Overhead Line Design Manual: LV ABC

This document provides specifications for the design and construction of low voltage aerial bundled conductor (ABC) lines and services operating at or below 1kV. It covers ABC distribution networks on wood poles, ABC service connections, and ABC pole-mounted equipment. Design and construction details are given for ABC conductors with 2 or 4 cores of 35mm2 or 95mm2 cross-sectional area. Appendices provide drawings, materials, pole designs, span lengths, and other technical specifications. The document establishes requirements to ensure the safe and compliant design, installation and maintenance of low voltage overhead line infrastructure.

Uploaded by

wael El-Begearmi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
521 views98 pages

Overhead Line Design Manual: LV ABC

This document provides specifications for the design and construction of low voltage aerial bundled conductor (ABC) lines and services operating at or below 1kV. It covers ABC distribution networks on wood poles, ABC service connections, and ABC pole-mounted equipment. Design and construction details are given for ABC conductors with 2 or 4 cores of 35mm2 or 95mm2 cross-sectional area. Appendices provide drawings, materials, pole designs, span lengths, and other technical specifications. The document establishes requirements to ensure the safe and compliant design, installation and maintenance of low voltage overhead line infrastructure.

Uploaded by

wael El-Begearmi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 98

 

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Overhead Line Design Manual
Section 1

Aerial Bundled Conductor (ABC) Low


Voltage Mains and Services

Asset Management
Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 2
 

Table of Contents
1 Scope................................................................................................................................5
2 References.......................................................................................................................6
3 Definitions........................................................................................................................7
4 Introduction .....................................................................................................................9
5 Design Information....................................................................................................... 10
5.1 General Practice .................................................................................................... 10
5.2 Risk assessment..................................................................................................... 10
5.3 Earthing................................................................................................................. 10
5.4 Design Data ........................................................................................................... 10
6 Construction Information............................................................................................ 12
6.1 General Practice .................................................................................................... 12
6.1.1 Supports................................................................................................................................. 12

6.2 Clearances ............................................................................................................. 12


6.2.1 General ................................................................................................................................... 12
6.2.2 Tree Clearances ................................................................................................................... 13

6.3 Low Voltage Supports............................................................................................ 13
6.4 Augering................................................................................................................ 13
6.5 Foundations .......................................................................................................... 13
6.6 Stays...................................................................................................................... 14
6.7 General back‐filling and Compaction ..................................................................... 14
6.8 In‐Line Connections ............................................................................................... 15
6.9 Connections to the Bundle .................................................................................... 15
6.9.1 General ................................................................................................................................... 15
6.9.2 Limit on Number of Connections to the Bundle .......................................................... 15
6.9.3 Disconnections from the bundle ..................................................................................... 15
August 2012

6.10 Open points........................................................................................................... 15
6.10.1 General ................................................................................................................................. 15

6.11 Appendix A – GA Drawings and Materials ‐ Mains ................................................. 16


6.12 Appendix B – GA Drawings and Materials – Services ............................................. 37
6.13 Appendix C – GA Drawings and Materials – Pole Mounted Equipment.................. 48
6.14 Appendix D – GA Drawings and Materials – Earthing............................................. 57

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 3
Overhead Line Design Manual
 

6.15 Appendix E – Reference List of all Materials for this specification ......................... 61


6.16 Appendix F – Design Data for Conductor ABC, 4 x 120mm2 .................................... 66
6.17 Appendix G – Design Data for Conductor, ABC, 4 x 95mm2 .................................... 71
6.18 Appendix H – Design Data for Conductor, ABC, 2 x 95mm2 .................................... 76
6.19 Appendix I – Design Data for Conductor, ABC, 4 x 35mm2 ..................................... 81
6.20 Appendix J – Design Data for Conductor, ABC, 2 x 35mm2 ..................................... 86
6.21 Appendix K – Service Spans ................................................................................... 91
6.22 Appendix L – Un‐stayed Supports .......................................................................... 93
6.23 Appendix M – Stay base and angle conversion table ............................................. 95
6.24 Full list of tables .................................................................................................... 96
6.25 Full list of figures ................................................................................................... 98

Revision Record
Issue Date Prepared by Details
1.0 26/08/2010 Andy Horstead New document
1.1 11/03/2011 John Lowe Document rebranded
1.2 17/08/2012 Lee Strachan Reviewed for Publication on G81 Website

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 4


  Overhead Line Design Manual

1 Scope
 

This specification details the design and construction requirements for all new types of
Low Voltage (LV) Aerial Bundled Conductor (ABC) lines and services, operating in the
range up to and including 1kV. LV ABC structures can be considered as one of three
distinct types for design and construction purposes:

1. LV ABC distribution networks supported on wood poles.

2. LV ABC service connections (excludes terminations within property).

3. LV ABC pole-mounted equipment.

ABC conductors comprising the following number of cores and cross-sectional areas are
used in the above lines:

4. Conductor, ABC, 2x35mm2.

5. Conductor, ABC, 2x95mm2.

6. Conductor, ABC, 4x35mm2.

7. Conductor, ABC, 4x95mm2.

8. Conductor, ABC, 4x120mm2.

These conductors are specified in more detail in EAS 00-0001and BS 7870-5.

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 5
Overhead Line Design Manual
 

2 References

The following referenced documents are indispensable for the application of this
document. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.

Standard Number Standard Description


BS 1990 Wood pole for overhead lines (power and telecommunications
lines)
BS EN ISO 9001 Quality Management Systems – Requirements
BS EN ISO 14001 Environmental Management Systems – Specification with
guidance for use
UKPN EDS-06 0016 LV Networks Earthing Design
ENA TS 43-12 Insulated Aerial Bundled Conductors – erection requirements of
low voltage overhead distribution systems
ENA TS 43-13 Aerial Bundled Conductors (ABC) insulated with cross-linked
polyethylene for low voltage overhead distribution systems
ENA TS 43-14 Conductor fittings and associated apparatus for use with LV
aerial bundled conductors
BS 7870-5 Low Voltage Aerial Bundled Conductors

UKPN EM 01 Overhead line Construction Manual 2010


UKPN EDS 09-0019 Safety signs and labelling of equipment
UKPN EAS 00-0001 UK Power Networks' Materials List (Overhead Lines)
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 6


  Overhead Line Design Manual

3 Definitions

ABC Aerial Bundled Conductor


CNE Combined Neutral Earth
UKPN UK Power Networks
UK Power Networks DMS UK Power Networks Document Management System
EDS Engineering Design Standard
ENA TS Energy Networks Association Technical Specification
FoS Factor of Safety
GA General Arrangement
JC,s Job Cards
IPC Insulation Piercing Connector
Manufacturer An organisation supplying equipment for use on networks
owned by UK Power Networks
NI Not Illustrated (i.e. item numbers on Figures).
PME Protective Multiple Earthing
SJI Specific Job Instructions
XLPE Cross-linked Polyethylene

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 7
Overhead Line Design Manual
 
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 8


  Overhead Line Design Manual

4 Introduction

The body of this specification covers general design and construction requirements. How
to construct and maintain ABC is detailed in a separate manual known as the Overhead
Line Construction Manual. Appendix A to Appendix C of this document comprises General
Arrangement (GA) drawings with associated lists of materials for LV ABC structures as
follows:

1. Appendix A comprises GAs for LV ABC distribution networks supported on wood


poles. (Note that “inside” and “outside” angles are not as defined in ENA TS 43-12.)

2. Appendix B comprises GAs for LV ABC service connections, followed by a GA


summarising ABC and CNE service spans

3. Appendix C comprises GAs for LV ABC pole-mounted equipment.

Each list of materials identifies the components included in the associated GA and which
supplementary items are needed to complete that structure. Variations within each GA for
different conductors are covered by different columns in the associated list of materials.
Note that the lists of materials for the connections and plant shown in Appendix B and
Appendix C do not include the materials for the associated GA structure; many
combinations are possible and it is not practical to cover every possible
structure/connection variation here. (Refer to Appendix A for approved GA structures and
materials.)

 Appendix E – Reference List of all Materials for this specification comprises a


reference list of all materials used within this specification.

 Appendixes F to M are tables of design data for this specification: one Appendix
for each ABC type.

This specification fits into the overall design and construction process as outlined by the
following process summary:

(a) Carry out a risk assessment.

(b) Generate a proposal taking into account the risk assessment.

(c) Generate a proposal for a new line.

(d) Choose a proposed route and a line survey carried out.

(e) Plot pole positions, heights, clearances, and develop a line profile. (Note that the
development of a line profile will require some data and parameters from Appendix F
August 2012

and subsequent Appendices.)

(f) Compile a list of materials using the GAs and supplementary items identified in this
specification (Appendix A, Appendix B, Appendix C and appropriate ES and/or
ENA TS). The GAs and supplementary items shall be selected and used in
accordance with the design and construction information given below and the data
given in subsequent Appendices.

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 9
Overhead Line Design Manual
 

Appendix M provides a table to give distances in metres from pole base to stay base
dependant on pole size. This has been provided to support the minimum angle of stay
column provided in Appendix F to J.

5 Design Information
5.1 General Practice
Lines shall be designed using the GAs and supplementary items from Appendix A,
Appendix B, Appendix C and the data from Appendix F to M, etc. The following information
shall be taken into account during the design process.

5.2 Risk assessment

A risk assessment shall be carried out at the commencement of the design work to identify
the site specific safety hazards. The design shall incorporate mitigation measures to
control the risks, identified in the risk assessment, associated with the construction,
operation and maintenance of the proposed overhead line and its suitability compared with
an underground cable solution.

5.3 Earthing
System earthing shall meet the requirements of the current UK Power Networks LV
Network Earthing Design Manual EDS 06 0016 .

To provide a PME network the connection from the neutral of the bundle to the earth
electrode(s) shall be installed and connected in accordance with the drawings given in
Appendix D. (The PME connections are split across two drawings, because all pole
mounted equipment GAs incorporate connections from bundle neutral to neutral/earth as
mandatory requirements.)

5.4 Design Data


Each set of design data (Appendix F to M) contains all the information necessary for the
conductor bundle specified, with the exception of poles supporting electrical plant. Design
parameters used to construct the tables of design data are given for reference. Note that
the basic span for this design is 50m. If ABC is to be installed onto an existing pole it is
then assumed that the pole depth will be 1500 mm. The maximum wind loading span shall
then be limited to the figures supplied in Table 6 and Table 12 (Appendix F and G). If an
existing pole has to be changed due to decay or clearance problems then refer to tables
for planting depth for new build.

For poles supporting electrical plant, strut loadings need to be re-calculated as necessary.
March 2011

(Note that 1000kg additional weight can be approximated to 1000kgf additional loading for
this purpose.)

Data in Appendix F to J, etc, are based on the minimum pole diameters included in
BS 1990. In practice, if it is found that strut loadings exceed the values given in Appendix
F to J, etc, the minimum pole top diameter needs to be re-calculated. Maximum service
spans shall be in accordance with Figure 15: Concentric Service Spans and Figure 16:
ABC Service Spans.

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 10


  Overhead Line Design Manual

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 11
Overhead Line Design Manual
 

6 Construction Information
6.1 General Practice
Construction practices shall be in accordance with the UK Power Networks Overhead Line
Construction Manual. For reference, ABC phases and neutral shall be identified by the
number of ribs on the insulation as follows:

 Phase L1: 1 rib.

 Phase L2: 2 ribs.

 Phase L3: 3 ribs.

 Neutral: fully ribbed. (Note that this applies


whenever ABC is used; e.g. when neutral is
run down the pole for connection to the
neutral/earth connection.)

6.1.1 Supports
All fittings supporting the ABC system shall provide an insulating barrier rated at 1000V
between the core insulation and the mechanical attachment. The ABC shall be attached in
such a manner that it cannot make contact with any metalwork or stays.

The maximum pole height for a service or service line shall be 9 metres.

Weak links will be used on all poles except for the following:

1. Terminal poles

2. Section poles or

3. Either side of a road crossing.

6.2 Clearances

6.2.1 General
Clearances from external objects and structures (e.g. buildings, trees and roads) shall
comply with ENA TS 43-12 In-line construction clearances shall comply with those
specified in the specific job instructions detailed in the Overhead Line Construction
Manual.

In addition to the above, the following rules shall be followed:


March 2011

1. Wherever possible, ABC conductors shall not pass directly over buildings and roofs.

2. Wherever it is necessary to over sail a building or roof, the relevant span shall not
contain any in-line connections.

3. Where ABC is attached to a building which has a thatched roof, the attachment shall
be a minimum of 0.5m from the thatched roof.

4. Once terminated, ABC shall be converted to concentric cable or insulated and


sheathed (mechanically protected) cable within 0.5m of the point of attachment to a

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 12


  Overhead Line Design Manual
building. Service cable lead-ins into the building shall be installed in accordance with
the Overhead Line Construction Manual.

6.2.2 Tree Clearances


Where an ABC system is erected through trees, the following points shall be considered:

1. For additional information regarding overhead line clearances, refer to ENA TS 43-12.

2. Risks of the ABC being abraded by trees.

3. Sag variations and conductor swing due to the effects of the wind.

4. The effect of wind and snow loading on trees or branches bearing onto the ABC.

5. The danger of trees providing climbing access.

6. The amount of tree cutting required for ABC compared with conventional open wire
systems can be significantly reduced. However, the XLPE insulation is susceptible to
abrasion and shall not be allowed to come into contact with tree trunks, mature
branches or heavy outer growth, under any circumstances.

7. Clearances through trees shall take account of maximum and minimum conductor
sags, conductor swing and the anticipated tree growth rate and cutting periods.

6.3 Low Voltage Supports

All supports shall be fitted with a Safety Sign (Danger of Death) in accordance with UK
Power Networks EDS 09-0019.

6.4 Augering
Augering the pole hole is the preferred method when the ground is suitable.

After pole erection, the remaining hole shall be backfilled with suitable material based on
soil condition. If there is a risk of movement due to poor soil conditions then a suitable
cement mixture shall be used.

6.5 Foundations
Un-stayed angle poles shall be installed 0.5m deeper than the planting depth given in the
Appendices to this specification. (Care shall be taken when planning un-stayed angle
poles, particularly near walls.)
August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 13
Overhead Line Design Manual
 

6.6 Stays
Only the following types of stay are suitable for lines designed to this specification:

Load-lock anchors (Light)

Screw-in (Heavy)

Concrete blocks:
Light – 500 x 300 x 90mm
Heavy – 640 x 430 x 140mm

Refer to tables for staying arrangements.

Heavy duty stay plates are useful for structures of restricted height: the overall distance
between the fixing at the top of the pole and the stay insulator is less than that of an
equivalent pole-top make-off.

The distance of the stay-base from the pole-base are given in Appendix F – J using angles
in degrees from 0o to 45o measured between the pole and stay. This information is then
March 2011

supported by a further table 42 provided in Appendix M which gives the spread in metres
between the stay and the pole at ground level.

6.7 General back-filling and Compaction


All holes shall be backfilled with the excavated material but consideration should be given
to soil condition. It may be necessary to import suitable material which can be mixed with a
cement based compound for reinstatement around the pole.

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 14


  Overhead Line Design Manual
Any poles erected in the highway (excluding grass verges) shall be backfilled with suitable
material with reference to NRSWA requirements.

6.8 In-Line Connections


Compression fittings shall be used for all tension and in line non-tension connections.
(Under no circumstances shall IPC’s) be used to make in-line connections.)

6.9 Connections to the Bundle

6.9.1 General
Only ABC to ABC connections to the conductor bundle are permitted.

Table 1 – Number of IPC’s required for Mains and service connections

Scenario Phase Neutral


120mm² Mains or Service 1 double bolt IPC 2 double bolt IPCs
95mm² Mains or Service 1 single bolt IPC 2 single bolt IPCs
35mm² Mains or Service 1 single bolt IPC 2 single bolt IPCs

6.9.1.1 Service Connections


For single phase and three phase connections to 95mm2 ABC and below, one single-bolt
IPC shall be used on each phase conductor and two single-bolt IPC’s shall be used on the
neutral/earth conductor. For single phase and three phase connections to 120mm2 ABC,
one double-bolt IPC shall be used on each phase conductor and two double-bolt IPC’s
shall be used on the neutral/earth conductor (as illustrated in the appropriate GAs).

6.9.1.2 Mains Connections


For all mains connections to 95mm2 and below, one single-bolt IPC shall be used on each
phase conductor and two single-bolt IPC’s shall be used on the neutral/earth conductor

For all mains connections to 120mm2, one, double-bolt IPC shall be used on each phase
conductor and two, double-bolt IPCs shall be used on the neutral/earth conductor (as
illustrated in the appropriate GAs).

6.9.2 Limit on Number of Connections to the Bundle


Only two single phase or two three phase connection to the bundle is permitted at any pole
position. If this number of connections is to be exceeded then a distribution box is to be
provided.

6.9.3 Disconnections from the bundle


IPC’s shall not be removed from the bundle.

Disconnections shall be made on the ABC tail. Refer to the appropriate SJI in the
August 2012

Overhead Lines Construction Manual for method of disconnection.

6.10 Open points

6.10.1 General
The following method is adopted when creating or replacing an open point.

1. Fuse Links see Figure 18

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 15
Overhead Line Design Manual
 

6.11 Appendix A – GA Drawings and Materials - Mains


Table 2: List of GA Drawings and Materials - Mains
Figure Drawing Title

Figure 1: ABC General Drawing Arrangement

Figure 2: ABC Stay Arrangement, Make-Off (No Auxiliary Pole-Mounted


Equipment)

Figure 3: ABC Stay Arrangement, Make-Off (Restricted Height or Auxiliary


Pole-Mounted Equipment)

Figure 4: ABC Stay Arrangement, Stay Plate (Restricted Height, Auxiliary


Pole-Mounted Equipment or Live Line Working)

Figure 5: ABC Intermediate GA (Inside Angle up to 60o Line Deviation)

Figure 6: ABC Intermediate GA (Outside Angle up to 30o Line Deviation)

Figure 7: ABC Angle Section GA (up to 20o Line Deviation)

Figure 8: ABC Angle Section GA (20o to 90o Line Deviation)

Figure 9: ABC Terminal GA

Figure 10: ABC Tee-off Intermediate GA


March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 16


  Overhead Line Design Manual

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 17
Overhead Line Design Manual
 

Figure 1: ABC General Drawing Arrangement


March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 18


  Overhead Line Design Manual

Figure 2: ABC Stay Arrangement, Make-Off (No Auxiliary Pole-Mounted


Equipment)

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 19
Overhead Line Design Manual
 

Ref No Component Stores No


(Manufacturer’s references are available in UKPN EAS 00-0001)

1 Pole-top make-off, 7/3.25mm 08237U


or 08244Y
2 Guy grip dead-end, 7/3.25mm 09532A
or 08233F
or 08245J
3 Insulator, stay, LV, ENA TS type 1, 110kN MFL 08911W
4 Stay wire, 7/3.25mm, 1150 grade 08316A or
13816S
5 Steelwork, thimble, stay, type 1 09924P
6&7 Anchor, stay, load lock 0944D
and/or
0944T
- Staples, wire [NI] ** TBA
- Stay marker [NI] *** 13818M
1 Pole-top make-off, 7/4.00mm 08237U
or 08244Y
2 Guy grip dead-end, 7/4.00mm 09354U,
09532A,
08233F or
08245J
3 Insulator, stay, LV, ENA TS type 1, 110kN MFL 08911W
4 Stay wire, 7/4.00mm, 1150 grade 08315Q
or
13817C
5 Steelwork, thimble, stay, type 1 09924P
6 Anchor, stay rod, type 2 09735S
& 7* Concrete stay block, 640 x 430 x 140 09447X
6 & 7* Anchor, stay, screw-in, 8", single helix 08719K
6 & 7* Anchor, stay, screw-in, 10", single helix 08720F
6 & 7* Anchor, stay, screw-in, 10", twin helix 08725E
6 & 7* Anchor, stay, screw-in, 12", single helix 08721Q
6 & 7* Anchor, stay, screw-in, 14", single helix 08730P
- Staples, wire [NI] ** TBA
- Stay marker [NI] *** 13818M
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 20


  Overhead Line Design Manual

Figure 3: ABC Stay Arrangement, Make-Off (Restricted Height or Auxiliary


Pole-Mounted Equipment)

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 21
Overhead Line Design Manual
 

Ref Component Stores No


No (Manufacturer’s references are available in UKPN EAS 00-0001)

1 Pole-top make-off, 7/3.25mm 08237U


or 08244Y
2 Stay wire splice, 7/3.25mm 09356P
3 Stay wire, 7/3.25mm, 1150 grade 08316A or
13816S
4 Guy grip dead-end, 7/3.25mm 09532A
or 08233F or
08245J
5 Insulator, stay, LV, ENA TS type 1, 110kN MFL 08910M
6 Steelwork, thimble, stay, type 1 09924P
7&8 Anchor, stay, load lock 0944D
and/or 0944T
- Staples, wire [NI] ** TBA
- Stay marker [NI] *** 13818M
1 Pole-top make-off, 7/4.00mm 08237U
or 08244Y
2 Stay wire splice, 7/4.00mm 09357Y
3 Stay wire, 7/4.00mm, 1150 grade 08315Q
or
13817C
4 Guy grip dead-end, 7/4.00mm 09354U,
09532A,
08233F or
08245J
5 Insulator, stay, LV, ENA TS type 1, 110kN MFL 08911W
6 Steelwork, thimble, stay, type 1 09924P
7 Anchor, stay rod, type 2 09735S
& 8* Concrete stay block, 640 x 430 x 140 09447X
7 & 8* Anchor, stay, screw-in, 8", single helix 08719K
7 & 8* Anchor, stay, screw-in, 10", single helix 08720F
7 & 8* Anchor, stay, screw-in, 10", twin helix 08725E
7 & 8* Anchor, stay, screw-in, 12", single helix 08721Q
7 & 8* Anchor, stay, screw-in, 14", single helix 08730P
- Staples, wire [NI] ** TBA
- Stay marker [NI] *** 13818M
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 22


  Overhead Line Design Manual

Figure 4: ABC Stay Arrangement, Stay Plate (Restricted Height, Auxiliary


Pole-Mounted Equipment or Live Line Working)

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 23
Overhead Line Design Manual
 

Ref Component Stores No


No (Manufacturer’s references are available in UKPN EAS 00-0001)

1 Steelwork, stay plate, heavy duty TBA


- Bolt, M20, length 260mm, c/w hex full nut [NI] 13370X
- Washer, square curved, M20 [NI] 13803U
2 Guy grip dead-end, 7/3.25mm 09532A
or 08233F or
08245J
3 Steelwork, thimble, stay, type 1 09924P
4 Stay wire, 7/3.25mm, 1150 grade 08316A or
13816S
5 Insulator, stay, LV, ENA TS type 1, 110kN MFL 08910M
6&7 Anchor, stay, load lock 0944D
and/or 0944T
- Stay marker [NI] ** 13818M
1 Steelwork, stay plate, heavy duty TBA
- Bolt, M20, length 260mm, c/w hex full nut [NI] 13370X
- Washer, square curved, M20 [NI] 13803U
2 Guy grip dead-end, 7/4.00mm 09354U,
09532A,
08233F or
08245J
3 Steelwork, thimble, stay, type 1 09924P
4 Stay wire, 7/4.00mm, 1150 grade 08315Q
or
13817C
5 Insulator, stay, LV, ENA TS type 1, 110kN MFL 08911W
6 Anchor, stay rod, type 2 09735S
& 7* Concrete stay block, 640 x 430 x 140 09447X
6 & 7* Anchor, stay, screw-in, 8", single helix 08719K
6 & 7* Anchor, stay, screw-in, 10", single helix 08720F
6 & 7* Anchor, stay, screw-in, 10", twin helix 08725E
6 & 7* Anchor, stay, screw-in, 12", single helix 08721Q
6 & 7* Anchor, stay, screw-in, 14", single helix 08730P
- Stay marker [NI] ** 13818M
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 24


  Overhead Line Design Manual

Figure 5: ABC Intermediate GA (Inside Angle up to 60o Line Deviation)

Alternative arrangement showing 
weak link 

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 25
Overhead Line Design Manual  

Materials for
Figure 5: ABC Intermediate GA (Inside Angle up to 60o Line Deviation)

Conductor
2
ABC, 2x35mm

ABC, 2x95mm
2
ABC, 4x35mm
2
ABC, 4x95mm
2
ABC, 4x120mm

Ref Component Stores No


no (Manufacturer’s references are available in UKPN EAS 00-
0001)

1 Nut, M20, open-ended hook, ABC 09375W or 1 1 1 1 1


08365J
2
2 Conductor fitting, clamp, suspension, ABC, 2/4x35mm 08372N - - 1 - 1
2
2 Conductor fitting, clamp, suspension, ABC, 2x95mm 08369X - - - 1 -
2
2 Conductor fitting, clamp, suspension, ABC, 4x95mm 08374H - 1 - - -
2
2 Conductor fitting, clamp, suspension, ABC, 4x120mm 08367D 1 - - - -

3 Washer, square curved, M20 08302C 1 1 1 1 1

4 Bolt, M20 * 1 1 1 1 1

5 Wood pole * 1 1 1 1 1

Notice, danger of death [NI] 20010P 1 1 1 1 1

Supplementary components needed to complete the structure


6 Stay * As required

ACD [NI] 08136C As required

7 Conductor fitting, clamp, weak link suspension, ABC [NI] 09385F ** As required

Notices [NI] * As required

* Select from specification identified in previous


column.

** The adjacent drawing is for Illustration purposes to
show position for the weak link if required as per
6.1.1Supports
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 26


  Overhead Line Design Manual
Figure 6: ABC Intermediate GA (Outside Angle up to 30o Line Deviation)

Alternative arrangement showing 
weak link 

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 27
Overhead Line Design Manual
 

Materials for
Figure 6: ABC Intermediate GA (Outside Angle up to 30o Line Deviation)

Conductor
2
ABC, 2x35mm
2
ABC, 2x95mm
2
ABC, 4x35mm
2
ABC, 4x95mm
2
ABC, 4x120mm

Ref Component Stores No


No (Manufacturer’s references are available in UKPN
EAS 00-0001)

1 Steelwork, hook outrigger, pole, ABC 09376G 1 1 1 1 1


2
2 Conductor fitting, clamp, suspension, ABC, 2/4x35mm 08865W - - 1 - 1
2
2 Conductor fitting, clamp, suspension, ABC, 2x95mm 08866G - - - 1 -
2
2 Conductor fitting, clamp, suspension, ABC, 4x95mm 08867R - 1 - - -
2
2 Conductor fitting, clamp, suspension, ABC, 4x120mm 08868B 1 - - - -
3 Washer, square curved, M20 08302C 1 1 1 1 1
4 Bolt, M20, 320mm 09372S 1 1 1 1 1
5 Wood pole * 1 1 1 1 1
Notice, danger of death [NI] 20010P 1 1 1 1 1

Supplementary components needed to complete the structure


6 Stay * As required
ACD [NI] 08136C As required
7 Conductor fitting, clamp, weak link suspension, ABC [NI] 09385F ** As required
Notices [NI] e.g pole number * As required

* Select from specification identified in previous


column.

** The adjacent drawing is for Illustration purposes to
show position for the weak link if required as per
6.1.1Supports
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 28


  Overhead Line Design Manual
Figure 7: ABC Angle Section GA (up to 20o Line Deviation)

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 29
Overhead Line Design Manual  

Materials for
Figure 7: ABC Angle Section GA (up to 20o Line Deviation)

Conductor
2
ABC, 2x35mm
2
ABC, 2x95mm
2
ABC, 4x35mm
2
ABC, 4x95mm
2
ABC, 4x120mm

Ref Component Stores


No (Manufacturer’s references are available in UKPN EAS
No
00-0001)
2
1 Conductor fitting, clamp, anchor, 2x35mm 08857H - - - - 2
2
1 Conductor fitting, clamp, anchor, 2x95mm 08858S - - - 2 -
2
1 Conductor fitting, clamp, anchor, 4x35mm 08859C - - 2 - -
2
1 Conductor fitting, clamp, anchor, 4x95mm 08860X - 2 - - -
2
1 Conductor fitting, clamp, anchor, 4x120mm 08861H 2 - - - -
2 Bolt, eye, M20, 300mm 08052X 1 1 1 1 1
3 Conductor fitting, compression non tension, ABC, 08740X - - 4 - 2
2
35mm
3 Conductor fitting, compression non tension, ABC, 08743C - 4 - 2 -
2
95mm
3 Conductor fitting, compression non tension, ABC, 08744M 4 - - - -
2
120mm
4 Washer, square curved, M20 08302C 2 2 2 2 2
5 Nut, eye, M20 08057W 1 1 1 1 1
6 Wood pole * 1 1 1 1 1
Notice, danger of death (wood poles) [NI] 20010P 1 1 1 1 1

Supplementary components needed to complete the structure


7 Stay * As required
8 Cleat, stand-off, plastic, ABC TBA As required
ACD [NI] * As required
Notices [NI] e.g pole number * As required

* Select from specification identified in previous column.


March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 30


  Overhead Line Design Manual
Figure 8: ABC Angle Section GA (20o to 90o Line Deviation)

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 31
Overhead Line Design Manual  

Materials for
Figure 8: ABC Angle Section GA (20o to 90o Line Deviation)

Conductor
2
ABC, 2x35mm
2
ABC, 2x95mm
2
ABC, 4x35mm
2
ABC, 4x95mm
2
ABC, 4x120mm

Ref Component Stores No


No (Manufacturer’s references are available in UKPN EAS
00-0001)
2
1 Conductor fitting, clamp, anchor, 2x35mm 08857H - - - - 2
2
1 Conductor fitting, clamp, anchor, 2x95mm 08858S - - - 2 -
2
1 Conductor fitting, clamp, anchor, 4x35mm 08859C - - 2 - -
2
1 Conductor fitting, clamp, anchor, 4x95mm 08860X - 2 - - -
2
1 Conductor fitting, clamp, anchor, 4x120mm 08861H 2 - - - -
2 Bolt, eye, M20, 300mm 08052X 2 2 2 2 2
3 Washer, square curved, M20 08302C 2 2 2 2 2
4 Wood pole * 1 1 1 1 1
Notice, danger of death (wood poles) [NI] 20010P 1 1 1 1 1

Supplementary components needed to complete the structure


5 Stay * As required
ACD [NI] * As required
Notices [NI] e.g pole number * As required

* Select from specification identified in previous column.


March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 32


  Overhead Line Design Manual
Figure 9: ABC Terminal GA

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 33
Overhead Line Design Manual  

Materials for
Figure 9: ABC Terminal GA

Conductor
2
ABC, 2x35mm
2
ABC, 2x95mm
2
ABC, 4x35mm
2
ABC, 4x95mm
2
ABC, 4x120mm

Ref Component Stores No


No (Manufacturer’s references are available in UKPN EAS
00-0001)
2
1 Conductor fitting, clamp, anchor, 2x35mm 08857H - - - - 2
2
1 Conductor fitting, clamp, anchor, 2x95mm 08858S - - - 2 -
2
1 Conductor fitting, clamp, anchor, 4x35mm 08859C - - 2 - -
2
1 Conductor fitting, clamp, anchor, 4x95mm 08860X - 2 - - -
2
1 Conductor fitting, clamp, anchor, 4x120mm 08861H 2 - - - -
2 Bolt, eye, M20, 300mm 08052X 1 1 1 1 1
3 Conductor fitting, cap, end, ABC 08881A 4 4 4 2 2
4 Washer, square curved, M20 08302C 2 2 2 2 2
5 Wood pole * 1 1 1 1 1
Notice, danger of death (wood poles) [NI] 20010P 1 1 1 1 1

Supplementary components needed to complete the structure


6 Stay * As required
ACD [NI] * As required
Notices [NI] e.g pole number * As required

* Select from specification identified in previous column.


March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 34


  Overhead Line Design Manual
Figure 10: ABC Tee-off Intermediate GA

August 2012

Note – This drawing illustrates connections for a 120mm2 ABC.


For connections of 95mm2 and below refer to the material lists.

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 35
Overhead Line Design Manual  

Materials for
Figure 10: ABC Tee-off Intermediate GA
Conductor
2
ABC, 2x35mm
2
ABC, 2x95mm
2
ABC, 4x35mm
2
ABC, 4x95mm
2
ABC, 4x120mm
Ref Component Stores
No (Manufacturer’s references are available in UKPN EAS No
00-0001)
2
1 Conductor fitting, clamp, suspension, ABC, 2/4x35mm 08865W - - 1 - 1
2
1 Conductor fitting, clamp, suspension, ABC, 2x95mm 08866G - - - 1 -
2
1 Conductor fitting, clamp, suspension, ABC, 4x95mm 08867R - 1 - - -
2
1 Conductor fitting, clamp, suspension, ABC, 4x120mm 08868B 1 - - - -
2 Nut, M20, open-ended hook, ABC 09375W 1 1 1 1 1
2
Conductor fitting, insulating piercing connector, ABC, 35mm – 08845E - - 5 - 3
3 2
ABC, 35mm , single bolt
2
Conductor fitting, insulating piercing connector, ABC, 95mm – 08846P - 5 - 3 -
3 2
ABC, 95mm , single bolt
2
Conductor fitting, insulating piercing connector, ABC, 120mm 08848J 5 - - - -
3 2
– ABC, 120mm ,double bolt
2
4 Conductor fitting, clamp, anchor, 2x35mm 08857H - - - - 2
2
4 Conductor fitting, clamp, anchor, 2x95mm 08858S - - - 2 -
2
4 Conductor fitting, clamp, anchor, 4x35mm 08859C - - 2 - -
2
4 Conductor fitting, clamp, anchor, 4x95mm 08860X - 2 - - -
2
4 Conductor fitting, clamp, anchor, 4x120mm 08861H 2 - - - -
5 Bolt, eye, M20, 300mm 08052X 1 1 1 1 1
6 Washer, square curved, M20 08302C 1 1 1 1 1
7 Wood pole * 1 1 1 1 1
Notice, danger of death (wood poles) [NI] 20010P 1 1 1 1 1
Supplementary components needed to complete the structure
8 Stay * As required
ACD [NI] * As required
Cable tie [NI] TBA As required
Cleat, stand-off, plastic, ABC [NI] TBA As required
Notices [NI] e.g pole number * As required

* Select from specification identified in previous column.


March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 36


  Overhead Line Design Manual
6.12 Appendix B – GA Drawings and Materials – Services
Table 3: List of GA Drawings and Materials – Services
Figure Drawing Title

Figure 11: ABC Service Connection (Three Phase) GA

Figure 12: Concentric Service Connection GA

Figure 13: Insulated Open Wire Service Connection GA

Figure 14: Street Lighting Service Connection GA

Figure 15: Concentric Service Spans

Figure 16: ABC Service Spans

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 37
Overhead Line Design Manual
 
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 38


  Overhead Line Design Manual

Figure 11: ABC Service Connection (Three Phase) GA

Note – This drawing illustrates connections for 95mm2 ABC and


August 2012

below. For connections of 120mm2 and below refer to the material


lists.

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 39
Overhead Line Design Manual
 

Materials for
Figure 11: ABC Service Connection (Three Phase) GA

Conductor
2
ABC, 4x35mm
2
ABC, 4x95mm
2
ABC, 4x120mm

Ref Component Stores No


No (Manufacturer’s references are available in UKPN EAS 00-0001)

1 Conductor fitting, cap, end, ABC 08881A 4 4 4


2
Conductor fitting, insulating piercing connector, ABC, 35mm – ABC, 08845E - - 5
2 2
35mm , single bolt
2
Conductor fitting, insulating piercing connector, ABC, 95mm – ABC, 08847Y - 5 -
2 2
35mm , single bolt
2
Conductor fitting, insulating piercing connector, ABC, 120mm – ABC, 08848J 5 - -
2 2
35mm , double bolt
3 Steelwork, hook bolt, pole, ABC 09372S 1 1 1
2
4 Conductor fitting, clamp, anchor, 4x35mm 08859C - - 1
2
4 Conductor fitting, clamp, anchor, 4x95mm 08860X - 1 -
2
4 Conductor fitting, clamp, anchor, 4x120mm 08861H 1 - -

Supplementary components needed to complete the structure


5 Cleat, stand-off, plastic, ABC TBA As required
6 Cable tie TBA As required
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 40


  Overhead Line Design Manual
Figure 12: Concentric Service Connection GA (3ph service cable shown)

Note – This drawing illustrates connections for 95mm2 ABC and


below. For connections of 120mm2 refer to the material lists.
August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 41
Overhead Line Design Manual  

Materials for
Figure 12: Concentric Service Connection GA – single phase

Conductor
2
CNE, 1-phase, 35mm

Ref Component Stores No


No (Manufacturer’s references are available in UKPN EAS 00-0001)

1 Conductor fitting, cap, end, ABC 08885P 2


2 2
Conductor fitting, insulating piercing connector, ABC, 35mm – ABC, 35mm , 08845E 3**
2
single bolt
2 2
Conductor fitting, insulating piercing connector, ABC, 95mm – ABC, 35mm , 08847Y 3**
2
single bolt
2 2
Conductor fitting, insulating piercing connector, ABC, 120mm – ABC, 35mm , 08848J 3**
2
double bolt
3 Conductor fitting, non-tension, ABC tailed out fitting to match CNE * 2
Cable termination, break-out kit, 2-core 02805T 1
4
02806D
5 Cable, CNE, 1-phase * L*
6 Conductor fitting, helical dead end, CNE, 1-phase * 1
7 Insulator, coach screw, service 08927P 1

Conductor
2
CNE, 3-phase, 35mm

Ref Component Stores No


No
1 Conductor fitting, cap, end, ABC 08885P 4
2 2
Conductor fitting, insulating piercing connector, ABC, 35mm – ABC, 35mm , 08845E 5**
2
single bolt
2 2
Conductor fitting, insulating piercing connector, ABC, 95mm – ABC, 35mm , 08847Y 5**
2
single bolt
2 2
Conductor fitting, insulating piercing connector, ABC, 120mm – ABC, 35mm , TBA 5**
2
double bolt
3 Conductor fitting, non-tension, ABC tailed out fitting to match CNE * 4
Cable termination, break-out kit, 4-core 02805T 1
4
02806D
5 Cable, CNE, 3-phase 05177J L*
6 Conductor fitting, helical dead end, CNE, 3-phase 08243P 1
7 Insulator, coach screw, service 08927P 1

Supplementary components needed to complete the structure for 3ph and single 1ph
March 2011

services
8 Cleat, stand-off, plastic, ABC TBA As req’d
9 Cable tie TBA As req’d

L* Length as required.
* Select from specification identified in previous column.
** Select to fit ABC.

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 42


  Overhead Line Design Manual
Figure 13: Insulated Open Wire Service Connection GA

August 2012

Note – This drawing illustrates connections for 95mm2 ABC and


below. For connections of 120mm2 refer to the material lists.

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 43
Overhead Line Design Manual 

Materials for
Figure 13: Insulated Open Wire Service Connection GA

Conductor
Insulated open-wire

Ref Component Stores No


No (Manufacturer’s references are available in UKPN EAS 00-0001)
2
1 Conductor, ABC, 2x35mm 06200R L*
2
1 Conductor, ABC, 2x95mm 06202L L*
2
1 Conductor, ABC, 4x35mm 06205Q L*
2
1 Conductor, ABC, 4x95mm 06207K L*
2
1 Conductor, ABC, 4x120mm 06208U L*
2 2
Conductor fitting, insulating piercing connector, ABC, 35mm – ABC, 35mm , 08845E **
2
single bolt
2 2
Conductor fitting, insulating piercing connector, ABC, 95mm – ABC, 35mm , 08847Y **
2
single bolt
2 2
Conductor fitting, insulating piercing connector, ABC, 95mm – ABC, 95mm , 08846P **
2
single bolt
2 2
Conductor fitting, insulating piercing connector, ABC, 120mm – ABC, 35mm , 08848J **
2
double bolt
2 2
Conductor fitting, insulating piercing connector, ABC, 120mm – ABC, 95mm , 08848J **
2
double bolt
2 2
Conductor fitting, insulating piercing connector, ABC, 120mm – ABC, 120mm , 08848J **
2
double bolt
3 Conductor fitting, cap, end, ABC 08881A 4
2
Conductor fitting, non-tension, ABC, 35mm – tail 400mm long transformed – * ***
4
insulated wire
2
Conductor fitting, non-tension, ABC, 95mm – tail 400mm long transformed – * ***
4
insulated wire
2
Conductor fitting, non-tension, ABC, 120mm – tail 400mm long transformed – * ***
4
insulated wire
5 Insulator, coach screw, service 08927P 4
6 Conductor fitting, helical dead end * 4

Supplementary components needed to complete the structure


7 Cleat, stand-off, plastic, ABC TBA As req’d
8 Cable tie TBA As req’d

L* Length as required.
* Select to fit insulated wire from specification identified in previous column.
** Select to fit ABC (5 required for three phase; 3 required for single phase).
March 2011

*** Select to fit ABC and insulated wire from specification identified in previous column (4 required for three phase; 2
required for single phase).

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 44


  Overhead Line Design Manual
Figure 14: Street Lighting Service Connection GA

August 2012

Note – This drawing illustrates connections for 95mm2 ABC and


below. For connections of 120mm2 refer to the material lists.

Lamp, control gear and tails are the property of the local Street
Lighting Authority

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 45
Overhead Line Design Manual  

Materials for
Figure 14: Street Lighting Service Connection GA

Conductor
ABC, all

Ref Component Stores No


No (Manufacturer’s references are available in UKPN EAS 00-0001)

1 Conductor fitting, cap, end, ABC 08881A 2


2 2
Conductor fitting, insulating piercing connector, ABC, 35mm – ABC, 35mm , 08845E *
2
single bolt
2 2
Conductor fitting, insulating piercing connector, ABC, 95mm – ABC, 35mm , 08847Y *
2
single bolt
2 2
Conductor fitting, insulating piercing connector, ABC, 120mm – ABC, 35mm , 08848J *
2
double bolt
2
3 Conductor, ABC, 2x35mm 06200R L*
2 2
Conductor fitting, compression non tension, ABC, 35mm – Al 16mm 08765P 2
4
08757A
5 Cable termination, break-out kit, 2-core 02805T 1
2 2
6 Cable, Concentric, 1-phase, 4mm or 16mm TBA L*
7 Service box cut-out (diamond) 08361U 1
7 Cut-Out Street Lighting PME 25 Amp 12000K 1

Supplementary components needed to complete the structure


8 Cleat, stand-off, plastic, ABC TBA As req’d
9 Local Authority Street Light Tails TBA As req’d

L* Length as required.
* Select to fit ABC.
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 46


  Overhead Line Design Manual
Figure 15: Concentric Service Spans

Figure 16: ABC Service Spans

Table 11.1 Service Clearances


Location Minimum Clearance (m)
August 2012

Along the line of hedgerows, fences and boundary walls 4.0


etc.
Domestic driveways with an access width of 2.5 m or less
4.3
which is defined by gateposts, hedges or other fixed
features.
Between buildings where there is no vehicular access. 3.5

Normal Ground 3.5

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 47
Overhead Line Design Manual
 

6.13 Appendix C – GA Drawings and Materials – Pole Mounted Equipment


Table 4: List of GA Drawings and Materials – Pole Mounted Equipment
Figure Drawing Title

Figure 17: ABC to Two Distribution Boxes

Figure 18: ABC to ABC via Fuses GA

Figure 19: ABC Intermediate with Cable Termination and LV Fuses GA

Figure 20: ABC Terminal with Cable Termination and LV Fuses GA


March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 48


  Overhead Line Design Manual
Figure 17: ABC to Two Distribution Boxes

August 2012

Note – This drawing illustrates connections for 120mm2 ABC. For


connections of 95mm2 and below refer to the material lists.

Please ensure that ABC droppers (Ref No 3) are adequately


cleated to the pole as above drawing is for illustration purposes
only.

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 49
Overhead Line Design Manual
 

Materials for
Figure 17: ABC to Two Distribution Boxes
Conductor
2
ABC, 4x95mm
Ref No Component Stores No
(Manufacturer’s references are available in UKPN EAS 00-0001)
1 Conductor fitting, cap, end, ABC 08881A 8
2
Conductor fitting, insulating piercing connector, ABC, 95mm – ABC, 08846P 8
2 2
95mm , single bolt
2
Conductor fitting, insulating piercing connector, ABC, 120mm – ABC, 08848J 8
2 2
95mm , double bolt
2 2
3 Conductor, ABC, 4x50mm or 95mm (line to distribution box) 06207K L*
2 2
4 Conductor, ABC, 4x50mm or 95mm (line to distribution box) 06207K L*
5 Distribution box, overhead, 3-phase 08360K 2
Supplementary components needed to complete the structure
Cable tie [NI] TBA As
req’d
Cleat, stand-off, plastic, ABC [NI] TBA As
req’d

L* Length as required.
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 50


  Overhead Line Design Manual

Figure 18: ABC to ABC via Fuses GA

August 2012

Note – This drawing illustrates connections for 120mm2 ABC. For


connections of 95mm2 and below refer to the material lists.

Please ensure that ABC droppers (Ref No 3) are adequately


cleated to the pole as above drawing is for illustration purposes
only.

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 51
Overhead Line Design Manual
 

Materials for
Figure 18: ABC to ABC via Fuses GA
Conductor
2
ABC, 4x35mm
2
ABC, 4x95mm
2
ABC, 4x120mm
Ref Component Stores No
No (Manufacturer’s references are available in UKPN EAS 00-0001)
2
Conductor fitting, insulating piercing connector, ABC, 35mm – ABC, 08845E - - 2
1 2
35mm , single bolt
2
Conductor fitting, insulating piercing connector, ABC, 95mm – ABC, 08846P - 2 -
1 2
95mm , single bolt
2
Conductor fitting, insulating piercing connector, ABC, 120mm – ABC, 08848J 2 - -
1 2
120mm , double bolt
2
2 Conductor fitting, compression full tension, ABC, 35mm 08740X - - 1
2
2 Conductor fitting, compression full tension, ABC, 95mm 08743C - 1 -
2
2 Conductor fitting, compression full tension, ABC, 120mm 08744M 1 - -
3 Fuse unit, pole mounted, LV ABC 12050D 3 3 3
2 2
4 Conductor fitting, compression non tension, ABC, 35mm – Cu, 16mm 08765P - - 1
2 2
4 Conductor fitting, compression non tension, ABC, 95mm – Cu, 16mm TBA - 1 -
2 2
4 Conductor fitting, compression non tension, ABC, 120mm – Cu, 16mm TBA 1 - -
Earthing components * * 1 1 1
Supplementary components needed to complete the structure
Cable tie [NI] TBA As required
Cleat, stand-off, plastic, ABC [NI] TBA As required
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 52


  Overhead Line Design Manual
Figure 19: ABC Intermediate with Cable Termination and LV Fuses GA

August 2012

Note – This drawing illustrates connections for 120mm2 ABC. For


connections of 95mm2 and below refer to the material lists.

Please ensure that ABC droppers (Ref No 3) are adequately


cleated to the pole as above drawing is for illustration purposes
only.

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 53
Overhead Line Design Manual  

Materials for
Figure 19: ABC Intermediate with Cable Termination and LV Fuses GA
Conductor
2
ABC, 2x95mm
2
ABC, 4x95mm
2
ABC, 4x120mm

Ref Component Stores No


No (Manufacturer’s references are available in UKPN EAS 00-0001)
2
Conductor fitting, insulating piercing connector, ABC, 95mm – ABC, 08846P - 5 5
1 2
95mm , single bolt
2
Conductor fitting, insulating piercing connector, ABC, 120mm – ABC, TBA 7 - -
1 2
95mm , double bolt
2 Conductor fitting, cap, end, ABC 08881A 5 5 3
2
3 Conductor, ABC, 2x95mm (main to fuse) 06202L - - L*
2
3 Conductor, ABC, 4x95mm (main to fuse) 06207K - L* -
2
3 Conductor, ABC, 4x120mm (main to fuse) 06208U L* - -
4 Cable guard, LV ABC 08172X 1 1 1
2 2
5 Conductor fitting, compression non tension, ABC, 95mm – Cu, 16mm TBA 1 1 1
2
6 Conductor fitting, compression full tension, ABC, 95mm 08743C - 1 1
2 2
6 Conductor fitting, compression full tension, ABC, 120mm – ABC, 95mm TBA 1 - -
7 Fuse unit, pole mounted, LV ABC 12050D 3 3 1
Earthing components ** ** 1 1 1

Supplementary components needed to complete the structure


Cable tie [NI] TBA TBA As required
Cleat, stand-off, plastic, ABC [NI] TBA TBA As required

L* Length as required.
* Select from specification identified in previous column.
** Refer to Figure 22.
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 54


  Overhead Line Design Manual

Figure 20: ABC Terminal with Cable Termination and LV Fuses GA

August 2012

Note – This drawing illustrates connections for 120mm2 ABC. For


connections of 95mm2 and below refer to the material lists. Please
ensure that ABC droppers are adequately cleated to the pole as
above drawing is for illustration purposes only.

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 55
Overhead Line Design Manual  

Materials for
Figure 20: ABC Terminal with Cable Termination and LV Fuses GA
Conductor
2
ABC, 2x95mm
2
ABC, 4x95mm
2
ABC, 4x120mm
Ref Component Stores No
No (Manufacturer’s references are available in UKPN EAS 00-0001)
1 Fuse unit, pole mounted, LV ABC 12050D 3 3 1

2 Cable guard, LV ABC 08172X 1 1 1


2 2
3 Conductor fitting, compression non tension, ABC, 95mm – Cu, 16mm TBA 1 1 1
2
4 Conductor fitting, compression full tension, ABC, 95mm 08743C - 1 1
2 2
4 Conductor fitting, compression full tension, ABC, 120mm – ABC, 95mm TBA 1 - -
2
Conductor fitting, insulating piercing connector, ABC, 95mm – ABC, 08846P - 2 2
5 2
95mm single bolt
2
Conductor fitting, insulating piercing connector, ABC, 120mm – ABC, 088485 2 - -
5 2
95mm , double bolt
6 Conductor fitting, cap, end, ABC 08881A 1 1 1
Earthing components ** ** 1 1 1
Supplementary components needed to complete the structure
Cable tie [NI] TBA As required
Cleat, stand-off, plastic, ABC [NI] TBA As required

* Select from specification identified in previous column.


** Refer to Figure 22.
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 56


  Overhead Line Design Manual
6.14 Appendix D – GA Drawings and Materials – Earthing
Table 5: List of GA Drawings and Materials – Earthing

Figure Drawing Title

Figure 21: ABC Earthing – ABC Bundle to Neutral/Earth Bracket


Figure 22: ABC Earthing – Neutral/Earth Bracket to Earth Electrodes

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 57
Overhead Line Design Manual  

Figure 21: ABC Earthing – ABC Bundle to Neutral/Earth Bracket

Materials for
Figure 21: ABC Earthing – ABC Bundle to Neutral/Earth Bracket
Conductor
2
ABC, 2x35mm
2
ABC, 2x95mm
2
ABC, 4x35mm
2
ABC, 4x95mm
2
ABC, 4x120mm
Ref Component Stores No
No (Manufacturer’s references are available in UKPN EAS
00-0001)
1 Conductor fitting, cap, end, ABC 08881A 1 1 1 1 1
2
Conductor fitting, insulating piercing connector, ABC, 35mm – 08845E - - 2 - 2
2 2
ABC, 35mm , single bolt
2
Conductor fitting, insulating piercing connector, ABC, 95mm – 08847Y - 2 - 2 -
2 2
ABC, 35mm , single bolt
2
Conductor fitting, insulating piercing connector, ABC, 120mm 08848J 2 - - - -
2 2
– ABC, 35mm , double bolt
2
Conductor fitting, non-tension, ABC, 35mm – tail 400mm long 08765P 1 1 1 1 1
3 2
transformed – Cu, bare, 16mm
March 2011

2
4 Cable, Cu, 16mm , green/yellow insulated earth wire 05280G L* L* L* L* L*
Earthing components * * 1 1 1 1 1

* Refer to Figure 22.

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 58


  Overhead Line Design Manual
Figure 22: ABC Earthing – Neutral/Earth Bracket to Earth Electrodes

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 59
Overhead Line Design Manual  

Materials for
Figure 22: ABC Earthing – Neutral/Earth Bracket to Earth Electrodes
ABC, all
Ref Component Stores No
No (Manufacturer’s references are available in UKPN EAS 00-0001)
2
1 Cable, Cu, 16mm , green/yellow insulated earth wire 05280G 6m
2 Cable guard 08172X 1
Earth electrode 02463T As
3
req’d
2
Cable, Cu, 16mm , bare earth wire TBA As
4
req’d

Supplementary components needed to complete the structure


Earth electrode, coupling ** 02467K As
req’d
Earth electrode, clamp ** 02466A As
req’d
Earth electrode, extension ** TBA As
req’d

L* Length as required.
* Select from specification identified in previous column.
** For use with earth electrode as required.
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 60


  Overhead Line Design Manual
6.15 Appendix E – Reference List of all Materials for this specification

Reference List of all Materials for this specification


(supplementary components are included at the end of this list)

Component Stores GA Figure Ref


(Manufacturer’s references are available in UKPN EAS 00-0001)
No

Bolt, eye, M20, 300mm 08052X Figure 7, Figure 8,


Figure 9 & Figure 10
Bolt, M20, lengths as required TBA Figure 4, Figure 5, &
Figure 6
Cable, CNE, 1-phase Various Figure 12
Cable, CNE, 3-phase Various Figure 12
2 2
Cable, Concentric, 1-phase, 4mm or 16mm TBA Figure 14
2
Cable, Cu, 16mm , bare earth wire TBA Figure 21
2
Cable, Cu, 16mm , green/yellow insulated earth wire 05280G Figure 21 & Figure 22
Cable guard 08172X Figure 19, Figure 20
& Figure 22
Cable termination, break-out kit, 2-core 02805T Figure 12
02806D Figure 14
Cable termination, break-out kit, 4-core 02805T Figure 12
02806D
2
Conductor, ABC, 2x35mm 06200R Figure 13
Figure 14
2
Conductor, ABC, 2x95mm 06202L Figure 13
Figure 19
2
Conductor, ABC, 4x35mm 06205Q Figure 13
2
Conductor, ABC, 4x95mm 06207K Figure 13, Figure 17
& Figure 19
2
Conductor, ABC, 4x120mm 06208U Figure 13 & Figure
19
Conductor fitting, cap, end, ABC 08881A Figure 9, Figure 11,
Figure 13, Figure 14,
Figure 17 Figure 19,
Figure 20 & Figure 21
Conductor fitting, cap, end, ABC 08885P Figure 12
2
Conductor fitting, clamp, anchor, 2x35mm 08857H Figure 7, Figure 8,
Figure 9 & Figure 10
2
Conductor fitting, clamp, anchor, 2x95mm 08858S Figure 7, Figure 8,
Figure 9 & Figure 10
2
Conductor fitting, clamp, anchor, 4x35mm 08859C Figure 7, Figure 8,
Figure 9 & Figure 10
August 2012

2
Conductor fitting, clamp, anchor, 4x95mm 08860X Figure 7, Figure 8,
Figure 9 & Figure 10
2
Conductor fitting, clamp, anchor, 4x120mm 08861H Figure 7, Figure 8,
Figure 9 & Figure 10
2
Conductor fitting, clamp, suspension, ABC, 2/4x35mm 08372N Figure 4
2
Conductor fitting, clamp, suspension, ABC, 2/4x35mm 08865W Figure 6 & Figure 10
2
Conductor fitting, clamp, suspension, ABC, 2x95mm 08369X Figure 5
2
Conductor fitting, clamp, suspension, ABC, 2x95mm 08866G Figure 6 & Figure 10

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 61
Overhead Line Design Manual
 

Reference List of all Materials for this specification


(supplementary components are included at the end of this list)

Component Stores GA Figure Ref


(Manufacturer’s references are available in UKPN EAS 00-0001)
No
2
Conductor fitting, clamp, suspension, ABC, 4x95mm 08374H Figure 5
2
Conductor fitting, clamp, suspension, ABC, 4x95mm 08867R Figure 6 & Figure 10
2
Conductor fitting, clamp, suspension, ABC, 4x120mm 08367D Figure 5
2
Conductor fitting, clamp, suspension, ABC, 4x120mm 08868B Figure 6 & Figure 10

2
Conductor fitting, compression full tension, ABC, 35mm 08740X Figure 7 & Figure 18
2
Conductor fitting, compression full tension, ABC, 95mm 08743C Figure 7, Figure 18,
Figure 19 & Figure 20
2
Conductor fitting, compression full tension, ABC, 120mm 08744M Figure 7 & Figure 18
2 2
Conductor fitting, compression full tension, ABC, 120mm – ABC, 95mm TBA Figure 7 & Figure 18
2
Conductor fitting, compression non tension, ABC, 35mm 08740X Figure 7 & Figure 18
2
Conductor fitting, compression non tension, ABC, 35mm – 08765P Figure 14, Figure 18
2
Al, 16mm 08757A & Figure 21
2 2
Conductor fitting, compression non tension, ABC, 35mm –Cu, 16mm 08765p Figure 14, Figure 18
& Figure 21
2
Conductor fitting, compression non tension, ABC, 95mm 08743C
2 2
Conductor fitting, compression non tension, ABC, 95mm –Cu, 16mm TBA Figure 14
Figure 16
to
Figure 18
to
Figure 22
2
Conductor fitting, compression non tension, ABC, 120mm 08744M Figure 3
2 2
Conductor fitting, compression non tension, ABC, 120mm –Cu, 16mm TBA Figure 16
to
Figure 18
2
Conductor fitting, compression non tension, Cu, 16mm TBA Figure 23
Conductor fitting, helical dead end TBA Figure 10
Conductor fitting, helical dead end, CNE, 1-phase Various Figure 9
Conductor fitting, helical dead end, CNE, 3-phase Various Figure 9
2 2
Conductor fitting, insulating piercing connector, ABC, 35mm – ABC, 35mm , 08845E Figure 6 to 11
single bolt Figure 17
Figure 18
Figure 23
2 2
Conductor fitting, insulating piercing connector, ABC, 95mm – ABC, 35mm , 08847Y Figure 8
single bolt to
Figure 11
Figure 23
March 2011

2 2
Conductor fitting, insulating piercing connector, ABC, 95mm – ABC, 95mm , 08846P Figure 6
single bolt Figure 7
Figure 10
Figure 14
to Figure 22
2 2
Conductor fitting, insulating piercing connector, ABC, 120mm – ABC, 35mm , 08848J Figure 8
double bolt to
Figure 11
Figure 23

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 62


  Overhead Line Design Manual
Reference List of all Materials for this specification
(supplementary components are included at the end of this list)

Component Stores GA Figure Ref


(Manufacturer’s references are available in UKPN EAS 00-0001)
No
2 2
Conductor fitting, insulating piercing connector, ABC, 120mm – ABC, 95mm , 08848J Figure 10
double bolt Figure 14
Figure 15
Figure 19
to
Figure 22
2 2
Conductor fitting, insulating piercing connector, ABC, 120mm – ABC, 120mm , 08848J Figure 6
double bolt Figure 7
Figure 10
Figure 16
to
Figure 18
Conductor fitting, non-tension, ABC tailed out fitting to match CNE TBA Figure 9
2
Conductor fitting, non-tension, ABC, 35mm – tail 400mm long transformed – Cu, 08765P Figure 23
2
bare, 16mm
2
Conductor fitting, non-tension, ABC, 35mm – tail 400mm long transformed – TBA Figure 10
insulated wire
2
Conductor fitting, non-tension, ABC, 95mm – tail 400mm long transformed – TBA Figure 10
insulated wire
2
Conductor fitting, non-tension, ABC, 95mm – tail 400mm long transformed – Cu 087715 Figure 16
2
70mm
2
Conductor fitting, non-tension, ABC, 120mm – tail 400mm long transformed – TBA Figure 10
insulated wire
2
Conductor fitting, non-tension, ABC, 120mm – tail 400mm long transformed – Cu TBA Figure 16
2
100mm
Conductor fitting, non-tension, ABC tailed out fitting to match CNE Various Figure 9
Distribution box, overhead, 3-phase 08360K Figure 14
Figure 15
Earth electrode TBA Figure 24
Earth electrode, coupling TBA Figure 24
Earth electrode, clamp TBA Figure 24
Fuse unit, pole mounted, LV ABC 12050D Figure 17
Figure 21
Figure 22
Insulator, coach screw, service 08927P Figure 9
Figure 10
Notice, danger of death 20010P Figure 5
to
Figure 10
Nut, eye, M20 08057W Figure 3
August 2012

Figure 7
Nut, M20, open-ended hook, ABC 09375W Figure 1
Figure 6
Steelwork, hook bolt, pole, ABC 09372S Figure 8
Steelwork, hook outrigger, pole, ABC 09376G Figure 2
Washer, square curved, M20 08302C Figure 1
to
Figure 7

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 63
Overhead Line Design Manual
 

Reference List of all Materials for this specification


(supplementary components are included at the end of this list)

Component Stores GA Figure Ref


(Manufacturer’s references are available in UKPN EAS 00-0001)
No

Wood pole Various Figure 1


to
Figure 7

Supplementary components to be used as required


Anti-climbing device (ACD) Various Figure 1
to
Figure 7
Cable tie TBA As required
Cleat, stand-off, plastic, ABC TBA Figure 3
Figure 6
to
Figure 11
Figure 14
to
Figure 22
Conductor fitting, clamp, weak link suspension, ABC 09385F Figure 5
Figure 6
Notices Various Figure 1
to
Figure 7
Stays
Anchor, stay rod, type 2 Concrete stay block, 640 x 430 x 140 09735S Figure 2 to Figure 4
Anchor, stay, screw-in, 8", single helix (Various sizes) 08719K Figure 2 to Figure 4
Anchor, stay, load lock 0944D Figure 2 to Figure 4
and/or
0944T
Bolt, M20, length 260mm, c/w hex full nut 13370X Figure 4

Guy grip dead-end, 7/3.25mm 09532A Figure 2 to Figure 4


or 08233F
or
08245J
Guy grip dead-end, 7/4.00mm 09354U, Figure 2 to Figure 4
09532A,
08233F or
08245J
Insulator, stay, LV, ENA TS type 1, 110kN MFL 08911W Figure 2 to Figure 4
Pole-top make-off, 7/3.25mm 08237U Figure 2 to Figure 4
or 08244Y
Pole-top make-off, 7/4.00mm 08237U Figure 2 to Figure 4
March 2011

or 08244Y
Stay wire, 7/3.25mm, 1150 grade 08316A or Figure 2 to Figure 4
13816S
Steelwork, thimble, stay, type 1 09924P Figure 2 to Figure 4
Staples, wire Figure 2 to Figure 4
Stay marker 13818M Figure 2 to Figure 4
Steelwork, stay plate, heavy duty TBA Figure 4

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 64


  Overhead Line Design Manual

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 65
Overhead Line Design Manual
 

6.16 Appendix F – Design Data for Conductor ABC, 4 x 120mm2


Table 6: Conductor ABC, 4 x 120mm2: Design Data Summary

Recommended Span = 50m.


A maximum span of 90m is allowed.
A FoS value of 2.5 is used on stays, wind-span, foundation and single pole strut
loading capabilities.

In Line Structures Existing

Drawing Support Type Support Class Support Max Based on medium


No Size Span
Refer to Intermediate or Section Medium <12m 90m 9m 87m
Figure 5 Medium 12m only 83m 10m 78m
to Medium >12m 90m
Figure 7 11m 69m
Stout Any 90m
12m 62m
13m 55m

Angle Structures

Drawing Support Type Support Support Max Line Min Stay Angle Max
No Class Size Deviation Span
Heavy Light
Ref to 6.6 Stays
o
Refer to Intermediate Medium Any 30 1 x 40o 1 x 40o 90m
Figure 5 Angle Stout <14m 30o 1 x 20o 1 x 25o 90m
to
Figure 8 Intermediate Medium Any 45o 1 x 45o 1 x 45o 90m
Heavy Angle Medium <11m 60o 1 x 45o 1 x 45o 90m
Stout Any 60o 1 x 40o 1 x 40o 90m
Stout <12m 60o 1 x 25o 2 x 20o 90m
Section Angle Medium <11m 60o 1 x 45o 1 x 45o 90m
Stout Any 60o 1 x 40o 1 x 40o 90m
Stout <12m 60o 1 x 25o 2 x 25o 90m
Medium 9m only 90o 1 x 45o 1 x 45o 90m
Stout <14m 90o 1 x 30o 2 x 30o 90m
Stout 9m only 90o 2 x 20o 2 x 25o 90m

Terminal Structures

Drawing Support Type Support Support Size Min Stay Angle Max
No Class Span
March 2011

Heavy Light
o
Refer to Tee off Medium <11m 1 x 45 1 x 45o 90m
Figure 9 or Stout Any 1 x 45o 1 x 45o 90m
& Terminal Stout <12m 2 x 30o 2 x 30o 90m
Figure 10

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 66


  Overhead Line Design Manual
Table 7: Conductor ABC, 4 x 120mm2: Design Sag/Tension

120 mm² 4 core LV ABC


380N/mm² wind – 4.75mm radial ice – EDS limit (1000/2.62) x conductor mass
at 10°C – basic span 50m

Temp Tension Design Sag (m) for Span Length (m)


(°C) (kgf)
10 20 30 40 50 60 70 80 90

-5.6 793.9 0.03 0.10 0.23 0.40 0.63 0.91 1.23 1.61 2.04
0 714.2 0.03 0.11 0.25 0.45 0.70 1.01 1.37 1.79 2.27
5 657.4 0.03 0.12 0.27 0.49 0.76 1.10 1.49 1.95 2.46
10 610.7 0.03 0.13 0.29 0.52 0.82 1.18 1.60 2.10 2.65
15 571.7 0.03 0.14 0.31 0.56 0.87 1.26 1.71 2.24 2.83
20 538.7 0.04 0.15 0.33 0.59 0.93 1.34 1.82 2.38 3.01
25 510.4 0.04 0.16 0.35 0.63 0.98 1.41 1.92 2.51 3.17
30 485.9 0.04 0.16 0.37 0.66 1.03 1.48 2.02 2.63 3.33
35 464.4 0.04 0.17 0.39 0.69 1.08 1.55 2.11 2.76 3.49
40 445.3 0.04 0.18 0.40 0.72 1.12 1.62 2.20 2.87 3.64
45 428.3 0.05 0.19 0.42 0.75 1.17 1.68 2.29 2.99 3.78
50 413.1 0.05 0.19 0.44 0.77 1.21 1.74 2.37 3.10 3.92
55 399.3 0.05 0.20 0.45 0.80 1.25 1.80 2.45 3.21 4.06
60 386.7 0.05 0.21 0.47 0.83 1.29 1.86 2.53 3.31 4.19
65 375.2 0.05 0.21 0.48 0.85 1.33 1.92 2.61 3.41 4.32
70 364.7 0.05 0.22 0.49 0.88 1.37 1.97 2.69 3.51 4.44
75 354.9 0.06 0.23 0.51 0.90 1.41 2.03 2.76 3.61 4.56
80 345.9 0.06 0.23 0.52 0.93 1.45 2.08 2.83 3.70 4.68

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 67
Overhead Line Design Manual
 

Table 8: Conductor, ABC, 4 x 120mm2: Pole Data (Ground Good/Average)

Lengt Grade Top Dia 1.5m Planting Single pole Maximum


h (m) dia from butt depth strut strength wind load
(mm) (mm) (mm) (kgf) span (m)
9 Medium 150 220 1800 7308 112
10 Medium 150 230 1800 6077 101
11 Medium 150 240 1800 5201 92
12 Medium 150 250 1800 4550 83
13 Medium 160 260 2400 5000 139
14 Medium 160 275 2400 4624 150
9 Stout 190 275 1800 18368 140
10 Stout 190 285 1800 15030 125
11 Stout 190 295 1800 12662 112
12 Stout 190 305 1800 10915 101
13 Stout 195 320 2400 11227 266
14 Stout 195 335 2400 10192 252

Table 9: Conductor, ABC, 4 x 120mm2: Single Pole Stay Capability

Maximum angle of line deviation for stated stay type and angle of stay slope

Angle of stay Grade 1150 Grade 1150 Grade 1150 Grade 1150
slope
1 x 7/3.25 2 x 7/3.25 1 x 7/4.00 2 x 7/4.00

20º 27º 63º 51º 90º


25º 37º 90º 68º 90º
30º 47º 90º 86º 90º
35º 56º 90º 90º 90º
40º 66º 90º 90º 90º
45º 75º 90º 90º 90º
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 68


  Overhead Line Design Manual
Table 10: Conductor, ABC, 4 x 120mm2: Single Pole Strut Loading (Level Conditions)

Strut load in pole with one or two stays (kgf)

Line Angle Stay Angle (Degrees)


(Degrees)

20 25 30 35 40 45

Level
Conditions

0 2439 2031 1752 1547 1387 1257


5 3240 2657 2257 1963 1735 1549
10 4037 3279 2760 2378 2080 1839
15 4829 3897 3259 2789 2424 2127
20 5614 4509 3754 3197 2764 2413
25 6390 5116 4243 3601 3101 2696
30 7157 5714 4727 3999 3434 2975
35 7912 6303 5203 4392 3761 3250
40 8655 6883 5671 4778 4083 3520
45 9383 7451 6130 5156 4399 3785
50 10096 8008 6579 5527 4708 4044
55 10792 8551 7018 5889 5010 4297
60 11469 9080 7445 6241 5304 4544
65 12127 9593 7860 6583 5589 4784
70 12764 10090 8262 6914 5866 5015
75 13379 10571 8649 7234 6133 5239
80 13971 11033 9022 7541 6389 5455
85 14539 11476 9380 7836 6636 5661
90 15081 11899 9722 8118 6871 5859
August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 69
Overhead Line Design Manual
 

Table 11: Conductor, ABC, 4 x 120mm2: Single Pole Strut Loading (1:10 Downpull
Conditions)

Strut load in pole with one or two stays (kgf)

Line Angle Stay Angle (Degrees)


(Degrees)

20 25 30 35 40 45

Downpull 1:10

0 3105 2697 2418 2213 2053 1924


5 3906 3323 2924 2629 2401 2215
10 4703 3945 3426 3044 2746 2505
15 5495 4563 3925 3455 3090 2793
20 6280 5176 4420 3863 3430 3079
25 7057 5782 4910 4267 3767 3362
30 7823 6380 5393 4665 4100 3641
35 8578 6970 5869 5058 4427 3916
40 9321 7549 6337 5444 4749 4186
45 10049 8117 6796 5823 5065 4451
50 10762 8674 7245 6193 5374 4710
55 11458 9217 7684 6555 5676 4964
60 12135 9746 8111 6907 5970 5210
65 12793 10259 8526 7249 6255 5450
70 13430 10757 8928 7580 6532 5682
75 14045 11237 9315 7900 6799 5905
80 14637 11699 9689 8207 7055 6121
85 15205 12142 10046 8503 7302 6327
90 15747 12565 10388 8784 7537 6525
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 70


  Overhead Line Design Manual

6.17 Appendix G – Design Data for Conductor, ABC, 4 x 95mm2


Table 12: Conductor, ABC, 4 x 95mm2: Design Data Summary

Recommended Span = 50m.


A maximum span of 90m is allowed.
A FOS value of 2.5 is used on stays, wind span, foundation and single pole
strut loading capabilities.

In Line Structures Existing

Drawing Support Type Support Support Max Based on


No Class Size Span medium
Refer to Intermediate or Section Medium <12m 90m 9m 87m
Figure 5 Medium 12m only 88m 10m 78m
to Medium >12m 90m
Figure 7 11m 69m
Stout Any 90m
12m 62m
13m 55m

Angle Structures

Drawing Support Type Support Support Max Line Min Stay Angle Max
No Class Size Deviation Span
Heavy Light
Ref to 6.6 Stays
°
Refer to Intermediate Medium Any 30 1 x 35o 1 x 35o 90m
Figure 5 Angle Stout <14m 30o 1 x 20o 1 x 20o 90m
to
Figure 8 Intermediate Medium Any 55o 1 x 45o 1 x 45o 90m
Heavy Angle Medium <14m 60o 1 x 45o 1 x 45o 90m
Stout Any 60o 1 x 30o 1 x 35o 90m
Stout <14m 60o 1 x 20o 1 x 35o 90m
Section Angle Medium <14m 60o 1 x 45o 1 x 45o 90m
Stout Any 60o 1 x 30o 1 x 35o 90m
Stout <14m 60o 1 x 20o 1 x 35o 90m
Medium <11m 90o 1 x 45o 1 x 45o 90m
Stout Any 90o 1 x 45o 1 x 45o 90m
Stout <11m 90o 2 x 20o 1 x 45o 90m

Terminal Structures
August 2012

Drawing Support Type Support Support Size Min Stay Angle Max
No Class Span
Heavy Light
o
Refer to Tee off Medium <14m 1 x 45 1 x 45o 90m
Figure 9 or Stout Any 1 x 45o 1 x 45o 90m
& Terminal Stout <14m 2 x 25o 1 x 45o 90m
Figure 10

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 71
Overhead Line Design Manual
 

Table 13: Conductor, ABC, 4 x 95mm2: Design Sag/Tension

95 mm² 4 core LV ABC


380N/mm² wind – 4.75mm radial ice – EDS limit (1000/2.62) x conductor mass
at 10°C – basic span 50m

Temp Tension Design Sag (m) for Span Length (m)


(°C) (kgf)
10 20 30 40 50 60 70 80 90

-5.6 644.1 0.03 0.10 0.23 0.40 0.63 0.91 1.24 1.61 2.04
0 579.8 0.03 0.11 0.25 0.45 0.70 1.01 1.37 1.79 2.27
5 534.0 0.03 0.12 0.27 0.49 0.76 1.10 1.49 1.95 2.47
10 496.2 0.03 0.13 0.29 0.52 0.82 1.18 1.60 2.10 2.65
15 464.6 0.03 0.14 0.31 0.56 0.87 1.26 1.71 2.24 2.83
20 437.9 0.04 0.15 0.33 0.59 0.93 1.34 1.82 2.38 3.01
25 414.9 0.04 0.16 0.35 0.63 0.98 1.41 1.92 2.51 3.17
30 395.0 0.04 0.16 0.37 0.66 1.03 1.48 2.02 2.63 3.33
35 377.5 0.04 0.17 0.39 0.69 1.08 1.55 2.11 2.75 3.49
40 362.0 0.04 0.18 0.40 0.72 1.12 1.62 2.20 2.87 3.64
45 348.2 0.05 0.19 0.42 0.75 1.17 1.68 2.29 2.99 3.78
50 335.8 0.05 0.19 0.44 0.77 1.21 1.74 2.37 3.10 3.92
55 324.6 0.05 0.20 0.45 0.80 1.25 1.80 2.45 3.20 4.06
60 314.4 0.05 0.21 0.47 0.83 1.29 1.86 2.53 3.31 4.19
65 305.0 0.05 0.21 0.48 0.85 1.33 1.92 2.61 3.41 4.32
70 296.5 0.05 0.22 0.49 0.88 1.37 1.97 2.69 3.51 4.44
75 288.5 0.06 0.23 0.51 0.90 1.41 2.03 2.76 3.60 4.56
80 281.2 0.06 0.23 0.52 0.92 1.44 2.08 2.83 3.70 4.68
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 72


  Overhead Line Design Manual
Table 14: Conductor, ABC, 4 x 95mm2: Pole Data (Ground Good/Average)

Lengt Grade Top Dia 1.5m Planting Single pole Maximum


h (m) dia from butt depth strut strength wind load
(mm) (mm) (mm) (kgf) span (m)
9 Medium 150 220 1800 7308 119
10 Medium 150 230 1800 6077 107
11 Medium 150 240 1800 5201 97
12 Medium 150 250 1800 4550 88
13 Medium 160 260 2400 5000 148
14 Medium 160 275 2400 4624 159
9 Stout 190 275 1800 18368 148
10 Stout 190 285 1800 15030 133
11 Stout 190 295 1800 12662 119
12 Stout 190 305 1800 10915 107
13 Stout 195 320 2400 11227 282
14 Stout 195 335 2400 10192 268

Table 15: Conductor, ABC, 4 x 95mm2: Single Pole Stay Capability

Maximum angle of line deviation for stated stay type and angle of stay slope

Angle of stay Grade 1150 Grade 1150 Grade 1150 Grade 1150
slope
1x7/3.25 2 x 7/3.25 1x7/4.00 2x7/4.00

20º 32º 76º 61º 90º


25º 44º 90º 82º 90º
30º 56º 90º 90º 90º
35º 68º 90º 90º 90º
40º 80º 90º 90º 90º
45º 90º 90º 90º 90º August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 73
Overhead Line Design Manual
 

Table 16: Conductor, ABC, 4 x 95mm2: Single Pole Strut Loading (Level Conditions)

Strut load in pole with one or two stays (kgf)

Line Angle Stay Angle (Degrees)


(Degrees)

20 25 30 35 40 45

Level
Conditions

0 2280 1888 1620 1422 1269 1144


5 2969 2426 2054 1781 1568 1395
10 3655 2961 2487 2137 1865 1645
15 4336 3493 2916 2491 2161 1892
20 5011 4020 3342 2842 2453 2138
25 5678 4541 3762 3189 2743 2381
30 6337 5055 4178 3531 3029 2621
35 6986 5561 4587 3869 3310 2857
40 7624 6059 4989 4200 3587 3089
45 8249 6547 5383 4525 3858 3317
50 8861 7024 5768 4843 4123 3539
55 9457 7490 6145 5153 4382 3756
60 10038 7944 6511 5455 4634 3968
65 10602 8384 6867 5748 4879 4173
70 11148 8810 7211 6032 5115 4372
75 11675 9221 7543 6306 5344 4564
80 12182 9617 7862 6569 5564 4748
85 12668 9996 8168 6822 5774 4925
90 13131 10358 8461 7063 5976 5094
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 74


  Overhead Line Design Manual
Table 17: Conductor, ABC, 4 x 95mm2: Single Pole Strut Loading (1:10 Downpull
Conditions)

Strut load in pole with one or two stays (kgf)

Line Angle Stay Angle (Degrees)


(Degrees)

20 25 30 35 40 45

Downpull 1:10

0 2853 2461 2193 1996 1842 1717


5 3543 2999 2628 2354 2141 1968
10 4228 3535 3060 2710 2439 2218
15 4909 4066 3489 3064 2734 2466
20 5584 4593 3915 3415 3027 2711
25 6252 5114 4336 3762 3316 2954
30 6911 5628 4751 4105 3602 3194
35 7559 6135 5160 4442 3883 3430
40 8197 6632 5562 4773 4160 3662
45 8822 7120 5956 5098 4431 3890
50 9434 7598 6342 5416 4696 4112
55 10031 8064 6718 5727 4955 4330
60 10612 8517 7084 6029 5207 4541
65 11176 8957 7440 6322 5452 4746
70 11722 9383 7784 6606 5689 4945
75 12249 9795 8116 6879 5917 5137
80 12755 10190 8436 7143 6137 5321
85 13241 10569 8742 7395 6348 5498
90 13705 10931 9034 7636 6549 5667
August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 75
Overhead Line Design Manual
 

6.18 Appendix H – Design Data for Conductor, ABC, 2 x 95mm2


Table 18: Conductor, ABC, 2 x 95mm2: Design Data Summary

Recommended Span = 50m.


A maximum span of 90m is allowed.
A FOS value of 2.5 is used on stays, windspan, foundation and single pole
strut loading capabilities.

In Line Structures

Drawing Support Type Support Class Support Size Max Span


No
Refer to Intermediate or Medium Any 90m
Figure 5 Section Stout Any 90m
to
Figure 7

Angle Structures

Drawing Support Type Support Support Max Line Min Stay Angle Max
No Class Size Deviation Span
Heavy Light
Ref to 6.6 Stays
Refer to Intermediate Medium Any 30o 1 x 20o 1 x 20o 90m
Figure 5 Angle Stout Any 30o 1 x 20o 1 x 20o 90m
to
Figure 8 Intermediate Medium Any 60o 1 x 25o 1 x 25o 90m
Heavy Angle Stout Any 60o 1 x 20o 1 x 20o 90m
Section Angle Medium Any 60o 1 x 25o 1 x 25o 90m
Stout Any 60o 1 x 20o 1 x 20o 90m
Medium Any 90o 1 x 30o 1 x 30o 90m
Stout <14m 90o 1 x 20o 1 x 25o 90m

Terminal Structures

Drawing Support Type Support Support Size Min Stay Angle Max
No Class Span
Heavy Light
o
Refer to Tee off Medium Any 1 x 30 1 x 30o 90m
Figure 9 or Stout Any 1 x 25o 1 x 25o 90m
& Terminal
Figure 10
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 76


  Overhead Line Design Manual
Table 19: Conductor, ABC, 2 x 95mm2: Design Sag/Tension

95 mm² 2 core LV ABC


380N/mm² wind – 4.75mm radial ice – EDS limit (1000/3.86) x conductor mass
at 10°C – basic span 50m

Temp Tension Design Sag (m) for Span Length (m)


(°C) (kgf)
10 20 30 40 50 60 70 80 90

-5.6 190.5 0.04 0.17 0.38 0.68 1.07 1.54 2.09 2.73 3.45
0 181.7 0.04 0.18 0.40 0.72 1.12 1.61 2.19 2.86 3.62
5 174.7 0.05 0.19 0.42 0.74 1.16 1.67 2.28 2.98 3.77
10 168.4 0.05 0.19 0.43 0.77 1.21 1.74 2.36 3.09 3.91
15 162.8 0.05 0.20 0.45 0.80 1.25 1.80 2.45 3.19 4.04
20 157.6 0.05 0.21 0.46 0.82 1.29 1.86 2.53 3.30 4.18
25 152.9 0.05 0.21 0.48 0.85 1.33 1.91 2.60 3.40 4.30
30 148.6 0.05 0.22 0.49 0.87 1.37 1.97 2.68 3.50 4.43
35 144.6 0.06 0.22 0.51 0.90 1.40 2.02 2.75 3.60 4.55
40 140.9 0.06 0.23 0.52 0.92 1.44 2.08 2.82 3.69 4.67
45 137.5 0.06 0.24 0.53 0.95 1.48 2.13 2.90 3.78 4.79
50 134.3 0.06 0.24 0.54 0.97 1.51 2.18 2.96 3.87 4.90
55 131.3 0.06 0.25 0.56 0.99 1.55 2.23 3.03 3.96 5.01
60 128.5 0.06 0.25 0.57 1.01 1.58 2.28 3.10 4.05 5.12
65 125.9 0.06 0.26 0.58 1.03 1.61 2.32 3.16 4.13 5.23
70 123.4 0.07 0.26 0.59 1.05 1.65 2.37 3.23 4.21 5.33
75 121.1 0.07 0.27 0.60 1.07 1.68 2.42 3.29 4.30 5.44
80 118.9 0.07 0.27 0.62 1.09 1.71 2.46 3.35 4.38 5.54

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 77
Overhead Line Design Manual
 

Table 20: Conductor, ABC, 2 x 95mm2: Pole Data (Ground Good/Average)

Length Grade Top Dia 1.5m Planting Single pole Maximum


(m) dia from butt depth strut strength wind load
(mm) (mm) (mm) (kgf) span (m)
9 Medium 150 220 1800 7308 171
10 Medium 150 230 1800 6077 154
11 Medium 150 240 1800 5201 140
12 Medium 150 250 1800 4550 127
13 Medium 160 260 2400 5000 206
14 Medium 160 275 2400 4624 196
9 Stout 190 275 1800 18368 213
10 Stout 190 285 1800 15030 190
11 Stout 190 295 1800 12662 171
12 Stout 190 305 1800 10915 154
13 Stout 195 320 2400 11227 254
14 Stout 195 335 2400 10192 239

Table 21: Conductor, ABC, 2 x 95mm2: Single Pole Stay Capability

Maximum angle of line deviation for stated stay type and angle of stay slope

Angle of stay Grade 1150 Grade 1150 Grade 1150 Grade 1150
slope
1x7/3.25 2 x 7/3.25 1x7/4.00 2x7/4.00

20º 89º 90º 90º 90º


25º 90º 90º 90º 90º
30º 90º 90º 90º 90º
35º 90º 90º 90º 90º
40º 90º 90º 90º 90º
45º 90º 90º 90º 90º
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 78


  Overhead Line Design Manual
Table 22: Conductor, ABC, 2 x 95mm2: Single Pole Strut Loading (Level Conditions)

Strut load in pole with one or two stays (kgf)

Line Angle Stay Angle (Degrees)


(Degrees)

20 25 30 35 40 45

Level
Conditions

0 1687 1372 1157 999 876 776


5 1998 1615 1354 1161 1011 889
10 2307 1857 1549 1322 1145 1002
15 2614 2096 1742 1481 1278 1113
20 2917 2333 1933 1639 1410 1224
25 3216 2566 2122 1794 1539 1333
30 3511 2797 2308 1947 1667 1440
35 3801 3023 2490 2098 1793 1545
40 4086 3245 2670 2246 1916 1649
45 4364 3462 2845 2391 2037 1750
50 4635 3674 3016 2532 2155 1849
55 4900 3880 3183 2669 2269 1945
60 5156 4081 3345 2803 2381 2039
65 5405 4275 3501 2932 2489 2129
70 5645 4462 3653 3056 2593 2216
75 5876 4642 3798 3176 2693 2300
80 6097 4815 3938 3291 2789 2381
85 6308 4980 4071 3401 2880 2458
90 6509 5137 4198 3506 2968 2531
August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 79
Overhead Line Design Manual
 

Table 23: Conductor, ABC, 2 x 95mm2: Single Pole Strut Loading (1:10 Downpull
Conditions)

Strut load in pole with one or two stays (kgf)

Line Angle Stay Angle (Degrees)


(Degrees)

20 25 30 35 40 45

Downpull 1:10

0 1946 1632 1417 1258 1135 1035


5 2257 1875 1613 1420 1270 1148
10 2567 2116 1808 1581 1404 1261
15 2873 2355 2001 1740 1537 1373
20 3176 2592 2192 1898 1669 1483
25 3476 2826 2381 2053 1799 1592
30 3771 3056 2567 2207 1927 1699
35 4060 3282 2750 2357 2052 1805
40 4345 3504 2929 2505 2176 1908
45 4623 3721 3104 2650 2296 2009
50 4894 3933 3275 2791 2414 2108
55 5159 4139 3442 2928 2529 2204
60 5416 4340 3604 3062 2640 2298
65 5664 4534 3761 3191 2748 2388
70 5904 4721 3912 3316 2852 2476
75 6135 4901 4057 3436 2952 2560
80 6356 5074 4197 3551 3048 2640
85 6567 5239 4330 3661 3140 2717
90 6768 5396 4457 3765 3227 2790
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 80


  Overhead Line Design Manual

6.19 Appendix I – Design Data for Conductor, ABC, 4 x 35mm2


Table 24: Conductor, ABC, 4 x 35mm2: Design Data Summary

Recommended Span = 70m.


A maximum span of 70m is allowed.
A FOS value of 2.5 is used on stays, windspan, foundation and single pole
strut loading capabilities.

In Line Structures

Drawing No Support Type Support Class Support Size Max Span


Refer to Intermediate or Medium Any 70m
Figure 5 Section Stout Any 70m
to
Figure 7

Angle Structures

Drawing No Support Type Support Support Max Line Min Stay Angle Max
Class Size Deviation Span
Heavy Light
Ref to 6.6 Stays
Refer to Intermediate Medium Any 30o 1 x 20o 1 x 20o 70m
Figure 5 Angle Stout Any 30o 1 x 20o 1 x 20o 70m
to
Figure 8 Intermediate Medium Any 60o 1 x 20o 1 x 20o 70m
Heavy Angle Stout Any 60o 1 x 20o 1 x 20o 70m
Section Angle Medium Any 60o 1 x 20o 1 x 20o 70m
Stout Any 60o 1 x 20o 1 x 20o 70m
Medium Any 90o 1 x 20o 1 x 25o 70m
Stout Any 90o 1 x 20o 1 x 20o 70m

Terminal Structures

Drawing No Support Type Support Support Size Min Stay Angle Max
Class Span
Heavy Light
Refer to Tee off Medium Any 1 x 20o 1 x 20o 70m
Figure 9 or Stout Any 1 x 20o 1 x 20o 70m
& Terminal
Figure 10
August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 81
Overhead Line Design Manual
 

Table 25: Conductor, ABC, 4 x 35mm2: Design Sag/Tension

35 mm² 4 core LV ABC


380N/mm² wind – 4.75mm radial ice – EDS limit (1000/4.87) x conductor mass
at 10°C – basic span 70m

Temp Tension Design Sag (m) for Span Length (m)


(°C) (kgf)
10 20 30 40 50 60 70

-5.6 111.0 0.06 0.23 0.53 0.94 1.46 2.11 2.87


0 109.5 0.06 0.24 0.53 0.95 1.48 2.14 2.91
5 108.1 0.06 0.24 0.54 0.96 1.50 2.16 2.95
10 106.9 0.06 0.24 0.55 0.97 1.52 2.19 2.98
15 105.6 0.06 0.25 0.55 0.98 1.54 2.22 3.02
20 104.4 0.06 0.25 0.56 1.00 1.56 2.24 3.05
25 103.3 0.06 0.25 0.57 1.01 1.57 2.27 3.08
30 102.2 0.06 0.25 0.57 1.02 1.59 2.29 3.12
35 101.1 0.06 0.26 0.58 1.03 1.61 2.31 3.15
40 100.0 0.06 0.26 0.58 1.04 1.62 2.34 3.18
45 99.0 0.07 0.26 0.59 1.05 1.64 2.36 3.22
50 98.0 0.07 0.27 0.60 1.06 1.66 2.39 3.25
55 97.1 0.07 0.27 0.60 1.07 1.67 2.41 3.28
60 96.1 0.07 0.27 0.61 1.08 1.69 2.43 3.31
65 95.2 0.07 0.27 0.61 1.09 1.71 2.46 3.34
70 94.4 0.07 0.28 0.62 1.10 1.72 2.48 3.38
75 93.5 0.07 0.28 0.63 1.11 1.74 2.50 3.41
80 92.7 0.07 0.28 0.63 1.12 1.75 2.52 3.44
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 82


  Overhead Line Design Manual
Table 26: Conductor, ABC, 4 x 35mm2: Pole Data (Ground Good/Average)

Lengt Grade Top Dia 1.5m Planting Single pole Maximum


h (m) dia from butt depth strut strength wind load
(mm) (mm) (mm) (kgf) span (m)
9 Medium 150 220 1800 7308 163
10 Medium 150 230 1800 6077 147
11 Medium 150 240 1800 5201 133
12 Medium 150 250 1800 4550 121
13 Medium 160 260 2400 5000 197
14 Medium 160 275 2400 4624 187
9 Stout 190 275 1800 18368 203
10 Stout 190 285 1800 15030 181
11 Stout 190 295 1800 12662 163
12 Stout 190 305 1800 10915 147
13 Stout 195 320 2400 11227 242
14 Stout 195 335 2400 10192 228

Table 27: Conductor, ABC, 4 x 35mm2: Single Pole Stay Capability

Maximum angle of line deviation for stated stay type and angle of stay slope

Angle of stay Grade 1150 Grade 1150 Grade 1150 Grade 1150
slope
1x7/3.25 2 x 7/3.25 1x7/4.00 2x7/4.00

20º 90º 90º 90º 90º


25º 90º 90º 90º 90º
30º 90º 90º 90º 90º
35º 90º 90º 90º 90º
40º 90º 90º 90º 90º
45º 90º 90º 90º 90º August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 83
Overhead Line Design Manual
 

Table 28: Conductor, ABC, 4 x 35mm2: Single Pole Strut Loading (Level Conditions)

Strut load in pole with one or two stays (kgf)

Line Angle Stay Angle (Degrees)


(Degrees)

20 25 30 35 40 45

Level
Conditions

0 1470 1188 996 854 744 654


5 1686 1357 1132 967 838 733
10 1901 1525 1268 1078 931 811
15 2113 1690 1401 1188 1023 888
20 2323 1854 1534 1298 1114 965
25 2530 2016 1664 1405 1204 1040
30 2734 2175 1793 1511 1292 1114
35 2934 2331 1919 1615 1379 1187
40 3130 2484 2043 1717 1464 1259
45 3322 2634 2163 1817 1547 1328
50 3508 2780 2281 1914 1628 1396
55 3690 2921 2396 2008 1707 1463
60 3866 3059 2507 2100 1783 1527
65 4037 3192 2614 2188 1857 1589
70 4201 3320 2718 2274 1928 1648
75 4359 3443 2817 2356 1997 1706
80 4510 3561 2912 2434 2062 1761
85 4654 3673 3003 2509 2125 1813
90 4790 3780 3089 2580 2184 1863
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 84


  Overhead Line Design Manual
Table 29: Conductor, ABC, 4 x 35mm2: Single Pole Strut Loading (1:10 Downpull
Conditions)

Strut load in pole with one or two stays (kgf)

Line Angle Stay Angle (Degrees)


(Degrees)

20 25 30 35 40 45

Downpull 1:10

0 1650 1368 1176 1034 924 834


5 1866 1537 1312 1147 1018 913
10 2081 1705 1448 1258 1111 991
15 2293 1871 1581 1369 1203 1069
20 2503 2034 1714 1478 1294 1145
25 2710 2196 1844 1585 1384 1220
30 2914 2355 1973 1691 1472 1294
35 3114 2511 2099 1795 1559 1367
40 3310 2664 2223 1897 1644 1439
45 3502 2814 2343 1997 1727 1508
50 3688 2960 2461 2094 1808 1576
55 3870 3101 2576 2188 1887 1643
60 4046 3239 2687 2280 1963 1707
65 4217 3372 2794 2368 2037 1769
70 4381 3500 2898 2454 2109 1828
75 4539 3623 2997 2536 2177 1886
80 4690 3741 3092 2614 2242 1941
85 4834 3853 3183 2689 2305 1993
90 4970 3960 3269 2760 2364 2043
August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 85
Overhead Line Design Manual
 

6.20 Appendix J – Design Data for Conductor, ABC, 2 x 35mm2


Table 30: Conductor, ABC, 2 x 35mm2: Design Data Summary

Recommended Span = 70m.


A maximum span of 70m is allowed.
A FOS value of 2.5 is used on stays, windspan, foundation and single pole
strut loading capabilities.

In Line Structures

Drawing No Support Type Support Class Support Size Max Span


Refer to Intermediate or Medium Any 70m
Figure 5 Section Stout Any 70m
to
Figure 7

Angle Structures

Drawing No Support Type Support Support Max Line Min Stay Angle Max
Class Size Deviation Span
Heavy Light
Ref to 6.6 Stays
o
Refer to Intermediate Medium Any 30 1 x 20o 1 x 20o 70m
Figure 5 Angle Stout Any 30o 1 x 20o 1 x 20o 70m
to
Figure 8 Intermediate Medium Any 60o 1 x 20o 1 x 20o 70m
Heavy Angle Stout Any 60o 1 x 20o 1 x 20o 70m
Section Angle Medium Any 60o 1 x 20o 1 x 20o 70m
Stout Any 60o 1 x 20o 1 x 20o 70m
Medium Any 90o 1 x 20o 1 x 20o 70m
Stout Any 90o 1 x 20o 1 x 20o 70m
Terminal Structures
Drawing No Support Type Support Support Size Min Stay Angle Max
Class Span
Heavy Light
o
Refer to Tee off Medium Any 1 x 20 1 x 20o 70m
Figure 9 or Stout Any 1 x 20o 1 x 20o 70m
& Terminal
Figure 10
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 86


  Overhead Line Design Manual
Table 31: Conductor, ABC, 2 x 35mm2: Design Sag/Tension

35 mm² 2 core LV ABC


380N/mm² wind – 4.75mm radial ice – EDS limit (1000/4.87) x conductor mass
at 10°C – basic span 70m

Temp Tension Design Sag (m) for Span Length (m)


(°C) (kgf)
10 20 30 40 50 60 70

-5.6 55.4 0.06 0.23 0.53 0.94 1.47 2.11 2.88


0 54.6 0.06 0.24 0.54 0.95 1.49 2.14 2.92
5 53.9 0.06 0.24 0.54 0.96 1.51 2.17 2.95
10 53.3 0.06 0.24 0.55 0.98 1.52 2.20 2.99
15 52.7 0.06 0.25 0.56 0.99 1.54 2.22 3.02
20 52.1 0.06 0.25 0.56 1.00 1.56 2.25 3.06
25 51.5 0.06 0.25 0.57 1.01 1.58 2.27 3.09
30 51.0 0.06 0.26 0.57 1.02 1.59 2.30 3.12
35 50.4 0.06 0.26 0.58 1.03 1.61 2.32 3.16
40 49.9 0.07 0.26 0.59 1.04 1.63 2.34 3.19
45 49.4 0.07 0.26 0.59 1.05 1.64 2.37 3.22
50 48.9 0.07 0.27 0.60 1.06 1.66 2.39 3.26
55 48.4 0.07 0.27 0.60 1.07 1.68 2.42 3.29
60 48.0 0.07 0.27 0.61 1.08 1.69 2.44 3.32
65 47.5 0.07 0.27 0.62 1.09 1.71 2.46 3.35
70 47.1 0.07 0.28 0.62 1.10 1.73 2.48 3.38
75 46.7 0.07 0.28 0.63 1.11 1.74 2.51 3.41
80 46.3 0.07 0.28 0.63 1.12 1.76 2.53 3.44

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 87
Overhead Line Design Manual
 

Table 32: Conductor, ABC, 2 x 35mm2: Pole Data (Ground Good/Average)

Lengt Grade Top Dia 1.5m Planting Single pole Maximum


h (m) dia from butt depth strut strength wind load
(mm) (mm) (mm) (kgf) span (m)
9 Medium 150 220 1800 7308 224
10 Medium 150 230 1800 6077 202
11 Medium 150 240 1800 5201 183
12 Medium 150 250 1800 4550 167
13 Medium 160 260 2400 5000 271
14 Medium 160 275 2400 4624 258
9 Stout 190 275 1800 18368 280
10 Stout 190 285 1800 15030 250
11 Stout 190 295 1800 12662 225
12 Stout 190 305 1800 10915 203
13 Stout 195 320 2400 11227 334
14 Stout 195 335 2400 10192 314

Table 33: Conductor, ABC, 2 x 35mm2: Single Pole Stay Capability

Maximum angle of line deviation for stated stay type and angle of stay slope

Angle of stay Grade 1150 Grade 1150 Grade 1150 Grade 1150
slope
1x7/3.25 2 x 7/3.25 1x7/4.00 2x7/4.00

20º 90º 90º 90º 90º


25º 90º 90º 90º 90º
30º 90º 90º 90º 90º
35º 90º 90º 90º 90º
40º 90º 90º 90º 90º
45º 90º 90º 90º 90º
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 88


  Overhead Line Design Manual
Table 34: Conductor, ABC, 2 x 35mm2: Single Pole Strut Loading (Level Conditions)

Strut load in pole with one or two stays (kgf)

Line Angle Stay Angle (Degrees)


(Degrees)

20 25 30 35 40 45

Level
Conditions

0 1204 962 797 675 581 504


5 1367 1089 900 760 651 563
10 1528 1216 1002 844 722 622
15 1689 1341 1103 928 791 681
20 1847 1465 1203 1010 860 738
25 2004 1587 1301 1091 928 795
30 2157 1707 1398 1171 994 851
35 2309 1825 1494 1250 1060 906
40 2457 1940 1587 1327 1124 960
45 2601 2053 1678 1402 1187 1013
50 2743 2163 1767 1475 1248 1064
55 2880 2271 1854 1547 1308 1114
60 3013 2375 1938 1616 1366 1163
65 3142 2475 2019 1683 1422 1210
70 3266 2572 2098 1748 1476 1255
75 3386 2666 2173 1810 1527 1298
80 3500 2755 2245 1869 1577 1340
85 3609 2840 2314 1926 1624 1380
90 3713 2921 2379 1980 1669 1417
August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 89
Overhead Line Design Manual
 

Table 35: Conductor, ABC, 2 x 35mm2: Single Pole Strut Loading (1:10 Downpull
Conditions)

Strut load in pole with one or two stays (kgf)

Line Angle Stay Angle (Degrees)


(Degrees)

20 25 30 35 40 45

Downpull 1:10

0 1339 1098 933 811 717 640


5 1502 1225 1036 896 787 699
10 1664 1352 1138 980 857 758
15 1825 1477 1239 1063 927 816
20 1983 1600 1339 1146 996 874
25 2139 1722 1437 1227 1064 931
30 2293 1842 1534 1307 1130 987
35 2444 1960 1629 1386 1196 1042
40 2592 2076 1723 1463 1260 1096
45 2737 2189 1814 1538 1323 1149
50 2878 2299 1903 1611 1384 1200
55 3016 2406 1990 1683 1444 1250
60 3149 2510 2074 1752 1502 1298
65 3278 2611 2155 1819 1557 1345
70 3402 2708 2233 1883 1611 1391
75 3522 2801 2309 1946 1663 1434
80 3636 2891 2381 2005 1713 1476
85 3745 2976 2449 2062 1760 1515
90 3849 3057 2515 2116 1805 1553
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 90


  Overhead Line Design Manual
6.21 Appendix K – Service Spans
Table 36: Conductor, ABC, 2 x 35mm2 or 4 x 35mm2

Conductor, ABC, 2 x 35mm2 or 4 x 35mm2


380N/mm² wind – 4.75mm radial ice – MWT limit 132.6 kgf under design
conditions – basic span 30m

Temp Tension Design Sag (m) for Span Length (m)


(°C) (kgf)
10 12.5 15 17.5 20 22.5 25 27.5 30

-5.6 * 0.16 0.26 0.37 0.50 0.65 0.83 1.02 1.24 1.47
0 * 0.17 0.26 0.37 0.51 0.66 0.84 1.03 1.25 1.49
5 * 0.17 0.26 0.38 0.51 0.67 0.84 1.04 1.26 1.50
10 * 0.17 0.26 0.38 0.51 0.67 0.85 1.05 1.27 1.51
15 * 0.17 0.26 0.38 0.52 0.68 0.86 1.06 1.28 1.53
20 * 0.17 0.27 0.38 0.52 0.68 0.87 1.07 1.29 1.54
25 * 0.17 0.27 0.39 0.53 0.69 0.87 1.08 1.30 1.55
30 * 0.17 0.27 0.39 0.53 0.69 0.88 1.09 1.31 1.56
35 * 0.18 0.27 0.39 0.54 0.70 0.89 1.09 1.32 1.58
40 * 0.18 0.28 0.40 0.54 0.71 0.89 1.10 1.33 1.59
45 * 0.18 0.28 0.40 0.54 0.71 0.90 1.11 1.34 1.60
50 * 0.18 0.28 0.40 0.55 0.72 0.91 1.12 1.35 1.61
55 * 0.18 0.28 0.41 0.55 0.72 0.91 1.13 1.36 1.62
60 * 0.18 0.28 0.41 0.56 0.73 0.92 1.14 1.37 1.64
65 * 0.18 0.29 0.41 0.56 0.73 0.93 1.14 1.38 1.65
70 * 0.18 0.29 0.41 0.56 0.74 0.93 1.15 1.39 1.66
75 * 0.19 0.29 0.42 0.57 0.74 0.94 1.16 1.40 1.67
80 * 0.19 0.29 0.42 0.57 0.75 0.95 1.17 1.41 1.68

* Note that sags are given for 2-core and 4-core ABC of the same conductor size, therefore tensions are
not given above; it is unlikely that a service span will be sagged using a dynamometer.
August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 91
Overhead Line Design Manual
 

Table 37: Conductor, ABC, 2 x 95mm2 or 4x95mm2

Conductor, ABC, 2x95mm2 or 4x95mm2


380N/mm² wind – 4.75mm radial ice – MWT limit 132.6 kgf under design
conditions – basic span 30m

Temp Tension Design Sag (m) for Span Length (m)


(oC) (kgf)
10 12.5 15 17.5 20 22.5 25 27.5 30

-5.6 * 0.27 0.43 0.61 0.84 1.09 1.38 1.71 2.06 2.46
0 * 0.27 0.43 0.62 0.84 1.10 1.39 1.71 2.07 2.46
5 * 0.27 0.43 0.62 0.84 1.10 1.39 1.72 2.08 2.47
10 * 0.28 0.43 0.62 0.84 1.10 1.40 1.72 2.08 2.48
15 * 0.28 0.43 0.62 0.85 1.11 1.40 1.73 2.09 2.49
20 * 0.28 0.43 0.62 0.85 1.11 1.40 1.73 2.10 2.50
25 * 0.28 0.43 0.63 0.85 1.11 1.41 1.74 2.10 2.50
30 * 0.28 0.44 0.63 0.85 1.12 1.41 1.74 2.11 2.51
35 * 0.28 0.44 0.63 0.86 1.12 1.42 1.75 2.12 2.52
40 * 0.28 0.44 0.63 0.86 1.12 1.42 1.75 2.12 2.53
45 * 0.28 0.44 0.63 0.86 1.13 1.43 1.76 2.13 2.53
50 * 0.28 0.44 0.64 0.87 1.13 1.43 1.77 2.14 2.54
55 * 0.28 0.44 0.64 0.87 1.13 1.43 1.77 2.14 2.55
60 * 0.28 0.44 0.64 0.87 1.14 1.44 1.78 2.15 2.56
65 * 0.29 0.45 0.64 0.87 1.14 1.44 1.78 2.16 2.57
70 * 0.29 0.45 0.64 0.88 1.14 1.45 1.79 2.16 2.57
75 * 0.29 0.45 0.65 0.88 1.15 1.45 1.79 2.17 2.58
80 * 0.29 0.45 0.65 0.88 1.15 1.46 1.80 2.17 2.59

* Note that sags are given for 2-core and 4-core ABC of the same conductor size, therefore tensions are
not given above; it is unlikely that a service span will be sagged using a dynamometer.
March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 92


  Overhead Line Design Manual
6.22 Appendix L – Un-stayed Supports
Table 38: In-line Support with Service Span Attachments

Note: the effect of the unbalanced loading imposed by a single service span attachment has been
converted to an equivalent addition to the actual wind loading span of the main line conductor. The
addition is shown in the table below.
The sum of the actual main line wind loading span and the addition is used to determine the required
pole size. The pole is selected from the appropriate main line conductor table.
It has been assumed that wind loading affects only the main line conductor; the service span being at
right angles to the main – the latter then having a MWT based on ice loading with no wind.

4x95mm2 service 4x35mm2 service 2x95mm2 service 2x35mm2 service

4x120mm2 main 50 m 41 m 26 m 23 m

4x95mm2 main 53 m 44 m 28 m 24 m

4x35mm2 main -- 59 m 38 m 33 m

2x95mm2 main -- -- 39 m 35 m

2x35mm2 main -- -- -- 45 m

Table 39: Angle Support with no Service Span Attachments (Medium Poles)

Note: un-stayed angle supports shall have one 1.3m foundation block fitted at 0.5 m below the ground
line. Permitted maximum line deviation angles have been calculated based on the worst case wind
loading span capability for medium or stout grades of pole, with pole top horizontal loadings due to
MWT and line deviation angle converted to an equivalent wind loading span.
Maximum angle of line deviation for stated lv abc main line conductor size on Medium poles for wind
loading spans:

Up to 40m 41m – 50m 51m – 60m 61m – 70m 71m – 80m 81m – 90m

4x95mm2 7º 7º 6º 5º 4º 3º
and
4x120mm2

4x35mm2 31º 29º 27º 25º ** **

2x95mm2 23º 22º 20º 19º 18º 16º

2x35mm2 46º 44º 42º 40º ** **


August 2012

Note: ** - not permitted

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 93
Overhead Line Design Manual
 

Table 40: Angle Support with no Service Span Attachments (Stout Poles)

Maximum angle of line deviation for stated lv abc main line conductor size on Stout poles for wind
loading spans:

Up to 40m 41m – 50m 51m – 60m 61m – 70m 71m – 80m 81m – 90m

4x95mm2 11º 10º 9º 8º 7º 7º


and
4x120mm2

4x35mm2 42º 40º 38º 36º ** **

2x95mm2 32º 31º 29º 28º 26º 25º

2x35mm2 62º 60º 58º 56º ** **

Note: ** - not permitted

Table 41: Angle Support with One Service Span Attachment (Medium Poles)

Note: un-stayed angle supports shall have one 1.3m foundation block fitted at 0.5 m below the ground
line. Permitted maximum line deviation angles have been calculated based on the worst case wind
loading span capability for medium or stout grades of pole, with pole top horizontal loadings due to
MWT and line deviation angle converted to an equivalent wind loading span. A single service span
attachment within the included angle of deviation is assumed.
Maximum angle of line deviation with one service span attachment for stated LV ABC main line
conductor size on Medium poles for wind loading spans:

Up to 40m 41m – 50m 51m – 60m 61m – 70m 71m – 80m 81m – 90m

4 x 95mm2 3º 2º 2º ** ** **
and
4 x 120mm2

4 x 35mm2 19º 17º 15º 13º ** **

2 x 95mm2 18º 16º 15º 13º 12º 11º

2 x 35mm2 37º 35º 33º 31º ** **

Note: ** - not permitted


March 2011

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 94


  Overhead Line Design Manual
Table 42: Angle Support with One Service Span Attachments (Stout Poles)
Maximum angle of line deviation with one service span attachment for stated LV ABC main line conductor size on Stout
poles for wind loading spans:

Up to 40m 41m – 50m 51m – 60m 61m – 70m 71m – 80m 81m – 90m

4 x 95mm2 7º 6º 5º 4º 3º 2º
and 4 x
120mm2

4 x 35mm2 31º 29º 27º 25º ** **

2 x 95mm2 26º 25º 24º 22º 21º 19º

2 x 35mm2 53º 51º 49º 47º ** **

Note: ** - not permitted

6.23 Appendix M – Stay base and angle conversion table


Table 43: Stay conversion all conductor sizes

Pole length in Stay Angle (Degrees)


metres

20 25 30 35 40 45

Minimum distance from base of pole to stay base (m)

8 2.36 3.03 3.75 4.55 5.46 6.50


9 2.72 3.49 4.33 5.25 6.29 7.50
10 3.09 3.96 4.90 5.95 7.13 8.50
11 3.34 4.29 5.31 6.44 7.71 9.20
12 3.71 4.75 5.88 7.14 8.55 10.2
13 4.07 5.22 6.46 7.84 9.39 11.2
14 4.44 5.68 7.04 8.54 10.23 12.2
This table is provided to support Appendix G – J which gives the angle of the stay
mathematically measured from the pole top information required in degrees 0o to 45o from the
pole top.
August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 95
Overhead Line Design Manual  

6.24 Full list of tables


Table 1 – Number of IPC’s required for Mains and service connections ......................................15 
Table 2:  List of GA Drawings and Materials - Mains ...................................................................16 
Table 3:  List of GA Drawings and Materials – Services..............................................................37 
Table 4:  List of GA Drawings and Materials – Pole Mounted Equipment .................................48 
Table 5:  List of GA Drawings and Materials – Earthing..............................................................57 
Table 6:  Conductor ABC, 4 x 120mm2: Design Data Summary..................................................66 
Table 7:  Conductor ABC, 4 x 120mm2: Design Sag/Tension .....................................................67 
Table 8:  Conductor, ABC, 4 x 120mm2: Pole Data (Ground Good/Average) ............................68 
Table 9:  Conductor, ABC, 4 x 120mm2: Single Pole Stay Capability.........................................68 
Table 10:  Conductor, ABC, 4 x 120mm2: Single Pole Strut Loading (Level Conditions) ..........69 
Table 11:  Conductor, ABC, 4 x 120mm2: Single Pole Strut Loading (1:10 Downpull Conditions)
...........................................................................................................................................70 
Table 12:  Conductor, ABC, 4 x 95mm2: Design Data Summary...................................................71 
Table 13:  Conductor, ABC, 4 x 95mm2: Design Sag/Tension ......................................................72 
Table 14:  Conductor, ABC, 4 x 95mm2: Pole Data (Ground Good/Average) ..............................73 
Table 15:  Conductor, ABC, 4 x 95mm2: Single Pole Stay Capability...........................................73 
Table 16:  Conductor, ABC, 4 x 95mm2: Single Pole Strut Loading (Level Conditions) ............74 
Table 17:  Conductor, ABC, 4 x 95mm2: Single Pole Strut Loading (1:10 Downpull Conditions)75 
Table 18:  Conductor, ABC, 2 x 95mm2: Design Data Summary...................................................76 
Table 19:  Conductor, ABC, 2 x 95mm2: Design Sag/Tension ......................................................77 
Table 20:  Conductor, ABC, 2 x 95mm2: Pole Data (Ground Good/Average) ..............................78 
Table 21:  Conductor, ABC, 2 x 95mm2: Single Pole Stay Capability...........................................78 
Table 22:  Conductor, ABC, 2 x 95mm2: Single Pole Strut Loading (Level Conditions) ............79 
Table 23:  Conductor, ABC, 2 x 95mm2: Single Pole Strut Loading (1:10 Downpull Conditions)80 
Table 24:  Conductor, ABC, 4 x 35mm2: Design Data Summary...................................................81 
Table 25:  Conductor, ABC, 4 x 35mm2: Design Sag/Tension ......................................................82 
Table 26:  Conductor, ABC, 4 x 35mm2: Pole Data (Ground Good/Average) ..............................83 
Table 27:  Conductor, ABC, 4 x 35mm2: Single Pole Stay Capability...........................................83 
Table 28:  Conductor, ABC, 4 x 35mm2: Single Pole Strut Loading (Level Conditions) ............84 
Table 29:  Conductor, ABC, 4 x 35mm2: Single Pole Strut Loading (1:10 Downpull Conditions)85 
Table 30:  Conductor, ABC, 2 x 35mm2: Design Data Summary...................................................86 
Table 31:  Conductor, ABC, 2 x 35mm2: Design Sag/Tension ......................................................87 
March 2011

Table 32:  Conductor, ABC, 2 x 35mm2: Pole Data (Ground Good/Average) ..............................88 
Table 33:  Conductor, ABC, 2 x 35mm2: Single Pole Stay Capability...........................................88 
Table 34:  Conductor, ABC, 2 x 35mm2: Single Pole Strut Loading (Level Conditions) ............89 
Table 35:  Conductor, ABC, 2 x 35mm2: Single Pole Strut Loading (1:10 Downpull Conditions)90 
Table 36:  Conductor, ABC, 2 x 35mm2 or 4 x 35mm2 ....................................................................91 
Table 37:  Conductor, ABC, 2 x 95mm2 or 4x95mm2 ......................................................................92 
Table 38:  In-line Support with Service Span Attachments...........................................................93 

Overhead Line Design Manual – Section 1 – LV ABC v1.2 Page 96


  Overhead Line Design Manual
Table 39:  Angle Support with no Service Span Attachments (Medium Poles) ..........................93 
Table 40:  Angle Support with no Service Span Attachments (Stout Poles)...............................94 
Table 41:  Angle Support with One Service Span Attachment (Medium Poles)..........................94 
Table 43:  Stay conversion all conductor sizes..............................................................................95 

August 2012

OHL Design Manual - Section 1 - Aerial Bundled Conductor (ABC) Low Voltage Mains And
Services LS BH PW Page 97
Overhead Line Design Manual  

6.25 Full list of figures


 

Figure 1:  ABC General Drawing Arrangement ..............................................................................18 


Figure 2:  ABC Stay Arrangement, Make-Off (No Auxiliary Pole-Mounted Equipment) ............19 
Figure 3:  ABC Stay Arrangement, Make-Off (Restricted Height or Auxiliary Pole-Mounted
Equipment) .......................................................................................................................21 
Figure 4:  ABC Stay Arrangement, Stay Plate (Restricted Height, Auxiliary Pole-Mounted
Equipment or Live Line Working)...................................................................................23 
Figure 5:  ABC Intermediate GA (Inside Angle up to 60o Line Deviation) ...................................25 
Figure 6:  ABC Intermediate GA (Outside Angle up to 30o Line Deviation) ................................27 
Figure 7:  ABC Angle Section GA (up to 20o Line Deviation) .......................................................29 
Figure 8:  ABC Angle Section GA (20o to 90o Line Deviation) ......................................................31 
Figure 9:  ABC Terminal GA .............................................................................................................33 
Figure 10:  ABC Tee-off Intermediate GA .........................................................................................35 
Figure 11:  ABC Service Connection (Three Phase) GA .................................................................39 
Figure 12:  Concentric Service Connection GA (3ph service cable shown) .................................41 
Figure 13:  Insulated Open Wire Service Connection GA ...............................................................43 
Figure 14:  Street Lighting Service Connection GA ........................................................................45 
Figure 15:  Concentric Service Spans...............................................................................................47 
Figure 16:  ABC Service Spans..........................................................................................................47 
Figure 17:  ABC to Two Distribution Boxes......................................................................................49 
Figure 18:  ABC to ABC via Fuses GA ..............................................................................................51 
Figure 19:  ABC Intermediate with Cable Termination and LV Fuses GA .....................................53 
Figure 20:  ABC Terminal with Cable Termination and LV Fuses GA ...........................................55 
Figure 21:  ABC Earthing – ABC Bundle to Neutral/Earth Bracket ................................................58 
Figure 22:  ABC Earthing – Neutral/Earth Bracket to Earth Electrodes ........................................59 
March 2011