Typical Wiring Diagram: Function Action

The document provides installation instructions for a DSE9000 battery charger. It warns of live parts within the enclosure that should not be accessed. It recommends charging one battery bank at a time and provides mounting and connection details. Key specifications are listed such as input voltage ranges, fuse sizes, dimensions, and operating temperature range.

Uploaded by

MH..2023
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
576 views2 pages

Typical Wiring Diagram: Function Action

The document provides installation instructions for a DSE9000 battery charger. It warns of live parts within the enclosure that should not be accessed. It recommends charging one battery bank at a time and provides mounting and connection details. Key specifications are listed such as input voltage ranges, fuse sizes, dimensions, and operating temperature range.

Uploaded by

MH..2023
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

053-049

Typical Wiring Diagram ISSUE 4 DEEP SEA ELECTRONICS

9000 Battery Charger Installation Instructions

DANGER OF DEATH : LIVE PARTS exist within the DSE9000 enclosure.


The enclosure cover must not be removed.

x Installation
NOTE : The DSE9000 series battery charger should only be used to charge
one battery bank at a time. It is not recommended to parallel batteries as the
tolerance of the batteries leads to imbalance in the charging of the batteries.

The DSE9000 battery charger is designed to be mounted within a control panel, on


the panel DIN rail utilising the integral mounts or on a chassis utilising the mounting
holes. For dimension and mounting details, see overleaf.
The DSE9000 battery charger is fit-and-forget. It can be permanently connected to the
supply and the load, with no requirement to disable the charger during times of heavy
load (such as engine cranking) or when in parallel with a charging alternator.

Battery suitability
The charger is factory set by DSE to suit Lead Acid batteries but can be adjusted at
the time of ordering to suit other battery types. Care should be taken to ensure the
batteries connected to the charger are of the correct ‘technology’ to suit the setting of
the charger.
Indications
The DSE9000 Battery Charger features an LED indicator to show Charger Status.

Connection type Screw terminal, rising clamp, no internal spring Function Action
Min cable size 0.5mm² (AWG 20) Charger • Off when AC supply is not present.
Max cable size 2.5mm² (AWG 14) Status • Steady during normal operation with AC supply above minimum
Recommended AC fuse operating voltage.
DSE9130 12V 5A charger 2.0A anti-surge • Slow flashing when connected to an operating charging alternator.
DSE9150 12V 2A charger 1.5A anti-surge • Fast pulsing during overload conditions.
DSE9250 24V 3.7A charger 2.5A anti-surge
DSE9255 24V 5A charger 3.5A anti-surge Boost Mode
Recommended cable
Refer to operator manual DSE part number 057-085
size CAUTION : Boost mode is intended for equalisation of the cells in lead
acid batteries and should not be operated when the battery charger is
connected to other battery types or when the charger is used as a power
Deep Sea Electronics Plc. Deep Sea Electronics Inc. Deep Sea Electronics Plc. supply only. If in doubt, consult your battery manufacturer.
Tel:+44 (0)1723 890099 Phone: +1 (815) 316-8706 (Far East)
Fax: +44 (0)1723 893303 Fax: +1 (815) 316- 8708 Tel:+66 2 670 6228
LO CALL (from UK BT landlines) : TOLL FREE (USA only) : Tel: 1 866 636 9703 Fax: +66 2 678 3028
Telephone 0845 260 8900 Email: [email protected] Email: [email protected] Boost mode is operated by connecting the BOOST terminals together (for instance
Email: [email protected]
Web: www.deepseaplc.com
Web: www.deepseausa.com Web: www.deepseaplc.com with an external switch or timer circuit). This will raise the battery charger floating
voltage by 0.8V DC.
Dimensions and Mounting Dimensions and Mounting
DSE9130 12V 5A DSE9150 12V 2A
DSE9250 24V 3.7A
DSE9255 24V 5A Overall size 108.03mm x 101.10mm x 48.6mm
(4.25” x 3.98” x 1.91”)
Overall size 136.48mm x 140.41mm x 63.40mm Weight 0.16kg
(5.37” x 5.53” x 2.5”) Mounting type DIN rail or chassis mounting
Weight 0.5kg Din rail type EN 50022 35mm type only
Mounting type DIN rail or chassis mounting Mounting holes Suitable for M4
Din rail type EN 50022 35mm type only Mounting hole centres 91mm x 89mm (4.25” x 3.51”)
Mounting holes Suitable for M4 Input voltage (nominal) 110V-240V
Mounting hole centres 119.36mm x 128.36mm (4.7” x 5.05”) Input voltage (absolute range) 90V-250V
Input voltage (nominal) DSE9250-001 24V 3.7A 110V-240V Charge failure relay rating 3A DC resistive, 30V maximum
DSE9250-002 24V 3.7A 110V-277V Operating Temperature -30°C to 55°C
DSE9130 12V 5A 110V-277V (-22°F to 131°F)
DSE9255 24V 5A 110V-277V
Input voltage (absolute range) DSE9250-001 24V 3.7A 90V-265V
DSE9250-002 24V 3.7A 90V-305V
DSE9130 12V 5A 90V-305V
DSE9255 24V 5A 90V-305V
Charge failure relay rating 3A DC resistive, 30V maximum
Operating Temperature -30°C to 55°C
(-22°F to 131°F)

Dimensions in mm unless stated

This document is intended as a ‘quick start’ guide only. For full operating instructions and specifications, refer to operator manual DSE part number 057-085