0% found this document useful (0 votes)
56 views2 pages

Intrinsically Safe Power Supply SG160

The SG160 is an intrinsically safe power supply that can be mounted in hazardous areas. It has an intrinsically safe output of 18V, 15V or 12V at currents of 25, 50 or 70mA. It has protection class IP65 and temperature ratings of -20°C to 65°C. An optional control port allows the SG160 to be switched on and off remotely with an 8-30V signal. Restricted inductances and capacities for the intrinsically safe output are provided depending on the model.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views2 pages

Intrinsically Safe Power Supply SG160

The SG160 is an intrinsically safe power supply that can be mounted in hazardous areas. It has an intrinsically safe output of 18V, 15V or 12V at currents of 25, 50 or 70mA. It has protection class IP65 and temperature ratings of -20°C to 65°C. An optional control port allows the SG160 to be switched on and off remotely with an 8-30V signal. Restricted inductances and capacities for the intrinsically safe output are provided depending on the model.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Intrinsically safe, electronic

Power supply
Gönnheimer
Elektronic GmbH

SG160
For mounting in hazardous area
TÜV 01 ATEX 1693
Block diagram The SG160 is available with an additional control
port option. An active non intrinsically safe 8 up to
Option:
30V signal switches the SG160 power supply on
hazardous area
Control port: 0-Signal < 2V, 1-Signal > 8V and off.
+ -

4 5
Type code
+L 1
Output current
Line
6 + Speisegerät SG160 . . .
-N 2
24V, 120V, 230V AC 7 -
PE 3 intrinsically safe
24V DC 18V, 15V or 12V, Mains:
70 mA, 50 mA
230V AC............................... .0
U

resp. 25 mA
i
120V AC............................... .2
24 V DC................................ .6
Description Power output
15V DC,70mA ............................. .0
The intrinsically safe power supply SG160 is 15V DC, 50mA............................. .1
mountable in explosion endangered areas (zone 12V DC, 70mA ............................ .2
1). Its intrinsically safe output current (category 1b) 12V DC, 50mA ............................ .3
has a rectangular characteristic. The output volt- 18V DC, 25mA ............................ .4
ages are 18V, 15V and 12V at an output current of 15V DC, 25mA ............................ .5
25, 50 or 70 mA. 12V DC, 25mA ............................ .6
The housing as well as the input terminals of the 10V DC, 100mA .......................... .7
SG160 have protection class „increased safety“. control entrance:
The supply voltage can be connected directly to Ohne ................................................ .0
the SG160 - an additional EEx e-terminal box is Vorhanden ....................................... .1
unnecessary.

Dimensions
160 mm 56,5 mm
148 mm 8,5 mm
4,5 mm
46 mm
75 mm

7,5 mm

M16 x 1,5 Sp 5-10 Additonal port M16 x 1,5 Sp 5-10


on Option
Control port
Technical Details
Line voltage [V] AC: 230, 120, 24; 48 ..62 Hz DC: 24 V
Power consumption 2W
Ex group II 2 G/D
Ex- protection II 2 G, EEx e m [ib] IIC T5 bei ϑU bis 40°C
II 2 G, EEx e m [ib] IIC T4 bei ϑU bis 65°C
II 2 D, Ex tD [ibD] A21 IP 66 T135°C
Mounting Inside hazardous area
Intrinsically safe U ≈ 18V U ≈ 15V U ≈ 12V U ≈ 10V
output I = 100 mA SG160.x.7.x
I = 70 mA - SG160.x.0.x SG160.x.2.x
I = 50 mA - SG160.x.1.x SG160.x.3.x

I = 25 mA SG160.x.4.x SG160.x.5.x SG160.x.6.x


Control entrance 1-Signal 8 ..30V; 0-Signal 0 .. 2V Um < 40V
Housing protection IP65
Housing material Polyester
Ambient temperature -20°C .. 65°C at temperature class T4
-20°C .. 40°C at temperature class T5

Ex- limits intrinsically safe output


SG 160.x.0.x 160.x.1.x 160.x.2.x 160.x.3.x 160.x.4.x 160.x.5.x 160.x.6.x 160.x.7.x
Uo 16,8 V 16,8 V 12,6 V 12,6 V 20 V 16,8 V 12,6 V 10,5 V
Io 80 mA 58 mA 80 mA 58 mA 27 mA 27 mA 27 mA 110 mA
Po 1340 mW 947 mW 1000 mW 731 mW 540 mW 454 mW 341 mW 1155 mW
See also EC- TYPE Certificate: TÜV 01 ATEX 1693

Restricted inductivities and capacities

Zünd- Typ Typ Typ Typ Typ Typ Typ Typ


schut- SG160.x.0.x SG160.x.1.x SG160.x.2.x SG160.x.3.x SG160.x.4.x SG160.x.5.x SG160.x.6.x SG160.x.7.x
zart
Lo Co Lo Co Lo Co Lo Co Lo Co Lo Co Lo Co Lo Co
[mH] [nF] [mH] [nF] [mH] [nF] [mH] [nF] [mH] [nF] [mH] [nF] [mH] [nF] [mH] [nF]
EEx ib 0,17 140 0,5 130 0,15 700 0,15 480 0,15 110 2 200 1 360 0,2 1200
IIC 0,9 100 0,5 240 0,5 270 1 100 5 150 2 300 0,5 750
1 190 1 240 2 70 5 200 1 480
EEx ib 1 590 2 560 1 1200 1 1300 0,15 1000 0,5 2000 0,15 5000 0,5 5400
IIB 2 490 5 340 2 960 2 1100 5 500 5 1000 5 2000 2 2900
5 250 10 270 5 520 5 690 5 1600
Ex 2 1150 4 1120 2 2400 2 2600 0,5 1500 1 4000 0,5 7500 1 9000
ibD 4 980 10 680 4 1920 4 2200 10 1000 10 2000 10 4000 4 5800
10 500 20 540 10 1040 10 1380 10 3200
See also EC- TYPE Certificate: TÜV 01 ATEX 1693

Gönnheimer
Dr.-Julius-Leber-Straße 2
Zertifiziertes
67433 Neustadt/Weinstraße
Qualitäts- Postfach 10 05 07
Elektronic GmbH Managementsystem
DI
NE
nach
N ISO 90
01
67405 Neustadt
phone: +49 (6321) 49919- 0
http://www.goennheimer.de Email: [email protected] fax: +49 (6321) 49919 - 41