1250A CIRCUIT BREAKER
Item Manufacturer
Description Unit
No. Data
1 Manufacturer ABB
2 Place of manufacture China
3 Manufacturer reference/designation LTB145D1/B
4 Applicable standards IEC 62271-100 or equivalent
5 Type Out door, 03 poles, live tank
6 Insulating medium SF6
7 Rated voltage kV 123
8 Highest voltage kV 123
9 Rated current A 1250
10 Frequency Hz 50
Rated three phase symmetrical short-circuit breaking
11 kA rms. 31.5
current
Rated three phase symmetrical short circuit making
12 kA peak 80
current
13 Rated duration of short-circuits sec 3
14 Rated Operating Sequence O-0.3sec.-CO-3 min -CO
15 Lightning impulse withstand voltage (1.2/50us) kV peak 550
16 Power frequency withstand voltage, 50 Hz, one minute kV rms. 230
17 First-pole-to-clear factor 1.5
18 Insulator creepage distance to earth mm/kV 31
19 Rated out-of phase breaking current kA 40
20 Rated line charging breaking current A rms. 50
21 Rated cable change breaking current A rms. 160
22 Rated capacitive breaking current A rms. 400
23 Rated transient recovery voltage for terminal faults kV 249 kV
24 Operating mechanism - 3-pole or 3 single pole 3-pole
25 Operating mechanism drive type Motor Spring
Spring charged (motor/ manual) shall be provided Yes
Spring charged indicator shall be provided Yes
Mechanical operation duration: ≥ 10,000 times Yes
Rated current operation duration: ≥ 5,000 times Yes
Local/remote control switch shall be provided Yes
Anti-pumping device shall be provided Yes
Pole discrepancy device shall be provided Yes
0
26 Contact resistance at 32 C µOhm <40
27 Circuit breaker opening time ms 20~25
28 Circuit breaker closing time ms ≤40
29 Circuit breaker min. arcing time ms
(a) Terminal fault ≤25
(b) Short- line fault ≤25
30 Circuit breaker rated interrupting (break) time ms ≤40
Rated short current operation duration: ≥ 20 times
32 Minimum clearance between poles mm 1240
33 Minimum clearance to earth mm 2503
34 Total weight of complete circuit breaker kg 1840
Operation load
35 Max. impact load due to circuit breaker operation kg
1500Nm
36 Rated mechanical terminal load N N 3000
37 Number of spare auxiliary contacts
1
Item Manufacturer
Description Unit
No. Data
Normally open 12
Normally closed 12
38 Auxiliary power supply
- Heating voltage Vac 220
Tolerance range % +10/-15
- Control, closing, tripping and motor driver voltage Vdc 220
Tolerance range % +10/-10
39 Number of tripping coil 2
Number of closing coil 1
40 SF6 gas
- SF6 mass for one three-pole circuit breaker kg 5
- Rated SF6 density bar 0.5Mpa
- First threshold of SF6 density bar 0.45Mpa
- Second threshold of SF6 density bar 0.43Mpa
- Is there any monitor for SF6 gas pressure? Yes
Gas leakage rate: 0.5%/year Yes
Local control cubicle shall be provided Yes
41 HV terminal
Materials Aluminum alloy
Dimensions. mm 510*267*20mm
No . of holes. holes IEC 9+NEMA 4
Size of holes mm dia Ø14mm
Spacing of holes mm IEC 40mm NEMA 44.5mm
42 Supporting structure Yes
43 Operating conditions
o
Maximum ambient temperature C 50
Maximum relative humidity % 100
Climatic conditions Tropicalization
44 Protection lever IP55
45 Standards of quality management ISO 9001: 2008
46 Drawings Yes
47 Spare part (For each substation)
Tripping coil 1
Closing coil 2
Motor Spring 1
SF6 tank 20kg 1
2
1250A DISCONNECTOR WITH 02 EARTHING SWITCH
Item Manufacturer
Description Unit
No. Data
1 Manufacturer ABB
2 Place of manufacture China
3 Manufacturer reference/designation GW55-126DII
4 Applicable standards IEC 62271-102
Outdoor, 03 poles, center-
5 Type
break, horizontal mounting
6 Disconnector drive
- Main blade Motor and Manual
- All earthing blades (02 pcs) Comply
- Motor driver voltage Vdc 220
7 Rated voltage kV 123
8 Rated current A 1250
9 Frequency Hz 50
10 Short time withstand current (3 sec.) kArms 31.5
11 Short time withstand current (3 sec) (earth switch) kArms 31.5
12 Making current (peak, earth switch only) kA peak 80
Rated short-circuit duration s 3
13 Lighting impulse withstandvoltage (1.2/50us)
- line to earth kV peak 550
- across open disconnector kV peak 630
- between phases kV peak 550
14 Power frequency withstand voltage (1 min.)
- line to earth kV rms 230
- across open disconnector kV rms 265
- between phases kV rms 230
15 Type of operating mode Three phase group operation
16 Minimum creepage distance mm 31mm/kV
17 Rated mechanical terminal load kN 3
0
18 Contact resistance of blade at 32 C <100
19 Number of auxiliary contacts of DS
- normally open 8
- normally closed 8
20 Number of auxiliary contacts of ES
- normally open 6
- normally closed 6
Number of limit contacts of DS
- normally open
2NO+2NC (1NO+1NC for
customer, 1NO+1NC for
- normally closed
operation circuit)
21 Minimum clearance
- between live parts and earth mm 1220
- between phases mm 2200
- across open disconnector mm refer drawing
22 Auxiliary power supply
- Heating voltage Vac 220
Tolerance range % +10/-10
- Motor driver of DS, interlocking coil of ES Vdc 220
Tolerance range % +10/-15
- Control, closing & tripping voltage Vdc 220
Tolerance range % +10/-15
1
Item Manufacturer
Description Unit
No. Data
Overload protection, over current protection for Motor
Yes
driver shall be provided.
Local control cubicle shall be provided Yes
23 Total weight of 3-pole unit kg 1295
24 HV terminals
- Material alluminum
- Dimensions, mm 100*190
- Holes - No. , size and spacing mm 4-M12+4-φ14
25 Electrical interlocking coil for DS and ES yes
Mechanical interlocking for DS and ES Yes
26 Operating conditions
o
Maximum ambient temperature C 50
Maximum relative humidity % 100
Climatic conditions Tropicalization
27 Standards of quality management ISO 9001: 2008
28 Supporting structure Yes
29 Drawings Yes
2
1250A DISCONNECTOR WITH 01 EARTHING SWITCH
Item Manufacturer
Description Unit
No. Data
1 Manufacturer ABB
2 Place of manufacture China
3 Manufacturer reference/designation GW55-126D
4 Applicable standards IEC 62271-102
Outdoor, 03 poles, center-
5 Type
break, horizontal mounting
6 Disconnector drive
- Main blade Motor and Manual
- All earthing blades (01 pcs) Manual
- Motor driver voltage Vdc 220
7 Rated voltage kV 123
8 Rated current A 1250
9 Frequency Hz 50
10 Short time withstand current (3 sec.) kArms 31.5
11 Short time withstand current (3 sec) (earth switch) kArms 31.5
12 Making current (peak, earth switch only) kA peak 80
Rated short-circuit duration s 3
13 Lighting impulse withstandvoltage (1.2/50us)
- line to earth kV peak 550
- across open disconnector kV peak 630
- between phases kV peak 550
14 Power frequency withstand voltage (1 min.)
- line to earth kV rms 230
- across open disconnector kV rms 265
- between phases kV rms 230
15 Type of operating mode Three phase group operation
16 Minimum creepage distance mm 31mm/kV
17 Rated mechanical terminal load kN 3
0
18 Contact resistance of blade at 32 C <100
19 Number of auxiliary contacts of DS
- normally open 8
- normally closed 8
20 Number of auxiliary contacts of ES
- normally open 6
- normally closed 6
Number of limit contacts of DS
- normally open 2NO+2NC (1NO+1NC for
- normally closed customer, 1NO+1NC for
21 Minimum clearance operation circuit)
- between live parts and earth mm 1220
- between phases mm 2200
- across open disconnector mm refer drawing
22 Auxiliary power supply
- Heating voltage Vac 220
Tolerance range % +10/-10
- Motor driver of DS, interlocking coil of ES Vdc 220
Tolerance range % +10/-15
- Control, closing & tripping voltage Vdc 220
Tolerance range % +10/-15
Overload protection, over current protection for Motor
Yes
driver shall be provided.
1
Item Manufacturer
Description Unit
No. Data
Local control cubicle shall be provided Yes
23 Total weight of 3-pole unit kg 1295
24 HV terminals
- Material alluminum
- Dimensions, mm 100*190
- Holes - No. , size and spacing mm 4-M12+4-φ14
25 Electrical interlocking coil for DS and ES yes
Mechanical interlocking for DS and ES shall be provided Yes
26 Operating conditions
o
Maximum ambient temperature C 50
Maximum relative humidity % 100
Climatic conditions Tropicalization
27 Standards of quality management ISO 9001: 2008
28 Supporting structure Yes
29 Drawings Yes
2
110kV CURRENT TRANSFORMER
Item Manufacturer
Description Unit
No. Data
1 Manufacturer ABB
2 Place of manufacture China
3 Manufacturer reference/designation LB7-126
Oil, outdoor, seamless
4 Type
body
IEC 61869-2, or
5 Standard Specification
Equivalent
6 Rated Voltage kV 123
7 Highest System Voltage kV 123
8 Impulse Voltage (1.2/50us) withstand kV 550
9 Power Frequency Voltage Withstand, one minute, 50Hz
- Primary windings kV 230
- Secondary windings kV 3
10 Insulator Creepage Distance mm/kV 31
11 Rated Primary Current
Type: 200-400-800
% of rated
12 Extended Current Rating 120
primary current
13 Rated Transformation Ratios
Type: A 200-400-800/1
14 Rated Thermal withstand Current ( 3 sec.) kArms 31.5
15 Rated Dynamic Withstand Current kAp 80
Maximum Partial Discharge Level at 1.1 Un (highest
16 pC 10@Um
system voltage)
17 Secondary Winding Resistance Ohm NA, for PX only
18 Targent of loss angle (tan d), 50Hz (complete unit) ≤ 0.5%
19 Oil level indicator (if oil immersed type) Yes
Oil drain valve Yes
20 Total Weight kg 600
21 Calculated Wind Load Moment about Base kN 3
Core Characteristics : Ratio, Rated Burden, Accuracy
22
Class
Type: A 200-400-800/1
Ratings:
- Core No. 1: for protective A 1
- Core No. 2: for measuring A 1
- Core No. 3: for protective A 1
- Core No. 4: for protective A 1
- Core No. 5: for measuring A 1
A ccuracy class for line bay:
- Measuring 1 Cl 0.5
- Measuring 2 Cl 0.5
- Protection 3 Cl 5P20
- Protection 4 Cl 5P20
- Protection 5 Cl 5P20
Rated output:
1
Item Manufacturer
Description Unit
No. Data
- Measuring 1 VA 20
- Measuring 2 VA 20
- Protection 3 VA 20
- Protection 4 VA 20
- Protection 5 VA 20
23 HV terminals
- Material alluminum
- Dimensions, 100*105
- Holes - No. , size and spacing 50*50,4*φ18
24 Operating conditions
o
Maximum ambient temperature C 50
Maximum relative humidity % 100
Climatic conditions Tropicalization
25 Standards of quality management ISO 9001:2008
28 Supporting structure Yes
29 Drawings Yes
2
110kV CAPACITIVE VOLTAGE TRANSFORMER
Item Manufacturer
Description Unit
No. Data
1 Manufacturer ABB
2 Place of manufacture China
3 Manufacturer reference/designation TYD-126
Oil, Capacitive, Outdoor,
4 Type
seamless body
IEC 61869-5, or
5 Standard Specification
Equivalent
6 Rated Voltage kV 123
7 Highest System Voltage kV 123
8 Impulse Withstand Voltage (1.2/50us) kV peak 550
9 Power Frequency Withstand Voltage kV rms. 230
12 Rated secondary voltage (for Line feeder) V 110/sqrt(3)& 110/sqrt(3)
13 Rated voltage factor
- Continous 1.2
- During 30 seconds 1.5
14 Rated capacitance pF 20,000
15 Burden, accuracy class
- Measuring Cl 0.5
- Protection Cl 3P
- Measuring VA 30
- Protection VA 30
16 Guaranteed Limits of Rated capacitance % -5~+5
17 Tangent of the Loss Angle 50Hz (tan d)
- Capacitor unit % ≤0.5
- Complete unit % ≤1
18 Rated Maximum HF Current A 1
19 Temperature Co-efficient of capacitance per oC -2×10^(-4)
20 Maximum Partial/Discharge Level .pC 10
21 Insulator Creepage Distance mm/kV 31mm/kV
22 Phase to Earth Clearance mm 1190
23 Rated Mechanical Terminal Load kN 3
24 Calculated Wind Load Moment about Base kNm 334
25 HV Terminals
- Material alluminum
- Dimensions 110*100*20
27 Weight of capacitor voltage transformer Kg 550
28 Power Frequency Withstand Voltage:
- Primary Winding kV 230
- Secondary Winding kV 3
29 Recommended Fuse Ratings A MCB
30 Oil level indicator (if oil immersed type) Yes
31 HV terminals
1
Item Manufacturer
Description Unit
No. Data
- Material alluminum
- Dimensions, 110*100*20
- Holes - No. , size and spacing mm 4*R7
32 Operating conditions
o
Maximum ambient temperature C 50
Maximum relative humidity % 100
Climatic conditions Tropicalization
33 Standards of quality management ISO 9001: 2008
34 Supporting structure Yes
35 Drawings Yes
2
SURGE ARRESTER
Item Manufacturer
Description Unit
No. Data
1 Manufacturer ABB
2 Place of manufacture China
3 Manufacturer reference/designation YH10W-96/250
4 Applicable standards IEC 60099-4
5 Type Metal oxide
6 Rated voltage (Ur) kV 96
7 Rated frequency Hz 50
8 Maximum continuous operating voltage Uc kV 77
9 Nominal discharge current kA 10
10 IEC long duration discharge class 3
11 Maximum energy absorption capability kJ/kV 7.1
12 Maximum residual voltage of complete arrestor for
(a) Nominal discharge current impulse with rise time 1ms kV 280 at 1/5 μs
(b) Nominal discharge current 8/20-ms impulse 250
(c) Switching impulse kV 213
Wave shape ms 30/80
With peak current of A 500
13 High current impulse (4/10ms) withstand 100kA
Leakage current through the complete arrestor at max.
14
continuous operating voltage
resistive component mA 0.2
capacitive component mA 1
(state whether peak or rns. value)
15 Material employed in series non-linear resistor ZnO
16 Filling medium Patent material
17 Sensitivity of surge counter:
(a) Current A 600
(b) Corresponding wave shape ms 2000
Peak voltage across surge counter when a 8/20 ms current surge
18 of peak value equal to the nominal discharge current of the V <2000
arrestor is applied
RMS voltage across surge counter when continuous operating
19 V N/A
voltage is applied to arrestor
20 Leakage current meter range 5mA
21 Arrester housing:
- Material Polymer
- Lightning impulse withstand kVp 550
- Power frequency withstand
- Wet for 10 minutes kV (rms.) 230
- Creepage distance mm 31mm/kV
- Colour Red
23 Seismic withstand capability 0.2g
24 Calculated Wind Load Moment about the base of the arrestor kN-m 0.14
25 Cantilever strength of arrestor kN-m 2.2
26 Terminal materials/dimension
- HV Steel
- Earth Steel
27 Surge counter Yes
+Manufacturer/Original ABB/China
28 Insulating bases Yes
29 Leakage current indicator Yes
30 Operating conditions
1
Item Manufacturer
Description Unit
No. Data
o
Maximum ambient temperature C 50
Maximum relative humidity % 100
Climatic conditions Tropicalization
31 Standards of quality management ISO 9001: 2008
32 Supporting structure Yes
33 Temporaty overvoltage (TOV) in 10s kV ≥89
34 Drawings Yes