0% found this document useful (0 votes)
227 views1 page

6SL3244 0BB12 1FA0 Datasheet en

The document provides technical specifications for the SINAMICS G120 Control Unit CU240E-2 PN, including its electrical data, ambient conditions, inputs/outputs, communication capabilities, and mechanical data. Key specifications include an operating voltage of DC 24 V, power consumption of 0.5 A, support for PROFINET communication, 6 standard digital inputs, 2 digital outputs as relay contact, 2 analog inputs and outputs, and IP20 degree of protection.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
227 views1 page

6SL3244 0BB12 1FA0 Datasheet en

The document provides technical specifications for the SINAMICS G120 Control Unit CU240E-2 PN, including its electrical data, ambient conditions, inputs/outputs, communication capabilities, and mechanical data. Key specifications include an operating voltage of DC 24 V, power consumption of 0.5 A, support for PROFINET communication, 6 standard digital inputs, 2 digital outputs as relay contact, 2 analog inputs and outputs, and IP20 degree of protection.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Data sheet for SINAMICS G120 Control Unit CU240E-2 PN

Ordering data
6SL3244-0BB12-1FA0

Client order no. : Item no. :


Order no. : Consignment no. :
Offer no. : Project :
Remarks :

Electrical data Ambient conditions

Operating voltage via Ambient temperature


the Power Module DC 24 V Operation -10 ... 55 °C (14 ... 131 °F)

external power supply DC 20 ... 29 V Storage -40 ... 70 °C (-40 ... 158 °F)

Max. power consumption 0.5 A Relative humidity


Power loss 5.5 W Max. operation 95 %

Inputs/ outputs Communication


Communication PROFINET
Standard digital inputs
Number 6 Closed-loop control techniques
Switching level: 0→1 11 V V/f linear / square-law / parameterizable Yes

Switching level: 1→0 5V V/f with flux current control (FCC) Yes

V/f ECO linear / square-law


Fail-safe digital inputs Yes

Number 1 (Use of 2 × DI Standard) Sensorless vector control Yes

Vector control, with sensor No


Digital outputs
Encoderless torque control Yes
Number as relay changeover contact 2
Torque control, with encoder No

Analog/ digital inputs


Number 2 (Differential input)
Mechanical data
Degree of protection IP20
Analog outputs
Net weight 0.5 kg
Number
2 (Non-isolated output) Width 73.0 mm

Height 199.0 mm
Connections
Depth 46.0 mm
Signal cable
Conductor cross-section 0.05 ... 1.50 mm² (30 ... 16 AWG)

Technical data are subject to change! There may be discrepancies between calculated and rating plate values.