Technical data sheet H7..
N
Globe valve, 3-way, Flange, PN 16
• For closed cold and warm water systems
• For modulating control of air-handling and
heating systems on the water side
Type overview
Type DN kvs Stroke PN n(gl) Sv min.
[m³/h]
H711N 15 0.63 15 mm 16 3 50
H712N 15 1 15 mm 16 3 50
H713N 15 1.6 15 mm 16 3 50
H714N 15 2.5 15 mm 16 3 50
H715N 15 4 15 mm 16 3 50
H720N 20 6.3 15 mm 16 3 100
H725N 25 10 15 mm 16 3 100
H732N 32 16 15 mm 16 3 100
H740N 40 25 15 mm 16 3 100
H750N 50 40 15 mm 16 3 100
H764N 65 58 18 mm 16 3 100
H765N 65 63 30 mm 16 3 100
H779N 80 90 18 mm 16 3 100
H780N 80 100 30 mm 16 3 100
H7100N 100 145 30 mm 16 3 100
H7125N 125 220 40 mm 16 3 100
H7150N 150 320 40 mm 16 3 100
Technical data
Functional data Fluid Cold and warm water, water with glycol up to
max. 50% vol.
Fluid temperature -10...120°C
Fluid temperature note At a fluid temperature of -10...2°C, a spindle
heating is needed.
Flow characteristic Control path A – AB: equal percentage (VDI/VDE
2173) n(gl) = 3, optimised in the opening range,
Bypass B – AB: linear (VDI/VDE 2173)
Leakage rate Control path A – AB: max. 0.05% of the kvs
value; Bypass B – AB: max. 1% of the kvs value
Closing point Top (▲)
Pipe connection Flange PN 16 according to ISO 7005-2
Installation position upright to horizontal (in relation to the stem)
Servicing maintenance-free
Materials Valve body EN-GJL-250 (GG 25)
Body finish with protective paint
Closing element Stainless steel
Spindle Stainless steel
Spindle seal EPDM O-ring
Seat GG25 / Niro (Bypass)
www.belimo.com H7..N • en-gb • 2021-11-23 • Subject to change 1/4
Technical data sheet H7..N
Safety notes
• The valve has been designed for use in stationary heating, ventilation and air-conditioning
systems and must not be used outside the specified field of application, especially in aircraft or
in any other airborne means of transport.
• Only authorised specialists may carry out installation. All applicable legal or institutional
installation regulations must be complied during installation.
• The valve does not contain any parts that can be replaced or repaired by the user.
• The valve may not be disposed of as household refuse. All locally valid regulations and
requirements must be observed.
• When determining the flow rate characteristic of controlled devices, the recognised directives
must be observed.
Product features
Mode of operation The globe valve is adjusted by a globe valve actuator. The actuators are controlled by a
commercially available modulating or 3-point control system and move the valve cone, which
acts as a mixing device, to the opening position dictated by the positioning signal.
Flow characteristic An equal percentage flow characteristic in the flow direction is produced by the profile of the
valve cone. The bypass exhibits a linear characteristic curve.
Fluid velocity Standard values for low-noise operation in HVAC systems are medium velocities of 1...2 m/s. At
fluid velocities above 2 m/s, further flow effects as well as cavitation can occur. This can reduce
the service life of a valve depending on the situation.
Accessories
Electrical accessories Description Type
Stem heater DN 15...50 (45 W) ZH24-1
Stem heater DN 65...100 (60 W) ZH24-1-C
Stem heater DN 125...250 (60 W) ZH24-1-D
Mechanical accessories Description Type
Blanking flange PN 16 for globe valve DN 15 ZH715
Blanking flange PN 16 for globe valve DN 20 ZH720
Blanking flange PN 16 for globe valve DN 25 ZH725
Blanking flange PN 16 for globe valve DN 32 ZH732
Blanking flange PN 16 for globe valve DN 40 ZH740
Blanking flange PN 16 for globe valve DN 50 ZH750
Blanking flange PN 16 for globe valve DN 65 ZH765
Blanking flange PN 16 for globe valve DN 80 ZH780
Blanking flange PN 16 for globe valve DN 100 ZH7100
Blanking flange PN 16 for globe valve DN 125 ZH7125
Blanking flange PN 16 for globe valve DN 150 ZH7150
Installation notes
Recommended installation positions The globe valve may be mounted upright to horizontal. It is not permissible to mount the globe
valves with the stem pointing downwards.
Water quality requirements The water quality requirements specified in VDI 2035 must be adhered to.
Belimo valves are regulating devices. For the valves to function correctly in the long term, they
must be kept free from particle debris (e.g. welding beads during installation work). The
installation of a suitable strainer is recommended.
www.belimo.com H7..N • en-gb • 2021-11-23 • Subject to change 2/4
Technical data sheet H7..N
Servicing Globe valves and globe valve actuators are maintenance-free.
Before any service work on the final controlling device is carried out, it is essential to isolate the
globe valve actuator from the power supply (by unplugging the electrical cables if necessary).
Any pumps in the part of the piping system concerned must also be switched off and the
appropriate slide valves closed (allow all components to cool down first if necessary and always
reduce the system pressure to ambient pressure level).
The system must not be returned to service until the globe valve and the globe valve actuator
have been reassembled correctly in accordance with the instructions and the pipeline has been
refilled by professionally trained personnel.
Flow direction The direction of flow, specified by an arrow on the housing, is to be complied with, since
otherwise the valve could become damaged.
Differential and close-off pressure
The maximum differential and close-off pressure of globe valves depends on the mounted
globe valve actuator. To ensure optimum operation and maximum service life, the maximum
differential and close-off pressure in the table below must not be exceeded.
www.belimo.com H7..N • en-gb • 2021-11-23 • Subject to change 3/4
Technical data sheet H7..N
Dimensions
Dimensional drawings
X/Y: Minimum distance with respect to the valve centre.
The actuator dimensions can be found on the respective actuator data sheet.
Further documentation
• The complete product range for water applications
• Data sheets for globe valve actuators
• Installation instructions for valves and/or globe valve actuators
• Notes for project planning 2-way and 3-way globe valves
www.belimo.com H7..N • en-gb • 2021-11-23 • Subject to change 4/4