Aci 515.1R-79
Aci 515.1R-79
1R-79
cies of the Department of Defense and for listing in
the DoD Index of Specifications and Standards. (Revised 1985)
This Guide updates and expands the scope of the cember 1966 ACI JOURNAL. William H. Kuenning was
committee report "Guide for the Protection of Con- chairman when this Guide was published. Albert M.
crete Against Chemical Attack by Means of Coatings Levy was chairman from 1974 to 1977 when some of
and Other Corrosion Resistant Materials:' which ap- the information, found in the chapters on "Water-
peared in the December 1966 ACI JOURNAL. The pre- proofing Barrier Systems" and "Dampproofing Bar-
vious Guide has been revised and is found in rier Systems," was developed.
Chapter 6 of this Guide entitled "Protective Barrier
Systems." In addition, there are new chapters on
"Waterproofing Barrier Systems:' "Dampproofing
Barrier Systems," and "Decorative Barrier Systems." Chapter I-Introduction, page 5I5.IR-2
A separate chapter on conditioning and surface 1.1-General discussion
preparation of concrete is included because it is rele- 1.2- The systems concept for barriers
vant to all the other chapters. 1.3-Barrier performance difficult to define
This Guide is not to be referenced as a complete 1.4-Economic factors for barrier selection
1.5-lnspection during application
unit.
1.6-Safety requirements
plication work, and to make sure the barrier is ap- proofing given in ACI Special Publication 192 is:
plied in accordance with the specification. Inspec- "Treatment of concrete or mortar to retard the pas-
tion should commence before the barrier is installed sage or absorption of water, or water vapor, either by
and the final inspection should be made after the application of a suitable coating to exposed surfaces,
barrier has been placed. Use technical assistance
available from the materials manufacturer or retain
an independent inspection agency familiar with the
specified barrier system.
1.6-Safety requirements
Appropriate safety requirements should be fol-
HYDROSTATIC
lowed with respect to all materials, operations and PRESSURE
procedures described in this Guide. J.2
Not harmful
Disintegrates. especially in presence of Disintegrates. especially in presence of
air air
Chromic acid, all Attacks steel in porous or cracked See automobile and diesel exhaust
concentrations concrete gases
Snlfides le<lching from d<lmp coh may See ammonium sulfate. ammonium
oxidize to sulfurous or sulfuric acid superphosphate. manure. potassium.
(which se"l nitrate. sodium nitrate
Copl",r pl<lliug
solutions Ipl
Ilot gases (-lO()-1100 F) cause thermal
Ilisinlegr<lt"s cOllu"l" 01 ill,,,I'''lu<lte stress"s, Cool"d, C!lndensed sulfurous.
"dLII" n'Sisl;lIll:l~ hl'druchloric ,,,:ins disinlegrall, slowly
-Formic acid. 30
percent Liquid disintegrates slowly. Dried or
drying films are harmless
-Formic acid. 90
percent May disintegrate moist concrete by
action of carbonic. nitric or sulfurous
acids (see also automobile and diesel
Hydrofluoric. other acids. and sugar
exhaust gases)
cause disintegration (see also
fermenting fruits. grains. vegetables.
extracts)
d
sulfall! Nickel plating Nickel ammonium sulfate disintegrates
snlutions (v) slowly
Disintegrates concrete of inadequate Potassium hydroxide.
sulfate resistance 25 percent or over
Perchloric acid. 10
percent
See text. Also calcium chloride.
magnesium chloride. sodium chloride
Potassiulll h\'droxid."
15 IwrCl,nt
Not harmful. except to calcium
aluminate cement
·Sodium hydroxide.
1-10 percent Organic acids. if present. disintegrate
slowly
'Sodium hydroxide.
20 percent or over
With moisture forms sulfurous acid 'Zinc refining solut;ons Hydrochloric or sulfuric acids. if
(which see) (x) present. disintegrate concrete
'Sulfuric acid. 80
percent oleum
SO'lletimes used in food processing or as food or beverage ingredient. Ask for advisory opinion of Food and Drug Administration
regarding coatings for use with food ingredients.
a Waters of pH higher than 6.5 may be aggressive if they also contain bicarbonates. (Natural waters 'lre usually of pH higher than 7.0
and seldom lower than 6.0. though pH values as low as 0.4 have been reported. For pH values below 3. protect as for dilute acid.)
b Frequently used as a deicer for concrete pavements. If the concrete contains too little entrained air or has not been aged more than
one month. repeated application may cause surface scaling. For protection under these conditions. see "deicing salts."
c Carbon dioxide dissolves in natural waters to form carbonic acid solutions. When it dissolves 10 extent of 0.9 to 3 parts per million it
is destructive to concrete.
d Frequently used as deicer for airplanes. Heavy-spillage on runway pavements containing too little entrained air may cause surface
scaling.
e In addition to the intentional fermentation of many raw materials. much unwanted fermentation occurs in the spoiling of foods and
food wilstes. also producing lactic acid.
h However. in those limited areas of the United States where concrete is made with reactive aggregates. disruptive expansion may be
produced.
n Composed mostly of nitrogen. oxygen. carbon dioxide. carbon monoxide. and water vapor. Also contains unburned hydrocarbons.
partially burned hydrocarbons. oxides of nitrogen. and oxides of sulfur. Nitrogen dioxide and oxygen in sunlight may produce
ozone. which reacts with some of the organics 10 produce formaldehyde. peracylnitrates. and other products.
o These either contain chromium trioxide and a small amount of sulfate. or ammonium chromic sulfate (nearly saturated) and sodium
sulfate.
Reference here is to combustion of coal, which produces carbon dioxide. water vapor. nitrogen. hydrogen. carbon monoxide. carbo-
hydrates. ammonia. nitric acid. sulfur dioxide. hydrogen sulfide. soot. and ashes.
u Porous concrete which has absorbed considerable molten paraffin and then been immersed in water after the paraffin has solidified
has been known to disintegrate from sorptive forces.
w May contain various mixtures of blood. fats and oils. bile and other digestive juices. partially digested vegetable mailer. urine. and
manure. with varying amounts of water.
x Usually contains zinc sulfate in sulfuric acid. Sulfuric acid concentration may be low (about 6 percent in "low current density"
process) or higher (about 22-28 percent in "high current density" process).
saponification reaction between animal fats and the Corrosion of Metals in Concrete. SP-49, American Concrete In-
hydration products of portland cement consumes stitute, Detroit, 1975, 142 pp.
ACI Committee 210, "Erosion Res'sti'nrp of Concrete in
lhese hydration products. producing salts arId alco-
Hydraulic Structures, "(ACI 21OR-55)(Reaffirmed 1979), American
hols, in & reaction analogous to that of acids. Concrete Institute, Detroit, 1955, 10pp. Also. ACI Manual of Con-
Many agents attack concrete and destructively al- crete Practice. Part 1.
ter its chemical composition by means of reaction
mechanisms which are only partially or incom-
pletely understood. Sea water. perhaps largely be-
cause of its sulfate content, may be destructive to CHAPTER 3-CONCRETE CONDITIONING
permeable concrete or those made with cement hav- AND SURFACE PREPARATION
ing a high tricalcium aluminate content. Some poly- 3.1-General requirements
hydroxy organic compounds such as glycols. This chapter provides recommendations for condi-
glycerol, and sugars slowly attack concrete. tioning or repairing the concrete surface by removing
2.5.3 Materials that do not attack concrete- There surface defects that can affect the performance of the
are a large number of chemical's which do not attack barrier system and for surface preparation by chem-
concrete. Many of these are listed in Table 2.5.2. ical and blast cleaning methods to insure good adhe-
Among the common I1eutral salts w. icI1 do not sion between he I)arrier mater' I ?nr thp r0'1rrptp
attack concrete are most carbonates and nitrates. The documents issued by ACI Committees 301. 302.
some chlorides. fluorides, and silicates. Lime water and 311 should help to assure the desired concrete
is usually beneficial to concrete because it promotes quality.1.Z.12 New concrete must be structurally
hydration without removal of lime from the concrete. sound, dry and clean to prevent loss of bond. How-
Other weak alkaline solutions are not usually ever, some proprietary barrier systems can be applied
harmful. Products derived from petroleum. when to green or wet concrete, but their use should be
free of fatty oil additives or other potentially acidic based on the recommendations and detailed instruc-
materials. are normally harmless to mature concrete. tions of the materials manufacturer.
Some of these materials can, however, cause undesir- The three types of surface contamination that can
able discoloration. result in poor adhesion of the barrier material to the
concrete are described below.
2.6-When decorative painting barrier systems 3.1.1 Release agents on forms-Release agents on
are used forms. such as oil, wax. grease and silicone. which
In addition to changing color or appearance of the will transfer to the concrete surface during place-
concrete surface for esthetic reasons, a decorative ment. should not be used if a barrier system will be
paint barrier can minimize concrete suface degrada- applied later. If materials are not completely removed
tion by rust stains from improperly filled form-tie they cause poor adhesion between the barrier system
holes. from embedded steel and from mold or algae and the concrete. Since these materials are usually
growing on a moist surface. These materials may also invisible. their complete removal may be difficult. In
function as a protective barrier system as defined in addition, the procedure for their removal will de-
Section 6.1 in Chapter 6. pend on the nature of the specific contaminant. Pro-
prietary paint systems applied to forms and
References formulated to prevent contamination of the concrete
1. "Standard Definitions of Terms Relating to Bituminous and surface should be used.
Other Organic Materials for Roofing, Waterproofing. and Related 3.1.2 Curing. compounds-Curing compounds
Building or Industrial Uses," (ASTM D 1079-74), ASTM, Phila- should not be used on concrete surfaces on which an
delphia, 1974. I . adhesive-bonded barrier is to be applied unless it
2. ACI Committee 11/;. "Cement and ConcretE' er inology,"
(ACI116R-78). American Concrete Institute, Detroit. 1978,50 pp.
car. be completely removed oetore appllcauon at t e
3. ACI Committee 201, "Guide to Durable Concrete," (ACI barrier, or unless the curing compound is compatible
201.2R-77)(Reaffirmed 1982), American Concrete Institute. De- with the barrier material and the concrete surface.J
troit, 1977, 37 pp. Liquid, meTllPrane.-forming curing compounds
4. Biczok, (mre. Concrete Corrosion-Concrete Protection, 8th consisting of waxes, resins. chlorinated rubber and
Edition, Akademiai Kiado, Budapest, 1972,545 pp.
5. Woods, Hubert. Durability of Concrete Construction. ACI
solvents are used extensively for curing concrete. Re-
Monograph No.4, American Concrete Institutellowa State Univer- cently, curing compounds based on two component.
sity Press. Detroit. 1968. 190 pp. epoxy resin paints have been developed which may
6. ACI Committee 515. "Guide for the Protection of Concrete be more compatible with barrier systems; however.
Against Chemical Attack by Means of Coatings and Other Corro- field testing is necessary to establish compatibility.
sion Resistant Materials," ACI JOURNAL. Proceedings V. 63. No.
12, Dec. 1966, pp. 1305-1392. 3.1.3 Admixtures in concrete-Some special pur-
pose admixtures, such as water-immiscible chem-
icals intended to retard evaporation of water during
Additional sources of information
Polymers in Concrete. SP-40. American Concrete Institute, De-
cure, when added to the concrete during mixing may
troit, 1973, 362 pp. \';i'cci,e adhesion problems.
Polymers in Concrde: Inlernational Symposium. SP-5!l. Ameri- The barrier material should be compatible with the
can Concrete Institute. Detroit. 197!l, 426 pp. surface of the concrete.
Description of concrete
problems
Small surface voids 1:1 grout. made with portland cement and sand passing
and rutted cracks the No. 30 sieve. Mixed to a creamy consistency.
Epoxy. urethane. or resin latex with inert fill- The latex or resin should have high filler content.
ers blended to a thick consistency.
Large surface voids 1:2.5 to 1:3 mortar. made with portland cement. and
and rutted cracks sand passing a No. 16 sieve. mixed to a stiff consistency.
. C
Polymer (latex or epoxy) modified composi- Latex or Ppoxy with portland cement and suitable aggre-
tion gates.
3.2-Repair of surface defects patches with white portland cement replacing part of
ACI Committee 301 has developed procedures for the gray portland cement should be made on ex-
the repair of surface defects in cast-in-place concrete, posed concrete to select the patch proportions with
and these are described in this section.! For addi- the best color match. The quantity of mixing water
tional information review the procedures developed should be limited to that necessary for handling and
by the Bureau of Reclamation.4 Precast concrete is placing. The patching mortar should be thoroughly
normally produced in a shop operation. Sharp off- mixed and worked with a trowel to the extent that it
sets between precast sections should be corrected as is the stiffest consistency that will permit placing.
indicated for new cast-in-place concrete. Surface de- 3.2.1.2 Application of patching material-After
fects, including tie holes, unless otherwise specified surface water has evaporated from the area to be
by the contract documents, should be repaired im- patched, the bond coat should be well brushed into
mediately after form removal (see Table 3.2). the surface. When the bond coat begins to lose the
3.2.1 Removal and repair of defects-Pro· water sheen, the premixed patching mortar should
cedure- All honeycombed and defective concrete be applied. The mortar should be thoroughly consol-
areas should be removed down to sound concrete. If idated into place and struck off so as to leave the
chipping is necessary, the edges should be perpen- patch slightly higher than the surrounding surface.
dicular to the surface or slightly undercut. No feath- To allow for some initial shrinkage. it should be left
eredges should be permitted. The area to be patched undisturbed for at least 1 hour before being finally
and a band at least 6 in. (150 mm) wide surrounding finished. The patched area should be kept damp for 7
it should be dampened to prevent absorption of days. Metal tools should not be used in finishing a
water from the patching mortar. A bonding grout or patch in a formed wall which will be exposed.
bond coat should be prepared using a mix of approx- 3.2.1.3 Special patching procedures for protec-
imately one part cement to one part fine sand (sand tive barriers-The repair of defects in concrete
passing a No. 30 mesh sieve). mixed to a consistency which will be covered with a protective barrier sys-
of thick cream, and should then be well brushed into tem for intermediate service (see Table 6.3) requires
the surface. ACI 546.IR and ACI 303 also describe special attention. Conventional portland cement-
patching with portland cement concretell.H based patching materials should not be used unless
3.2.1.1 Patching material-The patching mix- specifically recommended by the barrier material
ture should be made from the same materials and manufacturer. Adhesion of these patching materials
with approximately the same proportions used for to cured concrete may not be high enough to prevent
the concrete if esthetics are important. The coarse loss of bond caused by the internal stresses in the
aggregate should be omitted. The mortar should con- barrier material (see Sections 6.1 and 6.2 for a more
sist of no more than one part cement to 2 '1~ parts detailed explanation of this phenomenon). The use
sand by damp loose volume. Where appropriilte. trial of proprietary patching materials with polymer addi-
tions should improve adhesion to the concrete, but it The use of cementitious quick-setting materials
must be determined whether the polymer addition should be considered as water stops only until per-
will affect the adhesion between the patching and manent surface repairs can be made. Epoxy injection
barrier materials. Patching with resin-based mate- or chemical grouts can be either a temporary or per-
rials, using the same resin that is used for the protec- manent repair depending on the following condi-
tive barrier material, may be the most reliable tions. If the crack is nonmoving. epoxy injection
method. However, it is necessary to obtain specific could be a permanent repair. If cracks move enough
recommendations from the manufacturer. to destroy adhesion between the concrete and the
3.2.2 Tie holes-After being cleaned and thor- epoxy, the repair should be considered to be tempo-
ougly dampened. tie holes should be completely rary. Chemical grout can be effective on a permanent
filled with patching mortar. basis if it is not allowed to dry out.
3.2.3 Proprietary materials-Proprietary com- 3.3.2.1 Cementitious quick-setting materials-
pounds may be used in lieu of. or in addition to. the These materials are made from portland cement,
foregoing patching procedures.1O Such compounds sand (in some cases) and a chemical that will accel-
must be used in accordance with the manufacturer's erate the setting time or hardening. If metals (rein-
recommendations. Specific approval from the barrier forcement, conducts, etc.) are embedded in the
manufacturer should be obtained before proprietary concrete of the structure being treated, materials con-
compounds are used for patching. These materials taining chloride should not be used that would pro-
should be compatible with the barrier system and duce in the quick-setting mix a chloride ion content
not interfere with good adhesion between the two. exceeding the limits suggested in Section 4.5.4 of the
3.2.4 Fins and sharp offsets--Fins, protrusiuns or ACI 201 "Guide to Durable Concrete" for the various
similar irregularities projecting from the concrete construction and environmental conditions de-
surface should be removed back to the surface by scribed therein. Setting time may be from 15 seconds
chipping. bushhammering. needlegunning, or wire to several minutes, depending on the formulation
brushing. Care should be exercised to obtain a rea- used. mix proportions and temperature. Because of
sonably planar surface for application of the barrier the alkaline nature of these materials, rubber gloves.
system. Sharp offsets in the surface, such as those goggles and protective clothing should be worn. Mix-
caused by form work misalignment, should be me- tures of plaster of paris and cement should not be
chanically abraded to provide gradual and smooth used because of the danger of excessive expansion
transitions between the offset surfaces. For some bar- that could cause cracking of the patching material.
rier systems. it is normally not necessary to have all All loose and weakened concrete should be re-
surfaces of a concrete area in exactly the same plane, moved and the sides of a crack should be under-cut
so long as the transitions are gradual and smooth. before patching proceeds. Detailed instructions con-
The barrier material manufacturer should be con- cerning sl1rface preparation. type of quick-setting
tacted for recommendations. materials, and mixing and application procedures
should be obtained from the manufacturer of the
quick-setting materials.
3.3-Stopping or rerouting of water
Water. seeping or flowing into or through a con- 3.3.2.2 Epoxy injection-Temporarily seal the
crete structure must be stopped before a barrier sys- crack at the surface, using an epoxy resin paste. to
tem can be applied. Before deciding upon a repair withstand injection pressures. A low viscosity epoxy
procedure to stop the water. the type of defects pre- adhesive is then injected under pressure through
sent in the concrete and source of the water should ports which have been established in the surface
be determined. Three options to solving this problem seal. The injected adhesive displaces the water in the
are: crack and after curing binds both faces of the crack to
1. Stop or reroute water at its source. form a seal. Qualified and experienced applicators
2. Stop water on surface opposite source. should be used for this work.
3. Reroute water on surface opposite ~ource. 3.3.2.3 Chemical grouts-Small grout holes up
3.3.1 Stopping or rerouting water at source-Ex- to 1 in. (25 mm) diameter are drilled tlirough the
cavation outside the structure and installation of new concrete wall in the area of the leaks. Pipes are in-
drainage should be considered. Submarine ioca- serted and a low viscosity (2 cps). 2-part plastic
tions, bedrock. or abutting buildings may make ex- monomer solution is pumped into the soil. The soil
cavation impossible or uneconomical. However, becomes saturated with monomer which hardens to
partial treatment to reduce flow of water from the form a seal. The use of chemical grouts require
water-source side may facilitate work on the opposite qualified and experienced applicators and should be
side. limited to special applications.
3.3.2 Stopping water' on surface not in contact 3.3.3 Rerouting water on surface not in can fact
with the source-When water is coming through a with the source-Each crack through which water is
crack, hole. or porous area because the water cannot flowing should be covered with a small hollow en-
be stopped or re'routed at its source, it may be possi- closure to form a channel. As an example. wire mesh
ble to stop the flow from the side opposite the water. formed in a semicircle is placed over the crack and a
cementitious quick-setting material is used to cover 3.4.3 Mechanical cleaning
the holes in the mesh and to hold the mesh in place. 3.4.3.1 Scarification-Scarification by a me-
Several of these enclosures or channels are then con- chanical impacting device on concrete surfaces is
nected together to route the water to a central loca- useful to remove thick overlays of dirt or weakened
tion. Once the flow of water has been controlled, material. However, after scarification it is usually
other repair methods listed in Table 3.2 can be used considered necessary to water blast or sand blast to
prior to applying a barrier system. remove aggregate weakened by the mechanical im-
pacting. c;inding may be useful when small areas
3.4-Surface Preparation are to be cleaned or when the cleaned surface must
be smooth.
3.4.1 General-An important step toward achiev-
3.4.3.2 Blast cleaning-Blast or abrasive clean-
.ing adequate bond strength is to pay careful attention
ing is the most effective way to remove"laitance, dirt,
to the preparation of surfaces to receive barrier mate-
efflorescence and weak surface material. There are
rials. Good barrier performance depends on proper
three types of blast cleaning procedures: dry sand-
surface preparation. The concrete surface must not
blasting, wet sandblasting, and high-pressure water
be contaminated by chemicals that can prevent good
jetting. Abrasive cleaning methods other than sand-
adhesion between the barrier material and the con-
blasting can also be used provided that the surface is .
crete. The surfaces must be newly exposed concrete
not contaminated by the abrasive used. Selection of
free of loose, weak and unsound materials. Concrete
an abrasive cleaning method will depend in part on
surfaces should generally be dry; however, there are
local environmental restrictions and upon tests to
barrier systems that can be applied over damp con-
evaluate the effectiveness of the method used. Oil
crete. In these cases, the recommendation of the bar-
and grease that have soaked into the surface should
rier material manufacturer should be followed. Care
be removed prior to blast or abrasive cleaning (see
must be taken to prevent moisture from collecting at
Section 3.4.2).
the interface between the concrete and the barrier
The compressed air used for sandblasting must be
material during curing.
clean and free of oil particles. This means that the air
Bond strength is of critical importance for negative
compressor must be equipped with efficient oil and
side waterproofing barrier systems since the hydro-
water traps. Care must be exercised to assure that
static force is trying to force the barrier material off
clean water is used for wet blast cleaning.
the surface. For positive side waterproofing~arrier
systems, bond strength is critical for traffic-bearing 3.4.3.3 Amount removed by blast cleaning-The
applications and to prevent blistering and delamina- surface should be abraded to an extent that small
tion for exposed and above-grade applications. How- aggregate particles are exposed. If the surface of the
ever, for below-grade and positive side applications concrete is weak, more material should be removed.
where the barrier system will be pushed against the The amount removed should be sufficient to result in
concrete by hydrostatic pressure, bond strength may a strong, souhd substrate suitable for the intended
be considered important to prevent lateral movement barrier material.
of water that has been trapped behind the barrier 3.4.3.4 Blast cleaning methods-Comparisor:-
system. Wet sandblasting has an advantage over conventional
Prior to the application of a barrier material, it is (dry) sandblasting because the need for a dust collec-
generally considered necessary to test for adequacy tion system is eliminated. However, there may be a
of surface preparation. The strength of the prepared water removal problem. Water jetting remuves less
concrete surface, as well as the ability of the material surface material because no abrasive is used. It is
to adhere to the concrete, are the two major items to usually .::;onsidered to be a satisfactory cleaning pro-
check and are reviewed in 3.4.5. ACI Committee 503 cedure for a decorative painting (Chapter 7); how-
has developed detailed surface preparation pro- ever, for protective barrier systems (Chapter 6), it may
cedures, and these are found in 3.4.2, 3.4.3, and not remove enough weak surface material to enable
3.4.4." ASTM Recommended Practice C8ll-8t also these systems to perform satisfactorily.
covers surface preparation. II 3.4.4 Acid etching-In the past acid etching has
3.4.2 Chemical cJeaning- This step may be neces- been considered as a completely reliable method of
sary prior to blast cleaning or acid etching to remove surface preparation but experience has indicated that
surface contaminants such as oil. grease and dirt. it is not as dependable as mechanical abrading meth-
Solutions of caustic soda or trisodium phosphate ods. Acid etching is now only recommended for
may be used. as well as proprietary detergents spe- areas where no alternative means of cleaning are pos-
cially formulated for use on concrete. They should be sible. If acid etching must be employed, it should be
applied with vigorous scrubbing, followed by flush- performed by those experienced in its use.
ing with water to remove all traces of both the de- 3.4.4.1 Cleaning before acid elching- The sur-
tergent allJ the contaminant. Solvents should not be face to be acid etched should first be examined to
used for this purpose because they tend to dissolve determine the necessity for precleaning (see Section
the material and spread the contamination over a 3.4.2) to remove surface contaminants that acid etch-
larger area. ing will not remove. If contamination is only laitance
or a normal amount of dirt or traffic soil, other than A test to determine quality (i.e., strength) of concrete
grease or oil, precleaning is not required. A surface at and near the surface to a depth of Y4 in. (6 mm) is
moderately contaminated with oil should be pre- discussed in Section 3.4.5.4. The reason for this test
cleaned with a detergent. If oily, caked deposits of is explained in Section 6.2.3.
surface contaminants are present, the bulk of the ma- The applicable tests, described below, for various
terial should be removed by scraping before the de- barrier systems are listed in Table 3.4.5.
tergent treatment. Animal fats should be removed by 3.4.5.1 Cleanliness of surface
scrubbing with a 10 percent solution of caustic soda 3.4.5.1.1 Dusty condition-Wipe the surface
to saponify them. Other heavy deposits can be re- with a dark cloth. If a white powder is on the cloth,
moved by mechanical abrading methods. Detergents the surface is considered to be too dusty and there-
used for precleaning should be of a heavy-duty, non- fore unsatisfactory for some barrier systems.
ionic type. They should be scrubbed vigorously into 3.4.5.1.2 Oily condition-Sprinkle water on
the surface with a brush or power broom followed by the dried concrete surface. If the water spreads out
flushing with water until the surface is neutral or immediately instead of standing as droplets, it may
slightly alkaline (as indicated by litmus or pH paper) be concluded that the surface is not contaminated by
before beginning the acid treatment. oils or dust. The test will not reveal the presence of
other surface contaminants such as carbonates and
3.4.4.2 Acid etching procedure-The acid used
alkalies.
for etching should be a 10/90 to 20/80 dilution ratio
3.4.5.1.3 Acid condition-Use pH paper to
of commercial grade hydrochloric acid in water solu-
determine the acidity at the concrete surface. A pH
tion applied at the rate of 1 qt per sq yd (1.0 1/sq m).
below 4 is considered unacceptable.
When the presence of chlorides cannot be tolerated,
due to possible corrosion of the reinforcing steel, a 3.4.5.2 Dryness of surface-Test method-For
15 percent phosphoric acid solution should be used. some barrier systems, a qualitative moisture test for
For large areas, low pressure automatic spray equip- normal weight concrete is recommended by ACI
ment should be used to apply the acid solution. For Committee 503.6 Moisture content is considered ex-
small areas, plastic sprinkling cans can be used for cessive if moisture collects at the bond line between
dispensing the acid solution. A stiff bristle street the concrete and the barrier material before the bar-
broom, brush, or similar implement should be used rier has cured. This may be evaluated by taping a 4 x
4 ft (1.2 x 1.2 m) clear, polyethylene sheet to the
to spread the acid solution uniformly over the sur-
face. The foaming action of the acid will subside in 3 concrete surface and determining the time required
to 5 min, after which time the surface should be thor- for moisture to collect on the underside of a poly-
oughly flushed with water while scrubbing with stiff ethylene sheet. Also the ambient conditions. i.e.,
bristle or wire brushes to remove the salts formed by sunlight, temperature and humidity during the test
the reaction of the acid with the alkaline constitu- should simulate, as much as practical, the condi-
ents in the concrete and to dislodge loose particles. tions existing during application and curing of the
A second treatment may be necessary to insure an barrier. The time for moisture to collect should be
absolutely clean surface. compared with the time required for the barrier ma-
The adequacy of the flushing operation should be terial to cure-a value that should be supplied by the
checked at several points within the cleaned area by material manufacturer. If it cures in a time that is less
placing litmus or pH paper on the wet surface to than that required for moisture to collect, it may be
determine whether the acid has been completely concluded that the concrete is adequately dry.
neutralized. After it has been determined that flush- 3.4.5.2.1 Water-based barriers-To promote
ing is adequate, the surface should be allowed to dry. adhesion, water-based barriers should be applied to
On a normal sunny, summer day, concrete will usu- damp concrete surfaces. However, there should be no
ally dry sufficiently in about 1 to 2 hr. When forced . free-standing water on the surface of the concrete
drying is necessary, heat may be applied, or, if neces- 6l
when they are applied.
sary, dry, oil~free air may be blown over the surface. 3.4.5.3 Strength of surface when laitance is pre-
sent- The strength of the surface can be significantly
3.4.5 Tests for surface quality prior to applica- reduced by laitance. Laitance is defined as a layer of
tion- The quality of the concrete surface is an weak and nondurable material containing cement
important factor affecting adhesion of barrier sys- and fines from aggregates, brought by bleeding water
tems. Tests for cleanliness, dryness, and strength of to the top of overwet concrete, the amount of which
the surface will indicate whether good adhesion will is generally increased by overworking or over-
result. Tests will give a good indication of surface manipulating concrete at the surface by improper
quality. This is particularly true when evaluating the finishing.7
effect of concrete patching compounds and form re- 3.4.5.3.1 Test for laitance- The presence of
lease agents. The number of tests and the areas to be laitance may be detected by scraping the surface
tested shall be mutually agreed upon between the with a putty knife. If a loose powdery material is
manufacturer. applicator of the barrier material and observed, excessive laitance is present' Adhesion
owner's representatives and specified in the contract. could be adversely affected by this laitance.
Surface
strength to
depth of V.
Cleanliness Dryness Laitance Patch test in.
(3.4.5.1) [3.4.5.2) (3.4.5.3.1) (3.4.5.3.2) (3.4.5.4)
Waterproofing barriers
(Chapter 4)
Hot-applied bituminous-reinfQrced
Hot-applied bituminous-
nonreinforced
Prefabricated bituminous
Prefabricated nonbituminous
Cold-applied bituminous-reinforced
Cold-applied bituminous-
nonreinforced
Cold-applied nonbituminous
reinforced
Cold-applied nonbituminous
nonreinforced
Cementitious barriers
Dampproofing barriers
(Chapter 5)
Protective barriers
(Chapter 6 and Tab~ 6.3)
Decorative systems
(Chapter 7)
Water-based paints
Solvent-based one-component paints
Solvent-based two-component paints
3.4.5.3.2 Patch tests for surface strength-Ap- Appendix A of ACI Committee 503~ report. A
ply the barrier system to be used to an area of clean smaller, less cumbersome testing device called an
and dry concrete. After the barrier system has cured, Elcometer Adhesion Tester-O to 1000 lb/in.~ (0 to 6.9
the adhesion of the system should be checked. There MPa) range could be used to test the surface strength
is no standard test so the method of test and the of concrete.H
evaluation of test results will depend on the type and It is normally used for epoxy and polyester protec-
properties of the barrier system used. The manufac- tive barrier systems having thicknesses in excess of
turer of the barrier material should be asked to rec- '/\\; in. (1 Yz mm) (see Table 6.3). However, it has not
ommend test methods. been established that this test is necessary prior to
The patch test for surface strength will also indi- the application of all types of protective barrier mate-
cate whether the cleanliness (see Section 3.4.5.1) rials. The epoxy and polyester barriers usually fail by
and dryness (see Section 3.4.5.2) are satisfactory. a cohesive failure of the concrete just below the inter- .
3.4.5.4 Strength of surface to (J depth of '/~ ill. (6 face. The failure occurs when the internal stresses in
mm)-A practical field test method to measure the the material exceed the tensile strength of the con-
tensile strength of a concrete surface is described in crete. Three main sources of stresses arc: shrinkage of
the barrier material during curing, thermal stresses, of adhesion of the barrier material. The use of a ce-
and stresses from external loading. mentitious or a breather type barrier can minimize
3.4.6 Moisture in concrete and effect on barrier the problem.
adhesion-Concrete should be dry before the barrier
material is applied. Not only is surface moisture ob- References
1. ACI Committee 301, "Specifications for Structural Concrete
jectionable, but moisture within the concrete may
for Buildings (ACI301-84)." American Concrete Institute, Detroit.
also affect the ability of a coating to adhere to the 1984, 33 pp. Also. ACI Manual of Concrete Practice, Part 3.
surface. There are no precise guidelines to indicate 2. ACI Committee 311, "Guide for Concrete Inspection," (ACI
when moisture will be a problem, although a qualita- 311.4R-80) (Revised 1984)," American Concrete Institute, Detroit.
tive test is described in Section 3.4.5.2. A brief expla- 1980, 5 pp. Also, ACI Manual of Concrete Practice, Part 2.
nation of how the moisture in concrete can affect the 3. ACI Committee 308, "Standard Practice for Curing Concrete
(ACI 308-81)," American Concrtlte Institute, Detroit. 1981. 11 pp.
adhesion of a barrier follows. Also, ACI Manual of Concrete Practice, Part 2.
Poor barrier adhesion to the concrete can result if 4. Concrete Manual, 8th Edition, U.S. Bureau of Reclamation,
water vapor diffuses out to the concrete surface. A Denver, 1975, pp. 393-429.
surface that is too damp may produce voids in the 5. ACI Committee 503, "Use of Epoxy Compounds with Con-
material and lead to blistering or peeling after it has crete," (ACI 503R-80) (Revised 1984), America!'! Concrete Institute,
Detroit, 1984, 33 pp. Also, ACI Manual of Concrete Practice, Part 5
cured to a hard film. The following factors should be 6. ACI Committee 503, "Standard Specification for Producing"
considered in determining whether or not this will Skid-Resistant Surface on Concrete by the Use of a Mulli-
be a problem: Component Epoxy System {ACI 503.3-79)," American Concrete
1. The rate of vapor transmission through and from Institute, Detroit, 1979, 6 pp.
7. ACI Committee 116, "Cement and Concrete Terminology,"
the concrete.
(ACI 116R-78), American Concrete Institute, Detroit, 1978, 50 pp.
2. The amount of moisture remaining in the con-
8. Berger, D. M" and Mroz, S. E .. "Instruments for Inspection of
crete at any given stage. Coatings," Journal of Testing and Evaluation, V. 4, No. 1. 1976.
3. The ability of the coating to "breathe." and 9. ACI Committee 506, "Recommended Practice for Shotcreting
therefore, allow moisture to pass through itself. (ACI 506-66) (Revised 1983)." American Concrete Institute.
4. The temperature differential between the con- Detroit, 1983. 16 pp. Also, ACI Manual of Concrete Practice, Part 5.
10. "Special Products Evaluation List (SPELl." Report No.
crete surface and ambient air temperature while the FHWA·RD-83-093. Federal Highway Administration. Washington,
coating is curing. If the concrete temperature is be- 0, c., Aug. 1983, pp. 176-249.
low that of the dewpoint of the surrounding air, 11. "Standard Practice for Surface Preparation of Concrete for
moisture will condense on the surface. Application of Chemical-Resistant Resin Monolithic Surfacings,"
(ASTM C 811-Ell). ASTM, Philadelphia. 1981. 3 pp.
5. The ability of the material to displace moisture
12. ACI Committee 302. "Guide for Concrete Floor and Slab
from the surface. Construction," (ACI 302.1R-80), American Concrete Institute,
Proprietary cementitious materials are available Detroit, 1980.46 pp. Also, ACI Manual of Concrete Practice, Part 2.
which can be applied to damp concrete and concrete 13. ACI Committee 546, "Guide ior Repair of Concrete Bridge
which is subjected to hydrostatic pressure. These Superstructures," (ACI 546.1R-80), American Concrete Institute,
Detroit, 1980. 20 pp. Also, ACI Manual of Concrete Practice, Part 2.
materials can provide a dry surface for barriers re-
14. ACI Committee 303. "Guide to Cast-in-Place Architectural
quiring this property for good adhesion. Concrete Practice," (ACI 303R-74}(Revised 1982), American Con-
3.4.6.11nfluence of ambient conditions on adhe- crete Institute. Detroit. 1982, 30 pp. Also, ACI Manual of Concrete
sion-It has been found by experience that there is Practice, Part 3.
better adhesion between a concrete surface and the
barrier material when it is applied in the afternoon. It Additional sources of information
is reasoned that the concrete was exposed to sun and ACI Manual of Concrete Practice:
Recommendations for Construction of Concrete
air for at least 6 hr and this resulted in a lower surface Pavements and Concrete Bases (Part 21
moisture content. A secondary benefit for applying a Standard Practice for Selecting Proportions for Nor-
barrier material in the afternoon is that the surface mal. Heavyweight. and Mass Concrete (Revised
has, in most cases, reached its maximum tem- 1984) (Part 1)
Recommended Practice for Measuring. Mixing.
perature so no further expansion of air in the con-
Transporting, and Placing Concrete (Reaffirmed
crete pores will occur. This will eliminate the ten- 1983) (Part 2) .
dency for expanding air to cause blistering of the 305R-77 Hot Weather Concreting (Revised 1982) (pari 2)
applied barrier material while it is curing. 306R-78 Cold Weather Concreting (Revised 1983) (Part 2)
• No freeze/thaw protection on above grade or exposed • Membrane inaccessible. if sandwiched or backfilled for
applications inspection
• No corrosion protection if aggressive chemicals are present • Repairs
• May have to stop moisture flow to install the system • Additional excavation costs for installation of membrane
• Damage possible during backfill
used (Applicable to liquid-applied system-see Sec- When selecting a negative or positive side water-
tion 4.2.4.) proofing system, the specifier should thoroughly re-
15. Do not use barrier systems as surface applica- view the advantages and disadvantages of placing
tions over concrete decks that already have a barrier the waterproofing barrier on the negative or positive
on the underside. Blistering and/or delamination can side and of each type of waterproofing barrier mate-
result from entrapped moisture (see Section 3.4.6.2). O rial (see Table 4.2).
An exception is an unbonded barrier which is vented 4.2.1 Positive side waterproofing barrier sys-
or a barrier system that has an adequate transmission tems-Positive side waterproofing barrier systems
rate. (Applicable to liquid-applied systems-see are placed on the same side as the hydrostatic pres-
Section 4.2.4.) sure. Application methods are classified as hot-ap-
16. When barrier materials are exposed to the plied systems or cold-applied systems.
weather, they must be resistant to ultraviolet and Although hot-applied systems enjoy widespread
ozone or provisions should be made to protect ex- use, field conditions. experience. type of contractor,
posed areas with weather resistant flashing mate- safety, and personal preferences may dictate other
rials. As an example, some preformed 'barriers (see waterproofing systems. Cold-applied systems may be
Section 4.2.6) use clear polyethylene films which bituminous or elastomeric systems applied either as
should not be left exposed. (Applicable to sheet- a solid (roll or sheet) or applied as a liquid. Cold-
applied systems-see Section 4.2.5.) applied systems can be advantageous when smog
17. Require flood test for horizontal installations control or fire considerations prohibit the use of bi-
after work is complete (see Section 4.4.2). tuminous heating equipment. On tall buildings or for
18. Do not use liquid-applied materials over unre- remote locations. it may be more economical to use a
inforced lightweight aggregate concrete fills or thin cold system rather than hoist or transport the equip-
veneers that use PYA or latex additives or bonding ment needed for hot systems. The cold-applied sys-
adhesives. tems can be used on irregularly-shaped surfaces with
19. Liquid-applied barriers may not cover. hide, or less difficulty than that encountered with felt-
level surface irregularities. reinforc.ed, hot-applied bituminous systems. The liq-
20. The installation of subsurface and surface uid-applied elastomeric systems generally result in
drainage systems to reduce water pressure is membranes with excellent elongation characteristics
encouraged. at moderate temperatures. However, these same
me.mbranes may not have the same tensile strength
4.2-Guide tQ selection characteristics as membranes which use felt or fabric
When selecting a waterproofing system, the spec- as reinforcement.
ifier should use his experience and judgment. He Two types of reinforcing fiber constructions are
should consider the severity of the water conditions. used in waterproofing systems: namely, felt and fab-
the type of construction and the conditions under ric. Fabric has two advantages over felt: (1) It is
which the materials will be applied. The manufac- stronger, more pliable and conforms more readily to
turer should also be consulted concerning the thick- irregular surfaces, therefore, it is generally used as
ness, number of plies or coats- (where applicable), reinforcement at corners and angles; (2) It can absorb
details of openings. joints, cants, coves, penetrations, vibration and movement better than felt, so it is pre-
crack repair. termination details, application charac- ferred on bridge decks, tunnels, roadways, and under
teristics, protective covering, and other pertinent floors that support heavy machinery. Glass fabric is
data that will assure satisfactory performance of the more resistant to deterioration than cotton or jute
barrier system. and is therefore more useful for applications where it
.,: . ' .' ~
S'RUCIURAl SlAB
.ROIECIlOH BMRO ;:.:.' .:}: j ~ PROTECTION BOARD
f£ll OR fABRIC
... , .'
;
. ...
~.' ,.
Fig. 4.2.1.1-a-Schematic view. wall and slab water- Fig. 4.2.1.1-b-Schematic view. typical waterprO!lfing at
proofing.· base corner.
is not possible to use a protective covering (see Sec- and/or elastomeric materials; they may be "built-up"
tion 4.3.4]. in a manner similar to hot-applied systems or may be
Systems employing felts are generally considered applied as a liquid to form a membrane or may be
to be less permeable than fabrics containing cotton factory fabricated into sheets or rolls and then joined
or glass. in the field to form the barrier system. Within each of
4.2.1.1 Hot-applied bituminous barrier mate- these categories. there are several variations avail-
rials- The materials used for hot-applied systems able.
are bituminous substances of either coal tar pitch or Cold bituminous systel11s use asphalt emulsions _
asphalt derived from petroleum (see Sections 6.4.1 (see Section 6.4.2) or solvent cut-back asphaltic mas-
and 6.4.3]. tics and are reinforced with fabric. These mastics
The bitumens (coal tar pitch and asphalt] used in and emulsions have little strength within them-
hot-applied systems have very little strength within selves. The fabric acts as a reinforcement in the same
themselves. Fabrics and felts act as reinforcement to way that it does in hot-applied systems. Materials
withstand the strains of expansion. contraction. tem- used for waterproofing should be protected from the
perature changes. vibration. and building movement. weather.
Fig. 4.2.1.1-a is a schematic view of the waterproof- Many of the manufacturers do not recommend the
ing system for a wall and slab using hot-applied bi- use of asphalt emulsions below grade because they
tuminous barrier materials and fiber reinforcing may reemulsify if not fully cured before contacting
materials of either felt or fabric.· Nailers (see Section water. It is difficult to determine when the emulsion
4.3.2] and protection board (see Section 4.3.4) are has become fully cured. However, they may be used
also shown. Fig. 4.2.1.1-b is a more detailed view of a as a dampproofing barrier (see Chapter 5).
corner section.
4.2.1.3 Liquid-applied elastomeric barrier
Felts used in a waterproofing system are usually
materials
the same as those used for roofing purposes. Cotton
fabrics weigh a minimum of 10 oz per square yard 4.2.1.3.1 General description of materials-
(0.34 kg/m2) and have a long record of use. Glass Elastomeric materials are liquids that are applied by
fabric has been in use since 1946. It is the strongest of means of squeegee, roller, brush. trowel, or spray.
the fabrics in use. having a minimum tensile strength When cured. they form a film. resistant to water and
of 75 lb per in. (1.35 kg/mm) of width. Jute (treated many other chemicals. With some of these materials.
burlap) is sometimes used because of its coarse tex- the manufacturer may require reinforcement with
ture. All of the fabrics are available in a variety of glass fabric. An elastomer is defined in ASTM D1566
widths ranging from 3 in. (75 mm) to 48 in. (1220 as a "macromolecular material that returns rapidly to
mm). approximately the initial dimensions and shape after
Felt or felt-type materials in roll form should be substantial deformation by a weak stress and release
stacked on ends and protected from the weather. It is of the stress. "13 Some barrier materials may be used
extremely important that the rolls be stored to pre- as exposed coatings on roofs or floors for pedestrian
vent the ends from absorbing moisture. Fabrics or wheel traffic. while others may be protected by
should be stored on their side. surfacings such as concrete, asphaltic concrete.
Overheating and subsequent thermal degradation brick, or tile.
of the bituminous material occurs unless the kettle Liquid-applied membranes are formulated as sin-
temperature is controlled. Keep within the manufac- gle- or multiple-component products such as neo-
turer's recommended temperature limits. prene (polychloroprene). neoprene-bituminous
4.2.1.2 Cold-applied bituminous barrier mate- blends, polyurethane. polyurethane-bituminous
rials-Cold-applied systems may use bituminous blends. and epoxy-bituminous blends.
4.2.1.3.2 General application charac- sian joint can result in unwanted chemical reactions
teristics-Each of the liquid-applied systems has and deterioration of the joint sealant, sheet material
special application requirements that are peculiar to andlar barrier material.
that system. Some of the systems require a glass cloth
or mesh to reinforce the film. Others allow the film 4.2.1.3.3 Special application suggestions-
to stretch to provide maximum flexibility but require Liquid-applied systems can be vp-rysensitive to mis-
reinforcement with cloth or mesh over joints and handling and misuse during application. The follow-
cracks that are more than 60 mil (1Yz mm) in width. ing suggestions are made to eliminate or at least
The applicator should follow the manufacturer's di- minimize problems.
rections. When the directions or specifications are 1. Do not use liquid systems as surface applica-
not clear or appear to be contradictory, he should tions over concrete decks that already have a buried
request clarification. For surface preparation. refer to membrane under them. Blistering andlor delamina-
Chapter 3. Many of the systems require a dry film tion can result from entrapped moisture (see Section
thickness of at least 50 mil (1Y4 mm) where traffic is 3.4.6.2). Unlike an unbonded barrier, it is not possi-
expected. It is necessary to apply the material in ble to relieve pressure by venting.
multiple coats to minimize the effect of pin hole for- 2. Request that the manufacturer confirm that
mation, a characteristic of liquid-applied membrane membrane is suitable for the end use intended.
systems. 3. Follow manufacturer's guide specifications and
Weather conditions such as ambient temperature, resolve questions or disputed areas before contract
precipitation, and humidity can affect the quality of documents or final specifications are issued for bids
the application and subsequent performance of the and eventual award of contracts.
barrier system. Below a certain temperature. many of 4. Specify that the applicator must be approved
the materials will be too viscous to form a continu- and certified by the manufacturer of the system to be
ous film of the correct thickness and the adhesive used.
bond to the concrete is reduced in strength. In addi- 5. Specify that all technical data from the manufac-
tion, the development of required mechanical prop- turer and applicator be submitted to the specifier im-
erties may not occur as expected. Precipitation mediately after award of contracts.
during and immediately after applicaticn can also 6. Specify concrete surface quality and finishes to
adversely affect properties of the barrier material. meet requirements of Chapter 3.
The manufacturer should supply pertinent informa- 7. Do not use liquid-applied materials over light-
tion concerning cold and hot weather application as weight aggregate concrete fills or thin veneers that
well as the effect of moisture on the barrier material have polyvinyl acetate (PVA) or latex bonding agents.
during application. 8. Liquid-applied barriers will not cover. hide, or
Expansion joints should be fabricated in two steps. level surface irregularities.
First the two concrete sections should be joined with 9. Specify the type of flashing and reinforcing ma-
an eJastomeric sealant using standard procedures terials to be used. Provide flashings at all openings
'and recommendations of ACI Committee 504.10 After and projections where the membrane will terminate.
the barrier material is applied a sheet elastomer The various materials should be compatible and not
should be embedded into it and covered with addi- cause chemical reactions when in contact with each
tional liquid-applied barrier material to completely other. Compatibility should be determined by the
cover the sheet (see Fig. 4.2.1.3.2). material manufacturer.
The sheet elastomer must be compatible with the
chemical compounds used in the liquid-applied ma- 4.2.1.4 Sheet-applied barrier materials
terial as determined by the material manufacturer. 4.2.1.4.1 General description-Precured elas-
Using the wrong design and materials for the expan- tomeric sheet materials may be calendared, ex-
truded. or spread coated. The system may be fully
bonded to the substrate or laid loose (unbonded) ac-
cording to the manufacturer's rel::ommendations.
Sheet-applied materials. generally available. are
listed below:
1. Neoprene is a synthetic rubber identified as
polychloroprene. It has good resistance to intermit-
tent oil exposure and to bacteria. fungi, acids. ultra-
violet. and ozone. It is usually applied in 60 mil (1.5
mm) sheets and may be used either exposed or below
other wearing surfaces. 0
2. Butyl is a synthetic rubber identified as poly-
isobutylene. It is best suited for below grade. con-
cealed waterproofing installations. However, re-
Fig. 4.2.1.3.2-Schematic view, liquid applied barrier sistance to ozone, ultraviolet, bacteria, fungi, and
with expansion joinl.4 soil acids is good.
3. EPDM is a synthetic rubber resulting from the 1. Surfaces, on which an adhesive is to be applied,
polymerization of ethylene and propylene. Properly must be free of dust, dirt, and chemical contami-
formulated compounds based on EPDM provide nants, some of which may not be visible. Cleaning
good resistance to ozone, ultraviolet, and weather- such surfaces with detergent and/or solvents will
ing. The material supplier should provide test data to usually be effective.
indicate the degree of resistance to ultraviolet and 2. Adhesive peel tests before and during installa-
weathering. EPDM remains elastic through a wide tion should be conducted to determine the quality of
range of temperatures. the lap joints. The manufacturer of the material
4. Plasticized polyvinyl chloride (PVC) sheet is should be contacted for recommendations.
produced by adding a chemical, called a plasticizer, 3. The shelf-life of the adhesive should be checked.
to a hard and rigid polyvinyl chloride plastic. The Some adhesives that are stored beyond the recom-
r:esult is a soft, pliable material that has properties mended time or above the recommended tem-
similar to the three elastomeric materials listed perature, shown on the can label, will produce low
above. Some vinyls have relatively poor resistance to strength joints.
direct exposure to ultraviolet and weather compared 4. The "open-time" should also be given on the
to elastomeric materials. However, new plasticizers label. Many adhesive coated surfaces will not form a
for vinyls are now available to improve these strong bond if they have allowed to dry (solvent re-
properties. moval) for too long a period before joining. However,
4.2.1.4.2 Joining sheet materials-There are some solvent should be allowed to escape before
two methods of joining sheet-applied barrier mate- joining the two surfaces.
rials. One is adhesive bonding (or adhesive seaming) 5. Ambient temperature during application can af-
and the other is solvent cementing (or chemical fect "open-time." At low temperatures, the solvents
welding). In both casef>, a lap joint is formed where may evaporate too slowly and prevent formation of a
one sheet ovorlaps the other by 2 to 6 in. (5 to 15 cm). strong joint. At high ambient temperatures, the sol-
Adhesive bonding is used to join precured sheet vents may flash-off (evaporate) too fast to effect a
applied barrier materials such as neoprene, butyl, good joint.
6. The method of applying pressure just after the
and EPDM. The adhesives are usually solvent based
elastomers that are brush applied to the barrier sur- two adhesive-coated surfaces have been joined is
faces that are to be lap bonded. See Section 4.2.1.4.3 important. The manufacturer should give detailed
for details concerning the adhesive bonding instructions. The formation of "fish mouths" is one
procedure. problem encountered during joint preparation which
Solvent cementing, which is also known as chem- cannot always be solved by the use of extra pressure.
ical welding, is a special type of adhesive bonding A "fish mouth" describes a condition where the edge
and is usually used for joining sheets of plasticized of one sheet, because it is puckered or rippled, can-
Pve. In the case of solvent cemcnting, the adhesive not be completely bonded to the other sheet. The
is formed in-situ by dissolving the surface of PVC "fish mouth" can form a deep channel and be a
with a suitable solver-t. After the two surfaces to be source of leakage. The top of each "fish mouth" must
bonded develop a paste-like surface, they are then be slit to make it easy to join the unbonded rubber
pressed together. As the solvent diffuses away from pieces to the mating surface.
the joint, strength increases, developing full strength
in 24 to 48 hr. The comments in Section 4.2.1.4.3 4.2.1.4.4 Special application suggestions-
concerning adhesive bonding procedure also apply Like the liquid-applied systems, the sheet systems
to solvent cementing. can be very sensitive to misuse during application.
4.2.1.4.3 Adhesive bonding procedure-Each These suggestions are made to eliminate or at least
manufacturer should supply the adhesive suitable minimize problems:
for its material. Different adhesives may be needed 1. Barrier materials that are completely bonded to
for bonding to the substrates and the lap joints. The the concrete substrate are preferred over unbonded
manufacturer's recommendations and instructions ones.
for adhesive bonding should be followed because 2. Do not use curing compounds that interfere with
failure to do su will usually result in problems. When adhesion of the sheet to concrete (see Section 3.1.2).
using sheet barriers, the adhesive bonded lap joints 3. Minimize the number of penetrations through
or spliced butt joints are the most critical areas. The the barrier.
manufacturer should provide data about the long- 4. Provide continuous support for the sheet, other-
term strength retention properties, when exposed to wise punctures can be expected.
water, of adhesive bonds used to join these shect ma- 5. Provide protection board when work is per-
terials. The same kind of information should be re- formed over the barrier.
quested for adhcsive bonds betwecn concrete and the 6. Require a flood test after installation is
sheet materials. complete.
Succcssful adhcsive bonding requires that attcn- 7. Specify materials that are resistant to the ele-
tion bE givcn to the following items: ments in exposed situations.
4.2.1.5 Preformed barrier materials-A prefabri- such as pools. tanks, fountains, and concrete decks
cated waterproofing barrier usually consisting of (see Fig. 4.2.1.6). With proper design and attention to
polyethylene film, polyvinylchloride film, or non- accommodate for the rigid barrier, cementitious
woven plastic fabric, glass fabric, coated on one or membranes can also be used on below grade founda-
both sides with bituminous materials derived from tions. Special traffic bearing grades of cementitious
either asphalt or coal tar base materials and usually membranes are available for parking and pedestrian
modified with various polymers to improve physical areas.
properties. The overall thicknesses of these mem- 4.2.1.6.1 Special design considerations-
branes vary from product to product, usually ranging
Since cementitious membranes are rigid, they must
from 40-200 mil (1-5 mm). Preformed barrier mate-
be applied on sound concrete sections. Their rigid
rials are supplied in either sheet or roll form. The roll
nature requires careful design consideration with
form is generally more pliable and can be formed
particular attention required to joints and cracks sub-
around and into corners. Sheet material is not as ject to movement. Cementitious membranes with
pliable and must be cut to fit corners and other thermal coefficient of expansion and flexural proper-
changes in the form of the concrete surface.
ties comparable to that of concrete, as well as shrink-
4.2.1.5.1 Special application suggestions- age, are preferred; since they allow the membrane to
The following precautions should be followed when
move with the concrete and reduce the chance of the
specifying these membranes: membrane debonding or cracking. The following are
1. Provide complete backup for the barrier mate-
some general design considerations when using ce-
rial. Separation at laps may occur when the material
mentitious membranes:
is not fully supported when applied over large open 1. For above grade applications, characteristics of
areas. Further, these materials are more susceptible to the structure which cause movement at joints or
puncture when not supported. cracks deserve evaluation. These characteristics may
2. Anticipate substrate movement and provide suf- include thermal, shrinkage and normal structural
ficient expansion joints as required to preclude the response.
possibility of substrate cracks. 2. Cementitious membranes cannot span moving
3. Membranes that use clear polyethylene top
joints or cracks. Joints and cracks subject to thermal
films must not be left exposed. Plan to provide flash- and structural movement should be sealed with an
ing for protection from sunlight and physical damage elastomeric sealant or other material which would
as recommended by the manufacturer. accommodate such movement.
4. Provide protection to the membrane before
3. Before applying the cementitious membranes, it
backfilling. is recommended that the concrete be properly cured
4.2.1.6 Cementitious membrane barrier mate-
and allowed to complete its shrinkage.
rials-Cementitious membranes are waterproofing 4. Careful planning of joints is required to elimi-
barriers which become hard and rigid after being nate cracking of the concrete substrate. Design isola-
mixed. They can be applied by trowel, spray or by tion joints along all points of abutment between each
the dry-shake/power trowel method to the thickness substrate unit to accommodate for any differential
ranges between V8 in. (3 mm) for normal applications movement will protect the substrate and barrier from
and from Y4 to 1 in. (6 to 24 mm) for heavy traffic cracking.
bearing applications. Cementitious membranes are 5. Manufacturer's recommended architectural de-
available in various colors. They can be applied on tails and design guidelines should be closely fol-
damp. semi-smooth, rough, and irregular surfaces. lowed when utilizing cementitious membranes.
They can be dressed to provide a smooth. rough, or Cementitious materials have properties that are dif-
textured finish. Cementitious membranes are com- ferent from other membranes used for positive side
monly used on surfaces that will be left exposed, waterproofing.
4.2.2 Negative side waterproofing barrier sys-
tems---::Negative side systems are placed on the side
opposite the applied hydrostatic pressure. There are
WATER PRESSURE
FROM THIS SIDE two types of waterproofing barrier materials available
for negative side applications. They are cementitious
membrane waterproofing materials and metallic ox-
ide waterproofing materials.
1. Cementitious membrane waterproofing-Ce-
mentitious membranes are special, rigid, hydraulic
cement compositions which upon hardening form a
waterproofing cement coating. Cementitious mem-
branes. which are usually self-curing, are pre-
packaged, bagged mixes that require only the
Fig. 4.2.1.li-Sc:lwlJlotic vielV of positive side. above gra(h~. addition of water. Some manufacturers offer traffic
umwnlitious mcmbrune woterpruofing. bearing cementitious membranes which may be left
exposed to commercial and industrial traffic. Mate- 6. Additional properties to be considered when se-
rials are available for sealing active leaks, cracks, lecting a negative side barrier are flammability, tox-
penetrations, cants, coves. and fillets. Their applica- icity, effect on drinking water, resistance to efflo-
tion rates are normally specified in Va to V4 in. (3 to 6 rescence and discoloration, and ability to be
mm) thick applications. Some cementitious mem- patched.
branes resist very high hydrostatic pressures with a 4.2.2.2 Design considerations-Consideration
very low permeability, and therefore can be painted must be given to all joints and areas subject to move-
or coated with a protective barrier system if desired. ment since negative side waterproofing barrier sys-
2. Metallic oxide waterproofing materials-Metal- tems are rigid. Proper design and treatment of expan-
lic oxide waterproofings include a mix of fine metal- sion. control and construction joints are of vital im-
lic materials which chemically react, oxidize. portance. otherwise leakage will occur in those areas
penetrate and/or expand into the .capillaries of the which the barrier cannot span during movement (see
concrete, thereby decreasing the permeabiUty of the Fig. 4.2.2.2). Eacb substrate to receive the negative
concrete. Metallic oxide waterproofing materials re- side waterproofing barrier must be designed with the
quire surface preparation to yield an open pore and objective to move as an individual unit. Designing
capillary system to ensure capillary penetration. Ap- isolation joints along all points of abutment between
plication of metallic oxide waterproofing requires each substrate unit to accommodate for any differen-
field mixing of metallic filings, an oxidizing catalyst, tial movement will protect the substrate and the bar-
sand and cement with water. An application of 3 to 5 rier itself from cracking. The substrate unit must also
coats is normally required. Constant moist curing is be structurally sound. The structure and its founda-
also essential to promote oxidation. A sand/cement tion as a whole must also be designed to withstand
coat is usually applied as a finish coat. Metallic ox- the expected load and any hydrostatic pressure. Dif-
ide waterproofing, when properly mixed, applied ferential foundation settlement that could cause
and cured, results in a rigid waterproofing barrier. cracking should be eliminated. Existing structures
This type of barrier is highly dependent upon the undergoing attack. deterioration, settlement and
quality of workmanship. Close field supervision is structural failure must first be rendered sound prior
recommended to ensure proper mixing and that all to the application of any waterproofing barrier
steps are followed by the applicator. Material costs system.
are usually low, while the multicoat labor costs are 4.2.2.3 Installation
high. 4.2.2.3.1 Surface preparation-Proper surface
preparation is essential to ensure that a good bond is
achieved. Prepare the surface in accordallfe with the
4.2.2.1 Characteristics of negative side water- manufacturer's instructions. Surfaces mustb-e,Jree of
proofing barriers-For a negative side waterproofing loose, weak. and unsound concrete. Proper identifi-
barrier to perform effectively, a number of charac- cation of cracks subject to movement should be
teristics and properties are necessary, some of which made, and they must be isolated, and treated, to en-
may be unique and not required of positive side sure a properly sealed surface. See Chapter 3 for
waterproofing barrier systems. details.
1. The barrier must provide the lowest possible
The information in Section 3.4 should provide a
constant water permeability under hydrostatic pres- good guideline toward properly preparing surfaces to
sure immediately upon curing. This will ensure that receive negative side waterproofing barrier material.
the barrier will show no dampness on interior sur-
faces, or will not contribute to the humidity in the
sealed space.
2. The barrier must bond permanently to the sub-
strate, and the bond strength must be higher than the
expected hydrostatic pressure.
3. The barrier must be rigid to eliminate blistering,
ballooning, debonding, and rupturing under hydro-
static pressure.
4. Shrinkage in the plastic and hardened state
must be low enough to prevent cracking and debond-
ing. The thermal coefficient of expansion must also
be compatible with the concrete. These properties
are also important for properly sealing penetrations.
cants. coves. and cracks.
5. When required, the negative side barriers should WATER PRESSURE PIPE
FROM THIS SIDE PENETRATION
have good resistance to traffic. abrasion. erosion.
chemicals, and temperature resistance. Availability negoth'e
Fig. 4.2.2.2-Schemol it: view of below grode. showing
in various colors or the ability to be painted may be side. cenwllt it iow; lIlelll/)rolle woterproofing
desirable. p(~I1f!lrution.
4.2.2.3.2 Application rates and techniques- rely on the mechanical equipment supplier for de-
The application rates and techniques should be in sign detail that results in equipment supports that
accordance with manufacturer's recommendations. rest on the waterproof membrane. This should not be
Barrier materials which require field measuring and done because it results in conditions unfavorable to
mixing of bonding agents or additives, should be the waterproofing system. Poorly designed and ex-
avoided to eliminate the risk of improper measuring eCllted flashing can result in damage to the water-
and mixing. Prepackaged barrier materials with spe- proofing materials as well as to the contents of the
cific mixing instructions are preferred. building.
The techniques for applying negative side water- The surface of adjoining building elements that are
proofing barriers vary greatly. Generally, negative used to form the seal at the terminus of the water-
side barriers may be brushed, troweled, or sprayed proofing barrier should meet the same requirements
on cured concrete. Some proprietary cementitious as the surfaces that receive the waterproofing barrier.
powders may be dry-shaken and power troweled A treated wood nailer or other device may be needed
onto plastic concrete surfaces. Before initial set oc- so that the top edge of the flashing materials may be
curs, application rates are usually specified by thick- mechanically secured according to the man ufac-
ness or by average rate in Ib/sq ft. The specifier turer's recommendation. Reglets are not recom-
should insure that this rate can be controlled and mended as a substitute for a nailing strip or device.
inspected. In all cases the membrane flashing should be raised
4.2.2.3.3 Curing and protection-Self-curing well above the expected maximum "water line" of
materials are easier to install, provide more reliable the finished surface (see Fig. 4.3.1.1).
performance and are preferred. However, some ap- 4.3.1.2 Flashing below grade-In areas below
plied negative side waterproofing barriers require im- grade or below the wearing surface of plaza decks,
mediate additional moisture and a thorough moist flashing materials should be the same as or compati-
curing to complete their chemical reaction. Many ble with those used in the waterproofing system.
negative side waterproofing barriers require protec- Compatibility should be determined by the material
tion from traffic, abrasion, and erosion; however, cer- man ufact urer.
tain barrier materials are available which may be left
4.3.1.3 Flashing above grade-Elastomeric
exposed as a traffic bearing topping. Material proper-
flashing materials should be used with systems using
ties will dictate the necessary post curing protection
elastomers for waterproofing. Exposed edges must be
required.
water-tight, and stripped-in. Exposed material must
be resistant to sunlight and other weather condi-
4.3-Design and application
tions. Counterflashings, where desired for esthetic
4.3.1 Flashing
reasons, may be metal or a compatible elastomeric
4.3.1.1 General-The line or joint where the
material.
waterproofing membrane terminates at walls, etc.,
can be the most vulnerable area of the whole system. 4.3.2 Nailers-When vertical surfaces are to be
Many reports of failures or leaks can be traced back waterproofed and nailing is required, horizontal nail-
to faulty or poor construction details. The flashing ing strips, flush with the surface, should be provided
details are generally subject to the worst possible at least 4 in. (100 mm) above grade and at 6 ft (1.8 m)
conditions of weathering and mechanical damage. intervals along the height of the wall to permit in-
Many times the waterproofing system will not per- stallation of the barrier material in lifts or sections.
form satisfactorily because insufficient considera- The nailer should be treated to resist rot, decay and
tion was given to flashing design during the planning termites with a chemical that is compatible with the
stages. Often, the designer or building owner will bituminous materials used for waterproofing (see
Fig. 4.2.1.1-a and 4.3.2).
4.3.3 Joints-Joints in the concrete surface are ei-
ther construction joints, isolation joints, contraction
joints, or expansion joints. III Joints occurring be-
tween concrete placements that are reinforced by
continuing the slab or wall reinforcement through
the joints are construction joints. Joints that are not
reinforced must be treated as expansion joints ..
Expansion and isolation joints are designed to ac-
commodate movement in one or more directions, re-
spectively. They are an integral part of the structural
system and are designed to reduce stresses caused by
temperature fluctuations. differential foundation set-
tlements, and movements between different building
elements. Joints designed for seismic loading are
Fig. 4.3.1.1-Schematic view. waterproofing for slab below usually very large in order to accommodate move-
grade and at vertical surface.· ment due to earthquakes.
(grade line) ___ --- WEARING SURfAcr
Ext. face Int. face Ext. face Int. face Ext. face Int. face Ext. face Int. face
Water-based portland
cement paint X X X X X X
Portland cement
parging coated with
asphalt or coal tar X
Cold-applied asphalt X
Latex paints X X X X X X
Two-component epoxy
paints X X X X X
Solvent-based
chlorinated rubber
paint X X X X X X
Coal-tar-polyurethane
paint X X
Two-component or
moisture-cured
polyurethane paints X X X X X X
nor when the temperature is expected to drop to 32 F A protective barrier system consists of the barrier
(0 C) before the coating has dried or cured. Damp- material, the concrete surface it is protecting, the
proofing should not be applied in rain. snow, fog. concrete structure and the foundation. The quality of
mist, or when the relative humidity might result in concrete, especially at and near the surface will in-
condensation or frost formation on concrete surfaces fluence performance of the system because it affects
due to variations between the concrete surface tem- the ability of the barrier material to perform as ex-
peratures and ambient air temperatures. pected. The elements of a protective barrier system
5.3.2 Number of coats-At least two coats should are shown in Fig. 6.1 and the role of each is ex-
be applied, and often more, depending on the kind of plained in Section 6.2. An in-depth understanding of
coating and the severity of service. The number of 0 these elements is' essential in order to obtain op-
coats and thickness of each will depend on the timum performance of protective barrier systems.
nature of the service and upon the manufacturer's A major factor affecting performance of a protec-
recommendations. tive barrier is its ability to remain bonded to the con-
crete. Chapter 3 on surface preparation and section
3.2.1.3, in particular should be reviewed during the
CHAPTER 6-PROTECTIVE BARRIER SYSTEMS initial stages of design. to provide the basis for the
6.1-Characteristics of a protective barrier system construction specifications.
Protective barrier systems are used to protect con-
crete from degradation by chemicals and subsequent 6.2-Elements of a protective barrier system
loss of structural integrity, to prevent staining of con- 6.2.1 Barrier materiaJ- To be effective ill protect-
crete, or to protect liquids from being contaminated ing concrete. a barrier material should have certain
by concrete. basic properties:
(a) When the barrier material is exposed to a chem- CD Concrete to Depth
of 114 in. 16mml
ical environment. the chemicals should not cause
degradation. swelling, dissolving, cracking, or em-
brittlement of the barrier material. The chemicals
should not permeate or diffuse through the barrier so
as to destroy the adhesion between it and concrete.
(b) The abrasion resistance must be adequate to
prevent the barrier material from being abraded dur-
ing normal service.
(c) The adhesive bond strength of a nonbituminous
barrier to concrete should be at least equal to the
tensile strength Qf concrete at the surface. This bond
may also be affected by the cleanliness of the con-
crete surface.
Under40 mil Polyvinyl butyral, polyurethane, methyl • Protection against deicing salts.
(1 mm) methacrylate, alkyl-alkoxysilane, epoxy, acry lic, • Redu.::e exposure regarding freeze-
chlorinated rubber, styrene-acrylic copolymer thaw resistance.
• Prevent staining of concrete.
Asphalt, coal tar, chlorinated rubber, epoxy, • Use for high-purity water service.
polyurethane, vinyl, neoprene, coal tar epoxy, • Protect concrete in contact with
coal tar urethane chemical solutions having a pH as
low as 4, depending on the chemical.
125 to 375 mil Sand-filled epoxy, sand-filled polyester, sand- • Protect concrete from abrasion and
(3t09mm) filled polyurethane, and bituminous materials. intermittent exposure to dilute acids
This filler is usually silica sand. in chemical, dairy and food
processing plants.
20 to 250 mil Glass-reinforced epoxy, glass-reinforced • Protect concrete tanks and floors
lV' to 6 mm) polyester, precured neoprene sheet, plasticized during continuous exposure to dilute
PVCsheet mineral, (pH is below 3) organic
acids, salt solutions, strong alkalies.
freeze-thaw cycles. concr-ete staining. and high pu- phalt membrane covered with acid proof brick using
rity water service. Thickness of protective barriers a chemical-resistant mortar, and a sand-filled epoxy
are under 40 mil (1 mm). Some of the generic types of system top coated with an epoxy barrier.
materials used for the barriers include methyl meth- The thickness of the barrier usually increases as
acrylate, alkyl-alkoxysilane. polyvinyl butyral, the severity of the chemical service condition in-
acrylics. epoxy, polyurethane. chlorinated rubber, as- creases. Reference 1 should provide background in-
phalt, coal tar, and polyvinyl chloride. formation on this subject.
A recent study identified four barrier systems A description of the materials listed in Table 6.3 is
which were able to reduce chloride penetration in found in Sections 6.4 to 6.5.
concrete by 80 to 95% when compared with un- 6.3.1 Factors affecting selection-Selection of a
coated concrete." These were formulations based on barrier to protect concrete for a specific chemical ser-
epoxy, methyl methacrylate, and alkyl-alkoxysilane vice requires an awareness of the following items.:
materials. 1. The barrier material must be resistant to deterio-
2. Intermediate chemical service conditions- ration or degradation by the chemicals to which it
> Typical examples of intermediate service conditions will be exposed at the operating temperature.
are intermittent exposure to dilute acids in chemical,. 2. The barrier material must resist the diffusion or
dairy, and food processing plants. and abrasion in permeation of the chemical through it. Adhesion of
combination with chemicals. Thickness of protective the barrier material to concrete can be adversely af-
barriers are 125 to 375 mil (3 to 9 mm). Typical bar- fected by this phenomenon-especially when the
rier materials include filled epoxy, filled polyester, diffusing material is acidic.
filled polyurethanes, and bituminous formulations. Chemical resistance and permeation resistance are
3. Severe chemical service conditions-Some two separate properties. A chemical such as hydro-
chemical service conditions are dilute or concen- chloric acid can permeate through various plastic
trated mineral or organic acids and strong alkali so- and rubber barrier materials to cause loss of adhesion
lutions. Thickness of these barriers are typically 20 without any indication that the chemical has de-
to 250 mil (1/2 to 6 mm) or over 250 mil (6 mm) in graded the barrier material.
some cases. Some of the barrier systems are glass 3. The temperature of the chemicals contacting the
reinforced epoxy or polyester. precured neoprene barrier material will affect performance. Each mate-
sheet. plasticized polyvinyl chloride (PVC) sheet. as- rial has its own characteristic maximum operating
temperature for a given chemical environment. Ther- tions. Resistance to solvents is poor. Resistance to
mal shock caused by rapid changes in temperature water is often considered to be somewhat lower than
can crack some barrier materials or result in loss of coal tar-derived products.
bond between the barrier and concrete.
6.4.2 Bituminous emulsions-Bituminous emul-
.J.3.2 Selection and testing of barrier material- sions are made using either asphalt or coal tar base
There is no guarantee that materials made by differ-
binders. modified as required by the manufacture
ent manufacturers will perform the same. even when
prior to emulsification. These binders are dispersed
classified as the same generic type. They vary in the
in water, using either mineral stabilizers or chemical
types and amounts of ingredients. so their perform-
type emulsifying agents to assist in dispersion and to
ance will also vary. In addition. the application char-
retain emulsion stability. Coal tar base emulsions are
acteristics. such as ease of applying the material to
usually mineral stabilized.
concrete. sensitivity to moisture on a concrete sur- The performance of films deposited from emul-
face or a very limited temperature application range
sions differs from those from solvent "cutbacks" or
will affect performance.
from hot melt applications. For example. films de-
The type and thickness of the barrier required will posited from emulsions are likely to be more permea-
depend on the severity or aggressiveness of the en- ble to water vapor. They are often capable of with-
vironment. Barrier selection must be based on test- standing higher temperatures than the other two
ing or past experience. If tests are to be conducted. types. Films deposited from the mineral stabilized
the entire barrier system should be applied to con- form of emulsion are considered to have excellent
crete specimens before exposing them to the actual atmospheric exposure characteristics. having more
environment or one that simulates as closely as pos- resistance to alligatoring than even the chemical type
sible this environment. If selection must be made emulsion.
before tests of sufficient duration (as agreed between Drying or setting times vary with emulsion type
manufacturer and user) can be conducted, the barrier and film thickness; this characteristic becomes criti-
supplier should be asked to supply fully-docu- cal in the event of exposure to rain or ponded water
mented case histories where his system has pro- within 2-4 hr after application. Even high melting or
tected concrete under the same or similar environ- relatively insoluble material may be used as the
mental conditions. The selection of a reliable barrier emulsion base by the manufacturer without making
manufacturer and applicator is as important as the a major change in the consistency of the finished
selection of the barrier itself. product. Frequently, such emulsions possess thix-
otropic or false body characteristics, thus permitting
6.4-Description of barrier materials application of relativcly thick coats of materials with
A description of some of the materials used for a minimum of sagging. They may be brush. spray, or
protective barriers follows: roller applied. Storage stability of mineral stabilized
6.4.1 Asphalt-The term "asphalt" is applied to products are considered good.
two types of material. The first are natural asphalts, 6.4.3 Coal tar-The coal tar used in the manufac-
normally of high consistency, found either as min- ture of coal tar base barrier materials is obtained from
erai deposits (gilsonite type) or in open pits the destructive distillation of coal. This tar, in turn. is
(Trinidad Lake Asphalt). The second. and more com- distilled to produce the coal tar pitches, which may
mon, are those oil refinery products produced as the be subsequently modified by processing or by vari-
residue from the distillation of petroleum crudes; ous additives as was done with the asphaltic types to
these may vary significantly in consistency. Suitable produce products of various types ranging in consis-
products for use as barrier coatings may be made tency from thin liquids to hcavy mastics and/or
from either natural or refinery-produced materials semisolids. Coal tar based barrier materials may be of
which may have been processed further by the man- the hot-applied type or may. be applied cold. Cold-
ufacturer prior to incorporation into the barrier coat- applied coatings usually contain a solvent and are
ings. Suitable coatings may contain various fillers, known as cutbacks. Coal tar emulsions are also avail-
fibers. solvents, or even polymers. each added to im- able (see Section 6.4.2).
prove or modify certain physicai properties. As- The outstanding property of the coal tar pitch-
phaltic barrier materials as purchased may range in based barrier products is their excellent water re-
consistency from thin, coli-applied liquids to heavy, sistance. Their resistancc to acids is moderatc and to
hot-applied mastics. alkalis is good. They normally do not support bac-
Cold-applied types usually contain either a sol- terial growth. In the hot-applied form or as a solvent
vent (at which time they are known as "cutbacks") or cutback, they uftcn alligator sevr.rely when subjected
may be in the form of an emulsion (see Section 6.4.2). to atmospheric COIH.I itions. which may Iim it thc use
Because of their good resistance to acids and ox- of those particular types of products for abovc
idizing solutions. asphalt barrier coatings. may bc ground expusure. Coal tar emulsions. however. do
used alonc or in combination with reinforccments. have excellenl atmospheric (~XpOSllrecharacteristics.
such as bitllminized glass fabrics for protr.ctiun of It should b(~noll~d that some coal tar solvents will
concrete vessels used to contain acids and salt solu- impart o!JjectionalJlr. last(~and odor to potable water
supplies, so coal tar based products shO!..lldnot be either more or less than needed will adversely affect
used for that purpose without obtaining specific rec- the overall perfomance of the system.
ommendations from the manufacturer for the partic-
6.4.5.1 Epoxy resin-Filled-A low-viscosity
ular application being considered. epoxy resin is blended with graded fillers in the
6.4.4 Chlorinated rubber-Chlorinated .rubber res- range of 40 to 200 mesh to form a trowelable !'nix that
ins are produced by chlorinating isoprene rubber to a is applied approximately 1/~in. (6 mm) thick to a
chlorine content of as much as 67 percent. The re- concrete f100r.2 Vertical walls may be covered to this
sulting product no longer possesses the resiliency thickness by using specially-formulated materials.
and elasticity of the rubber from which it was The fillers are usually added in the proportion of 5
produced. to 1 by weight of activated resin. This high filler load-
Barrier materials using chlorinated rubber have ex- ing reduces the coefficient of thermal expansion and
cellent resistance to alkalies, moisture, and abrasion. makes it more resistant to thermal shock. The filler
Their adhesion to concrete is good. They are widely will also reduce the shrinkage stresses formed when
used for concrete floor coatings, traffic paints, and the liquid epoxy polymerizes to a solid.
swimming pools. They have adequate resistance to a Since these materials are normally formulated to
wide range of common acids, aliphatic hydrocar- protect concrete floors subject to intermittent ex-
bons, and lower alcohols. They are not resistant to posure to chemicals, the floors should be sloped V~
nitric, acetic, and sulfurous acids, nor to concen- in.lft (20 mm/m) and be free of low spots to assure
trated aqueous ammonia. They are dissolved or soft- complete drainage of chemicals into a collection
ened by aromatic hydrocarbons, fatty acids, and trench. Barrier systems described in Section 6.4.5.2
animal and vegetable oils. Chlorinated rubber may are also used to protect concrete floors.
be used in water service up to 140 F (60 C). A typical floor topping is applied in three steps:
They have limited resistance to heat and will de- 1. A low-viscosity epoxy resin, approximately 5
compose when used above 225 F (107 C). In continu- mil (VB mm) thick, is applied to a properly prepared
ous, direct sunlight, only the pigmented coatings, or concrete surface. The first coat or primer will pro-
those with ultraviolet absorbers, can satisfactorily be mote adhesion of the thick filled epoxy (see Step 2
used. below) to concrete. The low-viscosity primer wets
6.4.5 Epoxy resins-Although there are many the surface of the concrete and flows into the surface
types of epoxy resins available, the one normally pores. If the surface pores afl~ open, they will be
used for protective barriers is based on a reaction filled when the filled epoxy resin is applied. When
product of bisphenol A and epichlorohydrin.6 The resin flows from the filled epoxy material into the
epoxy resin, which is usually a liquid, must react surface pores, it becomes "resin starved" resulting in
with another chemical called a curing agent or hard- low strength and poor bond to concrete.
ener before it becomes a solid and develops chemical 2. A filled epoxy material is troweled on to a thick-
resistance, hardness, and abrasion resistance.· ness of approximately I/~in. (6 mm) thick. Compact-
The curing agent used with the epoxy resin has a ion by trowelling is necessary to eliminate porosity.
major influence on the mechanical and chemical re- pinholes, and discontinuities.
sistance properties of the hardened resin. Curing 3. A low-viscosity epoxy resin is then applied to
agents most commonly used are aliphatic amines. seal the surface of the previously-applied material.
amine adducts. amido-amines and polyamides. This step is not always used and will depend on the
The versatility of formulation that makes epoxies manufacturer's recommendation. However, a seal
attr~tive in many applications has lead to confusion coat will insure that chemicals will not reach the
with Jregards to the performance that can be ex- concrete if for some reason the troweling was not
pected. It is important to select an epoxy system that effective in eliminating porosity in the material.
is obtained from a proven source and that has been Timing of the three application steps shown above
designed specifically for the intended application. is important to ensure good adhesion between coats.
Properly selected and applied epoxy systems pro- The recommendations of the material manufacturer
vide a very tough, durable coating with excellent should be followed:
caustic, acid and solvent resistance. Epoxy formula- 6.4.5.2 Glass-reinforced epoxy resin- The glass-
tions are compatible with concrete. providing excel- reinforced epoxy barrier is multi-coat, in the dry-film
lent adhesion. Some formulations adhere to damp thickness range of 20 mil (V~mm) to 250 mil (6 mm).
surfaces. As thickness increases there is a greater chance that
Epoxy resins and their curing agents react in a discontinuities or pinholes in the barrier material
noncatalytic fashion. Each molecule of epoxy must will be eliminated. Because these materials are used
find a molecule of curing agent to react with. Thus. to protect concrete from acids and other aggressive
complete mixing of the system is extremely impor- chemicals that could cause rapid disintegration. it is
tant. Where possible. contrasting colors should be essential that none of the chemicals reach the
used for the two components to provide a visual concrete.
guide to adequate mixing. Only the precise amount A typ!cal barrier is built up in four steps:
,<PC- of curing agent recommended should be used. Using 1. A low-viscosity ep~Jxy resin, approximatdy 5
mil (Va mm) thick. is applied to a properly prepared 2. Air inhibits the cure of some polyesters. This
surface (see Section 5.4.5.1-Item 1 for more details). problem is solved by applying a final topcoat that
2. An activated and filled epoxy resin, 50 mil contains about 1-2 percent paraffin. The paraffin
(1 V4 mm) thick. is trowelled on a properly prepared rises to the surface and prevents direct contact be-
concrete surface. In this 'lpplication the inert filler is tween the polyester surface and air. Without paraffin
generally finer than No. 100 mesh (150 mm) and is in the topcoat, the surface will remain tacky.
used to produce a heavy bodied, trowelable material. 6.4.8.1 Polyester resin-Filled- The discussion
3. Woven glass fabric is then applied over the ep- in Section 6.4.5.1 applies.
oxy surface before the epoxy has hardened and an
unfilled, activated epoxy resin is brushed on the 6.4.8.2 Glass-reinforced polyester resin-The
glass fabric so it will be saturated with resin. glass reinforced polyester protective barrier is similar
4. After the epoxy resin has partially cured, as in- to the epoxy system described in Section 6.4.5.2. In
dicated by a 'tacky surf~ce, another heavy coat as in addition to the reasons for using a primer given in
Step 2 above, is applied. Section 6.4.5.2, a primer is also used with polyester
resins because they will not cure properly in the
6.4.6 Neoprene sheet-Precured-Precured neo- presence of water. Moisture in concrete may be suffi-
prene sheet, in thicknesses ranging from 60 to 125 cient to inhibit the cure.
mil (1 1/2 to 3 mm) can be applied to a smooth con- There are two types of glass reinforcement used
crete surface by using suitable neoprene adhesives. with polyester barrier materials. One type is glass
Neoprene adhesives have the same chemical re- fibers in the form of either nonwoven mat or woven
sistance as the sheet itself, so the joints between fabric. The other type uses glass flakes as the rein-
sheets will be reliable if properly made. If concrete to forcement. These flakes are approximately 5 mil (Va
be protected has a complicated geometry, a catalyzed mm) thick and 60 mil (1.5 mm) in diameter.
neoprene solvent-based formulation may be spray or
brush applied to a thickness of 50 mil (1.5 mm). This 6.4.9 Polyurethane resins-Urethane barrier mate-
material will have the same chemical resistance as rials are based on the reaction of two chemicals: a
the sheet material. resin component (polyol) and an isocyanate curing
agent.
6.4.7 Plasticized polyvinyl chloride sheet-Poly- The ability of the isocyanate curing agent to react
vinyl chloride (PVC), which is a rigid or stiff resin, is with a vast array of coreactant resins (polyols), each
made flexible by the addition of a plasticizer such as possessing varying properties, has led to a large fam-
dioctyl phthalate. The plasticized PVC sheet may be ily of barrier materials which are often lumped under
bonded to a surface using suitable adhesives. The the single name "urethane." Care must be taken,
joints between sheets are made using a heat sealing therefore. to match job sevice requirements with the
or thermal welding procedure. proper type of urethane barrier.
Vinyl sheets, extruded with anchor lugs on one Urethanes (see Table 6.3) have been used to protect
side. may be used to form a lining at the time the concrete from deicing salts and other chemicals.
concrete is placed. They have been used to prevent fungus growth on
6.4.8 Polyester resins-Although there are many concrete, to protect against winddriven rain while
generic types of polyester resins. there are two that lending self-washing properties. When urethanes are
are normally used for barrier materials in the more mixed with long lasting decorative pigments, they
severe chemical environments. One is based on the can be used to mask concrete discoloration.
reaction between maleic anhydride and bisphenol A. Generally speaking. urethanes have good re-
and the other is produced by reacting acrylic acid sistance to chemical attack, and excellent impact
with an epoxy and is commonly called a "vinyl es- and abrasion resistance. They have excellent adhe-
ter." These resins are mixed with approximately 50 sion characteristics, are hard, yet flexible. and exte-
percent styrene monomer to lower the viscosity (ap- rior grades exhibit excellent long-term gloss and
proximately 150 centipoise) to improve workability. color retention.
The styrene also reacts chemically with the polyester Although they are usually supplied as two package
resin after the appropriate catalysts or curing agents systems. single component systems, which are cured
are added. by moisture in the air, are available. Urethanes are
The liquid resin is converted to a solid by using a supplied in a wide range of viscosities. Some sys-
peroxide catalyst such as benzoyl peroxide and an tems contain solvents to obtain the required vis-
accelerator such as dimethyl aniline. The concentra- cosity; others do not. They are generally applied
tion of the catalyst may be varied to change the rate of using conventional coating techniques. They should
curing. not be applied to damp surfaces.
There are two conditions that can prevent poly- Because of the wide latitude of formulation ca-
ester resins from curing completely. pabilities presented by isocyanate curing agents,
1. Water will inhibit curing of polyesters; and many new urethane finishes are continually bei.ng
therefore. when they are used. a primer. which is not introduced into the market. Before a urethane barner
sensitive to water. should be applied to the concrete material is used. the application and end use recom-
firs t. mendations of the manufacturer should be fully UD-
derstood and closely followed. Work closely with a The acid-proof brick barrier is made up of two
technically oriented supplier in this regard. major components (Fig. 6.5):
6.4.9.1 Urethane resin-Filled-The discussion 1. The primary barrier is the chemical-resistant
in Section 6.4.5.1 applies. material applied directly to concrete. A solvent-
6.4.10 Polyvinyl butyral-Polyvinyl butyral resin based asphalt primer and an asphalt barrier. V4 in. (6
has excellent resistance to weathering and is used to mm) thick is one type commonly used. The asphalt
seal concrete surfaces. The resin is dissolved in a is a hot melt type material and is applied in two coats
solvent and is applied in thin films of less than 3 with a reinforcing glass fabric between them. Other
mils (0.08 mm) per coat. barrier systems may be used in place of asphalt.
6.4.11 Acrylic resins-These materials result from 2. The brick with chemical-resistant mortar joints
the vinyl polymerization of acrylic monomers which is then applied over the asphalt barrier. Since the
are modified by the addition of plasticizers and pre- brick and mortar joints may develop cracks. their
polymers. These are used as a thin unfilled coating primary function is to protect the relatively fragile
or as a thick sand-filled mortar. asphalt barrier from damage caused by mechanical
6.4.12 Glass reinforced furan resin-The glass- abuse and from excessive temperature. The thickness
reinforced furan resin barrier is similar to the epoxy of the brick is determined by service temperature and
system described in Section 6.4.5.2. In addition to mechanical loading.
the reasons for using a primer given in Section There are three types of brick used for this type of
6.4.5.2. a primer is used with furan resins for another barrier.7 Red shale is most frequently used and is
reason. The acid catalyst used to cure the furan will identified as Type L in ASTM C 279,5 Fireclay brick
react with the portland cement of the concrete. If the (Type H-ASTM C 279) is used mainly when the
acid catalyst at the concretelresin is neutralized. the barrier is subject to thermal shock. Carbon brick is
furan will not harden and the concrete surface will used when hydrofluoric acid or strong alkaline solu-
be attacked. resulting in poor bond and eventual tions (above a pH of 12.5) are present.
cracking of the furan. A typical red shale brick is 8 in. x 3 % in. x 2 V4 in.
After the primer has been applied. one coat of a (205 mm x 95 mm x 55 mm). A thinner brick, less
filled furan mortar is trowled on the surface and than 1 Vz in. (38 mm). identified as floor tile, is used
glass cloth is embedded in the furan before it hard- in the food and drug processing industry.
ens. After the furan has setup. a second trowel coat of A description of various chemical-resistant mortar
furan mortar is applied. Then. a 60 mil layer of a materials are in the next six sections.
neoprene latex is spray-applied to the hardened 6.5.1.1 Furan mortar-Furan resin mortars have
furan. The neoprene acts as a parting agent so the been used with acid-proof brick and tile sheathings
furan resin mortar. used with the acid-proof brick since 1941. They are supplied as two-part systems.
will not adhere to the glass-reinforced furan barrier. At the time of use the liquid furan resin is mixed
with the powder filler. which ordinarily consists of
6.S-Special composite barriers carbon. coke flour. or silica. The filler contains an
6.5.1 Acidproof brick composite construction- acid catalyst which polymerizes the resin to a hard.
This type of protective barrier has been used since infusible state. Once the resin and catalyst are mixed.
1934 to protect concrete floors from very aggressive. they have a relatively short working time under nor-
acidic chemicals.3.4•5 Another major use is in the food mal conditions. However. before mixing they have a
and drug processing industries where an easily- good shelf life and are stable in storage. The furan
cleanable surface is required. mortars may be generally used up to 350 F (177 C).
Since an acid catalyst is used to polymerize the
furan resin. it should not be applied directly to con-
crete. Concrete will neutralize the acid catalyst and
ACID RESISTANT BRICK inhibit the cure. resulting in poor adhesion of the
t furan to concrete.
6.5.1.2 Phenolic mortar-Phenolic resin mor-
~;~ tars. based on phenol-formaldehyde resin binder •
~~
•• ~ "I •
..
~ ~~:, ':'
)(3.,_.,."
~
..
.' ~ J~ ••.~,.
~.. ,
..:..: ..•.•...•...
'''a.·~1
'", ~ .
. have been used in chemical-resistant masonry in the
United States since 1937. Although still available.
. '··.,11. ,.. .
their use has largely been displaced by the furan
o
-,
...
-,.
•
. " .... :.
0
7.4.2.1 Application methods-The paint manu- dry film. The calculation then becomes
facturer must recommend whether brushing, spray- percent solids by vol. x 1,604 .
ing, or rolling should be used for applying the paint. · . f I = mil of dry film
sprea d Ing rate In sq t per ga .
As a general rule, many of the solvent-based paints,
e.g., vinyls, epoxies, and urethanes, are fast drying
and, therefore, are better adapted to spraying than to Allowances should be made for losses caused by
brushing. For most spray application airless spray is spillage and overspray.
recommended. The drying time required before additional coats of
To obtain a good appearance and serviceability of paint are applied, or before the finished application
the paint film, the paint should be applied as a full, is put into service will vary over a wide range de-
wet film, but not so heavily that it will run or sag. pending upon the type of paint and atmospheric dry-
Care must be taken to see that paint is worked into ing conditions. The paint manufacturer will advise
surface depressions; that the coverage is uniform; the proper drying times for his particular products.
and that good blending of the film is obtained at laps. The latex paints, both interior and exterior grades,
7.4.2.2 Thickness and number of coats-For are normally used only for decoration. Thickness is
purely decorative painting, where no factors such as more important than uniform color and appearance.
moisture resistance, strong cleaners or high gloss re-
quirements are involved, the number of coats and 7.S-Repainting procedures
coating thickness need only be that necessary to ob- When repainting with the same type of paint as
tain the required color uniformity, hiding power, and that on the surface, and the old paint is in good con-
texture. With smooth, clean surfaces such as cement- dition, simply clean the surface and apply a single
asbestos, one coat may be all that is required. When coat of paint. Washing with commercial detergents or
the surface to be painted is rough or granular in tex- solvents before painting may be necessary if dirt,
ture, it is advisable to use two or more coats; the first chalk, and grime accumulation is excessive and tena-
coat thinned to allow for penetration. A compatible cious, such as to resist ordinary dusting or hosing.
sealer coat could also be used. Consult the paint manufacturer for information
Some manufacturers provide a separate priming about cleaning procedures.
paint of increased alkali resistance for use with oil- 7.5.1 Compatibility of new paint on old paint-It
base paints. Such a primer is of particular value if the is difficult to determine the compatibility of old and
concrete must be painted before it is fully seasoned. newly-applied paint since poor intercoat adhesion or
Generally, the label on the paint container will pro- delamination may not occur for many months after
vide instructions concerning the need for a special application. It is essential to contact the manufac-
primer or for altering the paint by thinning or adding turer of the old and new paint before attempting to
a special ingredient for application as the first coat. apply new painl over old paint. Examples of com-
Where a decorative paint is to serve another func- patibility problems are shown below.
tion such as withstanding abrasion or frequent clean- Any paint can be applied over Portland cement
ing, or as a dampproofing barrier, the thickness of the paint, but Portland cement paint cannot be applied
over any other type of paint. In general, the latex Standard Specific:fion for White and Yellow
paints will normally adhere satisfactorily to other Thermoplastic Striping Material (Solid Form)
Standard Specification for White and Yellow Re-
types of paints, but any gloss on the old paint should
flective Striping Material (Flame-Spray Powder)
first be removed by sanding. Standard Specification for Ready-Mixed Alumi-
The adhesion between a fully-cured polyurethane num Paint
paint and newly-applied polyurethane will not be Standard Specification for Sheet Reflective Mate-
very good. Normally a thin coat of an epoxy-poly- rials for Traffic Control Devices
7. ASTM Standards, 1983, for Traffic Paints:
amide paint is applied before the polyurethane is
D 711-75 Test Method for No-Pick-Up Time of Traffic
applied. Specific instructions from the paint manu- Paint
facturer should be obtained when these particular D 713-81 Conducting Road Service Tests on Traffic Paint
paint systems are involved. D 821·47 Evaluating Degree of Abrasion, Erosion. or a
When applying solvent-based paints over oil- (1974) Combination of Hoth, in Road Service Tests of
Traffic Paint
based ones, wrinkling and lifting may be encoun- D 868-48 Evaluating Degree of Bleeding of Traffic Paint
tered. When this occurs the oil-based paint may have (1981)
to be removed or overcoated with a protective barrier D 869-78 Evaluating Degree of Settling of Traffic Paint
coat of the paint manufacturer's recommendation be- D 913-51 Method of Evaluating Degree of Chipping of Traf-
fore repainting. (1981) fic Paint
D 969-54 Method for Laboratory Test of Degree of Bleeding
Loose paint, curled edges, and blistered paint (1981) of Traffic Paint
must be removed before repainting. It may be D 1309-56 Test Method for Settling Properties of Traffic
preferable to remove all of the old paint. Light sand- (1975) Paints During Storage
blasting, water blasting, machine sanding, or paint D 2205-75 Recommended Practices for Testing Traffic Paints
strippers may be utilized. Filling of any cracks and 02743-68 Recommended Practices for Uniformity of Traffic
(1981) Paint Vehicle Solids by Spectroscopy and Gas
holes in the concrete should be done in the same Chromatography
manner as for new concrete (see Chapter 3). D 2792-69 Test Method for Solvent and Fuel Resistance of
If the old paint has become partially removed, but (1981) Traffic Paint
that remaining is in good condition, the bare areas 8. ASTM Standards. 1983. for Ceramic Tile:
should be painted first, followed by a coat over all. C 154-72 Standard Test Method for Warpage of Refractory
(1977) Brick and Tile, or Deviation from a Plane Surface
An additional coat may be necessary for best ap- C 482-81 Standard Test Method for Bond Strength of Ce-
pearance, especially if a pronounced change in color ramic Tile to Portland Cement
is involved. C 483-66 Standard Test Method for Electrical Resistance of
If the old paint is failing by blistering, peeling, or (1951) Conductive Ceramic Tile
disruption from efflorescence the cause of the prob- C 484-66 Standard Test Method for Thermal Shock Re-
(1981) sistance of Glazed Ceramic Tile
lem should be determined. The concrete may have C 485-83 Standard Method for Measuring Warpage of Ce-
been painted while too new, or a source of supply of ramic Tile
moisture to the concrete may still be present. If the Standard Test Method for Facial Dimensions and
latter is true, any new paint vvill probably also per- Thickness of Flat. Rectangular Ceramic Wall and
form unsatisfactorily unless the source of moisture Floor Tile
Standard Test Method for Relative Resistance to
can be eliminated. Consideration should also be Wear of Unglazed Ceramic Tile by the Taber
given to changing the type of paint. Abraser
C 502-78 Standard Test Method for Wedging of Flat. Rec-
(1983) tangular Ceramic Wall and Floor Tile
References C 609-81 Standard Method for Measurement of Small
Color Differences Between Ceramic Wall or Floor
1. "Painting Concrete." Concrete Informotion Sheet No.
Tile
IS134.03T. Portland Cement Association. Skokie. 1977,8 pp.
Standard Method for Evaluating Ceramic Floor
2. "Paints and Protective Coatings." Technical Manual No. TM
Tile Installation Systems
5-618, U.S. Department of the Army. Washington. D.C" 1969.
Standard Test Method for Breaking Strength of
3. Dolch. W. L., "Protective Coatings for Concrete." Technical
Ceramic Tile
Heport No. 2-29 (AD602727j. U.S. Arrny Engineer Division. Sept.
1963. pp. 1-51. Standard Test Method for Resistance of Ceramic
Tile to Chemical Substances
4. ACI Commiltp.e 616, "Recommended Practice for the Applica-
Standard Test Method for Color Permanency of
tion of Portland Cement Paint to Concrete Surfaces (ACI616-49),"
Glazed Ceramic Tile
ACI JOURNAL, Proceedings V. 46. No.1. Sept. 1949. pp. 1-16.
5. "Sp!!cial Products balualion List (SPEL)." Hepart No. FWHA-
RD-71l-31. Federal Highway Admi n is t ration. Washington. D.C..
Dec. 1977. pp. 167-180.210-223. and 237-255.
6. Standard Spp.cificotians for T'ronsportGtion Materials and
Additional Sources of Information
Methods of Sampling and Testing. Part 1. Specifications. 12th
Fcdcrul Sp"cij"icutiolls: .
Edition. American Association of Sta t c Highway and Transporta- TT-P-llO:15(1) Paint. Cem{mtiliolls. Powder. White and Colors
tion Officials, Washington. D.C., 1978. 82/l pp. The applicable TT-P-1411A Paint. Copolymer-Resin. Cementilious
specificat iOilS are:
n~p-ll03:1 Paint. l.atex Base, Exterior
M 247-77 Standard Specification for Class Heads Used in TT-I'-~J(jI) Paint. Lall!x Base. for Exterior Surfaces
Traffic Paint
'ITI'-!l1lJ Paint. Rubber Basc. for Interior Use
M 241l-7/l Standard Sp"cificat ion for Ready-Mixed White TI'-I'-'-l5C Paint. gllbbcr for Swimming Pools and Olher
and YP.l!owTraffic Pai nts Co)u:mte and Masonry Surfac{!s
Tf-P-97D Paint. Styrene-Butadiene Solvent Type, White Tf-C-535B Coating. Epoxy. Two Component
Tf-P-1181A(1) Paint. Styrene-Acrylate Solvent Types. Tints and (1)
Deep Tones Tf-C-542D Coating. Polyurethane. Oil Free. Moisture Curing
Coating: Polyester-Epoxy (Two Component) High- (2)
Build. Gloss and Semigloss. White and Tints MIL-C-22750C Coating. Epoxy-Polyamide
Tf-C-499A Coating Compound. Chemical Resistant, Clear (2)
Tf-C-1659A Coatings: Epoxy Emulsion. Two-Component
Gloss and Semigloss
Coating. Clear (Satin-Finish), Polyurethane Latex. This report was submitted to letter ballot of the committee and was
for Interior Use approved by at least a two-thirds affirmative vote.