User Manual: English
User Manual: English
English
Warning (3) Be sure that the input power is rated and sequence of phases is
correct in order to prevent from damage or fault.
Safety marks Marks Description
(4) Please do not supply power to the controller before complete the
wirings in order to prevent from electric shock or damage.
(5) Please do not install or store on places with flammable substance or Protective Earth/ground
explosive gas because this is not explosion proof.
(6) Do not allow any screw, metal material, water, oil, etc. to go inside of Danger Electric Shock Risk
controller.
(7) Please do not modify or add components to the product. Notice a high temperature
It may cause malfunction, electric shock, or fire.
(8) Please power off before installation or dismantling.
It may cause electric shock, malfunction, or fault.
(9) Check that earth/ground connection is in good condition.
(earth/ground connection is to prevent from electric shock.
Please comply with this for safety.)
02 03
2. Structure of Controller
3) Operating Procedure ▶Installation Condition : The bottom side is blocked for the safety.
(1) Check all of the cable connections of the mold (if required).
Be sure that all of the cables are free from wear of damage.
Check the thermocouple type.
(2) Check wiring standards whether Yudo standard (power and thermocouple
combined type) or DME standard, etc.
(3) Check power/thermocouple cable specifications.
(connector size, number of pins)
(4) Using an Ohmmeter, check the resistance and isolation of power cables.
Check the open thermocouple cables.
(5) Connect power/thermocouple cables to the mold only after the mold
is loaded on the injection molding machine.
(6) Check the main input power disconnect to be sure it is in the OFF
position prior to connection of the controller to the power source.
(7) Connect the controller to the power source if the power source and 3. Name of Components
controller’s main input power are same. (Controller’s main input power
is shown on the label on the backside of controller cabinet. If you find 1. PV FND Displays Measured Temperature
(Red 4 Digit-Position Value)of Hot Runner System
the differences between actual main input power and power shown on
the label, contact an authorized representative. Unless, it may cause 2. SV FND Displays the Set Temperature
damage to controller units and/or malfunction of controller.) (Green 4 Digit-Set Value)of Hot Runner System
(8) Check that the earth/ground connection is in good condition. 3. ℃/℉ LED Temperature unit Setting value display
Ensure that the system and the mold have the same ground reference 4. SOFT LED Displays SOFT START operation
* (Unless, noise may cause damage to fuse and/or triac, and it may cause 5. OUT LED Displays Power Output State
injury.) 6. J/K LED Termocouple type (TC) Setting value display
(9) Switch the controller on. 7. AUTO LED Displays Auto Mode is selected
(10) Switch the controller unit on by pressing the button. 8. STANDBY LED Displays Standby Mode is selected
(11) Enter the target temperature (SV : setting value). 9. MANUAL LED Displays Manual Mode is selected
(12) Verify whether the actual temperature (PV : point value) reach to the
10. MODE Operation switch, User Mode operation key
target temperature (SV).
11. ▲ Value Increase Key
12. ▼ Value Decrease Key
Caution If the fan of backside of controller stops, it may cause the unit damaged.
13. SET Changing cipher key
Please confirm the fan is working.
*SET+MODE Supplier's Menu
14. SEL/SAVE Select mode (AUTO, STANDBY, MANUAL) &
save the changes
15. Handle
16. Power Switch
17. Lock Bolt
※Caution. Keypad is made of Silicon rubber.
Don't touch the keypad by Drill, Ballpoint pen and the sharp edged things.
04 05
4. Controller Unit Specifications 5. Outline of controller and temperature control method
1) Input ■ Thermocouple Type TC-K (IEC-584), TC-J (IEC-584) 1) Outline of Controller The controller is a device that has a function to maintain the desired
Specifications ■ Control Range 40 ~ 400℃ temperature consistsently by sening the state of hot runner system with
■ Scan Rate 200 mS high-intellectual computer system named CPU and input proper power.
■ Scan Accuracy ±0.5% of F/S 2) Temperature (1) Temperature range : 40℃ ~ 400℃ / 104℉ ~ 752℉
■ Compensable Temperature Variation ±2.0℃(-15℃ ∼ 65℃) Control Method (2) Calibration of temperature deviation : It can calibrate the difference
between actual and setting temperatures manually.
2) Output ■ Transmission Output 15A(Max 16.5A), 1 zone/Unit
(3) Temperature control by : Auto Tuning , Auto PID, Manual PID control,
Specifications ■ Output Mode Phase Control, Zero Cross Control
On/Off control
■ Output Resolution Limit Phase Control : Approximately 1000 Resolution
① Auto Tuning
Zero Cross Control : 60Hz/50Hz-120/100 Resolution
■ Period of renewal 200 mS
Is a function to extract the control constant through analyzing the
capacity of heaters and the heat constant of the mold (latent heat,
3) System ■ Input radiant heat). It helps to make precise temperature control regardless
Specifications Disconnection Detection Up Scale action, and exceeding ±5% of input range of environmental change.
■ Output ② Auto PID control
Output Mode Phase Control, Zero Cross Control Is a method in order to maintain temperature at the set temperature
Display Range 40 ~ 400℃ by controlling output power reflecting proportion, integration, and
■ Control differentiation values.
Control Method PV Preceding Derivative PID ③ Manual PID control
P BAND 0~ 600.0℃ (at 0, output changes between On and Off) Is a function to control by manual input of PID constant in case that
I TIME 0 ~ 600.0 Sec temperature can not be controlled by auto tuning because the condition
D TIME 0 ~ 600.0 Sec of heater is non-controllable.
Hysteresis Range 0.1 ~ 5.0℃ ④ On/Off control
Self Tuning Quick Auto Tuning , Full Auto Tuning Is a function to relay tuning by inputting 0 at PID value in supplier’s
■ Alarm mode, in case that the temperature can not be controlled by auto tuning.
Range ± 99.9℃ of Set Value (SV) (Overshoot can occur in this case).
Alarm Type Alarm high, Alarm low
■ Running the controller 6. Protective Functions
RUN Auto run
STANDBY Duration, Target temperature
1) Ground Fault Is a function to self-inspect short-circuit between heater and frame ground,
MANUAL Change input (PV) and output
Inspection and stop input power.
4) Environment ■ Operating Temperature 0℃ ∼ 50℃ 2) Thermocouple Is a function to inspect itself thermocouple disconnection, short-circuit or
Specifications ■ Operating Humidity 20 ~ 90%RH(Non-condensing) Disconnection reverse connection, and stop input power.
■ Storage Temperature -25℃ ~ 70℃ Inspection
■ Insulation Resistance 500Vdc, over 20MΩ (Input Power-F/G, Input/output-F/G) 3) Overcurrent Is a function to stop input power to avoid damages by over current in case
■ Withstand Voltage 1,500Vac, 50/60Hz 1 min Inspection of heater short-circuit.
(Input power-F/G, Input/Output-F/G, Input/Output-Input Power)
4) Soft-Start Function When power on, output starts from 1% and increases by 1% per second
■ Vibration Resistance 10 ~ 55Hz, bandwidth 0.75mm, X,Y,Z (3) directions 3 swings, 5 min/swing
■ Impact Resistance 100 ㎨, X,Y,Z (3) directions 3 times
up to 50%. The output stays at 50% until 110℃. This function prevents
■ Warming-up time over 30 min heaters from humidity-caused damage by preheating slowly.
06 07
7. Operation Mode 8. Menu Setting
1) Operation Mode Operation Mode Select : key is converted by holding for 2 seconds. 1) User’s Setting Menu ( )
Selection
▶ Diagram of User’s Setting Menu
OPERATION MODE SELECTION
Normal operation mode in which the temperature is controlled and maintained SAVE & EXIT ( )
Start setting ( )
automatically in accordance with the setting value. [StSV] 0 : Change setting value Function to set standby temperature.
① Display conversion : key is pressed, the display on SV is converted as
SAVE & EXIT ( )
the following order. [Set Temperature]▶[Output%]▶[Ampere]▶[Set Temperature] Start setting ( ) Function to prohibit to change setting values of supplier's mode.
[LoCk] oFF : Set on/off
(2) STANDBY mode This is preventing from the change caused by user's mistake.
Down the output power to the given rate for the given time, SAVE & EXIT ( )
Start setting ( )
in production pause for a while. [-Id-] CH00
: Change setting value Optional function to control integratedly several modules.
: Move location of digit (controller unit)
① Holding key for 2 seconds in Auto mode will convert it into
SAVE & EXIT ( )
STANDBY mode. (Manual mode is automatically converted, in case Start setting ( ) : Change setting value Function to set entry time of auto standby mode.
STANDBY setting time is”0”. Default 1 hour) [ASEt] 0
: Move location of digit Can set up to max. 9999min(initial value 0 Min.)
② Temperature setting value (SV) is changed into % rate on the basis SAVE & EXIT ( )
of the set temperature during standby mode Start setting ( ) : Change setting value Function to set release time of auto standby mode.
[ASot] 9999
③ STANDBY mode finished after the given time is up, and moves to : Move location of digit Can set up to max. 9999min(initial value 9999 Min.)
Is a function to operate by manual on emergency that user can set SAVE & EXIT ( )
output volume with , key. Start setting ( ) : Change setting value
[IJEt] 10 Set available injection enable temperature range. (Use OUTLOCK)
① Push key 2 times each for 2 seconds in AUTO mode, : Move location of digit
ON ON ON
ON ON ON
10 11
(5) (LOCK Key Software lock device ) (8) (AUTO STANDBY release time setting) (Inter-Lock Option)
This function is to protect to change the set parameters which are Function to set quit time of auto standby mode
locked by parameter setting lock function by mistake. ① If press key for more than 2 sec, PV displays .
① If press key for more than 2 sec, PV displays . Then if unpress key, PV displays . If press key
Then if unpress key, PV displays . If press key seven(7) times, PV displays .
four(4) times, PV displays . ② If press key, setting value blinks every 0.1 sec. If press key,
② If press key, setting value blinks every 0.1 sec. If press , key, change the number of digit. Can change setting value by pressing
change ON/OFF. , key. Setting range is 1~9999min.
③ Press key to complete the setting. Factory default is ‘9999min.’
③ Press key to complete the setting.
(6) setting (when use UNIT ID integrated control function, optional)
When want to control several modules (unit of controller) integrally, (9) (AUTO STANDBY Temperature values setting) (Inter-Lock Option)
the computer at central control room recognizes each module by the Function to set the temperature using upon entering auto standby mode
designated identification number. ① If press key for more than 2 sec, PV displays .
① This function requires an optional device for integrated control system. Then if unpress key, PV displays . If press key
② If press key for more than 2 sec, PV displays . eight(8) times, PV displays .
Then if unpress key, PV displays . If press key ② If press key, setting value blinks every 0.1 sec. If press key,
five(5) times, PV displays . change the number of digit. Can change setting value by pressing
③ If press key, setting value blinks every 0.1 sec. If press key, , key. Setting range is 0~400℃.
change the number of digit. Can change setting value by pressing Factory default is ‘50℃’.
, key. Setting range is 0~99. ③ Press key to complete the setting.
Factory default value is ‘0’.
③ Press key to complete the setting. (10) (injection enable temperature range setting) (Inter-Lock Option)
Function to set available injection temperature range by ± set value
(7) (AUTO STANDBY Entry time setting)(Inter-Lock Option) ① If press key for more than 2 sec, PV displays .
Function to set the time to operate auto standby mode by checking Then if unpress key, PV displays . If press key
certain time of status that keep no injection signal nine(9) times, PV displays .
① if press key for more than 2sec, PV displays then ② If press key, setting value blinks every 0.1 sec. If press key,
if unpress key, PV displays . if press key, six(6) times, change the number of digit. Can change setting value by pressing
PV displays . , key. Setting range is 0~50℃.
② if press key, setting value blinks every 0.1sec. If press key, Factory default is ‘10℃’. (±10℃)
change the number of digit. Can change setting value by pressing ③ Press key to complete the setting.
, key. Setting range is 0~9999min.
Factory default value is ’0min’.
③ Press key to complete the setting.
12 13
2) Supplier’s Setting Menu ( ) ③ Press key to complete the setting.
④ Setting can be done only when LOCK function is OFF.
▶Diagram of Supplier’s Setting Menu
18 19
11. Connector and Cable
Connector means a component attached to the end part of cable in order
② If press key, setting value blinks every 0.1 sec. If press key, to make it easy to connect/disconnect the wire to the mold/controller.
change the number of digit. Can change setting value by pressing Various kinds of connectors are used depending on load capacities.
, key. Setting range is 0~100%. Factory default is ‘100%’.
③ Press key to complete the setting. * Standard Spec. : Integrated Wire(Power+T/C) * Optional Spec. : Separated Wire(Power, T/C)
9. Reset Function
This is a function which initializes the setting values of user mode and
supplier mode. Turn on the power switch while pressing both key
and key to display on SV and to initialize all setting values after
displaying countdown on PV (from 3 to 0).
Initialization 1) How to wire heater and T/C in connectors 24P Male standard connector
(5 ZONE~24 ZONE)
( + ): ON If power on while pressing + keys, all setting values change back to factory default
after PV counts down from 3 to 0.
4P Round Jack #4 #1
Power Switch ON
4 1
-
3→2→1→0 Display Return to main screen after initializing by displaying from 3 to 0 at PV. #1 T/C HEATER
+ #5 #2
3 2
RUN
20 21
13. Electric Wiring Diagram
(2) Options 1) 220V (3 Phases 3 Lines Type) * Max. 240V
As for option in wiring, separated power lines from that of thermocouple
can be selected depending on customer’s preference. But also the other
connector out of YUDO standard could be equipped when those are
supplied from customer. In case that a cable is fabricated according to
special order, controller connector must be fabricated in accordance
with the cable specifications.
#1 #1
#2 #2
#3 #3
#4 #4
#5 #5
#6 #6
#7 #7
#8 #8
#9 #9
#10 #10
#11 #11
#12 #12
※ As for Zone No. : Please refer to the standard spec. 2) 380V (3 Phases 4 Lines Type) * Max. 414V
RJC
SENSOR
(IN PUT)
HEATER
(OUT PUT)
100-240V~
(50/60Hz)
G
22 23
3) 220V (1 Phases 2 Lines Type) 1) Wire modification method from 3 phases 3 lines 220VAC to 3 phases 4 lines 380VAC
Red Red
R L1 R L1
Red
Supply Supply
White White Controller
Voltage S L2 Voltage S L2
White Controller
220 V 220 V 380 V 220 V
3 phases T Black 3 phases Black
L3 T L3
3 lines Black 4 lines NFB Red
NFB
N N N N White
Black
PE(G) PE PE(G) PE
2) Wire modification method from 3 phases 4 lines 380VAC to 3 phases 3 lines 220VAC
Red
R L1 Red R L1
Supply Supply Red
Voltage Voltage White
S L2 White S L2
380 V Controller 220 V White Controller
14. Wiring Modification Method 3 phases 220 V 3 phases Black 220 V
T L3 Black
4 lines 3 lines T L3 Black
NFB Red NFB
N N White N N
Black
YUDO Temperature Controller operates with supply voltage PE(G) PE PE(G) PE
220~240V AC. But even in case of supply voltage 380~414V AC
3phase 4 line, by re-wiring as shown below, 220~240V AC can be
taken between one phase(R, S or T) and Neutral(N). (1) Power off the controller
YUDO Temperature Controller be supplied with wiring for supply (2) Open the back cover of controller
voltage 220~240V AC unless special instruction. (3) Separate all three (3) blue-sleeved wires from N
Please check the current wiring. (4) Plug blue-sleeved RED wire into L1
WHITE wire into L2
Caution Before re-wiring, make sure AC main power OFF and BLACK wire into L3
Power Switch OFF on controller.
Warning PE(G) must be ground connection, do not permit to connect the Neutral.
Manufacturer cannot be held responsible for any troubles from Above.
24 25
15. Default Value 16. Troubleshooting
1) Default value for user’s menu (PA-1)
No Error Message Causes Action
No Menu Default Value Remarks
1. Sensor (thermocouple) is 1. Replace or re-wire sensor (thermocouple)
1 SV ℃ SV(Setting Temperature) 1
disconnected. if it’s disconnected after testing by a tester.
2 ℃ High Limit Alarm
1. Change the polarity (+,-) of sensor
3 ℃ Low Limit Alarm 1. Polarity (+,-) of sensor
2 (thermocouple) after checking connections
(thermocouple) are changed.
4 (1 hour) STANDBY time of connectors of mold and controller.
26 27
Czech
Germany Finland
Netherlands Russia
Poland
UK
France Slovakia
Ukraine
Italy Romania Weihai Japan
Portugal Turkey Iran Qingdao Korea Tokyo Michigan
Syria China USA
Spain Israel Bangladesh
Morocco Suzhou Kunshan Headquarters
Egypt Taiwan
India Dongguan Manufacturing & Sales 24
Hongkong
Thailand
Philippines Sales subsidiary 26 Mexico
Vietnam
Malaysia
Sales office 61
Singapore Agency 18 Peru
Indonesia
Australia
28 29