TC-2060 Instruction Manual V05
TC-2060 Instruction Manual V05
Tension Controller
      TC- 2060
 Instruction Manual
     TC-2060
                                                                                                                     RUN
ERROR
                                                                                                                     Kg
             TNSN.        3.0       KGF
             PUAUTO       3.0       KGF                                                                               N
             TQOUT        2.8V      V
             COUNT        120       PPR                                                                               %
MANUAL AUTO
SET P
6. Specification ---------------------------------------------------------------- 20
7. Application ---------------------------------------------------------------- 22
8. Communication ------------------------------------------------------------------- 43
                                               1
1. Introduction
1-1 Function and feature
TC-2060 High Performance Tension Controllers receives the signal from LMS series Tension
Detector (Load Cell) to control the web tension for the unwinding of long materials, the
guiding of middle roller, the rewinding of web material automatically. They can output
0~10Vdc, 4~20ma of torque or speed command signal to drive the servomotor drive, inverter.
TC-2060 even contains the driving amplifier (0~24Vdc max. 5A output) to control the
magnetic powder clutch, brake, or hysteresis clutch and brake to get constant tension
control.
Features:
(1) Setting up simple parameters to get tension control.
(2) High-tension stability, multifunctional parameters, which is adaptable to different kinds of
    material processing of industrial machine.
(3) Setting up and operating digitally, it is easy to operation and management.
(4) Having function of field economizing to the magnetic powder clutch, it can improve the
    issue of thread engagement and control effectively for low speed-high torque and
    acceleration and deceleration in the start of motor.
                                         Line線速度輸入
                                              Speed Input
                                            捲曲速度輸入
                                        Winding Speed Input
                             Power
                               電源                                                                                                                      啟動
                                                                                                                                                       Start/ 停止
                                                                                                                                                              / Stop接點輸入
                                                                                                                                                                     Contact Input
                          AC 180~245V
                           50/60HZ
                                                                                                                                                                      張力檢測器
                                                                                                                                                                     Tension Detector
                                           TC-2060
                                                                                                                                               RUN
ERROR
                                                                                                                                                Kg
                                                   TNSN.       3.0    KGF
                                                   PUAUTO      3.0    KGF                                                                       N
                                                   TQOUT       2.8V   V
                                                   COUNT       120    PPR                                                                       %
                                                                                                 MANUAL                       AUTO
                                             SET                               P
                                                                                             TENSIONSET                   TENSIONSET
                                                                                              4 5 6                        4 5 6
                                                   ON
                                                         D.RESET   LOCK     OUTPUT       3                7           3                7
                                                                                     2                        8   2                        8
                                                   OFF                                   1                9           1                9
                                                                                             0       10                   0      10
                                                                                                                                                                          TENSION DETECTOR
                                                                                                                                                                             LOAD CELL
            磁粉煞車器
            Magnetic Powder Brake       驅動器
                                        Drive                                                                                                                         驅動馬達
                                                                                                                                                                     Driving Motor
                                                                   2
1.2 Operation panel
                                                                                                                                                       張力顯示
                                                                                                                                                       Tension      (9)(9)
                                                                                                                                                               Display
                                TC-2060
                                                                                                                                                       運轉指示
                                                                                                                                                       Operation    (10) (10)
                                                                                                                                                                 Indicator
                                                                                                                                                       異常指示
                                                                                                                                                       Error Indicator(11)
                                                                                                                                                                       (11)
 (1)(1) 張力顯示值
                                                                                                                                                RUN
        & 參數顯示
     Parameter Display                  TNSN.
                                        PUAUTO
                                        TQOUT
                                                     3.0
                                                     3.0
                                                     2.8V
                                                               KGF
                                                               KGF
                                                               V
                                                                                                                                                Kg
                                                                                                                                                 N
                                                                                                                                                       張力指示單位
                                                                                                                                                       Tension Unit (12) (12)
                                        COUNT        120       PPR
                                                                                                                                                       輸出百分比量 Ratio (13) (13)
                                                                                                                                                 %
                                                                                                                                                       Output
 (2)(2) 參數設定鍵
     Parameter Setting Key                                                                                                                             顯示循環鍵
                                                                                                                                                       Circular         (14)(14)
                                                                                                                                                                Display Key
                                                                                           MANUAL                          AUTO
           (3)Key
 (3) Setting                      SET                                    P                                                                             自動操作
                                                                                                                                                       Auto.        (15)
                                                                                                                                                             Operation (15)
         (4) Key
 (4) Decrease
                                                                                      TENSION SET
                                                                                       4     5   6
                                                                                                                      TENSION SET
                                                                                                                       4    5     6
                                                                                                                                                       手動操作
                                                                                                                                                       Manual     (16) (16)
                                                                                                                                                              Operation
                                               D.RESET      LOCK     OUTPUT       3                   7           3                    7
                                          ON
          (5) Key
 (5) Increase
                                        OFF
                                                                              2                           8   2                            8           自動張力設定
                                                                                                                                                       Auto.              (17)
                                                                                                                                                             Tension Setting (17)
                                                                                  1                   9           1                    9
       (6) 電源開關
 (6) Power Switch                                                                      0         10                    0          10
       (8) 操作鎖定
 (8) Operation Lock                                                                                                                                    輸出鍵
                                                                                                                                                       Output Key(19)
                                                                                                                                                                  (19)
(1)Tension Value or Parameter Display: Normal display is tension Kg value or ouput state
    display; Parameter display is the display of parameter name and content.
(2) Parameter Setting Key or Taper Tension Setting Key: Normal setting is the tension value
    setting and the parameter display is the parameter content; Press key for 3 second, then
    the key become taper tension setting key.
(3)Setting Key / Change Key: The normal is input key; The key is Change Key and Input Key
    when setting parameter.
(4)Decrease Key: Decrease value or jump down to the next value in the setting of tension or
    parameter.
(5)Increase Key: Increase value or jump up to the next value in the setting of tension or
    parameter.
(6)Power Switch: Power Operation ON/OFF.
(7)Diameter Reset: The key of diameter reset.
(8)Operation Lock: The key of operation lock.
(9)Tension Display(LED): Display tension value(Kg, N, %), it is switched by the circular
    display key.
(10)Operation Indicator: Light ON at operation (Only the controller has output and control),
     when the Light is flashing, it means the controller is in retention tension control (The
     “STALL” terminal is enabled.
(11)Error or Fault Indicator: Error indication(when the light is flashing, it means the output is
     at max. or 0V, but the tension value isn’t at the setting value).
(12)Tension Unit: Display the tension value(Kg, N, %).
(13)Output Ratio: The light ON, the LED display is the output ratio.
(14)Circular Display Key: The switch key for LED display function.
(15)Auto. Operation Lamp: Automotive operation mode.
(16)Manual Operation Lamp: Manual operation mode.
(17)Auto. Tension Setting knob: Adjust tension setting(The Auto. Operation Lamp is ON).
     (The internal parameter could be selected by        key or using this knob to adjust tension,
     or input from terminal of external VR).
(18)Manual Tension Setting Knob: Adjust the tension setting(The Manual Operation Lamp is
     ON). (The internal parameter could be selected by          key or using this knob to adjust
     tension, or input from terminal of external VR).
(19)Output Key: Whwn the OUTPUT lamp is ON, controller has output(Output Key control
     the controller’s output); When the lamp is OFF, controller doesn’t have output.
                                                                        3
1.3 Function of DIP switch
   Function of SW1: Control feedback loop TQOUT,NROUT,SPOUT,FBKOUT; Signal
                     Selection (-10V~0~+10Vdc / -5V~0~+5Vdc switching).
                               250
         179
156
                         ¸ ¨¦ Mounted
                       Floor  a¦ ¡ ¦ w̧ Ë                                   Wall
                                                                            ¾À± ¾¦Mounted
                                                                                   ¡ ¦ w̧ Ë
                                                                  170
                                                      150
                    Opening dimension of
                       ±
                        ª O            }¤ Õ
                           ® r¤ J¦ ¡¶ type
                    Panel-inserted        ¤ Ø
                                            ¤ o
156
                                229
                                                                          ± ® r¤ J¦ ¡¦ w̧Mounted
                                                                           ª O
                                                                        Panel-inserted     Ë
                                                                                       ³Unit:
                                                                                         ¦ ì:mm
                                                                                         æ    mm
                                                  4
2.2 Wiring
Wiring method and cautions
 Please select the shielding cable as for I/P and O/P signal line, following the wiring
    diagram listed below in wiring.
 The wire diameter of Power Line is 0.75mm (minimum).
 Please also select shielding cable or independent cable as for I/P line at the digital input
    terminal.
 Please do not put the cable of control signal and the power cable in one pipe or bundle
    them together.
 Please do the grounding well. (Select the wire with above 2.0mm diameter).
 Concerning interference and noise please control the length of wire within 10m.
                                              5
Wiring Diagram:                 Example of “Compression” LOAD CELL
                            SHIELD
                            WIRE
                                       0V                                PN
           COMMUNICATION              485B                               PP
                  RS 485              485A
                                                                                             POWDER NEW REEL
                                       0V
                    PLUSE
                                      SENS                              P12V
                  SENSOR
                                      +12V                              N12V
          TORQUE CONTROL
         OUTPUT 0~+10Vdc  ¡ ¡         TQOUT
                                       0V
                                                                                BLACK
                                                                        BLKR
                          ¡ ¡
                                                                                WHITE
           SPEED CONTROL              SPOUT                             WH-R
                                                                                GREEN
         OUTPUT 0~+10Vdc               0V                               GR-R
                                                                                RED
                                                                        RED-R
                          ¡ ¡
                                                                                SHIELD
          TORQUE CONTROL              4~20mA                            SG-RL
                                                                                         TENSION DETECTOR
           OUTPUT 4~20mA               0V                                                    LOAD CELL
                          ¡ ¡
             NEW REEL
                                      NROUT
         TORQUE CONTROL                                                         SHIELD
         OUTPUT 0~+10Vdc               0V                               SG-RL
                                                                                BLACK
                                                                         BLKL
                                                                                WHITE
           TENSION METER              FBKOUT                            WH-L
                            M                                                   GREEN
                0~+10Vdc               0V                               GR-L
                                                                                RED
                                                                        RED-L
                                                                                         TENSION DETECTOR
                                                                                             LOAD CELL
         EXTERNAL TENSION              0V
         SETTING 0~+10Vdc             TENS                              MC4                   HAND / AUTO
                          ¡ ¡
            MULTI ANALOG
            SIGNAL INPUT
                                      ADIN2                             MC1                    SELECTION
                0~+10Vdc              ADIN1                             COM
           WINDER SPEED                0V
                0~+10Vdc              WIND                              COM                    DIAMETER RESET
                                                                       REST                     & FAULT RESET
Note:
   For “PULL-STRETCH” LOAD CELL, only switch the green wire and white wire of LOAD
    CELL(white wire connect to “GR”; green wire connect to “WH”).
   When TC-2060 leaves factory, the default line speed has been set to the maximum
    speed (the terminal of “+10V” is shorted to the terminal of “LINE”), otherwise the
    TC-2050P can’t be operated normally. If the TC-2060 will follow the production speed of
    system, opening the short connection between the terminal “+10V” and “LINE”, and
                                                         6
     input voltage 0 ~ +10V to the terminal of “LINE”.
    In the application of “Central Winding”, if there is no feedback speed signal, please also
     input voltage 0 ~ +10V to the terminal of “WIND”, it can avoid the calculation error of
     diameter (the diameter will be calculated to maximum value, and the “SPOUT” speed
     voltage will be less when the diameter is more).
                                               7
2.3 Dimension
                8
3. Parameter and Explanation
3.1 Setup of parameters
         生產操作Operation
         Production
         ± i¤ O³ Setting
         Tension  ]© w                                                                                                                                           衰減設定
                                                                                                                                                                 Taper Tension Setting
            TC-2060
                                                                                                                       RUN                                                                                                                                                                       TC-2060
                                                                                                                                                                                                                                                                                                                                                                                                                        RUN
                                                                                                                      ERROR
                                                                                                                                                                                                                                                                                                                                                                                                                       ERROR
                                                                                                                       Kg
                    TNSN.        3.0    KGF
                                                                                                                                                                                                                                                                                                                                                                                                                         Kg
                    PUAUTO       3.0    KGF                                                                             N                                                                                                                                                                                  TNSN.           3.0       KGF
                    TQOUT        2.8V   V                                                                                                                                                                                                                                                                  PUAUTO          3.0       KGF                                                                                 N
                    COUNT        120    PPR                                                                             %                                                                                                                                                                                  TQOUT           2.8V      V
                                                                                                                                                                                                                                                                                                           COUNT           120       PPR                                                                                 %
                                                                     MANUAL                          AUTO
                                                                                                                                                                                                                                                                                                                                                                 MANUAL                            AUTO
              SET                                  P
                                                                                                                                                                                                                                                                                                    SET                                         P
                                                                TENSION SET                     TENSION SET
                                                                 4     5   6                                                                                                                                                                                                                                                                                TENSION SET                       TENSION SET
                                                                                                 4
                           D.RESET             OUTPUT                                                                                                                                                                                                                                                                                                        4     5      6                         5
                      ON                                    3                   7           3                                                                                                                                                                                                                                                                                                  4          6
                                                                                                                                                                                                            OUT                                                                                                  D.RESET                   OUTPUT       3                     7           3                    7
                                                        2                           8   2                         8                                                                                                                                                                                        ON
                    OFF                                                                                                                                                                                                                                                                                                                             2                             8   2                            8
                                                            1                   9           1                 9
                                                                                                                                                                                                                                                                                                           OFF                                          1                     9
                                                                 0         10                    0                                                                                                                                                                                                                                                                                        1                    9
                                                                                                                                                                                                                                                                                                                                                             0         10                      0          10
        ° Ñ
          ¼Æ³ ]© Setting
       Parameter ¤ èª k Procedure
                 w
                                                                                                                                                                                                                                                                                                 TC-2060
                                                                                                                                                                    TC-2060                                                                                                                                                                                                                                             RUN
                                                                                                                                                                                                                                                                                                                                                                                                                       ERROR
                                                                                                                                                                                                                                                                                    RUN
                                                                                                                                                                                                                                                                                                                                                                                                                        Kg
                                                                                                                                                                                                                                                                                   ERROR                  TNSN.        3.0           KGF
                                                                                                                                                                                                                                                                                                          PUAUTO       3.0           KGF                                                                                 N
                                                                                                                                                                                                                                                                                    Kg
                                                                                                                                                                            TNSN.           3.0    KGF                                                                                                    TQOUT        2.8V          V
                                                                                                                                                                            PUAUTO          3.0    KGF                                                                               N                    COUNT        120           PPR                                                                                 %
                                                                                                                                                                            TQOUT           2.8V   V
                                                                                                                                                                            COUNT           120    PPR                                                                               %
MANUAL AUTO
                                                                                                                                                                                                                               MANUAL                          AUTO                                                                            P
                                                                                                                                                                      SET                                    P
                                                                                                                                                                                                                                                                                                                                                            TENSION SET                       TENSION SET
                                                                                                                                                                                                                                                                                                                                                                   5                                5
                                                                                                                                                                                                                                                                                                                                                             4         6                       4          6
                                                                                                                                                                                                                          TENSION SET                     TENSION SET
                                                                                                                                                                                                                                                                                                                 D.RESET          LOCK     OUTPUT       3                     7           3                    7
                                                                                                                                                                                                                           4     5   6                          5                                          ON
                                                                                                                                                                                                                                                           4          6
                                                                                                                                                                                      D.RESET            OUTPUT       3                   7           3                    7                                                                        2                             8   2                            8
                                         OUT                                                                                                                                    ON
                                                                                                                                                                                                                  2                           8   2                            8                                                                        1                     9           1                    9
                                                                                                                                                                                OFF
                                                                                                                                                                                                                                                                                                                                                             0         10                      0          10
                                                                                                                                                                                                                      1                   9           1                    9
                                                                                                                                                                                                                           0         10                    0          10
         the same time, then                                                                                                      parameter begin to falsh Parameter content                                                                                                                  then the “parameter setting”
         going to “parameter                                                                                                                                                                                                                                                                  is completed.
         setting”
OUT
                     « ö
        If parameter doesn’t be            ¤ £« ö¥ press
                                   Á ä If doesn’t    ô¦ óÁ äany key,
        changed, press   or          it will exit out the                                                                   P
                                                                                                                                                             9
3.2 Structure diagram of parameters
ALL PARAMETER
                                   MODE
                                   RATIO
                                             10
 3.3 List of parameters
 MAIN PARAMETER GROUP
                      SYMBOL                           SETTING
 SYMBOL                                DEFAULT                              EXPLANATION
                   DESCRIPTION                          RANGE
 MAIN                                                                Function programming for
                Main parameter
 PARAMETER                                                           main parameter
 TAPER                                                               Function
                Taper function of
                                                                     programming for
 PARAMETER      parameter group
                                                                     taper tension
 FUNC                                                                Assigned function
                Function parameter
                                                                     programming for Digital &
 PARAMETER      group
                                                                     Analog Input
 PID
                PID parameter group                                  Function programming for PID
 PARAMETER
 FBK            Specification                                        Function programming for
 PARAMETER      parameter group                                      specification
3.3.1:MAIN PARAMETER
                     SYMBOL
 SYMBOL                               DEFAULT         SETTING RANGE            EXPLANATION
                  DESCRIPTION
                                                                           0: Computing of line
                                                                              speed and winding
                                                     0: DIVIDER
 DIAMETER                                                                     speed
                Source of diameter
                                      DIVIDER        1: SENSOR             1: Proximity switch
 SOURCE         detection
                                                                              length calculation
                                                     2: TB(DIAMETER )      2: External diameter
                                                                              signal terminal input
                Ratio of line speed
 LINE RATIO                            100.0%            10~500.0%         LINE terminal input
                signal input
                Ratio of winding
 WIND RATIO                            100.0%             0~500.0%         WIND terminal input
                feedback signal
                                                11
TENS RATIO    Ratio of signal        100.0%           0~500.0%       TENS terminal input
                                                                     Use range(%) of
AUTO VR                                                              tension setting for
              Ratio of signal        100.0%           0~100.0%
MAXIMUN                                                              panel’s VR (including
                                                                     Terminal “TENS”)
MECH          Acceleration                                           Compensation amount
                                     100.0%           0~999.9%
COMPANSION    compensation                                           in acceleration
                                                                     Brake is multiplied
              Brake value within                                     owing to “STOP
STOP RATIO                           100.0%           0~500.0%
              the STOP time                                          RATIO” multiply by the
                                                                     diameter value
MAXIMUN
              Maximum diameter       1000mm          300~5000mm
DIAMETER
                                              12
MINIMUN
              Minimum diameter      100mm             50~300mm
DIAMETER
                                                                       When the parameter
                                                                       “DIAMETER SOURCE”
              Thickness setting
THICKNESS                            120um           10~10000um        is set to “SENSOR”,
              of winding material
                                                                       this parameter will be
                                                                       displayed
                                                                       When the parameter
DIAMETER                                              0=0~10VDC        “DIAMETER SOURCE”
              Logic selection of
                                    0~10VDC                            is set to “TB”, this
LOGIC         supersonic                              1=10~0VDC        parameter will be
                                                                       displayed
                                                                       When the parameter
DIAMETER      Zero point                                               “DIAMETER SOURCE”
              adjustment of           0.0V          -5.00V~+5.00V      is set to “TB”, this
ZERO          supersonic                                               parameter will be
                                                                       displayed
                                                                       When the parameter
DIAMETER                                                               “DIAMETER SOURCE”
              Multiple ratio of
                                    100.0%             0~500.0%        is set to “TB”, this
SPAN          supersonic
                                                                       parameter will be
                                                                       displayed
                                                                       When “RUN” terminal
START         Start torque                                             starts, then output
                                      0V              0 ~ +10Vdc
TORQUE        compensation                                             torque compensation
                                                                       right away
              Auto   run                                                 Parameter MANUAL
  MANUAL
              MANUAL VR               0V              0~+10VDC            VR SELECT=AUTO
  VR SCAL
              adjustment                                                   BIAS SET Enable
3.3.2:TAPER PARAMETER
                  SYMBOL
 SYMBOL                             DEFAULT       SETTING RANGE           EXPLANATION
               DESCRIPTION
  TAPER
                                                  0: LINER          0: Linear
            Mode setting of taper
  MODE                               LINER                          1: Non-Linear (multi
            tension curve                         1: NON-LINER         sectional, irregular)
   SELE
                                             13
  TAPER     The #1 turning                                         According to diameter
            point’s setting value                                  value(under the turning
   TENS                             300mm            0~2000mm
            of non-linear taper                                    point, the tension won’t be
   SET1     tension                                                tapered)
  TAPER     The #2 turning
            point’s setting value                                  According to diameter
   TENS                             500mm            0~2000mm
            of non-linear taper                                    value
   SET2     tension
  TAPER     The #3 turning
            point’s setting value                                  According to diameter
   TENS                             800mm            0~2000mm
            of non-linear taper                                    value
   SET3     tension
                                                  TENSION
                                                                   0: Jog increase for tension
                                                                      setting
   MC1                                            0: INCHING ADD
                                    INCHING                        1: Jog decrease for
            Function selection of
  SELECT                                          1: INCHING DEC      tension setting
            MC1 terminal             ADD                           2: Output signal is
   FUNC                                           2: OUT REMOTE       controlled by external
                                                                      remote control
                                             14
                                                                       0: Jog increase for tension
    MC2                                            0: INCHING ADD         setting
                                     INCHING                           1: Jog decrease for
             Function selection of
  SELECT                                           1: INCHING DEC         tension setting
             MC2 terminal              DEC                             2: Output signal is
   FUNC                                            2: OUT REMOTE          controlled by external
                                                                          remote control
                                                   0: NO FUNCTION      0: NO
                                                                       1: New reel’s tension
    AD1                                            1: NEW                setting
             Function selection of     NO                              2: Taper tension setting
  SELECT                                             REELVALUE
             AD1 Analog Input        FUNCTION                          3: Tension detecting
   FUNC                                            2: TAPER (linear)      input(power input is
                                                                          0~+/-10V without load
                                                   3: TENSION(FBK)        cell)
                                                   0: NO FUNCTION      0: NO
                                                                       1: New reel’s tension
    AD2                                            1: NEW                setting
             Function selection of     NO                              2: Taper tension setting
  SELECT                                           REELVALUE
             AD2 Analog Input        FUNCTION                          3: Tension detecting
   FUNC                                            2: TAPER (linear)      input(power input is
                                                                          0~+/-10V without load
                                                   3: TENSION(FBK)        cell)
                                                   0=MANUAL %
  MANUAL          Operation                                            0=MANUAL % :Manual
                                     MANUAL        1=AUTO BIAS
    VR           MANUAL VR                                             1=AUTO BIAB SET:
                                        %          SET
  SELECT            Select
                                              15
                                                                    The setting and actual
  TENSION                                              0~Scale      error are within the range
              Section 2 breakpoint
                                       1.0KG                        between PID FEEL and PID
  PID SLP1    of tension error                       (parameter)    SLP1 will be regarded as
                                                                    section 2
  TENSION     Tension error ratio of
                                       30.0%          0~500.0%
  CP GAIN     section 1                                             The section within PID
                                                                    FEEL and PID SLP will be
   TENSI      The rising time of                                    corrected by PI
              section 1 tension        150S            0~5000S
  CI+ GAIN    error integrator
                                                    0: REELS
LOADCELL       Load cell’s quantity                                  0: Two side detection
               and right-left side     REELS        1: L- REEL       1: Left single side
SELECT         Selection                                             2: Right single side
                                                    2: R- REEL
ZERO TUNE      Load cell’s tension
               Zero Reset               0.0KG       -SCALE~+SCALE
TEST           Correction
SPAN TUNE      Load cell’s tension
               highest point           0~500%       0~500%
TEST           correction
                                               16
3.3.6:DISP PARAMETER(parameter)
                    SYMBOL
SYMBOL                              DEFAULT         SETTING RANGE           EXPLANATION
                 DESCRIPTION
                                                    0~2(the value of   The number setting of
DISPLAY       The decimal point
                                                    tension setting    decimal point(the value
              number of tension     1
POINT                                               and display are    of tension setting and
              setting
                                                    valid)             display)
                                                                       4: Voltage of “ADIN2”
                                                    4: ADIN2              terminal
                                                                       5: Voltage of torque
DISP NO.3     The third row LCD    TORQUE           5: TORQUE OUT         command
              source selection
SOURCE                              OUT             6: NR OUT          6: Voltage of “NR OUT”
              display
                                                                         terminal
                                                    7: SP OUT          7: Voltage of “SP OUT”
                                                                         terminal
3.3.7:SERIAL PARAMETER(communication)
                    SYMBOL
  SYMBOL                            DEFAULT         SETTING RANGE           EXPLANATION
                 DESCRIPTION
                                               17
                                                                    0: External terminal
                                                                       control
                                                                       (RS-485 Read function
                                                                       is available)
                                                                    1: Digital input &
                                                                       parameter & SV
                                                   0:OUTSIDE TB        tension setting value
COMMAND                                            1:SERIAL            are controlled by
             Selection of digital
                                    OUTSIDE TB                         RS-485
             input command                         2:TB
SELECT                                                                 communication
                                                   (SV=RS485)       2: Digital input is
                                                                       controlled by terminal.
                                                                       Parameter & SV
                                                                       tension setting value
                                                                       are controlled by
                                                                       RS-485
                                                                       communication
                                                                    0: External terminal
                                                                       control
                                                                       (RS-485 Read function
                                                                       is available)
                                                                    1: Analog input &
                                                   0:OUTSIDE TB        parameter & SV
SINGLE                                             1:SERIAL            tension setting value
             Selection of analog
                                    OUTSIDE TB                         are controlled by
             input command                         2:TB
SELECT                                                                 RS-485 communication
                                                   (SV=Rs485)       2: Analog input is
                                                                       controlled by terminal.
                                                                       Parameter & SV
                                                                       tension setting value
                                                                       are controlled by
                                                                       RS-485 communication
                                                                    ☆ When the
                                                                       communication
             Communication                                             function is set, the
SERIAL       address                                                   following parameter
             (the number of             0              0 , 1~31        will be displayed
ADDRESS      station)                                               0: Don’t send back, all
                                                                       receive
                                                                    1~31: station address
                                                   (0)=4800 bps
             Communication baud                                     There are three kinds of
BAUD RATE                              9600        (1)=9600 bps
             rate                                                   baud rate can be set
                                                   (2)=19200 bps
                                                   0: NO PARITY
                                              18
                                                                0: Drive stops running
                                                0: DRIVE STOP   1: Drive stops running
                                                                   when the
                                                1: SERIAL          communication format
 SERIAL      Drive response state
                                                                   is not correct.
             after abnormal         RUNNING       FAULT/OT
                                                                2: if the communication
 ALARL SET   communication
                                                2: DRIVE           format is correct, but
                                                                   the communication is
                                                  RUNNING          interrupted, the drive
                                                                   keeps on running
                                           19
3.4 Parameter Explanation
                                              20
                  multi-function terminal for tension jog increase setting or tension jog
                  decrease setting(“SV” + “INCH ADD” or “DEC” equal to the actual tension
                  setting value).
PRESET SET VALUE: New reel’s tension pre-setting value, this setting are sent from
                          terminal “PRV”, “NRV”(0~24V), “NROUT”(0~+10V) separately for
                          providing new reel’s pre-tension.
CUT ADD/TE VALUE: The increased-tension in changing reel and cutting materials. In the
                         time of changing reel, tension setting value of changing reel and
                         cutting materials.
PRESET SET TIME: The time of changing reel. It will be enabled every time that “CHANGE”
                       terminal (Vs “COM” terminal) be opened or closed. The corresponding
                       cutting movement will be executed within this time.
START TORQUE: Start Torque compensation : Running Enable
STOP TIME: STOP TIME will be enabled and counted when “RUN” terminal(Vs “COM”
             terminal)is opened. There are two kinds of selection will be provide; One is PID
             is controlled continuously, the other is STOP RATIO for brake. In general, this
             parameter must be set as same as the time of speed decrease(the time from
             system off to zero speed). When the “RUN” terminal is opened, STOP TIME
             will be the delay time of system until the motor is stopped.
STOP FUNC SELE: The mode selection at stop. The measures be done within STOP
                      TIME(same as above).
STOP RATIO: The brake amount within STOP TIME; If select STOP RATIO within STOP
TIME, the brake amount will be the setting value of parameter multiply the current diameter
amount.
MAXIMUN DIAMETER: The maximum diameter amount of winding reel or unwinding reel.
MINIMUN DIAMETER: The minimum diameter amount of winding reel or unwinding reel.
THICKNESS: The thickness setting of winding materials. It is used to provide to SENSOR
              for calculating diameter. This parameter is only displayed when DIAMETER
              SOURCE is assigned to SENSOR.
START TORQUE: Start torque compensation. When “RUN” terminal is started, the start
                   torque compensation is sent out immediately, it can adjust this parameter
                   to overcome the slow start, which is caused by mechanical static friction.
TAPER RATIO: Linear taper tension; this parameter is valid when the “TAPER MODE
             SELE” is set to linear( the value of taper ratio is the multiplier, setting 100%
             means the tension won’t be tapered; setting 90% means the tension is
             attenuated 10%).
                                             21
When select “NON-LINER”(Non-linear), the following parameters will be valid.
TAPER TENS SET1: The #1 turning point’s setting value of non-linear taper tension;
                 according to diameter amount, under the turning point, the tension
                 won’t be tapered.
TAPER TENS SET2: The #2 turning point’s setting value of non-linear taper tension; when
                 diameter amount is between this parameter and “TAPER TENS SET1”,
                 then “TAPER SET RATIO1”(Taper Ratio) is the taper amount.
TAPER TENS SET3: The #3 turning point’s setting value of non-linear taper tension; when
                 diameter amount is between this parameter and “TAPER TENS SET2”,
                 then “TAPER SET RATIO2”(Taper Ratio) is the taper amount.
TAPER SET RATIO1: The taper ratio between #1 turning point and #2 turning point(this
                  parameter is multiplier), setting 100% means the tension won’t be
                  tapered; setting 90% means the tension is attenuated 10%.
TAPER SET RATIO2: The taper ratio between #2 turning point and #3 turning point(this
                  parameter is multiplier), setting 100% means the tension won’t be
                  tapered; setting 90% means the tension is attenuated 10%.
TAPER SET RATIO3: The taper ratio above #3 turning point(this parameter is multiplier),
                  setting 100% means the tension won’t be tapered; setting 90%
                  means the tension is attenuated 10%.
                                                                                       TAPER
                                                                TENSION                TENS
                                                                  SET                   SET1
                                                                 RATIO1                     TAPER
                        TARGET                                                              TENS
                        TENSION        PORTION OF DECREASE                                   SET2                      PORTION OF DECREASE
                                              DUE               TENSION                                               DUE TO TAPER SET RATIO3
                                                                  SET                                 TAPER
                                                                 RATIO2                               TENS
                                                                                                       SET3
                                                                TENSION
                                                                  SET
                                                                 RATIO3
                                                                22
1:INCHING DEC : Jog-decrease tension setting
2:OUT REMOTE : Output signal is controlled by external remote control
RLY FBK HI/LOW: Tension detection’s relay moving point; according to the above
                parameter “RLY SELECT FUNC” setting, if the mode is set to “HIGH”,
                detection is higher than relay moving point, then the relay will be active;
                if the mode is set to “LOW”, detection is lower than relay moving point,
                then the relay will be active.
                                             23
                      SLP” and “TENSION PID SLP1”, then the parameters value of
                      “TENSION CP 1 GAIN”, “TENSION CI1+ GAIN”, “TENSION CI1-
                      GAIN” will be as correction, if the value is larger than “TENSION PID
                      SLP1”, then the parameter value of “TENSION CP2 GAIN”,
                      “TENSION CI2+ GAIN”, “TENSION CI2 - GAIN” will be as correction.
TENSION CP GAIN: The first section’s tension slip ratio(0~500%)
TENSION CI+ GAIN: The rising time of the first section’s tension error integrator(0~500S);
                  when the setting value is larger than the actual value, the integrator
                  must increase progressively.
TENSION CI- GAIN: The falling time of the first section’s tension error integrator(0~500S);
                  when the setting value is smaller than the actual value, the integrator
                  must decrease progressively.
“CP”, “CI+”, “CI-“ will be as the calculation facor for PID in the first section
breakpoint(when the setting value is larger or smaller than actual value, integrator can set
the increased or decreased integral time separately. The more value of “CP” is, the more
amount of positive compensation is. The more value of “CI” is, the more integral time
is(correction will be more slow).
TENSION CP1 GAIN: The second section’s tension slip ratio(0~500%)
TENSION CI1+ GAIN: The rising time of the second section’s tension error
                   integrator(0~500S); when the setting value is larger than the actual
                   value, the integrator must increase progressively.
TENSION CI1- GAIN: The falling time of the second section’s tension error
                   integrator(0~500S); when the setting value is smaller than the actual
                   value, the integrator must decrease progressively.
“CP1”, “CI1+”, “CI1-“ will be as the calculation facor for PID in the second section
breakpoint(when the setting value is larger or smaller than actual value, integrator can set
the increased or decreased integral time separately. The more value of “CP” is, the more
amount of positive compensation is. The more value of “CI” is, the more integral time
is(correction will be more slow).
TENSION CP2 GAIN: The third section’s tension slip ratio(0~500%)
TENSION CI2+ GAIN: The rising time of the third section’s tension error integrator(0~500S);
                   when the setting value is larger than the actual value, the integrator
                   must increase progressively.
TENSION CI2- GAIN: The falling time of the third section’s tension error integrator(0~500S);
                   when the setting value is smaller than the actual value, the integrator
                   must decrease progressively.
“CP2”, “CI2+”, “CI2-“ will be as the calculation facor for PID in the second section
breakpoint(when the setting value is larger or lower than actual value, integrator can set the
increased or decreased integral time separately. The more value of “CP” is, the more
amount of positive compensation is. The more value of “CI” is, the more integral time
                                              24
     is(correction will be more slow).
No Correction
                                                                               No Correction
     CP2 GAIN        CP1 GAIN           CP GAIN         ¤£                     ¤£                CP GAIN          CP1 GAIN          CP2 GAIN
     CI2- GAIN       CI1- GAIN          CI- GAIN         ×                     ×               CI+ GAIN         CI1+ GAIN         CI2+ GAIN
                                                        ¥¿                     ¥¿
   The setting is   The setting is    The setting is                                           The setting is    The setting is   The setting is
     ³ ]©w
   smaller ¤than
              ©ó
              p        ³ ]©w
                    smaller ¤   ©ó
                                p
                             than        ³ ]©w
                                      smaller ¤   ©ó
                                                  p
                                               than     ¤£                     ¤£                 ³ ]©than
                                                                                               larger  ¤ j©ó
                                                                                                       w            ³ ]©than
                                                                                                                 larger  ¤ j©ó
                                                                                                                         w            ³ ]©  ¤ j©ó
                                                                                                                                            w
                                                                                                                                  larger  than
     ¹ »
       ê  ±
          Ú  ¤
             i  O
   actual tension     ¹  »
                         ê  ±
                            Ú  ¤
                               i
                    actual tensionO      ¹ »
                                           ê  ±
                                              Ú  ¤
                                                 i
                                      actual tensionO    ×                     ×                ¹ »
                                                                                                    ê  ±
                                                                                                       Ú  i¤ O
                                                                                               actual tension       ¹  »
                                                                                                                       ê ± i¤ O
                                                                                                                         Ú
                                                                                                                 actual tension       ¹  »
                                                                                                                                         ê  ± i¤ O
                                                                                                                                            Ú
                                                                                                                                  actual tension
     3Kg
   over   ¥H
        3Kg  ¤W       1 Kg ~ 1Kg
                    between    3Kg    0.1Kg ~1 Kg
                                      between           ¥¿                     ¥¿               0.1Kg ~0.1Kg
                                                                                               between   1 Kg      1 Kg ~ 1Kg
                                                                                                                 between    3Kg       3Kg
                                                                                                                                  over 3Kg¥ H  ¤W
                         ¤§
                    and 3Kg ¶¡        0.1Kg¤and
                                              ¶ ¡ 1Kg
                                              §                                                      ¤§
                                                                                               and 1Kg ¶¡              ¤§
                                                                                                                 and 3Kg ¶¡
PID FILTER TIME: The filter time of tension feedback, the filter time of load cell’s signal
feedback(the longer the time is, the slower the PID is)
     LOADCELL UNIT: The unit of tension detection and display; the setting is: 0:Kgf and 1:N
     LOADCELL SCALE: The specification of load cell; the range is 0 ~ 1000Kg, it is selected
     from load cell(single side) corresponding Kg.
     LOADCELL SELECT: The selection of load cell quantity and left-right side
     0:REELS Two sides detection
     1:L-REEL Single and left side
     2:R- REEL Single and right side
     ZERO TUNE TEST: The zero reset correction of load cell’s tension; the range is –SCALE ~
                     +SCALE.
     Load Cell Zero Reset Correction: When load cell is installed at machine(including roller),
                                      adjusting the display value to “0.0Kg”, then press “SET”
                                      key, the zero reset is completed.
                                                                          25
SPAN TUNE TEST: The highest point correction of load cell’s tension(0 ~ 500Kg).
Load cell highest point correction:
See the following Fig.: Drawing – LOAD(The load should be close to the full scale of Kg no.
                        of load cell.
Example:
If the load is 20Kg, pressing UP/DOWN key for adjusting SPAN value until the tension
display is 20Kg, press SET key, then load cell highest point correction is completed.
   If “LOADCELL L-ALARM”(Left side) and “LOADCELL R-ALARM “(right side) are
    displayed, it means the polarity of detector(load cell) is opposite, please swap the
    GREEN wire and WHITE wire of detector each other, and execuse the correction of
    ZERO and SPAN again.
   ZERO RESET and HIGHEST POINT correction should be completed within one time;
    when the ZERO RESET correction is completed, pressing SET key first, let SPAN
    display be flashing, suspending a Standard Weigt(POISE), the setting SPAN value, if
    the Standard Weight doesn’t be suspended, SET key should also be pressed, make
    SPAN display be flashing, if the SPAN display doesn’t flash, the parameter setting will
    be exited after 5 seconds.
                                                 26
Fun6: DISP PARAMATER GROUP
PUSV: Decimal point’s No. setting of tension setting and display(This parameter is vlaid only
        in the state of tension setting and display).
Setting “0” : It means no decimal point.
SPr: Display percentage(0 ~ 50 times); when SPr is set to 1 time, the display is basic unit,
     the top line display percentage(fixed one digit of decimal point).
                                             27
4. Adjustments and Test Run
4.1 Test Run Procedure
    The required preparation and task for automatic operation should be proceeded as the
    following adjustment:
   (1) Controller installation and wiring.
   (2) Controller DIP switch setting, tension detector adjustment
   (3) To do drive system check through by manual operation.
   (4) Proceeding operation check in the automatic control mode.
   (5) Adjusting operation parameter based on requirement.
   (6) Abnormal check.
   (7) Adjustment ends.
                                              28
(3) SPAN TUNE TEST adjustment of tension detector:
    The load from material which put on the tension detector will be different because of the
    installation angle of detector and passing angle of material. Therefore, it need adjust the
    span and proceed correction.
                                                                           A Standard
                                                                                    懸掛 已知的法碼Weight (POISE) is
                                                                           suspended    負載 Where,
                                                                                            in  ( N ) Load W (N ) =
                                                                           Mass x 9.8m/S2,               2
If “LOADCELL L-ALARM” appeared on the display, it means the stress direction of detector
of left side is opposite; If “LOADCELL R-ALARM” appeared on the display, it means the
                                                        29
stress direction of detector of right side is opposite. Please exchange GREEN wire and
WHITE wire of detector each other, pressing RESET terminal again, and re-execute the
correction of ZERO and SPAN(please refer the wiring diagram; there have two kinds of
wiring; press-type wiring, stretch-type wiring).
                                            30
4.4. The Central Winding or Unwinding Control
   First correctting whether the signal of line speed reach to termial stage “LINE”, “0V”(or
   connect terminal “+10V” and terminal “LINE”). Ensuring whether the feedback signal
   “DC 0 ~ +10V” of winding controller reach to termial stage “WIND”, “0V”.
※ When the mode is central winding(motor drives directly), the signal of line speed and
       motor feedback speed must be connected, so it could extend the functions of tension
       control and taper tension accurately; When using detector for counting length control,
       the signal of line speed shouldn’t be connected, but the signal of motor feedeback
       speed should be connected or connecting the terminal “+10V” to terminal “LINE”.
   ※ When the mode is brakedrive of central winding(magnetic powder brake or clutch),
     please use detector counting length control(diameter calculation), so it could extend
     the functions of tension control and taper tension accurately; The signal of line speed
     should be connected or connecting the terminal “+10V” to terminal “LINE”.
      The operation of this controller(terminal “RUN”) must start or stop with
      drive(Ex. Inverter) together.
※ When the mode is brake drive of central winding(magnetic powder brake or clutch),
      connecting terminal “STALL” to terminal “COM” in the zero speed when stop(the
      “RUN” terminal is not need to ON). Using the setting of retention tension (“STALL
      SV”), the tension setting is less, and rewinding roller will not loosen materials when
      the system is stopped.
※ When the winding feedback speed isn’t connected, please connect “WIND” and
      “LINE” terminal together, it can avoid that the “SPOUT” output speed will be less
      (Because the diameter of material roll is considered to be maximum diameter, and
      the output speed will be less if the diameter is increased progressively).
                                             31
5. Abnormal Message
(1) LOADCELL L-ALARM message: It means the polarity of left side load cell is opposite.
                                          (It is only shown in SPAN correction). Please
                                          exchange the green wire and white wire of left load
                                          cell.
(2) LOADCELL R-ALARM message: It means the polarity of right detector is opposite.
                                         (It is only displayed in SPAN correction). Please
                                         exchange the green wire and white wire of right load
                                         cell.
※ When LOADCELL L-ALARM or LOADCELL R-ALARM message appear, after it is
    corrected, you can reset the controller by connecting “RESET” and “COM” terminal or
    going to parameter setting to set “ZERO” and “SPAN” to clear the abnormal message.
(3) If the controller is in operation, and the panel’s ERROR light is flashing, it means the
    tension is continuous at the condition, which is not enough or is over (the tolerance of
    modification will approach to the value of +/- 10V). Please check the coordination
    condition between parameter and peripherals; for example, the roller is slipped, the front
    take-up roller is pulled by over-tension, or the drive can’t drive…etc.
(4) The “CELL” and the negative value display are flashing alternately: It means the position
    of LOAD CELL is error, and the display is negative Kg. The position offset is because an
    external force affects the load cell. Please check that the position of LOAD CELL Roller
    had offset or was jammed; or the fixed screw of Roller bearing is so long as to interfere
    the internal spring plate. When the above errors or faults were obviated, please install
    and do the adjustment of LOAD CELL again (refer chapter4, section4.2).
                                              32
6. Specification
                        Related
        Item                                                Specification
                        Terminal
                                   AC 180~245V 50/60Hz About 40VA
                           R       Built-in 2A fuse
               Input       T       F.G is earthed based on the third kind of grounding method
                          FG       (The Neutral Line of 3Φ4W Power is connected with the case
                                   of device to “Earth” )
   Power
                                   DC5V                   Power of tension detector:
                         RED-L                            (+) RED wire is connected to RED-L,
               Output                                     RED-R
                         RED-R     OV                     (-) Black wire is connected to BLKL,
                                                          BLKR
                         RUN       Run contact            ON=Auto. RUN      OFF=STOP
                         COM       Common contact         Need to active with drive’s relay together
                                   Input of changing      Normal open is REEL A, Normal close is
                        CHANGE     shaft movement         REEL B
                                   A terminal that
                                   retention tension is   ON= retention tension setting(the other
                                   enabled when           set is SV setting value)
                         STALL
                                   STOP                   OFF=Tension setting in the operation
                                   (“RUN” is flashing)    (SV setting value)
                         ALMA
   Contact                                                Capacity 250VAC, 0.5A, it could be set
               Output    ALMB      RLY output contact
    Signal                                                output of mode types by parameter
                         ALMC
                                   Tension value
                        FBK OUT    output                 Connect tension meter externally,
               Output
                          0V                              0~+10Vdc, Max 5ma
                                   Signal Common
   Signal
                        NR OUT     Output of new
               Output              roller’s torque        0~+10Vdc, Max 5ma
                          0V       signal
                                          33
                                Signal output of
                       4~20ma                         Connect EXTENDED RANGE
                                closed loop
              Output                                  TRANSDUCER(Current to Pressure
                         0V     control(current
                                                      Converter) externally
                                source)
                        GR-L
                                Tension detector input terminal 0~±500mv, Input impedance
                       GR-R
                                20KΩ
                       WH-L
                                (LMSseries)
                       WH-R
                                Input terminal of
                       TENS     external tension
               Input                                  0~+10VDC, Input impedance 20KΩ
                        0V      Signal Common
                                      34
7. Application Examples:
7-1 Central Unwinding Tension Control(cooperating to magnetic powder brake)
   Flow Chart: CIMR-G7 + TC-2060 + BRAKE
                                              Unwinding
                                                                              P owde r
                                                                              Bra ke
                           Loa d Ce ll
     Ta ke -Up
      Rolle r
TC-2060
                                              Ta ke -Up
                            Motor             Inve rte r
                                         35
Related Parameter (Central Unwinding Tension Control – Cooperating to magnetic powder
brake)
(1) Main guiding roller’s inverter (YASKAWA CIMR-G7 series)
    The above listing of parameters are only for reference, please refer the Instruction
    Manual for the other parameters which don’t list.
                                                  36
(2) TC-2060 Tension controller’s related parameters and DIP thumb switch position
      SW1→0~10VDC Position
               Ratio of line
LINE RATIO     speed signal       100.0%         10~500.0%    LINE terminal input
               input
              Ratio of winding
WIND RATIO                        100.0%         0~500.0%     WIND terminal input
              feedback signal
                                            37
             Static friction                                    The setting is enough if the
MECHANISN
             compensation of      0.0V          -5.00V~+5.00V   reel’s state is between
LOSS A
             A reel                                             moving and static
             Static friction                                    The setting is enough if the
MECHANISN
             compensation of      0.0V          -5.00V~+5.00V   reel’s state is between
LOSS B
             B reel                                             moving and static
INITIAL      Initial Tension                                    Setting of initial tension
                                  30.0%           0~100.0%
TENSION      Compensation                                       compensation
             Setting value of
INCH         tension increase                                   MC1~2 termial assigned
                                   5Kg     0~FULL SCALE Kg
ADD/DEC      and decrease
             Pre-setting value                                  Constant Value(Output from
PRESET SET   of new shaft                                       terminal “NROUT”, “P12V”,
                                  50.0%           0~100.0%
VALUE        tension                                            “N12V”
             Increased
CUT ADD/TE   tension in
                                                                T this value are actual
             changing reel       100.0%          0~500.0%       cutting material’s tension
VALUE        and cutting
             material
PRESET SET   Time of                                            Time of changing reel
                                 5.0SEC          0~10.0SEC
TIME         changing reel                                      procedure
MAXIMUN      Maximum
                                 1000mm         300~5000mm
DIAMETER     diameter
MINIMUN      Minimum
                                 100mm           50~300mm
DIAMETER     diameter
                                                                When the parameter
             Thickness                                          “DIAMETER SOURCE” is set
THICKNESS    setting of          120um          10~10000um      to “SENSOR”, this
             winding material                                   parameter will be displayed
                                                                When the parameter
DIAMETER     Logic selection                     0=0~10VDC      “DIAMETER SOURCE” is set
             of supersonic       0~10VDC                        to “TB”, this parameter will
LOGIC                                            1=10~0VDC
                                                                be displayed
                                                                When the parameter
             Zero point
DIAMETER                                                        “DIAMETER SOURCE” is set
             adjustment of        0.0V          -5.00V~+5.00V
ZERO                                                            to “TB”, this parameter will
             supersonic
                                                                be displayed
                                                                When the parameter
DIAMETER     Multiple ratio of                                  “DIAMETER SOURCE” is set
             supersonic          100.0%           0~500.0%      to “TB”, this parameter will
SPAN
                                                                be displayed
                                           38
                                               When “RUN” terminal starts,
START    Start torque
                        0V        0 ~ +10Vdc   then output torque
TORQUE   compensation
                                               compensation right away
                             39
3.2:TAPER PARAMETER (Parameter Setting)
                   SYMBOL
  SYMBOL                          DEFAULT    SETTING RANGE          EXPLANATION
                DESCRIPTION
               The #1 turning
                                                             According to diameter
 TAPER TENS    point’s setting
                                                             value(under the turning
               value of            300mm         0~2000mm
    SET1                                                     point, the tension won’t be
               non-linear taper
                                                             tapered)
               tension
               The #2 turning
 TAPER TENS    point’s setting
               value of            500mm         0~2000mm    According to diameter value
    SET2       non-linear taper
               tension
                                            40
                                             0:PLANE TENSION       0: Operation panel’s VR
   TENSION     Source                                                 setting
                                   PLANE
   SELECT      selection of                  1:PUSH TENSION        1: Up / Down key setting
                                  TENSION
    FUNC       tension setting               2:EXT VR TENSION      2: Input of Terminal “TENS”
                                                                   0: Jog increase for tension
                                                                      setting
               Function                      0:INCHING ADD         1: Jog decrease for tension
 MC1 SELECT                       INCHING                             setting
               selection of                  1:INCHING DEC
   FUNC                             ADD                            2: Output signal is
               MC1 terminal                  2:OUT REMOTE
                                                                      controlledby external
                                                                      remote control
                                                                   0: Jog increase for tension
                                                                      setting
               Function                      0:INCHING ADD         1: Jog decrease for tension
 MC2 SELECT                       INCHING
               selection of                  1:INCHING DEC            setting
   FUNC                             DEC                            2: Output signal is
               MC2 terminal                  2:OUT REMOTE
                                                                      controlledby external
                                                                      remote control
                                                                   0: NO
                                             0:NO FUNCTION         1: New reel’s tension setting
               Function                                            2: Taper tension setting
 AD1 SELECT                          NO      1:NEW REELVALUE
               selection of AD1                                    3: Tension detecting
    FUNC                          FUNCTION   2:TAPER (Linear)         input(power input is
               analog input
                                             3:TENSION(FBK)           0~+/-10V without load
                                                                      cell)
                                                                   0: NO
                                             0:NO FUNCTION         1: New reel’s tension setting
               Function                      1:NEW REELVALUE       2: Taper tension setting
 AD2 SELECT                          NO
               selection of AD2                                    3: Tension detecting
    FUNC                          FUNCTION   2:TAPER (Linear)
               analog input                                           input(power input is
                                             3:TENSION(FBK)           0~+/-10V without load cell)
                                                                   Relay’s function output
     RLY                                     0:HIGH                selection
               Mode selection                                      0: in high tension
   SELECT                           LOW      1:LOW
               of relay action                                     1: in low tension
    FUNC                                     2:ALARM
                                                                   2: abnormal
                                             41
 TENSION CP    Tension error
               ratio of section 1     30.0%        0~500.0%
    GAIN
                                                                The section within PID FEEL
                                                                and PID SLP will be
               The rising time                                  corrected by PI
    TENSI      of section 1
               tension error          150S            0~5000S
  CI+ GAIN
               integrator
               The falling time
    TENSI      of section 1
               tension error          150S            0~5000S
   CI- GAIN
               integrator
 TENSION CP1   Tension error
               ratio of section 2     30.0%        0~500.0%
    GAIN
                                                                The section within PID FEEL
               The rising time                                  and PID SLP1 will be
  TENSI CI1+   of section 2                                     corrected by PI
               tension error           75S            0~5000S
    GAIN
               integrator
               The falling time
   TENSI       of section 2
               tension error           75S            0~5000S
  CI1- GAIN
               integrator
 TENSION CP2   Tension error
               ratio of section 3     30.0%        0~500.0%
    GAIN
                                                                The section which is small
               The rising time                                  than SLP1 will be corrected
  TENSI CI2+   of section 3                                     by PI
               tension error           10S            0~5000S
    GAIN
               integrator
               The falling time
   TENSI       of section 3
               tension error           10S            0~5000S
  CI2- GAIN
               integrator
               The filter time of
  PID FILTER                                                    The filter time of load cell
               tension               100ms            0~500ms
     TIME                                                       feedback signal
               feedback
                                              42
3.6:DISP PARAMETER(Parameter)
                  SYMBOL
  SYMBOL                        DEFAULT      SETTING RANGE               EXPLANATION
               DESCRIPTION
              The decimal                   0~2(the value of      The number setting of
DISPLAY       point number of               tension setting and   decimal point(the value of
                                 1
POINT         tension setting               display are valid)    tension setting and display)
                                                                  0: Voltage of “LINE” terminal
              The first row                 0:LINE INPUT          1: Voltage of “WIND”
DISP NO.1     LCD source         FEED       1:WIND INPUT             terminal
SOURCE        selection          BACK       2TENSION INPUT        2: Tension setting’s value
              display                                             3: Voltage of “ADIN1”
                                            3:ADIN1                  terminal
                                                                  4: Voltage of “ADIN2”
                                                                     terminal
              The third row                 4:ADIN2               5: Voltage of torque
                                TORQUE
DISP NO.3     LCD source                    5:TORQUE OUT             command
                                  OUT
SOURCE        selection                     6:NR OUT              6: Voltage of “NR OUT”
              display                                               terminal
                                            7:SP OUT              7: Voltage of “SP OUT”
                                                                    terminal
                                                                  8: Voltage of “FBK OUT”
                                            8:FBK OUT               terminal
                                            9:SLP                 9: Error amount
                                                                  10: Voltage of error amount
                                            10:PID VOL
                                                                      compensation
              The fourth row                11:DIAMETER           11: Diameter amount
DISP NO.4     LCD source
                                  SP OUT    12:COUNT              12: Counting length amount
SOURCE        selection
                                                                  13: Total amount of tension
              display                       13:FEEDBACK
                                                                  14: Left side load cell’s
                                            14:FBK-L CELL             tension
                                            15:FBK-R CELL         15: Right side load cell’s
                                            16:SERIAL STATUS          tension
                                                                  16: Communication status
3.7:SERIAL PARAMETER(Communication)
                  SYMBOL
  SYMBOL                        DEFAULT      SETTING RANGE               EXPLANATION
               DESCRIPTION
                                                                  0: External terminal control
                                                                     (RS-485 Read function is
                                                                     available)
                                                                  1: Digital input & parameter
                                            0: OUTSIDE TB            & SV tension setting value
              Selection of
  COMMAND                       OUTSIDE                              are controlled by RS-485
              digital input                 1: SERIAL
   SELECT                       TB                                   communication
              command
                                            2: TB (SV=RS485)      2: Digital input is controlled
                                                                     by terminal. Parameter &
                                                                     SV tension setting value
                                                                     are controlled by RS-485
                                                                     communication
                                            0: OUTSIDE TB         0: External terminal control
                                                                     (RS-485 Read function is
              Selection of                  1: SERIAL                available)
   SINGLE     analog input      OUTSIDE     2: TB (SV=RS485)      1: Analog input & parameter
   SELECT     command           TB                                   & SV tension setting value
                                                                     are controlled by RS-485
                                                                     communication
                                            43
                                                                 2: Analog input is controlled
                                                                    by terminal. Parameter &
                                                                    SV tension setting value
                                                                    are controlled by RS-485
                                                                    communication
                                             0 , 1~31            ☆ When the communication
                                                                    function is set, the
               Communication
                                                                    following parameter will
   SERIAL      address
                                   0                                be displayed
  ADDRESS      (the number of
                                                                 0: Don’t send back, all
               station)
                                                                    receive
                                                                 1~31: station address
                                             (0)=4800 bps
               Communication                                     There are three kinds of
 BAUD RATE                         9600      (1)=9600 bps
               baud rate                                         baud rate can be set
                                             (2)=19200 bps
                                             0: NO PARITY
                                   NO
 PARITY SET    Parity setting                1: EVEN PARITY
                                   PARITY
                                             2: ODD PARITY
               Communication                                     The delay time between
 SERIAL TIME   delay interval of   15 ms     5~65ms              command message and
               time                                              response message
               Drive response
               state after                                      0: Drive stops running
               abnormal                                         1: Drive stops running when
               communication                                       the communication format
                                             0: DRIVE STOP         is not correct.
   SERIAL      (Including
               abnormal            RUNNING   1: SERIAL FAULT/OT 2: If the communication
  ALARL SET
               communication                 2: DRIVE RUNNING      format is correct, but the
               format and                                          communication is
               over-time                                           interrupted, the drive
               communication                                       keeps on running
               interrupt)
3.8:INSI PARAMETER (Cipher Parameter)
                                                                 0: Can change any
                                                                    parameter
                                                                 1234: Reset to DEFAULT
    PASS       Cipher                                                  (The power must be
               parameter           0         0~9999                    off and start again
    WORD
                                                                       after setting)
                                                                 1~9999: Can’t change
                                                                         parameter value
                                             44
Application Example Explanation: (Central Unwinding Tension Control – Cooperating to
                                        magnetic powder brake)
1. After running of take-up roller, according to take-up speed for offering TC-2060 as
   reference of line speedI(if there are no take-up speed, please connect terminal “+10V” to
   terminal “LINE”), setting feed-in tension at TC-2060 tension controller, controling brake
   amount of magnetic powder brake, LOAD CELL is weighted through by material tension,
   detecting tension and conduct the detection signal back to TC-2060, then it could achieve
   the objective of unwinding materials with constant tension.
2. When LOAD CELL is corrected, please follow the instruction described at Section4.3 to
   proceed correction.
3. When the materials is unwinding, if the variation of unwinding tension is too large in the
   acceleration and deceleration, can refer the description of Parameter Explanation PID
   Parameter Group, adjusting related parameter appropriately.
4. When the materials is unwinding, if the variation of tension is too large in the constant
   speed, can refer the description of Parameter Explanation PID Parameter Group,
   adjusting related parameter appropriately, or increase CI time(Integral time), and decrease
   CP amount(Proportional ratio).
5. The other related questions can refer related section description listed at this Instruction
   Manual.
                                              45
7-2 Central Unwinding Tension Control (cooperating to motor drive direct torque control –
    Unwinding materials)
    Flow Chart: CIMR-G7 + TC-2060 + CIMR-G7
                                                            Un win d ing
Lo a d C e ll
Mo tor
       Ta ke -Up
        R o lle r
                                                                                        Un win d ing
                                                                                         In ve rte r
TC -2 0 60
                                                           Ta ke -Up
                                                           In ve rte r
Mo tor
Wiring Diagram (The drive of main guiding roller and unwinding system are CIMR-G7
series)
                                                      46
Related Parameter (Central Unwinding Tension Control – Cooperating to Motor Drive -
Unwinding Materials)
(3) Main guiding roller’s inverter (YASKAWA CIMR-G7 Series)
    A1-00    Language                              0 (English)
    A1-01    Parameter access class                2 (High class)
    A1-02    Control Mode                          3 (Vector attached PG, if it doedn’t attach PG card, set
                                                       it to 2)
    b1-01    Frequency Instruction Selection       1 (Terminal)
    b1-02    Operation Instruction Selection       1 (Terminal)
    b1-03    Stop Method Selection                 0 (Reducing speed to stop)
    C1-01    Acceleration Time                     10s Main guiding roller’s inverter (It is set in
                                                   accordance with line speed’s requirement)
    C1-02    Deceleration Time                     10s Main guiding roller’s inverter (It is set in
                                                   accordance with line speed’s requirement)
    C1-04    Deceleration Time                     2 (Stop time, it is set in accordance with line speed’s
                                                   requirement)
    E1-01    Input Voltage Setting                 AC220V (According to power voltage)
    E1-03    V/F Curve Selection                   F (Arbitrary curve)
    E1-04    The Highest Ouput Frequency           60HZ (It is set in accordance with line speed’s
                                                   requirement)
    E1-05    The Maximum Voltage                   AC220V (According to the rated voltage of motor)
    E1-06    Base Frequency                        60HZ (According to the rated voltage of motor)
    E1-07    Central Output Frequency              3HZ
    E1-08    Voltage of Central Output Frequency 11V
    E1-09    The Lowest Output Frequency           0.5HZ
    E1-10    Voltage of the Lowest Output          3V
             Frequency
    F1-01    PG Parameter                          600P/R (According to the specification of PG)
    F1-02    PG Disconnection Detection
                                                   1 (Free Stop)
             Selection
    F1-03    The corresponding action in
                                                   1 (Free Stop)
             over-speed
    F1-04    Speed Offset which detected is too
                                                   3 (Motor keeps on running)
             large
    F1-05    PG Rotary Direction                   0 (Forward revolution)
    H1-09    S11 Terminal’s Function               7 (The switch of acceleration and deceleration time)
    H2-02    P1 Terminal’s Function                1 (Output when the speed is zero)
    H3-01    Terminal A1 of Frequency Instruction 0 (0 ~ +10VDC)
                                                  47
(4) Unwinding drives’s inverter (YASKAWA CIMR-G7 Series)
    A1-00   Language                                0 (English)
    A1-01   Parameter access class                  2 (High class)
    A1-02   Control Mode                            3 (Vector attached PG, if it doedn’t attach PG card, set
                                                        it to 2)
    b1-01   Frequency Instruction Selection         1 (Terminal)
    b1-02   Operation Instruction Selection         1 (Terminal)
    b1-03   Stop Method Selection                   0 (Reducing speed to stop)
    C1-01   Acceleration Time                       10s Main guiding roller’s inverter (It is set in
                                                    accordance with line speed’s requirement)
    C1-02   Deceleration Time                       10s Main guiding roller’s inverter (It is set in
                                                    accordance with line speed’s requirement)
    C1-04   Deceleration Time                       2 (Stop time, it is set in accordance with line speed’s
                                                    requirement)
    D5-01   Torque Control Selection                1 (Torque Control)
    D5-03   Select Speed Limit                      1 (This instruction will according to parameter
                                                        “b1-01”setting)
    E1-01   Input Voltage Setting                   AC220V (According to power voltage)
    E1-03   V/F Curve Selection                     F (Arbitrary curve)
    E1-04   The Highest Ouput Frequency             60HZ (It is set in accordance with line speed’s
                                                    requirement)
    E1-05   The Maximum Voltage                     AC220V (According to the rated voltage of motor)
    E1-06   Base Frequency                          60HZ (According to the rated voltage of motor)
    E1-07   Central Output Frequency                3HZ
    E1-08   Voltage of Central Output Frequency 11V
    E1-09   The Lowest Output Frequency             0.5HZ
    E1-10   Voltage of the Lowest Output
                                                    3V
            Frequency
    F1-01   PG Parameter                            600P/R (According to the specification of PG)
    F1-02   PG Disconnection Detection
                                                    1 (Free Stop)
            Selection
    F1-03   The corresponding action in
                                                    1 (Free Stop)
            over-speed
    F1-04   Speed Offset which detected is too
                                                    3 (Motor keeps on running)
            large
    F1-05   PG Rotary Direction                     0 (Forward revolution)
    H1-09   S11 Terminal’s Function                 7 (The switch of acceleration and deceleration time)
    H2-02   P1 Terminal’s Function                  1 (Output when the speed is zero)
    H3-01   Terminal A1 of Frequency Instruction 0 (0 ~ +10VDC)
    H3-05   Function Selection of multi function    13 (Torque Control)
            simulated terminal A3
                                                   48
    H3-06   Gain of terminal A3               100%
    H3-07   Bias of terminal A3               0.0%
    H4-01   FM Selection of multi function    2 (U1-2 output frequency)
            simulated output terminal
   The above listing of parameters are only for reference, please refer the Instruction
   Manual for the other parameters which don’t list.
(5) TC-2060 Tension controller’s related parameters and DIP thumb switch position
    SW1→0~10VDC Position
                                             49
TC-2060 Tension Controller’s Related Parameter (Central Unwinding Tension Control –
Cooperating to Motor Drive - Unwinding Materials)
3.1:MAIN PARAMETER
                    SYMBOL
   SYMBOL                             DEFAULT         SETTING RANGE          EXPLANATION
                 DESCRIPTION
                                                                        0: Magic powder clutch
                                                     0:POWER(CLUTCH)
 DRIVER                               MOTOR                             1: Motor(torque control)
               Drive Selection                       1:MOTOR(TORQUE)
 SELECT                               (TORQUE)                          2: Current to Pressure
                                                     2:E/P REQULATOR
                                                                           Converter
                                                                        0: Winding
               Winding and                           0: WINDER,
 FUNCTION                                                               1: Unwinding
               Unwinding              UNWIND
 SELECT                                              1: UNWIND          (Settting can’t be
               Selection
                                                                        changed in the RUN)
                                                                        0: Computing of line
                                                                           speed and winding
                                                     0: DIVIDER            speed
 DIAMETER      The Source of
                                      DIVIDER        1: SENSOR          1: Proximity switch
 SOURCE        Diameter Detection
                                                     2: TB(DIAMETER )      length calculation
                                                                        2: External diameter
                                                                           signal terminal input
               Ratio of line speed
 LINE RATIO                            100.0%            10~500.0%      LINE terminal input
               signal input
               Ratio of winding
 WIND RATIO                            100.0%            0~500.0%       WIND terminal input
               feedback signal
                                                50
CUT ADD/TE     Increased tension                                       T this value are actual
               in changing reel       100.0%             0~500.0%      cutting material’s
VALUE          and cutting material                                    tension
PRESET SET     Time of changing                                        Time of changing reel
                                      5.0SEC             0~10.0SEC
TIME           reel                                                    procedure
MINIMUN
               Minimum diameter       100mm              50~300mm
DIAMETER
                                                                       When the parameter
                                                                       “DIAMETER SOURCE”
               Thickness setting                                       is set to “SENSOR”, this
THICKNESS                              120um            10~10000um
               of winding material                                     parameter will be
                                                                       displayed
                                                                       When the parameter
                                                                       “DIAMETER SOURCE”
DIAMETER       Logic selection of                       0=0~10VDC
                                      0~10VDC                          is set to “TB”, this
LOGIC          supersonic                               1=10~0VDC      parameter will be
                                                                       displayed
                                                                       When the parameter
               Zero point                                              “DIAMETER SOURCE”
DIAMETER
               adjustment of            0.0V           -5.00V~+5.00V   is set to “TB”, this
ZERO           supersonic                                              parameter will be
                                                                       displayed
                                                                       When the parameter
                                                                       “DIAMETER SOURCE”
DIAMETER       Multiple ratio of
                                      100.0%             0~500.0%      is set to “TB”, this
SPAN           supersonic                                              parameter will be
                                                                       displayed
                                                51
                                                                      means the tension won’t
                                                                      be tapered; setting 90%
                                                                      means the tension is
                                                                      attenuated 10%)
                                                                      0: Linear
 TAPER MODE   Mode setting of                     0: LINER
                                     LINER                            1: Non-Linear (multi
    SELE      taper tension curve                 1: NON-LINER
                                                                         sectional, irregular)
              The #1 turning                                          According to diameter
 TAPER TENS   point’s setting                                         value(under the turning
                                    300mm             0~2000mm
  SET1        value of non-linear                                     point, the tension won’t
              taper tension                                           be tapered)
              The #2 turning
 TAPER TENS   point’s setting                                         According to diameter
                                    500mm             0~2000mm
  SET2        value of non-linear                                     value
              taper tension
              The #3 turning
 TAPER TENS   point’s setting                                         According to diameter
                                    800mm             0~2000mm
  SET3        value of non-linear                                     value
              taper tension
                                                                      the value of taper ratio is
              Taper Ratio                                             the multiplier, setting
  TAPER SET   between #1 turning                                      100% means the tension
                                    100.0%            0~100.0%
 RATIO1       point and #2                                            won’t be tapered; setting
              turning point                                           90% means the tension
                                                                      is attenuated 10%
                                             52
                                                                         0: Jog increase for
                                                                            tension setting
 MC2 SELECT                                        0: INCHING ADD        1: Jog decrease for
               Function selection    INCHING
   FUNC                                            1: INCHING DEC           tension setting
               of MC2 terminal         DEC                               2: Output signal is
                                                   2: OUT REMOTE
                                                                            controlled by external
                                                                            remote control
                                                                         0: NO
                                                                         1: New reel’s tension
                                                   0: NO FUNCTION          setting
 AD1 SELECT    Function selection
                                        NO         1: NEW REELVALUE      2: Taper tension setting
    FUNC       of AD1 Analog
                                     FUNCTION      2: TAPER (Linear)     3: Tension detecting
               Input
                                                                            input(power input is
                                                   3: TENSION(FBK)          0~+/-10V without load
                                                                            cell)
                                                                         0: NO
                                                                         1: New reel’s tension
                                                   0: NO FUNCTION          setting
               Function selection
 AD2 SELECT                             NO         1: NEW REELVALUE      2: Taper tension setting
               of AD2 Analog
    FUNC                             FUNCTION      2: TAPER (Linear)     3: Tension detecting
               Input
                                                                            input(power input is
                                                   3: TENSION(FBK)          0~+/-10V without load
                                                                            cell)
                                                                         Relay’s function output
     RLY                                           0: HIGH               selection
               Mode selection of
   SELECT                              LOW         1: LOW                0: in high tension
               relay action
                                                                         1: in low tension
    FUNC                                           2: ALARM
                                                                         2: abnormal
                                                                         Following the above
                                                                         assigned mode; when it
                                                                         is set to “HIGH”, relay
     RLY       Active point of                                           will be active if it is
    FBK        tension detection’s     3.0%             0~100.0%         higher than the active
               relay                                                     point, when it is set to
   HI/LOW
                                                                         “LOW”, relay will be
                                                                         active if it is lower than
                                                                         active point
                                              53
               The rising time of                                          be corrected by PI
   TENSI
               section 1 tension       150S                 0~5000S
  CI+ GAIN     error integrator
               The falling time of
    TENSI
               section 1 tension       150S                 0~5000S
   CI- GAIN    error integrator
 TENSION CP1   Tension error ratio
               of section 2            30.0%                0~500.0%       The section within PID
    GAIN
               The rising time of                                          FEEL and PID SLP1 will
  TENSI CI1+   section 2 tension                                           be corrected by PI
                                          75S               0~5000S
    GAIN       error integrator
               The falling time of
   TENSI
               section 2 tension          75S               0~5000S
  CI1- GAIN    error integrator
                                                                           The section which is
 TENSION CP2   Tension error ratio
                                       30.0%                0~500.0%       small than SLP1 will be
    GAIN       of section 3
                                                                           corrected by PI
               The rising time of
  TENSI CI2+   section 3 tension          10S               0~5000S
    GAIN       error integrator
               The falling time of
    TENSI
               section 3 tension          10S               0~5000S
  CI2- GAIN    error integrator
  PID FILTER   The filter time of                                          The filter time of load
               tension feedback       100ms                 0~500ms        cell feedback signal
     TIME
3.6:DISP PARAMETER(Parameter)
                    SYMBOL
   SYMBOL                             DEFAULT         SETTING RANGE             EXPLANATION
                 DESCRIPTION
                                                                           The number setting of
               The decimal point                     0~2(the value of
 DISPLAY                                                                   decimal point(the value
               number of tension      1              tension setting and
 POINT                                                                     of tension setting and
               setting                               display are valid)    display)
                                                54
                                                                         0: Voltage of “LINE”
                                                                            terminal
                                                     0: LINE INPUT       1: Voltage of “WIND”
               The first row LCD
 DISP NO.1                              FEED         1: WIND INPUT          terminal
               source selection
 SOURCE                                 BACK         2: TENSION INPUT    2: Tension setting’s
               display
                                                                            value
                                                     3: ADIN1            3: Voltage of “ADIN1”
                                                                            terminal
                                                                         4: Voltage of “ADIN2”
                                                                            terminal
                                                     4: ADIN2            5: Voltage of torque
               The third row LCD
 DISP NO.3                            TORQUE         5: TORQUE OUT          command
               source selection
 SOURCE                                 OUT          6: NR OUT           6: Voltage of “NR OUT”
               display
                                                                           terminal
                                                     7: SP OUT           7: Voltage of “SP OUT”
                                                                           terminal
                                                                         8: Voltage of “FBK OUT”
                                                                           terminal
                                                                         9: Error amount
                                                     8: FBK OUT          10: Voltage of error
                                                     9: SLP                  amount
                                                                             compensation
                                                     10: PID VOL
                                                                         11: Diameter amount
               The fourth row LCD                    11: DIAMETER        12: Counting length
 DISP NO.4
               source selection         SP OUT       12: COUNT               amount
 SOURCE        display                                                   13: Total amount of
                                                     13: FEEDBACK
                                                                             tension
                                                     14: FBK-L CELL      14: Left side load cell’s
                                                     15: FBK-R CELL          tension
                                                     16: SERIAL STATUE   15: Right side load cell’s
                                                                             tension
                                                                         16: Communication
                                                                             status
3.7:SERIAL PARAMETER(Communication)
                    SYMBOL
   SYMBOL                             DEFAULT         SETTING RANGE           EXPLANATION
                 DESCRIPTION
                                                                         0: External terminal
                                                                            control
                                                                            (RS-485 Read function
                                                                            is available)
                                                                         1: Digital input &
                                                                            parameter & SV
                                                                            tension setting value
                                                     0: OUTSIDE TB          are controlled by
 COMMAND       Selection of digital   OUTSIDE
                                                     1: SERIAL              RS-485
 SELECT        input command          TB                                    communication
                                                     2: TB (SV=RS485)
                                                                         2: Digital input is
                                                                            controlled by
                                                                            terminal. Parameter &
                                                                            SV tension setting
                                                                            value are controlled
                                                                            by RS-485
                                                                            communication
                                                55
                                                                        0: External terminal
                                                                           control
                                                                           (RS-485 Read
                                                                           function is available)
                                                                        1: Analog input &
                                                                           parameter & SV
                                                                           tension setting value
                                                    0: OUTSIDE TB          are controlled by
 SINGLE        Selection of analog   OUTSIDE
                                                    1: SERIAL              RS-485
 SELECT        input command         TB                                    communication
                                                    2: TB (SV=RS485 )
                                                                        2: Analog input is
                                                                           controlled by
                                                                           terminal. Parameter &
                                                                           SV tension setting
                                                                           value are controlled
                                                                           by RS-485
                                                                           communication
                                                                        ☆ When the
                                                                           communication
               Communication                                               function is set, the
 SERIAL        address                                                     following parameter
               (the number of            0               0 , 1~31          will be displayed
 ADDRESS
               station)                                                 0: Don’t send back, all
                                                                           receive
                                                                        1~31: station address
                                                    (0)=4800 bps
               Communication                        (1)=9600 bps        There are three kinds of
 BAUD RATE     baud rate               9600                             baud rate can be set
                                                    (2)=19200 bps
                                                    0: NO PARITY
 PARITY SET    Parity setting        NO PARITY      1: EVEN PARITY
                                                    2: ODD PARITY
                                               56
Application Example Explanation: (Central Unwinding Tension Control – Cooperating to
                                        Motor Drive - Unwinding Materials)
1. After running of take-up roller, according to take-up speed for offering TC-2060 as
   reference of line speedI(if there are no take-up speed, please connect terminal “+10V” to
   terminal “LINE”), setting feed-in tension at TC-2060 tension controller, controling brake
   amount of magnetic powder brake, LOAD CELL is weighted through by material tension,
   detecting tension and conduct the detection signal back to TC-2060, then it could achieve
   the objective of unwinding materials with constant tension.
2. When LOAD CELL is corrected, please follow the instruction described at Section4.3 to
   proceed correction.
3. When the materials is unwinding, if the variation of unwinding tension is too large in the
   acceleration and deceleration, can refer the description of Parameter Explanation PID
   Parameter Group, adjusting related parameter appropriately.
4. When the materials is unwinding, if the variation of tension is too large in the constant
   speed, can refer the description of Parameter Explanation PID Parameter Group,
   adjusting related parameter appropriately, or increase CI time(Integral time), and decrease
   CP amount(Proportional ratio).
5. The other related questions can refer related section description listed at this Instruction
   Manual.
                                              57
7-3 Central Winding Tension Control(Cooperating to drive direct torque control for driving)
Flow Chart:CIMR-G7 + TC-2060 + CIMR-G7 (Speed & Torque Control)
                                                      Ta ke -Up
                                                       R o lle r
Loa d C e ll
                                                                                       Ta ke -Up
                                                                                       In ve rte r
Motor
Wind ing
TC -20 60
                                                 Wind ing
                                                 In ve rte r
Motor
Wiring Diagram (All the drive of main guiding roller and winding roller are YASKAWA
IMR-G7 series)
                                                 58
7-4 Central Winding Tension Control (Cooperating to drive’s speed control and magnetic
    powder clutch for driving)
Flow Chart:CIMR-G7 + TC-2060P + CIMR-G7(Close loop or Open loop) +BRAKE
                                                       Ta ke -Up
                                                        R olle r
Loa d C e ll
                                                                                       Ta ke -Up
                                                                                       Inve rte r
Motor
Wind ing
TC -20 60
                                                  Wind ing
                                                  Inve rte r
                P owde r                  Motor
                C lu tch
Wiring Diagram (All the drive of main guiding roller and winding roller are YASKAWA
CIMR-G7 series)
                                                  59
Related Parameter (Central Winding Tension Control)
(1) Main Guiding Roller’s Inverter & Central Winding’s Inverter (YASKAWA CIMR-G7
    series)
    A1-00   Language                              0 (English)
    A1-01   Parameter access class                2 (High class)
    A1-02   Control Mode                          3 (Vector attached PG, if it doedn’t attach PG card, set
                                                      it to 2)
    b1-01   Frequency Instruction Selection       1 (Terminal)
    b1-02   Operation Instruction Selection       1 (Terminal)
    b1-03   Stop Method Selection                 0 (Reducing speed to stop)
    C1-01   Acceleration Time                     10s Main guiding roller’s inverter (It is set in
                                                  accordance with line speed’s requirement)
    C1-01   Acceleration Time                     1s Central Winding’s Inverter
    C1-02   Deceleration Time                     10s Main guiding roller’s inverter (It is set in
                                                  accordance with line speed’s requirement)
    C1-02   Deceleration Time                     1s Central Winding’s Inverter
    C1-04   Deceleration Time                     2 (Stop time, it is set in accordance with line speed’s
                                                  requirement)
    D5-01   Torque Control Selection              1 (Torque Control)
    D5-03   Select Speed Limit                    1 (This instruction will according to parameter “b1-01”
                                                  setting)
    E1-01   Input Voltage Setting                 AC220V (According to power voltage)
    E1-03   V/F Curve Selection                   F (Arbitrary curve)
    E1-04   The Highest Ouput Frequency           60HZ (It is set in accordance with line speed’s
                                                  requirement)
    E1-05   The Maximum Voltage                   AC220V (According to the rated voltage of motor)
    E1-06   Base Frequency                        60HZ (According to the rated voltage of motor)
    E1-07   Central Output Frequency              3HZ
    E1-08   Voltage of Central Output Frequency 11V
    E1-09   The Lowest Output Frequency           0.5HZ
    E1-10   Voltage of the Lowest Output
                                                  3V
            Frequency
    F1-01   PG Parameter                          600P/R (According to the specification of PG)
    F1-02   PG Disconnection Detection
                                                  1 (Free Stop)
            Selection
    F1-03   The corresponding action in
                                                  1 (Free Stop)
            over-speed
    F1-04   Speed Offset which detected is too
                                                  3 (Motor keeps on running)
            large
    F1-05   PG Rotary Direction                   0 (Forward revolution)
    H1-09   S11 Terminal’s Function               7 (The switch of acceleration and deceleration time)
                                                 60
    H2-02    P1 Terminal’s Function                  1 (Output when the speed is zero)
    H3-01    Terminal A1 of Frequency Instruction 0 (0 ~ +10VDC)
    H3-05    Function Selection of multi function    13 (Torque Control)
             simulated terminal A3
    H3-06    Gain of terminal A3                     100%
    H3-07    Bias of terminal A3                     0.0%
    H4-01    FM Selection of multi function          2 (U1-2 output frequency)
             simulated output terminal
    The above listing of parameters are only for reference, please refer the Instruction
    Manual for the other parameters which don’t list.
TC-2060 Tension controller’s related parameters and DIP thumb switch position
    SW1→0~10VDC Position
                                                    61
                                                                       0: Computing of line
                                                                          speed and winding
                                                                          speed
                                                                       1: Proximity switch
                                                                          length calculation
                                                                       2: External diameter
              Source of           DIVIDER or        0: DIVIDER            signal terminal input
DIAMETER      diameter            SENSOR            1: SENSOR          Please take attention that
SOURCE        detection           (POWDER)          2: TB(DIAMETER )   the “DARIVER SELECT”
                                                                       parameter is selected to
                                                                       “POWER”, need to select
                                                                       “SENSOR” counting
                                                                       length calculation or
                                                                       “TB(DIAMETER)”
                                                                       terminal diameter input
              Ratio of line
LINE RATIO    speed signal          100.0%              10~500.0%      LINE terminal input
              input
              Ratio of winding
WIND RATIO                          100.0%              0~500.0%       WIND terminal input
              feedback signal
                                               62
 START         Start   Torque
                                     0.5 V                0~5V       Running Enable
 TORQUE        compensation
                                                                     The time of stop when
 STOP TIME     STOP time             10.0S              0.0~60.0S    the “RUN” terminal is
                                                                     opened
                                                                     0: PID continue control
 STOP FUNC     Mode selection in    PID ON         0: PID ON            within the STOP time
 SELE          stop                                1: STOP RATIO     1: Follow “STOP RATIO”
                                                                        to brake
                                                                     Brake is multiplied owing
               Brake value
                                                                     to “STOP RATIO”
 STOP RATIO    within the STOP      200.0%              0~500.0%     multiply by the diameter
               time
                                                                     value
 MAXIMUN       Maximum
               diameter             1000mm            300~5000mm
 DIAMETER
 MINIMUN       Minimum
               diameter             100mm              50~300mm
 DIAMETER
                                                                     When the parameter
               Thickness                                             “DIAMETER SOURCE” is
 THICKNESS     setting of            120um            10~10000um     set to “SENSOR”, this
               winding material                                      parameter will be
                                                                     displayed
                                                                     When the parameter
                                                                     “DIAMETER SOURCE” is
 DIAMETER      Logic selection of                      0=0~10VDC
                                    0~10VDC                          set to “TB”, this
 LOGIC         supersonic                              1=10~0VDC     parameter will be
                                                                     displayed
                                                                     When the parameter
               Zero point                                            “DIAMETER SOURCE” is
 DIAMETER
               adjustment of         0.0V            -5.00V~+5.00V   set to “TB”, this
 ZERO          supersonic                                            parameter will be
                                                                     displayed
                                                                     When the parameter
                                                                     “DIAMETER SOURCE” is
 DIAMETER      Multiple ratio of
                                    100.0%              0~500.0%     set to “TB”, this
 SPAN          supersonic
                                                                     parameter will be
                                                                     displayed
                                                                     When “RUN” terminal
  START        Start torque
                                      0V               0 ~ +10Vdc    starts, then output torque
 TORQUE        compensation
                                                                     compensation right away
                                              63
             Mode setting of                                  0: Linear
TAPER MODE                                     0:LINER
             taper tension       LINER                        1: Non-Linear (multi
   SELE      curve                             1:NON-LINER       sectional, irregular)
             The #1 turning
                                                              According to diameter
             point’s setting
TAPER TENS                                                    value(under the turning
             value of            300mm            0~2000mm
 SET1                                                         point, the tension won’t
             non-linear taper
                                                              be tapered)
             tension
             The #2 turning
             point’s setting                                  According to diameter
TAPER TENS
             value of            500mm            0~2000mm
 SET2        non-linear taper                                 value
             tension
             The #3 turning
             point’s setting                                  According to diameter
TAPER TENS
             value of            800mm            0~2000mm
 SET3        non-linear taper                                 value
             tension
                                                              the value of taper ratio is
             Taper Ratio                                      the multiplier, setting
TAPER SET    between #1                                       100% means the tension
             turning point and   100.0%            0~100.0%   won’t be tapered; setting
RATIO1
             #2 turning point                                 90% means the tension is
                                                              attenuated 10%
                                          64
3.3:FUNC PARAMETER(Parameter Setting)
                   SYMBOL
   SYMBOL                           DEFAULT          SETTING RANGE              EXPLANATION
                DESCRIPTION
                                                                          0: Operation panel’s VR
   TENSION                                          0: PLANE TENSION         setting
               Source selection      PLANE
   SELECT                                           1: PUSH TENSION       1: Up / Down key setting
               of tension setting   TENSION
    FUNC                                                                  2: Input of Terminal
                                                    2: EXT VR TENSION
                                                                             “TENS”
                                                                          0: Jog increase for
                                                                             tension setting
               Function                             0: INCHING ADD        1: Jog decrease for
 MC1 SELECT                         INCHING
               selection of MC1                     1: INCHING DEC           tension setting
   FUNC        terminal               ADD                                 2: Output signal is
                                                    2: OUT REMOTE
                                                                             controlled by external
                                                                             remote control
                                                                          0: Jog increase for
                                                                             tension setting
               Function                             0: INCHING ADD        1: Jog decrease for
 MC2 SELECT                         INCHING
               selection of MC2                     1: INCHING DEC           tension setting
    FUNC       terminal               DEC                                 2: Output signal is
                                                    2: OUT REMOTE
                                                                             controlled by external
                                                                             remote control
                                                                          0: NO
                                                                          1: New reel’s tension
                                                    0: NO FUNCTION          setting
               Function
 AD1 SELECT                            NO           1: NEW REELVALUE      2: Taper tension setting
               selection of AD1
    FUNC                            FUNCTION        2: TAPER (Linear)     3: Tension detecting
               Analog Input
                                                                             input(power input is
                                                    3: TENSION(FBK)          0~+/-10V without load
                                                                             cell)
                                                                          0: NO
                                                                          1: New reel’s tension
                                                    0:NO FUNCTION           setting
               Function
 AD2 SELECT                            NO           1: NEW REELVALUE      2: Taper tension setting
               selection of AD2
    FUNC                            FUNCTION        2: TAPER (Linear)     3: Tension detecting
               Analog Input
                                                                             input(power input is
                                                    3: TENSION(FBK)          0~+/-10V without load
                                                                             cell)
                                                                          Relay’s function output
                                                    0: HIGH               selection
 RLY SELECT    Mode selection of
                                      LOW           1: LOW                0: in high tension
    FUNC       relay action
                                                                          1: in low tension
                                                    2: ALARM
                                                                          2: abnormal
                                                                          Following the above
                                                                          assigned mode; when it
                                                                          is set to “HIGH”, relay will
               Active point of
   RLY FBK                                                                be active if it is higher
               tension                3.0%               0~100.0%
   HI/LOW                                                                 than the active point,
               detection’s relay
                                                                          when it is set to “LOW”,
                                                                          relay will be active if it is
                                                                          lower than active point
                                               65
                                                                          The setting and actual
               Section 1                                                  error are within the range
 TENSION PID   breakpoint of                                              between PID FEEL and
                                      0.5KG         0~Scale (parameter)
    SLP        tension error                                              PID SLP will be regarded
                                                                          as section 1
                                                                          The setting and actual
               Section 2                                                  error are within the range
 TENSION PID   breakpoint of                                              between PID FEEL and
                                      1.0KG         0~Scale (parameter)
    SLP1       tension error                                              PID SLP1 will be regarded
                                                                          as section 2
  PID FILTER   The filter time of                                         The filter time of load cell
               tension feedback       100ms              0~500ms          feedback signal
     TIME
                                               66
 SPAN TUNE     Load cell’s
 TEST          tension highest     0~500%                0~500%
               point correction
3.6:DISP PARAMETER(Parameter)
                   SYMBOL
   SYMBOL                          DEFAULT          SETTING RANGE             EXPLANATION
                DESCRIPTION
                                                                         The number setting of
               The decimal point                   0~2(the value of
 DISPLAY                                                                 decimal point(the value of
               number of tension   1               tension setting and
 POINT                                                                   tension setting and
               setting                             display are valid)    display)
                                                                         0: Voltage of “LINE”
                                               0: LINE INPUT                terminal
               The first row LCD                                         1: Voltage of “WIND”
 DISP NO.1                         FEED        1: WIND INPUT
               source selection                                             terminal
 SOURCE        display             BACK        2: TENSION INPUT          2: Tension setting’s value
                                               3: ADIN1                  3: Voltage of “ADIN1”
                                                                            terminal
                                                                         4: Voltage of “ADIN2”
                                                                            terminal
                                               4: ADIN2                  5: Voltage of torque
               The third row LCD   TORUE
 DISP NO.3                                     5: TORQUE OUT                command
               source selection     OUT
 SOURCE                                        6: NR OUT                 6: Voltage of “NR OUT”
               display
                                                                           terminal
                                               7: SP OUT                 7: Voltage of “SP OUT”
                                                                           terminal
                                                                         8: Voltage of “FBK OUT”
                                                                           terminal
                                               8: FBK OUT                9: Error amount
                                                                         10: Voltage of error
                                               9: SLP                         amount compensation
                                               10: PID VOL               11: Diameter amount
                                               11: DIAMETER              12: Counting length
               The fourth row
 DISP NO.4                                                                    amount
               LCD source           SP OUT     12: COUNT
 SOURCE                                                                  13: Total amount of
               selection display
                                               13: FEEDBACK                  tension
                                               14: FBK-L CELL            14: Left side load cell’s
                                                                              tension
                                               15: FBK-R CELL            15: Right side load cell’s
                                               16: SERIAL STATUE              tension
                                                                         16: Communication
                                                                              status
 DISP FILTER                                                             The filter time of display
               Display time            5.0S              0~20.0S
 TIME                                                                    value
                                              67
3.7:SERIAL PARAMETER(Communication)
                    SYMBOL
   SYMBOL                          DEFAULT        SETTING RANGE        EXPLANATION
                 DESCRIPTION
                                                                  0: External terminal
                                                                     control
                                                                     (RS-485 Read function
                                                                     is available)
                                                                  1: Digital input &
                                                                     parameter & SV
               Selection of                   0: OUTSIDE TB          tension setting value
 COMMAND       digital input       OUTSIDE                           are controlled by
                                              1: SERIAL
 SELECT        command             TB                                RS-485 communication
                                              2: TB (SV=RS485)
                                                                  2: Digital input is
                                                                     controlled by terminal.
                                                                     Parameter & SV
                                                                     tension setting value
                                                                     are controlled by
                                                                     RS-485 communication
                                                                  0: External terminal
                                                                     control
                                                                     (RS-485 Read function
                                                                     is available)
                                                                  1: Analog input &
                                                                     parameter & SV tension
               Selection of                   0: OUTSIDE TB          setting value are
 SINGLE        analog input        OUTSIDE                           controlled by RS-485
                                              1: SERIAL
 SELECT        command             TB                                communication
                                              2: TB (SV=RS485)
                                                                  2: Analog input is
                                                                     controlled by terminal.
                                                                     Parameter & SV
                                                                     tension setting value
                                                                     are controlled by
                                                                     RS-485 communication
                                                                  ☆ When the
                                                                      communication
               Communication                                          function is set, the
 SERIAL        address                                                following parameter
               (the number of         0              0 , 1~31         will be displayed
 ADDRESS
               station)                                           0: Don’t send back, all
                                                                      receive
                                                                  1~31: station address
                                              (0)=4800 bps
               Communication                  (1)=9600 bps        There are three kinds of
 BAUD RATE     baud rate             9600                         baud rate can be set
                                              (2)=19200 bps
                                              0:NO PARITY
                                      NO      1:EVEN PARITY
 PARITY SET    Parity setting       PARITY
                                              2:ODD PARITY
               Communication                                      The delay time between
 SERIAL TIME   delay interval of    15 ms            5~65ms       command message and
               time                                               response message
                                             68
                Drive response
                state after                                         0: Drive stops running
                abnormal                                            1: Drive stops running
                communication                                          when the
                                               0: DRIVE STOP           communication format
 SERIAL         (Including                                             is not correct.
 ALARL          abnormal           RUNNING     1: SERIAL FAULT/OT   2: if the communication
 SET            communication                  2: DRIVE RUNNING        format is correct, but
                format and                                             the communication is
                over-time                                              interrupted, the drive
                communication                                          keeps on running
                interrupt)
                                               70
8. Communication
 TC-2060 Controller’s operation description for MODBUS communication
8.1 Introduction:
   TC-2060 Controllers use RS-485 serial communication and Modbus communication
   protocol to connect several TC-2060 Controllers and PLC ,or PC,HMI---etc, in order to
   get control and monitoring simultaneously.
8.2 Communication specification:
    (1) Hardware is RS-485 serial port.
    (2) Communication protocol is RTU communication protocol of Modbus.
    (3) Communication format is set by parameter group.
        (3.1) Set the source of RUN command to see if it is coming from RS-485:
              COMMAND SELECT = 0:OUTSIDE TB ------- Coming from external terminal
              control. (RS-485 Read function is available)
              COMMAND SELECT = 1:SERIAL ------- Digital input & Parameter & SV
              tension setting value are controlled by RS-485.
              COMMAND SELECT = 2:RS-485 PARAMETER ------- Digital input is
              controlled by terminal. Parameter & SV tension setting value is controlled by
              RS-485.
        (3.2) Set the source of analog signal to see if it is come from RS-485:
              SINGLE SELECT = 0: OUTSIDE TB ------- Analog signal is controlled by
              external terminal (RS-485 Read function is available).
              SINGLE SELECT = 1: SERIAL ------ Analog signal input & Parameter & SV
              tension setting value are controlled by RS-485.
              SINGLE SELECT = 2:RS485 PARAMETER ------ Analog signal input is
              controlledby terminal. Parameter & SV tension setting value are controlled by
              RS-485.
        (3.3) SERIAL ADDRESS = 0 ~ 31 ------- Communication Address(Default = 0).
        Each communication unit should have a unique and unrepeated communication
        address in the communication format.
       (3.4) BAUD RATE = 0 ~ 2 ------- Transmission Speed(Default = 1)
             BAUD RATE = 0 ------- 4800 Bps
             BAUD RATE = 1 ------- 9600 Bps
             BAUD RATE = 2 ------- 19200 Bps
        (3.5) PARITY SET = 0 ~ 2 ------- Parity Setting(Default = 0)
              PARITY SET = 0 ------- No Parity
              PARITY SET = 1 ------- Even Parity
              PARITY SET = 2 ------- Odd Parity
              Note: The stop bit is 1BIT.
       (3.6) Setting dealy time of communication reception
                                             71
               SERIAL TIME = 5ms ~ 65ms ------- Dealy time of communication reception,
               When the response time is over 5 seconds, the error message will be shown
               on digital controller. After it is corrected, the error message will be disappeared
               automatically.
        (3.7) The corresponding state of TC-2060 Controller after the abnormal
              communication happened (Including abnormal communication format and
              overtime for the interruption of communication).
               SERIAL ALARM SET= RUNNING
               0: Drive stops running.
               1: When the communication format is not corrected, TC-2060 Controller stops
                  running. When the communication format is corrected, but the
                  communication is interrupted, TC-2060 Controller keeps running.
               2: Drive continues to run.
        (3.8) RS-485 serial port has RXD and TXD contact points, which can be used as
               semi-duplex communication. For serial communication of RS-485 ports, just
               connected all RXD and all TXD in serial (Refer the following figure).
                                               Master            雙絞線
                                                                Twisted pair cable
                                               PLC
                                               TXD RXD
圖 1:RS-485 Connection
                                                72
   data, a warning message, “SERIAL ERROR ALM”, will be displayed at the panel, it
   means the communication is standby, if TC-2060 Controller receives the data, this
   message will not be displayed again.
8.4 Explanation for RTU communication protocol of Modbus :
(1) Definition of Character:
    In RTU mode of Modbus, every Character is composed of 11bits, including 1 start bit, 8
    Data bits, 1 Parity bit and 1 stop bit. If the parameter = “0” and no parity, the parity bit
    should be set as “1”. It will be transmitted from start bit in series. The format of Character
    is shown as follows:
                          Slave Function
          A time is over                 Data     CRC-16   A time is over
          3.5 bits, and  Address Code                      3.5 bits, and
          plus “SERIAL                                     plus “SERIAL
              TIME”       1 bit   1 bit  n bit CRC_L CRC_H     TIME”
                                                73
   Septum between Messages:
                                                                     Communication
                                                                     Delay Time, setting
                3.5 bits                                             “SERIAL TIME”
                                                                     parameter to 5ms
       Communication                                                 above
    Delay Time, setting
       “SERIAL TIME”                                                   3.5
     parameter to 5ms
                above
                                              74
         Message, and send back the result to the low byte.
   (3) If LSB of CRC_16 is “0”, shifting right a bit of CRC_16, and writing “0” to MSB of
        CRC_16; if LSB of CRC_16 is “1”, shifting right a bit of CRC_16, and writing “0” to
        MSB of CRC_16, doing an XOR calculation with A001H.
   (4) Repeat step of (3) until 8 bits have been shifted right.
   (5) As for the next byte of Message, repeating above steps from (2) to (4) until all bytes
       is accessed completely. After that CRC-16 value is the Check Code.
       Example: Use Basic Language to calculate CRC-16.
       Function CRC_16(message$) as long
       Crc16&=65535
       FOR CHAR%=1 to LEN(message$)
            Crc16&=crc16& XOR ASC (MID$(message$, C% ,1))
       FOR BIT%=1 to 8
             IF crc16& MOD 2 THEN
             Crc16&=(crc16&\2) XDR 40961
         ELSE
             Crc16&=crc16&\2
              END IF
              NEXT BIT%
          NEXT CHAR%
         Crc_hi%=crc16&\256
         Crc_lo%=crc16& MOD 256
         Message$ =message$ +CHR$ (crc_lo%) + CHR$(crc_hi%)
         Crc_16=crc16&
         END FUNCTION CRC_16
(V) Message mode:
    The Message can be divided into Command Message and Reply Message. The
    Message sent form Master to Slave is called Command Message. The Message sent
    form Slave to Master is called Reply Message. In general, after receiving Command
    Message, if the delaying time is over the length of 3.5bits including the communication
    delay time, the slave with designated address will be responsible for reply. Under the
    following condition, Slave will not send “Reply Message”.
   1. The Slave address in the Command Message is different to all connected addresses.
   2. The Slave detected communication error (Parity, Framing, Overrun, or CRC_16 error)
       from the receiving Message.Slave.
8.5 Message Format:
    This TC-2060 Controller only receive 4 kinds of Command Message, including Read
    (03H), Loop Test (08H) and Write (06H and 10H), and listed below:
                                             75
                                                  Command Message     Response Message
         Function
 Command                     Function               Byte      Byte      Byte     Byte    The
           code
                                                   (Min.)    (Max.)    (Min.)   (Max.)
                                             76
    Slave Reply Message (Error)
                                         77
   Slave Response Message (Error)
    Slave address                       01H
    80H+ Function code                  86H
                                        78
(4) Write Command(10H):
  Write multiple data into the Register, and the maximum 16 Registers can be written at
  a time. When Slave address is “0” in the Write Command, all Slaves will receive and
  will not reply. If using the Write Command to change the parameters, they will not be
  saved in EEPROM at power off. If they want to be saved, they have to be written into
  the address of 0200H. The content is 01H, then they can be saved in EEPROM.
  Master Command Message
   Slave address                             01H                Example
   Function code                             10H
                                        79
        Slave Reply Message (Error)
8.6.1 Control Data Register (Read/Write): Used to control the operation of TC-2060
                                          Controller.
           Name                     Description            Address               Content
                                                                     BIT0:RUN
                                                                     0 = OFF 1 = ON
                                                                     BIT1: A, B change
                                                                     0 = A shaft 1 = B shaft
                                                                     BIT2: STALL
                                                                     0 = OFF 1 = ON
TB                          Terminal input                   0300H
                                                                     BIT3: RESET
                                                                     0 = OFF 1 = ON
                                                                     BIT4: MC1
                                                                     0 = OFF 1 = ON
                                                                     BIT5: MC2
                                                                     0 = OFF 1 = ON
                                                  80
                                                                BIT6: MC3
                                                                0 = OFF 1 = ON
8.6.2 Monitor Data Register(read only): It is used for reading the status of TC-2060
controller’s operation.
          Name                     Description        Address               Content
                                                                BIT0: RUN
                                                                0 = OFF 1 = ON
                                                                BIT1: A, B change
                                                                0 = A shaft 1 = B shaft
                                                                BIT2: STALL
                                                                0 = OFF 1 = ON
TB                           Terminal Input Status              BIT3: RESET
                                                       0310H
                                                                0 = OFF   1 = ON
                                                                BIT4: MC1
                                                                0 = OFF 1 = ON
                                                                BIT5: MC2
                                                                0 = OFF   1 = ON
                                                                BIT6: MC3
                                                                0 = OFF 1 = ON
Digital Output                                                  BIT0: RELAY
                                                       0311H
                                                                0 = OFF   1 = ON
                                                                BIT0: CRC16 CODE ERROR
                                                                BIT1: SERIAL BRK OE PE FE
Abnormal Status Indication                                            ERROR
                                                                BIT2:
                                                                BIT3: SERIAL READ/WRITE
                                                                      ADDRESS
                                                       0312H    BIT4: SERIAL FUNCTION
                                                                      ERROR
                                                                BIT5: SERIAL TIME ERROR
ERROR                                                                 TIME>5S
                                                                BIT6:
                                                                BIT7: SERIAL RXD BRAKE
                                                                      TIME>3S
                                                 81
A/D input terminal TENS
                                                       0318H    0~+10Vdc : 0~4095 COUNT
Status
LOADCELL TOTAL Kg
                                                       031EH    0~+10Vdc : 0~4095 COUNT
Status
                                                       00H:POWER(CLUTCH)
DRIVER SELECT                                020AH     01H:MOTOR(TORQUE)
                                                       02H:E/P REQULATO
                                                       00H:WINDER
FUNCTION SELECT                              020CH
                                                       01H:UNWIND
                                                       00H:DIVIDER
DIAMETER SOURCE                              020EH     01H:SENSOR
                                                       02H:TB(DIAMETER )
                                              82
TENS RATIO         0214H   0~500.0%
                           00H:SELE PID
STOP FUNC SELE     022EH
                           01H:STOP RATIO
                           00H:LINER
TAPER MODE SELE    0250H
                           01H:NON_LINER
                   83
TAPER SET RATIO1   025AH   0~100.0%
                           00H:PLANE TENSION
TE SELECT FUNC     0260H   01H:PUSH TENSION
                           02H:EXT VR TENSION
                           00H:INCHING ADD
MC1 SELECT FUNC    0262H   01H:INCHING DEC
                           02H:OUT REMOTE
                           00H:INCHING ADD
MC2 SELECT FUNC    0264H   01H:INCHING DEC
                           02H:OUT REMOTE
                           00H:FUNCTION
                           01H:NEW REEL VALUE
AD1 SELECT FUNC    0266H
                           02H:TAPER
                           03H:TENSION(FBK)
                           00H:FUNCTION
                           01H:NEW REEL VALUE
AD2 SELECT FUNC    0268H
                           02H:TAPER
                           03H:TENSION(FBK)
                           00H:ALARM
RLY SELECT FUNC    026AH   01H:FBHI
                           02H:FBLO
                   84
ENSI CI2- GAIN                                0288H     0~500.0S
                                                        00H:Kgf
LOADCELL UNIT                                 028CH
                                                        01H:N
                                                        00H: REELS
LOADCELL SELECT                               0290H     01H:L-REEL
                                                        02H:R-REEL
                                                                  00H:LINE INPUT
                                                                  01H:WIND INPUT
DISP NO.1 SOURCE                              0298H     0~16      02H:TENSION INPUT
                                                                  03H:ADIN1
                                                                  04H:ADIN2
                                                                  05H:TORQUE OUT
                                                                  06H:NR OUT
                                                                  07H:SP OUT
DISP NO.3 SOURCE                              029AH     0~16      08H:FBK OUT
                                                                  09H:SLP
                                                                  0AH:PID VOL
                                                                  0BH:DIAMETER
                                                                  0CH:COUNT
                                                                  0DH:FEEDBACK
DISP NO.4 SOURCE                              029CH     0~16
                                                                  0EH:FBK-L CELL
                                                                  0FH:FBK-R CELL
                                                                  20H:SERIAL STATUS
                                               85
Communication Error Display::
1.   “SERIAL TIM ALARM”      No reply in communication interruption, and outran “Setting
                             Time” over 3s.
2.   “SERIAL FUN ALARM”     Communication function code error(Not 03H,06H,08H,10H).
3. “CPU SERIAL ALARM ”      Communication interruption is abnormal(Format isn’t correct).
4. “SERIAL R/W ALARM”       Read/write address error (The address must be a multiple of 2)
5. “SERIAL WR EEPROM” Write data into EPPROM over 30 times in communication.
6. “ SERIAL CRC ALARM”      Check code error.
7. “ SERIAL ERROR ALM”      Communication wait time is over the setting time 5 seconds.
8. No Reply     Communication data format is error, the receiving data format isn’t correct.
9. No Reply     UART error, Checking Parity in transmission
10. OVERRUN,FRAME error
                                     V 05 English Version        AUG    30. , 2010