Bridge Engineeing Drawings 10.2 - A4 - 3

This document provides details for installing conduits and junction boxes in a pedestrian barrier. It specifies: 1. Conduits are to be installed every 10 feet and junction boxes every 200 feet maximum. Conduits are to be steel transitioning to PVC. 2. Junction boxes are to be 8"x8"x18" and labeled. They are to be installed adjacent to the barrier ends and 5 feet minimum from the end of the bridge or wall. 3. Expansion fittings are required at expansion joints for the conduits and drain pipes installed to prevent water accumulation in the boxes.

Uploaded by

Adnan Najem
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
64 views1 page

Bridge Engineeing Drawings 10.2 - A4 - 3

This document provides details for installing conduits and junction boxes in a pedestrian barrier. It specifies: 1. Conduits are to be installed every 10 feet and junction boxes every 200 feet maximum. Conduits are to be steel transitioning to PVC. 2. Junction boxes are to be 8"x8"x18" and labeled. They are to be installed adjacent to the barrier ends and 5 feet minimum from the end of the bridge or wall. 3. Expansion fittings are required at expansion joints for the conduits and drain pipes installed to prevent water accumulation in the boxes.

Uploaded by

Adnan Najem
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

BUNDLE 2 B1 #5 OR 2 B8 #5

THRIE BEAM JUNCTION BOX & PULL BOX (TYP.) ADJACENT TO EACH END OF
OR W-BEAM END OF BRIDGE OR WALL FOR SIZE & LOCATION, SEE JUNCTION BOX (TYP.)
GUARDRAIL 2 ~ 10' STEEL JUNCTION BOX TABLE
CONDUITS 7 FACE OF BARRIER 2 ~ STAINLESS STEEL
MOUNTING TABS (TOP & BOT.)
TS LT

8" x 8" x 18" JUNCTION BOX 7


20'-0" MAX. PEDESTRIAN BARRIER
CONDUIT DEFLECTION FITTING A 2 ~ STEEL CONDUIT TO PVC
2'-0"

5'-0" MIN. WITH INTERNAL BONDING JUMPER. ADAPTORS IN STATIONARY ON STRUCTURE

1'-2"
SEE DETAIL THIS SHEET FORM BARRIER WHERE PVC É"ø POLYETHYLENE
PIPE INSTALLED IN BARRIER CONDUIT EXPANSION FITTING OR COPPER PIPE DRAIN
TS LT (TYP. AT EXPANSION JOINT)
JUNCTION BOX SIZED
PER ELECTRICAL PLANS.
LABEL JUNCTION BOX LIDS
PLAN
AS SHOWN (TYP.) CONDUITS & J-BOX IN PEDESTRIAN BARRIER
NOTE TO DESIGNERS A

MODIFY THE FOLLOWING TO MATCH PROJECT REQUIREMENTS:


SECTION A
1. BARRIER END SECTION.
¢ J-BOX & BARRIER PANEL ¢ J-BOX & BARRIER PANEL
2. REMOVE GUARDRAIL IF NOT CONNECTED TO BRIDGE ITEM.
3. CONDUIT ALIGNMENT 200'-0" MAX.
8 EXPANSION JOINT
¢ J-BOX & BARRIER PANEL ¢ J-BOX & BARRIER PANEL CONDUIT EXPANSION
200'-0" MAX. CONDUIT PIPE SIZED FITTING
5 10'-0" STEEL CONDUIT SECTION SECURE CONDUIT AND BUNDLE 2 B1 #5 OR 2 B8 #5 PER WIRING SCHEDULE
BETWEEN CONDUIT DEFLECTION BOX TO REBAR TO ADJACENT TO EACH END OF 8'-0" MIN. (L TYP.)
#4 x 3'-6" (TYP.)
FITTING A AND PVC CONDUIT IN PREVENT MOVEMENT JUNCTION BOX (TYP.)

¾"
STATIONARY FORM BARRIER L (TYP.)

STEEL CONDUIT,
INCLUDING TOP OF
ELBOWS AND SIDEWALK TS TS TS TS
SWEEPS BONDING JUMPER
1" TIES ~ SPACE @ 2½" MAX. 1"

TOP OF BRIDGE
TOP OF BRIDGE DECK 2"ø CONDUIT PIPES OR
CONDUIT EXPANSION FITTING
APPROACH SLAB BLOCKOUT FOR STEEL CONDUIT TO PVC ADAPTOR IN
AT CURB LINE SIZE CONDUIT PER CONDUIT FITTING - (TYPE AX FOR MOVEMENT OF ± 2")
CONDUITS STATIONARY FORM BARRIER WHERE
6 WIRING SCHEDULE AT BRIDGE EXPANSION JOINTS
CONDUIT DEFLECTION PVC PIPE INSTALLED IN BARRIER
FITTING A NOTES:
09/25/2020

STEEL CONDUIT SECTION


BETWEEN CONDUIT DEFLECTION
ELEVATION 1 WHERE CONDUIT IN A STRUCTURE IS ROUTED ACROSS A JOINT, WRAP STEEL CONDUIT PIPE
FOR 1'-0" ON EACH SIDE OF JOINT. PIPE WRAP TAPE SHALL BE 2" WIDE, 20 MIL THICK, AND
FITTING A AND JUNCTION BOX
CONDUITS & J-BOX IN PEDESTRIAN BARRIER INSTALLED WITH A MINIMUM OF 1" OVERLAP.

4 2 PLACE AT CONDUIT PIPE EXIT FROM STRUCTURE AND SHALL BE IN NEUTRAL STATE AFTER
INSTALLATION.
½" PREMOLDED JOINT FILLER
SEE STANDARD PLANS 3 CONDUIT PIPES PLACED THROUGH RETAINING WALL PEDESTRIAN BARRIER SHALL
1 BE FITTED WITH DEFLECTION FITTINGS AT A MAXIMUM SPACING OF 120'.
CONCRETE CONCRETE
THE DEFLECTION FITTINGS SHALL BE PLACED AT THE PEDESTRIAN BARRIER OPEN
1'-0" JOINT THAT COINCIDES WITH THE RETAINING WALL EXPANSION JOINT.
CONCRETE

1" TIES @ 2½" 1" ¾" POLYSTYRENE FOAM. WRAP


4 LABEL JUNCTION BOX COVER IN ACCORDANCE WITH STANDARD SPECIFICATION SECTION
1 1½ TIMES AROUND CONDUIT
9-29.2(4). ADJACENT JUNCTION BOXES ARE SHOWN CENTERED BETWEEN ADJACENT DUMMY
AND CONDUIT FITTING
JOINTS. IF THE DISTANCE BETWEEN ADJACENT DUMMY JOINTS IS 16'-0" OR GREATER,
PLACE ADJACENT JUNCTION BOXES SYMMETRICALLY ON EITHER SIDE OF THE CENTER OF
¾"

ONE DUMMY PANEL WHILE MAINTAINING 8'-0" MINIMUM BETWEEN CENTER LINES OF THE
3" MIN., 6" MAX. (CONDUIT AND JUNCTION BOXES.
SOIL

THREADS CAST OUTSIDE STRUCTURE)


END 5 TERMINATE STEEL CONDUIT IN JUNCTION BOX IF LESS THAN 10-'0" FROM ELBOW OR SWEEP.
CONDUIT DEFLECTION FITTING CONDUIT PIPE
B START
WITH INTERNAL BONDING JUMPER
CONDUIT DEFLECTOR FITTING 6 INSTALL ONLY WHERE CONDUIT IS HORIZONTAL.
CONDUIT PIPE WITH INTERNAL BONDING JUMPER
7 NEMA 4X IN STATIONARY FORM BARRIER, OR NEMA 3R IN SLIP FORM BARRIER. MOUNT

CONDUIT DEFLECTION FITTING A CONDUIT DEFLECTION FITTING B SECTION B JUNCTION BOX SO COVER IS FLUSH WITH BARRIER, CAN BE RECESSED UP TO Â".

CONDUIT FITTING - TYPE DX FOR DEFLECTION OF 30° AND ¾" MOVEMENT. CONDUIT FITTING - TYPE DX FOR DEFLECTION OF 30° AND ¾" MOVEMENT. 8 3'-0" LONG EXPANDED POLYSTYRENE SLEEVE AROUND CONDUIT. DUCT TAPE SEAMS AND
2 3 ENDS TO SEAL AND PREVENT CONCRETE FROM BONDING WITH FITTING AND CONDUIT.
10.2-A4 -3

M:\STANDARDS\Traffic Barriers\Pedestrian Barrier\PED BARRIER 3.MAN

Wed Oct 14 13:22:42 2020