitoring
•• One binary input with selectable function
•• Two relay outputs for on/off or three-step output or limit
alarms
•• One transistor output for fault alarms
•• Infrared interface for configuration
•• Plug-on screw terminals
•• Degree of protection (front) IP 65
•• Two internal set points and one external set point (fixed set
point control and follow-up control)
•• Set point ramp and output ramp
•• Control signal limitation
•• Linking of input variables (addition, subtraction)
•• Operation with code number or control key locking by bi-
nary input

Fig. 1: TROVIS 6493 Compact Controller

Edition July 2015

Data Sheet T 6493 EN


Inputs and outputs (Fig. 2) One analog output
Two analog inputs The controller output is issued at the analog output by default.
Optionally, an input signal (e.g. controlled variable, external
One input is used for the controlled variable. The second input
set point) or error signal can be issued. The output can be
can be used for the external set point, disturbance variable,
configured as:
position feedback of an actuator or as an input for differential
control. Both inputs can be configured as: –– 0 to 20 mA, 4 to 20 mA
–– 0 to 20 mA, 4 to 20 mA –– 0 to 10 V, 2 to 10 V
–– 0 to 10 V, 2 to 10 V Two relay outputs
–– Resistance thermometers Pt 100, Pt  1000, Ni 100, Ni 1000 The relays are double-throw contacts and can be used either
–– Potentiometer 1 kΩ as on/off outputs, three-step outputs or for status and limit
alarms.
One binary input
One transistor output
The binary input is activated by a voltage signal (4 to
31 V DC) and can be used as follows: The isolated transistor output issues the collective fault alarm.
If an internal fault exists or the configured signal monitoring of
–– Activation of the constant output value
the inputs responds, the externally connected voltage signal (3
(e.g. for enabling control)
to 50 V DC, max. 30 mA) is generated.
–– Set point switchover
One supply output
–– Start the set point ramp or output ramp
The supply output can be used to supply a voltage (20 V DC,
–– Manual/automatic switchover
max. 45 mA) to either a two-wire transmittter or the binary in-
–– Locking the control signal put.
–– Activatation of the relay outputs
–– Control key locking

mA, V TROVIS 6493


Pt 100
Analog IN 1 Y mA, V Analog output
Pt 1000
inputs
Ni 100 IN 2
Ni 1000 Relay outputs
Pot. 1 k 3-step
ON/OFF PWM 3-step PWM
BO 1
Binary input Limit alarms On/off or three-step
BI 1
output
BO 2

Interface TROVIS-
VIEW IR Transistor output

BO 3 Fault alarm

Supply voltage
Supply output

Fig. 2: Wiring diagram (inputs and outputs)

2 T 6493 EN
Operation (Fig. 3)
The controller is operated using six keys whose functions de-
pend on the selected level. 1

Operating level
After the compact controller is switched on, it runs in automat-
ic mode. The display shows the operating level with the con-
trolled variable and set point readings. The selector key (8)
can be used to switch the reading on the bottom row of the
Xd% 2
display (2): internal set point W or W2, external set point
WE, manipulated variable Y or error signal Xd%. The internal
W
set points W and W2 can be changed by pressing the cursor
keys (4 and 5).

Setup and parameter levels


Press the enter key (7) to access the setup and parameter lev- 3
els. In these levels, the compact controller is adapted to its 8
control task by configuring the functions and setting the pa-
9
rameters. The functions are arranged in hierarchical levels. 4
The cursor keys (4 and 5) are used to navigate to levels, sub- 7
levels, functions and parameters and the enter key (7) to open
them. Changes to settings are confirmed by pressing the enter
5
key (7). The user can return at any time to the next level by 6
pressing the escape key (6). The functions blocks, parameters
and calibration values can be protected by a key code against
unauthorized access.
1 Label (exchangeable) 5 Cursor key
TROVIS-VIEW 4 Software 2 Display (decrease, scroll back-
wards)
The infrared interface (Fig. 4) at the front allows the compact 3 Manual/automatic key
6 Escape key
controller to be configured and operated using SAMSON's 4 Cursor key
TROVIS-VIEW 4 software installed on a computer. (increase, scroll forwards) 7 Enter key
The TROVIS-VIEW software can be downloaded free of 8 Selector key
charge from our website (u www.samson.de > Services > 9 Infrared interface
Software > TROVIS-VIEW). The software can also be supplied Fig. 3: Operation
on a CD-ROM on request (order no. 6661, configuration ID
2938759). Refer to the Data Sheet u T 6661 for details on
the system requirements.
The compact controller can communicate with a PC over its in-
frared interface on the front of the controller next to the yellow
enter key. An infrared adapter (order no. 8864-0900) is re-
quired for data transmission between the serial RS-232 inter- Bracket
face on the PC and infrared interface on the controller. A (order no. 1400-9769)
bracket (order no. 1400-9769) ensures that the adapter is
properly aligned in front of the controller. The infrared adapt-
er can be connected to the USB port of the computer using the Infrared adapter
USB/RS-232 adapter (order no. 8812-2001). (order no. 8864-0900)

Connector to RS-
232 port of a PC

Fig. 4: Connecting an infrared adapter

T 6493 EN 3
Technical data
Inputs
Analog input IN1 Two analog inputs, optionally for controlled variable X or external set point WE
Analog input IN2 0/4 to 20 mA or 0/2 to 10 V,
resistance thermometer Pt 100, Pt 1000, Ni 100, Ni 1000 or
potentiometer 1 kΩ
Input for current and Signal range 0/4 to 20 mA or 0/2 to 10 V
voltage Maximum permissible values Current ±50 mA, voltage ±25 V
Internal resistance Current Ri = 50 Ω, voltage Ri = 20 kΩ
Permissible common mode 0 to 5 V
voltage
Error Zero < 0.2 %, span < 0.2 %, linearity < 0.2 %
Temperature influence < 0.1 %/10 K for zero and span (based on 20 °C)
Resolution < 0.0024 mA (< 0.012 % with 0 to 20 mA)
(< 0.015 % with 4 to 20 mA)
< 1.2 mV (< 0.012 % with 0 to 10 V)
Transmitter supply Acc. to DIN IEC 381 (NAMUR NE 06) 20 V DC, max. 45 mA, resistant to short
circuiting
Resistance thermometer For sensor Pt 100, Pt 1000 acc. to DIN EN 60751
Ni 100, Ni 1000 acc. to DIN 43760
Nominal measuring range Pt 100, Pt 1000: –100 to 500 °C
Ni 100, Ni 1000: –60 to 250 °C
Wire resistance Three-wire RL1 = RL2 = RL3 < 15 Ω
Error Zero < 0.2 %, span < 0.2 %, linearity < 0.2 %

Pt 100, Pt 1000 (in the range Zero < 0.1 %, span < 0.1 %, linearity < 0.1 %
between –40 and 150 °C)
Temperature influence < 0.2 %/10 K for zero and span (based on 20 °C)
Resolution < 0.04 °C  (< 0.007 % at –100 to 500 °C)
Potentiometer Nominal value 1 kΩ, three-wire
Wire resistance RL < 15 Ω per wire
Error Zero < 0.2 %, span < 0.2 %
Temperature influence Zero < 0.1%/10 K, span < 0.2 %/10 K (based on 20 °C)
Resolution < 0.07  (< 0.007 %)
Binary input Switching contact
– with external supply 24 V DC (4 to 31 V DC) or
– powered by the controller over terminals 14, 15 (20 V DC)
Signal state OFF with 0 to 2 V
Signal state ON with 4 to 31 V
Current consumption < 6.0 mA with 24 V DC
< 5.5 mA with 20 V DC
Outputs Continuous-action, on/off or three-step output
Analog output Signal range 0(4) to 20 mA; load < 740 Ω
0(2) to 10 V; load > 3 kΩ
Maximum modulation range 0 to 22 mA, 0 to 11 V
Error < 0.2 %
Temperature influence Zero < 0.1%/10 K, span < 0.1 %/10 K
Resolution < 0.0015 mA (< 0.0075 % with 0 to 20 mA)
(< 0.0094 % with 4 to 20 mA)
< 0.75 mV (< 0.0075 % with 0 to 10 V)
Binary output BO1 Two relays with floating switching contact,
Binary output BO2 max. 250 V AC, max. 250 V DC, max. 1 A AC, max. 0.1 A DC, cos Q = 1
Spark suppression Connected in series C = 2.2 nF and varistor 300 V AC, in parallel to each re-
lay contact
Binary output BO3 for fault alarms Isolated transistor output,
external supply 3 to 50 V DC, max. 30 mA

4 T 6493 EN
Infrared interface
Transmission protocol SAMSON-specific protocol (SSP)
Transmission rate 9600 bit/s
Angle of reflected beam 50°
Distance IR adapter – controller Max. 0.7 m
General specifications
Display Backlit LCD
Reading range –999 to 9999; start value, end value and decimal separator can be adjusted
Configuration Functions saved in read-only memory for fixed set point and follow-up control,
one control circuit
Supply voltage 90 to 250 V AC; 47 to 63 Hz
24 V AC/DC (20 to 30 V AC/DC), 47 to 63 Hz
Power consumption 13 VA (90 to 250 V AC), external fuse > 630 mA (slow)
  7 VA (24 V AC/DC), external fuse > 1.25 A (slow)
Temperature 0 to 50 °C (ambient)
–20 °C to 70 °C (storage and transport)
Mechanical environmental Sinusoidal vibrations acc. to    2 to    9 Hz; amplitude 3.5 mm
testing for storage, IEC 60068-2-6    9 to 200 Hz; acceleration 10 m/s²
transportation and operation 200 to 500 Hz; acceleration 15 m/s²
Random vibrations acc. to 1.0 m²/s³;   10 to   200 Hz
IEC 60068-2-64 0.3 m²/s³; 200 to 2000 Hz
Shocks acc. to IEC 60068-2- Acceleration 100 m/s²; duration 11 ms
27
Degree of protection IP 65 (front), IP 30 (housing), IP 00 (terminals) according to EN 60529
Device safety Acc. to EN 61010-1: Protection class II
Overvoltage category II
Degree of contamination 2
Design and testing according to EN 61010
Electromagnetic compatibility Requirements according to EN 61000-6-2, EN 61000-6-3 and EN 61326-1
Electrical connection 1.5 mm² screw terminals
Scanning time ≤ 80 ms
Weight Approx. 0.5 kg

Compliance ·

Dimensions in mm (inch)

Panel cut-out 45+0.6 x 92+0.8 (1.77+0.023 x 3.622+0.0315)

158 (6.18)
48 (1.89) 10 142 (5.59)
91,5 (3.60)
96 (3.78)

Fig. 5: Dimensions in mm (inch)

T 6493 EN 5
Electrical connection

Current Current Voltage Resistance Potentiometer


Two-wire thermometer
transmitter
Pt 100/Pt 1000
0/4...20 mA 4...20 mA 0/2...10 V Ni 100/Ni 1000 1000 Ω

Three-wire Two-wire Three-wire Two-wire


+
11 100 % 100 %
– + –
Analog input 12 ϑ ϑ
IN1 + –
13 0% 0%

14
Supply output
20 V, max. 45 mA 15 +

17 +
100 % 100 %
Analog input + –
19 ϑ ϑ
IN2
– + –
20 0% 0%
+ +
31
Analog output – –
32

81 + +
Binary input
24 V DC –
BI1 82 –
Binary + –
83 3...50 V DC,
output
84 max. 30 mA
BO3

Supply L L L/+
(90...250 V AC) 24 V AC/DC (20...30 V)
voltage N N N/–

Three-step output On/off Binary output Limit relay


for electric actuator output
41
Binary
output 42 L L BO1 LIM 1
BO1 +
43 L'(+)

51
Binary N
output 52 BO2 LIM 2
BO2 –
53

Fig. 6: Electrical connection

Article code Accessories

Compact controller TROVIS 6493-032 x Accessories Order no.

Supply voltage 90 to 250 V AC 4 CD-ROM with TROVIS-VIEW 4 6661,


software............................................ Var.-ID 2938759
24 V AC/DC 5

Infrared adapter (RS-232)................... 8864-0900

Bracket for infrared adapter................ 1400-9769

USB/RS-232 adapter......................... 8812-2001

6 T 6493 EN
T 6493 EN 7
Specifications subject to change without notice
2015-12-11 · English