Status:26/05/2009 SERVO3
Flashtool
Guide
File name: P:\usr\projekte\Servo3\03 Software\4 Design&Developement\FlashTool\Servo3 Flashtool Guide.doc Page 1/11
Status:26/05/2009 SERVO3
TABLE OF CONTENTS
1 INSTALLATION 3
1.1 Installation of Lexium CT 3
1.2 Installation of Flashtool 5
2 FLASHING 7
3 KNOWN PROBLEMS 11
File name: P:\usr\projekte\Servo3\03 Software\4 Design&Developement\FlashTool\Servo3 Flashtool Guide.doc Page 2/11
Status:26/05/2009 SERVO3
1 INSTALLATION
1.1 Installation of Lexium CT
Before installing the Flashtool, the commissioning tool "Lexium CT" has to be installed.
The commissioning tool can be downloaded from the Internet, see Download area under:
http://www.schneider-electric-motion.com
During installation, you may be requested to enter your proxy server address, because the Installer downloads
the real Lexium CT from the Internet.
Example proxy setting for access in Niederschopfheim
File name: P:\usr\projekte\Servo3\03 Software\4 Design&Developement\FlashTool\Servo3 Flashtool Guide.doc Page 3/11
Status:26/05/2009 SERVO3
You can choose the following components:
File name: P:\usr\projekte\Servo3\03 Software\4 Design&Developement\FlashTool\Servo3 Flashtool Guide.doc Page 4/11
Status:26/05/2009 SERVO3
1.2 Installation of Flashtool
After installation of ‘Lexium CT’, the flashtool for programming the firmware has to be installed by activating
the setup file: ‚setup_flash3_ES.exe’
Proceed with the following steps:
File name: P:\usr\projekte\Servo3\03 Software\4 Design&Developement\FlashTool\Servo3 Flashtool Guide.doc Page 5/11
Status:26/05/2009 SERVO3
After setup is completed, the following dialog is shown:
File name: P:\usr\projekte\Servo3\03 Software\4 Design&Developement\FlashTool\Servo3 Flashtool Guide.doc Page 6/11
Status:26/05/2009 SERVO3
2 FLASHING
After starting the Flashtool, the communication protocol has to be selected, use ModbusRS485.
File name: P:\usr\projekte\Servo3\03 Software\4 Design&Developement\FlashTool\Servo3 Flashtool Guide.doc Page 7/11
Status:26/05/2009 SERVO3
Then press "1. Select Firmware" and select the firmware file to be flashed
Info: The numbers for Program and Version are not displayed in without points.
File name: P:\usr\projekte\Servo3\03 Software\4 Design&Developement\FlashTool\Servo3 Flashtool Guide.doc Page 8/11
Status:26/05/2009 SERVO3
Then press "2. Connect" and select the COM port and the communication parameters as seen below.
Then press "Flash" and wait what happens. The download will take about 6 minutes (with 19200 Baud).
File name: P:\usr\projekte\Servo3\03 Software\4 Design&Developement\FlashTool\Servo3 Flashtool Guide.doc Page 9/11
Status:26/05/2009 SERVO3
After flash process finished you see:
After the flash procedure is finished successfully the firmware is rebooted automatically.
File name: P:\usr\projekte\Servo3\03 Software\4 Design&Developement\FlashTool\Servo3 Flashtool Guide.doc Page 10/11
Status:26/05/2009 SERVO3
3 KNOWN PROBLEMS
On some PCs, there are sometimes communication problems with the Schneider RS232/RS485 converter.
In this case Nudam converter or Universal cable is recommended.
File name: P:\usr\projekte\Servo3\03 Software\4 Design&Developement\FlashTool\Servo3 Flashtool Guide.doc Page 11/11