Master Table: General Energy Conservation Special Notes
Master Table: General Energy Conservation Special Notes
Type of Breaker
Building Description Type of Building Permit
Size
Load Meter Description Energy Conservation Special Notes
Total Load Active Load E/Meter W/ Meter W/ Meter W/ Main Pipe W/ Service
Type Floor No. Flat No. BP No. MOC IN MCCB/A MCB/A
(KW) (KW)
Meter No.
Serial No.
CT/Ratio A/5 DC/CT/VT
No. No. size Pipe size
General
SUPPLY FROM Design and conservation of building shall comply with
STORE N/A N/2019/0007441 500 A 470.28 275.81 800/5A CT 22 22
MV PANEL
the provisions of the following KAHRAMAA regulations
DIESEL GENERATOR
STORE N/A N/2019/0007441 500 A 800/5A CT
SUPPLY
1) Regulation for the installation of electrical wiring,
electrical equipment and air conditioning equipment
KAHRAMAA NOTES: December 2010 edition
* The electrical installation shall be carried out in compliance with the
current edition of " The Regulations For Installation Of Electrical Wiring,
Electrical Equipment And Air Conditioning Equipment". Electrical installation
* MV panel details/manufacturer's drawings shall be submitted to Qatar
General Electricity And Water Corporation (KAHRAMAA) for prior All possible energy saving measures adopted in lighting sector
approval before it is manufactured.
Energy saving lamps is proposed wherever applicable
* Total voltage drop shall be not exceed 2.5%.
* Power factor shall not be lower than 0.90. Control systems are provided for lighting and A/C as applicable
* This approval covers only the revision/modification as indicated in the Timer and / or photocell control is ensured for the external lighting
SLD/drawing. All others details shall be as per the previous approval
under BP# ______.
HVAC Installation
Necessary provisions are included in design / construction to
200 A TP ISOLATOR
roof and energy efficient windows as applicable
32 A TP ISOLATOR
32 A TP ISOLATOR
MSB4 = 153.90 KW
MSB2 = 70.90 KW
MSB5 = 77.50 KW
MSB6 = 37.38 KW
MSB3 = 36.4 KW
DBmv = 4.20 KW
MSB1 = 24.0KW
All air conditioning equipments are sized and selected as per
cooling load calculations
4Cx120mm²XLPE/SWA/PVC
4Cx300mm²XLPE/SWA/PVC
4Cx35mm²XLPE/SWA/PVC
4Cx16mm²XLPE/SWA/PVC
4Cx70mm²XLPE/SWA/PVC
4Cx35mm²XLPE/SWA/PVC
4Cx16mm²XLPE/SWA/PVC
4Cx16mm²XLPE/SWA/PVC
4Cx50mm²XLPE/SWA/PVC
2Cx10mm²MICC CABLE
+1Cx150mm²PVC/ECC
+1Cx10mm²PVC/ECC
+1Cx16mm²PVC/ECC
+1Cx16mm²PVC/ECC
+1Cx70mm²PVC/ECC
+1Cx35mm²PVC/ECC
+1Cx16mm²PVC/ECC
+1Cx70mm²PVC/ECC
+1Cx16mm²PVC/ECC
+1Cx16mm²PVC/ECC
+1Cx25mm²PVC/ECC
VD=1.1 volts
L=36.7 mtrs.
U.D.D STAMP MUNICIPALITY STAMP
4Cx50mm²XLPE/SWA/PVC
SPACE
+1Cx25mm²PVC/ECC
40A TP* 80A TP 50A TP 200A TP 100A TP 80A TP 200A TP 32A TP 32A TP 200A TP 200A TP
VD=1.1 volts
L=36.7 mtrs.
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB SPACE MCCB MCCB
LVP Note:
4Cx50mm²XLPE/SWA/PVC THERMAL INSULATION SPECFICATION ARE AS PER Enquiry No. : xx / xxxx / xx Application No : xx / xxxx / xx
+1Cx16mm²PVC/ECC
MINISTERIAL DECREE NO. 108 OF THE YEAR 2015. CONSULTANT REG. No : 264/L GRADE : C CONSULTANT REG. No : 000000 GRADE : A
GCP CABLE SHOULD NOT BE LE AT WET AREA. CONSULTANT STAMP & SIGNATURE : SUB-CONSULTANT STAMP & SIGNATURE :
2-MV PANEL DETAILS/MANUFACTURER'S DRAWINGS SHALL BE SUBMITTED TECHNIQAL MANAGER : MOHAMED DALAIN TECHNIQAL MANAGER XXXXX
TO QATAR GENERAL ELECTRICITY & WATER CORPORATION(KAHRAMAA) REGISTRATION No. : 2659 REGISTRATION No : XXXXX
FOR PRIOR APPROVAL BEFORE IT'S MANUFACTURED .
3-TOTAL VOLTAGE DROP SHALL NOT EXCEED 2.5 % .
4-POWER FACTOR SHALL NOT BE LOWER THAN 0.90 .
PANORAMA ENGENEERING CONSULTANCY
5-THIS APPROVAL COVERS ONLY THE REVISION/MODIFICATION AS
DESIGN - PLANING - SUPERVISION
INDICATED IN THE SLD/DRAWING.ALL OTHER DETAILS SHALL BE AS AND PROJECT MANAGEMENT
1:100