Makelsan Ups Powerack Se RT Series 1 10 Kva User Manual en
Makelsan Ups Powerack Se RT Series 1 10 Kva User Manual en
Powerpack SE
RT Series
1 - 10 KVA
Powerpack SE RT SERIES 1-10 KVA
USER MANUAL
Powerpack SE
RT Series
1 - 10 KVA
UDD-SD-123
This manual is prepared for the users of Powerpack SE RT Series 1-3 kVA.
Companion Manuals
For further information about this device and its options, please visit www.makelsan.com.tr
Updates
Please visit www.makelsan.com.tr for updates. Always use the latest manuals.
Shipment
Carrying vehicles or handling accessories must have enough features and characteristics to carry
UPS’s weight.
Be more careful of sudden movements, especially when batteries are inside of cabinet.
CONTENTS
1 SAFETY INSTRUCTIONS
The power output voltage may still have 220V or 120V even not connect to the mains power.
For the battery cable or power cord replacement, please contact our service station or
dealer to purchase, in order to avoid fire caused by inadequate capacity or heat ignition.
Do not place the battery or battery pack in the fire, which will injure due to explosion.
Please do not open the UPS case as you will, there is risk of electric shock
Do not touch the battery connection terminals. Battery loop and input voltage loop is without
isolation, which may cause high voltage risk between the battery terminal and ground.
Do not connect to the equipment like hair dryer or electric heater, to ensure the safety for the
UPS
2 INSTALLATION INSTRUCTIONS
Open the UPS package, please check the enclosed accessories including a user manual,
communication cable, support feet, CD-ROM. The long-back model also includes the cable for
connection to battery bank.
Check the UPS if any damage in transport. If find it’s damaged or parts missing, do not
power on, please turn to the carrier and dealer.
To determine whether this UPS is the model you want to buy. Check the model name
showed both on the front panel and rear panel of UPS to confirm.
NOTE:
Please save the packaging box and packaging materials for future transport use. As heavy
product, please transit the UPS with care.
The UPS installation environment must be with good ventilation, away from water, flammable
gases and corrosive entities.
Do not lie down the UPS against the wall so that front and side panel air intake hole, rear panel
air outtake hole will be unobstructed.
The peripheral environment temperature around the UPS should be within 0 ℃ ~ 40 ℃.
If dismantling the machine at low temperatures, there may be condensation droplets, users
can not install or operate it before UPS completely got dry both inside and outside, otherwise
there will be danger of electric shock.
Place the UPS near the mains socket to cut off AC mains without any delay at any emergent
case.
ATTENTION:
Make sure the load behind the UPS is off when users connect the load to UPS, and then turn on
the load one by one later.
Please connect the UPS with the socket which is over-current protected. Do not connect the
UPS with the socket which rated current is less than the Maximum input current of the UPS.
All the power socket should be configured with earthling device for safety.
UPS could be electrified or powered no matter the input power cable is tied or not, even when
the UPS is off. The only way to cut off the output is switching off the UPS, disable the EPO and
disconnecting the mains power supply.
For all standard type UPS, it is advised to charge the battery over 8 hours before used. Once the
AC mains power energizes the UPS, it will automatically charge the battery. Without prior
charging, UPS output remains as usual but with shorter back-up time than normal.
When connected to motor, display equipment, laser printer etc, UPS power selection should be
based on the startup power of the load which is usually twice as rated power.
NOTE:
Following diagrams take the type of 0.9PF for example, the type of 0.8PF is similar.
2.3.1 The Type of 120V (Output could be 100V, 110V, 115V, 127V)
A. Standard Model
2 3 4 2 11 7 8
5 6
RE SE T
T
O
OUT
R E SE T
R E S ET
FUSE 250VAC 35A
EPO RESET
T
TEL/MODEM/FAX
INTELLIGENT SLOT
O
R E SE T
+
INTELLIGENT SLOT
RS232
INPUT OUTPUT
EXT.BATTERY
RS232
24VDC 40A
EPO
FUSE 125VAC,15A
USB
RESET L N N L
+
EXT.BATTERY
72VDC 40A
USB
-
IN
-
IN OUT OUTPUT SOCKET
INPUT
OUTPUT SOCKET
TEL/MODEM/FAX
9 1 10 8 7 9 10 6 5 4
B. Long-Run Model
9 2 3 4 7
2 3 4 5 6
ON
INTELLIGEN T SLO T
RE S ET
EPO
T
O
+
RE S ET
INTELLIGENT SLOT
RS232
RS232
EXT.BATTERY
24VDC 40A
FUSE 125VAC,15A
RESET
EPO
USB
USB INP UT OUTP UT OFF
L N L N
-
IN OUT
INPUT
OUTPUT SOCKET
TEL/MODEM/FAX
11 5 8 6
9 1 10 8 7
2 10 3 4 6 9 9
OUT
R E SE T
T
O
DC OUTPUT DC OUTPUT
RE SE T
RS232
TEL/MODEM/FAX
INPUT OUTPUT
FUSE 125VAC,35A
RESET L N N L
USB
+ 72VDC - + 72VDC -
EPO
IN
INTELLIGENT
+ 72VDC 40A - OUTPUT SOCKET SLOT
EXT.BATTERY
9 11 8 5 7
2.3.2 The Type of 220V (Output could be 208V, 210V, 220V, 230V, 240V)
A. Standard Model
2 4 5 6 8 3 7 1 2
INTELLIGENT SLOT
RESET
EPO
R E SE T
T
IN
O
+
R ES T
T
RS232
EXT.BATTERY
O
INTELLIGENT SLOT
24VDC 40A
R E SE T
TEL/MODEM/FAX
FUSE 250VAC,8A
RESET USB INPUT FUSE 250VAC,20A
RESET
-
RS232
IN
OUT
INPUT
+ -
EPO
USB
TEL/MODEM/FAX 48VDC 40A
EXT.BATTERY
OUTPUT SOCKET
9 1 10 3 8 7 6 5 4 10 9
8 3 7 1 2
ON
INTELLIGENT SLOT
INTELLIGENT SLOT
R E SE T
IN
T
O
RS232
R E SE T
TEL/MODEM/FAX
EPO
USB
RESET
INPUT OUTPUT OFF
L N L N
RS232
OUT
EPO
USB
EPO
USB
+ 72VDC 40A -
EXT.BATTERY
OUTPUT SOCKET
6 5 4 10 9 11 5 8 6
B. Long-Run Model
2 4 5 6
2 1 4 6
RE SET
EPO
T
O
E
RE S T
+
OUT
RE SET
RS232
EXT.BATTERY
INTELLIGENT SLOT
24VDC 40A
T
O
RE SET
FUSE 250VAC,8A
RS232
RESET
TEL/MODEM/FAX
USB
FUSE 250VAC,15A INPUT
-
RESET
USB
OUTPUT SOCKET IN OUT
EPO
IN
INPUT TEL/MODEM/FAX
INTELLIGENT
+ 48VDC 40A - SLOT
EXT.BATTERY
OUTPUT SOCKET
9 1 10 3 8 7 9 10 8 5 7
9 2 3 4 7
2 1 4 6
ON
INTELLIGENT SLOT
R E SE T
OUT
T
O
RE SET
RS232
TEL/MODEM/FAX
RS232
EPO
USB
INTELLIGENT
+ 72VDC 40A - SLOT
EXT.BATTERY
OUTPUT SOCKET
9 10 8 3 5 7 6
11 5 8
NOTE:
Diagrams take the type of 0.9PF for example, the type of 0.8PF is similar. Due to the technology
upgrading and development, goods and diagrams might have some differences.
Output connection of 1~10KVA type is configured with sockets or terminal blocks, users can
plug the load cable into the UPS socket to energize the load as below. Make sure the mains wire
and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of
electric shock or fire.
NOTE:
To the type of 6-10KVA, do not use the wall receptacle as the input power source for the UPS,
which rated current is less than the UPS’s maximum input current. Otherwise the receptacle may
be burned and destroyed.
E
RE S T
ON
T
O
RE SE T
FUSE 125VAC,20A
INPUT OUTPUT Over Current
/MODEM/
RESET
L N N L
Protector
IN
Battery
Input output
LOAD
Input output
For different UPS type, users are instructed to configure different battery voltage as below
sheet. More or less units are forbidden, or else something abnormal or faulty will appear.
One end of battery cable is for UPS terminals while the other end with triple cables is for
battery terminals. Correct installation procedure is highly vital or else probable electric shock
will arise. Users are strictly required to follow the below procedure.
UDD-SD-123/ Release Date: 16.01.2015/Rev No: 1 /Rev. Date: 20.05.2015
12
Powerpack SE RT SERIES 1-10 KVA
Connect battery in
n correct waay and makee sure the to
otal battery voltage
v is avvailable for UPS.
U
Correcctly connectt the long baattery cable to battery terminals
t firrst, red wiree is to posittive plate
while black is to negative.
n If users conneect the UPS first, electrric shock or other dangger could
not be avoided.
Beforee connectingg load after UPS,
U users should supplly main pow
wer to UPS and energizee it.
Connect long batteery cable to UPS termin
nals with corrrect poles link
(red iss for “+”, blacck is for“-”),, UPS will staart the charging work automaticall
a y.
+ - + -
R E SE T
RED
T
O
R E SE T
FUSE 125VAC,20A
IN
NPUT OUTPUT
+
RESET
L N N L B
BLACK
- + -
+ - + -
Battery
B
2.6 Installation
UPS in
nstallation work
w d comply with local eleectrical stan
should ndard and o
only can be done by
professional techn
nician. 1KVA ower connection.
A~3KVA uniits could usee wall socket as input po
For alll type UPS, it
i is advised t battery over 8 hourrs before the first use. Once
d to charge the O the
t UPS, it will chargee the battery automaticcally. Witho
AC maains power energizes the out prior
charging, UPS outp
put remainss as usual bu
ut with shorrter back up time than n
normal.
ation steps:
Installa
1. Pleasse take out two
t groups of support feet from paackage, asseemble by em
mbedding th
hem with
each other as shoown below.
3. It also can be placed horizontally without support feet if you like, please remember not to put
the machine upside down. Please lie it down carefully and make sure the main power is off.
4. Machine and battery pack, can be put together, as two ways are showed in the pictures below,
the battery pack should be put under the machine. The battery pack is heavy, be careful when
you move it.
Inverter LED
Battery LED
Bypass LED
Warning LED
VAC
E
LIN
HZ
OUTPUT
25% 50% 75% 100%
ON/OFF ROTATE
TEST/MUTE
※ ON/OFF key ( + )
Press and hold this key for more than half a second to turn on/off the UPS.
※ TEST/MUTE key ( + )
Press and hold the key for more than 1 second in mains mode or economical mode: UPS runs the
self-test function.
Press and hold the key for more than 1 second in battery mode: UPS runs the mute function.
※ ROTATE key ( + )
Press and hold and for more than half a second (less than 2 seconds): Change the
direction to display items.
VAC
E
LIN
Press and hold keys
HZ
OUTPUT
for more than half a
second.
25% 50% 75% 100%
ON/OFF ROTATE
TEST/MUTE
picture.
HZ
OUTPUT
E
LIN
ON/OFF ROTATE
TEST/MUTE
After finishing that, the machine can be placed flat, as shown in the picture below.
E
LIN
※ INQUIRING key ( , )
Non-function setting mode:
1) Press and hold or for more than half a second (less than 2 seconds): display the items
orderly.
2) Press and hold for more than 2 seconds: Circularly and orderly display the items every 2
seconds, when press and hold the key for some time again, it will turn to output status.
From left to right is inverter LED, battery LED, bypass LED and warning LED.
Warning red LED is on: UPS fault. For example: Overload beyond the allowed time, inverter fault,
BUS fault, over temperature fault etc.
Bypass yellow LED is on: UPS is alarming. For example: Bypass mode supply power and etc.
Battery yellow LED is on: UPS is alarming. For example: Battery mode supply power and etc.
Inverter green LED is on: UPS is normally powered by mains or ECO mode or battery mode.
PS: LED display detail in different mode is listed in 5 items.
1. The top diagram is for load, battery, fan, fault and buzzer icon. When UPS is over loaded, the load
light will blink as same as the battery light blinks when the capacity of battery gets low or battery
is disconnected. The left icon and right icon are for load and battery capacity indication, each grid
of which represents 25%.
2. The fan icon is for fan working indication; when fan normally runs, the icon will display rotation; if
the fan is not connecting or faulty, the icon blinks;
3. Press the mute button under the battery mode, buzzer icon will blink; it will disappear under
other cases.
4. Fault icon will be on when UPS on fault mode, otherwise it will not.
VAC
E
LIN
Battery capacity
Load capacity
display area
display area
HZ
100%
Working mode
display area
Under none setting mode, it will display UPS output information when UPS normally runs in AC
mode; other information like input, battery, load and temperature will be showed after
pressing the inquiring key; Fault code will be told in fault mode.
Under setting mode, user could adjust different output voltage as well as activate ECO and
BYPASS mode by operating function setting key and inquiring keys.
After over 20 seconds, this area will display the working mode of the machine. e.g. STDBY(Standby
Mode), BYPASS(Bypass Mode), LINE(AC mode), BAT(Battery mode), BATT(Battery Self Test Mode ),
ECO(Economic Mode), SHUTDN(Shutdown Mode).
When UPS is on line mode, press and hold the self-test/mute key for more than 1 second,
LED light and go out circularly and orderly. UPS comes to self-test mode and tests its status. It
will exit automatically after finishing testing, LED resume.
When UPS is on battery mode, press and hold the self-test/mute key for more than 1 second,
the buzzer stops beeping. If you press and hold the self-test/mute key for one more second, it
will restart to beep again.
UPS has setting function. It can run the setting on any mode. After setting, it will become
effective at once when meets some standards. The set information can be saved only when the
battery connected and normally turning off the UPS.
Enter the setting interface. Press and hold the function setting key for more than 2
seconds, then come to setting interface, the letters “ECO” will flash.
Enter the ECO setting interface. Press and hold the function setting key for more than half
a second(less than 2 seconds), then come to setting interface of ECO, at this time, the letters
“ECO” will light for a long time. The “ON” (or OFF) will flash. Press and hold the inquiring key(
, )for more than half a second (less than 2 seconds) to determine whether the ECO
function is used or not. If used, the corresponding word is “ON”, if not, the word is “OFF”. It can
be determined by yourself.
Confirm the ECO selecting interface. After selecting ON or OFF, press and hold the function
setting key for more than half a second (less than 2 seconds). Now, the ECO setting
function is completed and the “ON” or “OFF” will light without flash.
Exit from the setting interface. Press and hold function setting key for more than 2
seconds, exit from the setting interface and turn to main interface.
E
LIN
Enter the setting interface. Press and hold the function setting key for more than 2
seconds, then come to setting interface, Press and hold the function setting key for more
than half a second(less than 2 seconds), select the function setting, choose the bypass output
interface, at the moment, the letters “BPS” will flash.
Enter the Bypass output selecting interface. Press and hold the function setting key for
more than half a second(less than 2 seconds), then come to setting interface of BPS, at this
time, the letters “BPS” will light for a long time. The “ON” letter will flash. Press and hold the
inquiring key( , )for more than half a second (less than 2 seconds) to determine
whether the BPS function is used or not. If used, the corresponding word is “ON”, if not, the
word is “OFF”. It can be determined by yourself.
Confirm the Bypass output selecting interface. After selecting ON or OFF, press and hold the
function setting key for more than half a second (less than 2 seconds), Now, the BPS
setting function is completed and the “ON” or “OFF” will light without flash.
Press and hold function setting key for more than 2 seconds, exit from the setting
interface and return to main interface.
After setting BPS as ON, when mains power plugged in without turning on the UPS or no mains
power plugged in, there is bypass output but no power down backup function.
VAC
E
LIN
E
LIN
HZ
INPUT 25% 50% 75% 100%
25% 50% 75% 100%
Enter the setting interface. Press and hold the function setting key for more than 2
seconds, then come to setting interface, Press and hold the inquiring key( , )for
more than half a second(less than 2 seconds), select the function setting, choose output voltage
setting interface, at the moment, the letters “OPU” will flash.
Enter the output voltage selecting interface. Press and hold the function setting key for
more than half a second(less than 2 seconds), then come to setting interface of output voltage
OPU, at this time, the letters “OPU” will light for a long time. The numerical value below the
OPU will flash. Press and hold the inquiring key( , ) for more than half a second (less
than 2 seconds), select the numerical value in accordance with “OPU” function. The provided
voltages are 100, 110V, 115V, 120V, 127V or 208V, 210V, 220V, 230V, 240V, you can choose
anyone by yourself.
Confirm the output voltage selecting interface. After selecting numerical value, press and hold
the function setting , for more than half a second (less than 2 seconds). Now, the OPU
setting function is completed and the numerical value will light without flash.
Exit from the setting interface. Press and hold function setting key for more than half a
second (less than 2 seconds), exit from the setting interface and return to main interface.
LIN
LIN
Enter the setting interface. Press and hold the function setting key for more than 2
seconds, then come to setting interface, Press and hold the inquiring key( , )for
more than half a second(less than 2 seconds), select the function setting, choose battery
voltage setting interface, at the moment, the letters “bat” will flash.
Enter the battery voltage selecting interface. Press and hold the function setting key for
more than half a second(less than 2 seconds), then come to setting interface of battery voltage,
at this time, the letters “bat” will light for a long time. The numerical value below the “bat” will
flash. Press and hold the inquiring key( , ) for more than half a second (less than 2
seconds), select the numerical value in accordance with “battery” function. The provided
voltages are 10V, 10.2V, 10.5V, numbers stand for the voltage of each battery, you can choose
anyone by yourself (The default is 10V), anyone has been chosen, the machine will shutdown
when its battery voltage achieve the voltage which you chose.
Confirm the battery voltage selecting interface. After selecting numerical value, press and hold
the function setting , for more than half a second (less than 2 seconds). Now, the battery
setting function is completed and the numerical value will light without flash.
Exit from the setting interface. Press and hold function setting key for more than half a
second (less than 2 seconds), exit from the setting interface and return to main interface.
Press and hold the inquiring key or for more than half a second(less than 2 seconds) to
inquire about items. The inquired items include input, battery, output, load, temperature. The
displayed items on LCD screen are showed as following:
Output:Display the output voltage and output frequency of the UPS. As the following picture
shows, the output voltage is 120V or 220V, the output frequency is 50Hz.
VAC VAC
E
E
LIN
LIN
HZ HZ
OUTPUT OUTPUT
25% 50% 75% 100% 75%
25 % 50% 100 %
Load: Display the numerical value of the active power (WATT) and apparent power (VA) of the
load. For example, as the following graphics shows: the WATT of the load is 800W or 900W, VA
is 1000VA (when disconnect load, it is a normal phenomenon to show a small numerical value of
WATT and VA). or 900W
2 5% 5 0% 7 5% 1 00%
25% 50% 75% 100%
W W
E
E
LIN
LIN
KVA KVA
LOAD LOAD
Temperature: Display the maximum temperature of the components in the UPS. As the
following picture shows: the maximum temperature is 40℃.
2 5% 50% 75 % 1 00 %
E
LIN
℃
TEMP
25 % 50% 7 5% 1 00 %
Input: Display the voltage and frequency of the input. As the following picture shows: the input
voltage is 120V or 220V, input frequency is 50Hz.
VAC VAC
E
E
LIN
LIN
HZ HZ
INPUT INPUT
25% 50% 75% 100% 2 5% 50 % 7 5% 1 00 %
Battery: Display the voltage and capacity of the battery (determined by type). As the following
picture shows: the battery voltage is 24V or 36V, the capacity of battery is 100%(the capacity of
battery is approximately reckoned according to the battery voltage).
VDC VDC
E
E
LIN
LIN
% %
BATTERY BATTERY
Press and hold the inquiring key for more than 2 seconds, LCD begins to display the items
circularly and orderly which transfer to another every 2 seconds. Press and hold the key for
some time again within 30s, it will return to output status.
Bypass yellow LED is on, the buzzer beeps once every 2 minutes. The warning red LED is on
when beeping, LCD displays are according to the exact load and battery capacity.
Turn to bypass mode under the following two conditions:
Turn off the UPS on line mode while start the bypass output.
Overload on line mode.
NOTE:
When UPS is working on bypass mode, it has no back up function.
LED indications on front panel on line mode are as following: The inverter green LED is on.
When input AC is in the range of working conditions, UPS will work on line mode.
LED indications on front panel on battery mode are as following: both the inverter green LED
and battery yellow LED are on, the buzzer beeps once every 4 seconds. The warning red LED is
on when beeping.
When the AC power is low or unstable, UPS will turn to battery mode at once.
LED indications on front panel on ECO mode are as following: both the inverter green LED and
bypass yellow LED are on.
When the input mains meets the input range of the ECO mode and start the ECO function, the
UPS will works on ECO mode. If input AC exceeds the range of ECO several times in a row in a
minute but stays in inverter input range, UPS will work on AC inverting mode automatically.
LED indications on front panel on Fault mode are as following: warning red LED is on and LCD
display fault code and related icon.
At the moment, you can press the mute key to make the buzzer stop beeping temporarily to wait
for maintenance. You can also press the OFF key to shut down the UPS when confirm that there
is no serious fault.
2 Battery mode
Battery voltage - One beep /
● ● ★
normal 4 sec
Warning for
One beep /
abnormal voltage ● ★ ★
sec
of battery
3 Bypass mode
Mains power –
normal(under One beep /
● ★
2 mins
Bypass)
6 TROUBLE SHOOTING
When the system runs in failure mode, the LCD will show as below:
Fault icon
LT
FAU
Fault code
ATTENTION: When the output is short-circuited, the action of the protection of the UPS will
show up. Before turning off the UPS, please make sure to disconnect the entire load and cut off
the AC mains power supply, otherwise will make the AC input short-circuit.
8 NETWORK COMMUNICATION
This series UPS offer intelligent network interface with a dedicated Ethernet card (optional
accessory), realizing network communication and management. For more information about
this function, please turn to our local distributor or service center.
NOTE:
The communication function is only realizable with the specific communion cable from the
supplier.
Rs232 interface is set as below:
Bit rate: 2400bps
Byte: 8bit
Completion code: 1bit
Bit Pattern: None
EMS
IEC61000-4-2(ESD) Level 4
IEC61000-4-3(RS) Level 3
IEC61000-4-4(EFT) Level 4
IEC61000-4-5(Suege) Level 4
EMI
GB9254-1998/IEC 62040-2 Class B
Turn on Overload
DC Battery
Display LCD/LED
WOIB / 12 13
Weight (Kg) Standard
WIB 12 14.5 28 33 33 /
Battery pack / 17 23 23 28
Long 440×468×88
TCP/IP
This model UPS can supply one Intelligent Slot at the rear panel, which was compatible with
most of the software and hardware all of the world, such as running HP open view, IBM net
view, SUN net manager and other operation system. UPS is with function login on internet
supplying information of UPS status and input power, and even capable of controlling UPS via
net management system.
For more information, please turn to local supplier or distributor.
10 GUARANTEE
10.1 Terms of Guarantee
Our products are under a two-year guarantee starting from the date of delivery against
malfunctions resulting from production, material and workmanship faults. Malfunctions
due to such type of faults will be removed without claiming any price of workmanship or
spare parts to be replaced.
Whether aforementioned malfunctions originate from usage faults or not are determined
with a report to be issued by service stations, if there exists no service stations, by one of
seller, dealer, agency, representative, importer or manufacturer or producer of those
products respectively.
Repair time of defective products is twenty business days at most. This period starts
from the date when products are delivered to one of seller, dealer, agency,
representative, importer or one of manufacturer or producer. Provided that products
break down within the period of guarantee, the time passing during the repair process is
added to the guarantee time. Provided that faults of products cannot be removed within
ten business days, manufacturer-producer or importer is obliged to assign another
product having similar features for the use of consumers until the faulty product has
been repaired.
Even though consumers exercise their repair rights, they can claim free replacement of
products, refund or price discount at the rate of faultin the events;
That, besides, the product,as of the date when the product is delivered to
the consumer, breaks down four times a year or six times within the
guarantee period to be determined by the manufacturer-producer and/or
importer at least, on the condition of being in guarantee period, such
malfunctions perpetuate passing over;
That maximum time required for the repair of products is exceeded;
That repair of the malfunction is determined as impossible through a
report to be issued by service station, if there exists no service station,
one of seller, dealer, agency, representative, importer or manufacturer or
producer of the company respectively.
The consumer is, on demand, obliged to submit guarantee certificate in terms of repairs
or replacements within the scope of guarantee.
It is essential that you definitely perform damage control over external packaging before
receiving the products to be sent through freight. In the event of any damage, delivery
Repairs of plug-and-play products in the places where no service point is around are
performed in the factory of MAKELSAN or the nearest service point according to the
direction to be made by the MAKELSAN head office. Defective product is delivered by
hand to the nearest service point or to the contracted freight company in its original
packaging to be sent to the factory of MAKELSAN according to the direction to be made
by the MAKELSAN head office. For malfunctions in the scope of guarantee, shipment fees
are under the responsibility of MAKELSAN on the condition that products are delivered
to the contracted freight company.
The device must be sent as packed in its original packaging as long as it is not desired by
the service. Original packaging of devices should be preserved in order to use them for
shipment of devices in terms of repairs to occur. Otherwise, no responsibility is assumed
with regards to any troubles to be experienced.
All defective products to be delivered by hand or through freight are to meet the
necessary shipment requirements. (Anti-static protective, bubble wrap or box etc.)It is
essential that legible barcode serial number belonging to the product be on the product.
Otherwise, it is not covered in the scope of the guarantee.
It is essential that products to be sent through freight definitely be together with delivery
note, and that serial/model/malfunction details be written on delivery note to be sent
(for example, breakdown report form), and that packaging content match with the
products specified in the delivery note. Otherwise, freight is not accepted.
The use of theGuarantee Certificate, submitted together with products with MAKELSAN
trademark,is permitted by the T.R. Ministry of Industry and Commerce and General
Directorate of Protection of Competition with no……. in accordance with the law, with no.
4077, and the notification, with no. TRKGM-95/116-117, issued basing the
aforementioned law. MAKELSAN acknowledges and undertakes to obey the liabilities
determined by the laws and legislations.
Breakdowns resulting from the use of products contrary to the issues or the
environment conditions (temperature, humidity etc.) specified in the user manual are
not covered in the scope of guarantee.
Damages and breakdowns resulting from the use of software, hardware, interface,
accessories or consumables apart from those used together with products or
recommended ones; changing place, wrong and insufficient maintenance, calibration or
In the general examination performed during the breakdown acceptance process, certain
troubles causing products not to be covered in the scope of guarantee might not be
understood. Provided that such faults come up in the detailed examination to be
performed via technical service equipment, products are returned to customers.
Products not covered in the scope of guarantee can, on demand of customer, be treated
in a fee-paying way within the bounds of possibilities of the authorized service. Products
out of the scope of guarantee, repairs of which are not possible are returned to
customers.
In the event that original serial numbers, guarantee labels and stamps on products are
removed or distorted, products are not covered in the scope of guarantee. No guarantee
is issued against the use of products for any other purpose, apart from those specified in
introduction or manual of products.
Shelf lives of VRLA batteries are 6 months under the ambient temperature of 15 °C and 3
months under the ambient temperature of 25 °C.
11 CONTACT INFORMATION
www.makelsan.com.tr
Headquarter: İstanbul Deri Organize Sanayi Bölgesi 2. Yol I -5 Parsel 34956 Tuzla/ İstanbul
Tel : 0216 428 65 80
Fax : 0216 327 51 64
E-mail : [email protected]
İzmir Office : Halkapınar Mah. 1348 Sok. 2AE Keremoğlu İş Merkezi Yenişehir – İzmir
Tel : 0232 469 47 00
Fax : 0232 449 47 00
E-mail : [email protected]
www.makelsan.com.tr
Headquarter: İstanbul Deri Organize Sanayi Bölgesi 2. Yol I -5 Parsel 34956 Tuzla/ İstanbul
Tel : 0216 428 65 80
Fax : 0216 327 51 64
E-mail : [email protected]
İzmir Office : Halkapınar Mah. 1348 Sok. 2AE Keremoğlu İş Merkezi Yenişehir – İzmir
Tel : 0232 469 47 00
Fax : 0232 449 47 00
E-mail : [email protected]