Differential Relay Calculations
Differential Relay Calculations
auto
transformer transformer
stability stability test
ain page
P643 slope 7ut 613 slope
calculation calculation
auto
transformer line drop
stability test copensation
main bage
Data
Sref mva 20
Ratio KV 132 33
CT ratio 800 3000
In Relay 1
Iinj1 0.035
Iinj2 -0.037
match factor( HV) 9.14496
I diff calculated without zero sequence 0.637289400
idiff calculated primary 55.75
I diff calculated with zero sequencc 0.4248596
I diff calculated primary 37.16666666667
Calculated
I pick up w1 0.033 I pick up w2
I pick up w1 with zero sequence 0.049 I pick up w2 with zero sequenc enabl
i pick up>> w1 0.656 i pick up >>w2
i pick up>> w1 with zero sequence 0.984 i pick up >>w2 with zero sequence
1. for alarm signal. We have to inject the all the phase not one phase
2. We have to set the (open core) off for CTs. Because it will block the Diffrential.On the slop
3. have
4.For to set
zero the zerocompensation
sequence sequence on to can get the slope. For getting the pick up and the drop off, we have to set the Zepp
If we inject 3 phase current. At a very low value below the Diffrential
for test of ref
Id min 0.3
Id unrstrain 6 It shall be noted that if the ze
Slop 1 0.4 contributions to the total diff
slope2 0.4 automatically eliminated from
max current inject 0.037 secondary injection from just
related matching factor 1.289 equal to the highest differenti
match factor(LV) 8.5734 through-load operation of the
I restraincalculated without zero sequenc 0.047693 maximum load current from t
I restrain pri 4.172
I restrain calculated with zero sequencc 0.03179533
I restrain calculated primary 2.781
33.000
349.920
3.000
2205.751
25.214
0.575
0.035
0.052
0.700
1.050
It shall be noted that if the zero-sequence currents are subtracted from the separate
contributions to the total differential current, then the zero-sequence component is
automatically eliminated from the bias current as well. This ensures that for
secondary injection from just one power transformer side the bias current is always
equal to the highest differential current regardless of the fault type. During normal
through-load operation of the power transformer, the bias current is equal to the
maximum load current from two (three) -power transformer windings
WW1
1- inject current in two phase R of winding 1 & R of winding 2 and phase shieft between them
until the relaytrip and read the measurment value of I base current and be surethat its
and chick the difrential value it must be equal to IS1
K1 1.714286
k2= 2.4
measurment without zero
50 I DIFF=(I1*CT matching factor of h
vt primary winding 2 33 I RESTRAIN=((I1*Ct matching of h
measurment with zero seq
ct winding 2primary 1200 I DIFF=(I1*CT matching factor of h
ct winding 2secondary 1 I RESTRAIN=0.5((I1*Ct matching o
TTING ct ratiowinding 2 1200 matching factor=ct ratio /
0.2
30.00
1.5
70
15
30
i2 injectd from low 1.34
match factor(lV) 1.371744
0.519
W2
est:
nd phase shieft between them 180 deg. And increase the value of current of phase R of winding 2
rent and be sure that ites value less than IS1 /K1
for other phses
nd phase shieft between them 180 deg. And increase the value of current of phase R of winding 2
ent and be surethat its
ibiase 0.35
IBIASE 1.6
2.4
measurment check
WI
I DIFF>pick up 0.216
I pick upwith zero se 0.325
I DIFF>>pick up 0.927
I pick upwith zero se 1.390725
I diff 0.38
SLOPE 1 0.253
I diff 1.25
SLOPE 2 0.50
DATA
sref 133
132 VMIN 132 vt primary winding 2 33
W2
I DIFF> DROP OFF 0.178 IDIFF> pick up 0.231
I pick upwith zero se 0.267 ` I pick upwith zero se 0.346
IDIFF>TRIP 0.271
I pick upwith zero se 0.407219
I REST 5
I DROP OFF 0.190
I pick upwith zero se 0.285
SLOPE1
I DIFF MEASURED 0.99 I RESTRAIN MEASURED
0.304615384615385
iw1 0.944101865758598
IR test 2 1.21218305346265
iw1 1.78882458775313
iw1 1.86403042627729
350
vt primary winding 2 132
3.25
TEST
iw2 0.408598550112047
iw2 0.194271575570719
iw2 0.153677515003703
1
8.133
main page
WHAT MEANINIG OF Z%
IT RATIO FROM RATED VOLTAGE IF APPLIED IN SHORT CIRUIT THE RATED CURRENT WILL FLOW
trtransformer data
sref
vt primary winding 1 33
HV CT RATIO 600
HV RATED CURRENT 349.9195
VECTOR GROUP
I S.C AT LV 297.31
I S.C AT LV 279.63
ansformer data
sref 20
vt primary winding 2 13.8
LVCT RATIO 1200
LV RATED CURRENT 836.7641
CTOR GROUP
transformer data
ww1
SETTING
sref 350
I DIFF> 0.3500
SLOPE 1 0.2500
rated voltage 380
SLOPE2 0.4000
BASE POINT OF SLOPE 1(K1) 0.0000
rated current 532
BASE POINT OF SLOPE2(K2) 2.5000
I DIFF>> 1.0000
ct 300 1
ct ratio 300
k matching 1.7726
vector groub y
kvg 1.0000
I diff(w1,w2) 0.4042
I diff(w1,w3) 0.4
transformer data
w2 w3
132 33 kv
1531 6124 A
1600 1 2000 1 A
1600 2000 A
1.0451 0.3266
0.9568 3.0618
y d1
0.2344 1.2977 A
0.3349 1.8539 A
Characteristic equation for the range
5≤I STAB≤16
I diff 1.2600
0.6698 3.7078 A
0.9568 5.2969 A
equation for the range:
IFF>/ SLOPE 1)
I REST 2.0000
SLOPE 1 0.2500
SLOPE 2 0.5040
transformer data
ww1(S)
SETTING
sref 350
078P 0.35
SPL1 30.00
rated voltage 380
SPL2 70.00
U87P 1.00
rated current 532
IRT1 1.17
IRT2 0.50
ct 300 1
DIOPR 1.20
DIRTR 1.20
ct ratio 300
TAP 1.7726
vector groub y
TNCTC 0
I diff(w1,w2) 1.0719
I diff(w1,w2) 1.0719
I diff(w1,w3) 0.51
w1-w2
iw1 1.01366726639344
iw1 1.78882458775313
iw1 1.86403042627729
transformer data
w2(T) w3(U)
132 33 kv
1531 6124 A
1600 1 2000 1 A
1600 2000 A
1.0451 0.3266
0.9568 3.0618
y d1
0 1
w1-w2
1.0000 0.8660
I DIFF MEASURED 0.51
SLOPE1 0.310975609756098
1.5000
SLOPE 2 DIFFERENTIAL T
I restraini (w1,w2) 1.0719
I restraini (w1,w2) 1.0719
0.3349 0.9280 A
0.9568 2.6515 A
IR test 1
IR test 2 1.21218305346265
iw2 0.194271575570719
iw2 0.153677515003703
IFFERENTIAL TEST
w1-w2 w1-w3
I RESTRAIN MEASURED 1.64 I DIFF MEASURED 0.16 I RESTRAIN MEASURED
2 DIFFERENTIAL TEST
1.03035559544326
w1-w3
1.21218305346265
iw3 0.538365390221576
iw2 0.425871129578262
main page
LDC-Z= Line Drop Compensation for Z Parameter,
Ipu= Iinjected/INOMINAL , Vcon= Voltage constant,
data
BW SETTING 2 VCON SEC 113.3 I INJECT
LCD-R 5 LDC-X 0 I NOMINAL
LCD-Z 10 FL 0 FL (Radian)
BW CALCULATION
U -RAISE 108.0 U -LOWER
BW-CALULATE 1.41 BW-ERROR%
V COMP 118.3
U -RAISE 115.9 U -LOWER
U -RAISE PH 66.94 U -LOWER PH
data
BW SETTING 1 VCON SEC 110 DV
VTPRIMARY 132000
SETTING OFF
111.0
No off tap change = Last tap-1st Tap=
64.1
1st Tap voltage -Last tap voltage
Tap ∆v= No off change
111.1
-0.6 Tap ∆v at prim.= Tap ∆v
Trans. Prim. Voltage
SETTING ON Tap ∆v At prim.*trans. sec voltage
Tap ∆v At sec.=
Sin(360- ØL) √3
118.3 (ZT1/100)*V²sec
ZT.=
120.7 Trans power
69.7
tap diff voltage at sec
ONE STEP DIFF CURRENT PRIM. SIDE=
Zloop(Tr1+Tr2)
123.3
125.8 TR NO NO OF TAP TAP (DV)
72.6 TR-1 20 1650
TR-2 20 1650
TR-3 20 1650
2 1/X1 1/X2
2 0.055 0.055
30
ZIV PASSWORD= 1793 & 2140
TRANSFORMER data
VT SECONDRY 33000 CT
EXAMBEL
Last tap-1st Tap= 21-1=20
Last tap voltage 145200-112200
. =
20
Tap ∆v = 1650
Trans. Prim. Voltage
.
132000
rans. sec voltage 0.0125*33000
=
3 √3
.
=
.
(20.06/100)*33000*33000
100000000
CT RATIO
=
.
TAP DV AT( PRM) TAP DV AT( SEC) ZT % 0ne step diff current
0.0125 238.163972286374 1.97109 T1&T2
0.0125 238.163972286374 1.97109 T2&T3
0.0125 238.163972286374 3.17988 T3&T1
20
VT
=
.
1650 V
RTV1
I1M
=
.
0.0125 V V1M
VCON
=
.
238.157 V
I CIRC
=
.
2.18453 Ω
=
.
53.21 A
53.21
1750/5 . = 0.152 A
PRIM(A) SEC(A)
60.4142815108326 0.173
46.236722847614 0.132
46.236722847614 0.132
50.9625757353535 0.146
KR(%)2TR KR(%)3TR
3.62 2.190
VComp (%) = VCO
data
33000 110 CT 1750 5
300 R1CT1 350 Q2M -19.959
2 ɸl 30 Q3M 0
33000 NTRF 1 Q4M 0