Kumpulan ManualBook Alstom Micom
Kumpulan ManualBook Alstom Micom
The current inputs are connected to 3 phase CTs + a core balanced CT.
P2 P1 P2 P1 P2 P1 37
A A 33 35
S2 S1 S2 S1 Auxiliary + WD Watch dog (4)
B B 36
voltage
}
C C _ 6
S2 S1 34
49 49 4
Programmable tripping
P121 RL1
2
} output
1A 1A
50 50 12
51 51 10
RL2 Programmable output
1A 1A P121 8
}
A only
52 52 16
53 53 RL3 Programmable output
14 }
1A 1A 20
54 54 RL4 18 Programmable output
55 55
Connection Diagrams
C B
}
1A 1A
Phase rotation
56 56
41 P121 41
5A 5A
42 42
43 43
5A 5A P121
only
44 44
MiCOM P120/P121/P122/P123
45 45
5A 5A
46 46
47 47
5A 5A MiCOM
48 48
+ P120/121
Programmable 22
input L1 Case earth connection
24
-
Alternative (P121 only): Connection to 2 phases CTs + a core balanced CT.
{ +
Programmable 26
P2 P1 P2 P1 input L2
28
A -
{
S2 S1 Case earth
B 29
Communication
C 30 cable shield
S2 S1 1 2 29 30 *
49
3 4 31 32
1A 31 _ RS 485
5 6 33 34
50 Port communication
7 8 35 36
51
9 10 37 38 32
1A +
11 12 39 40
}
( : terminating resistor for the
52 13 14 41 42 *
53 last relay to be connected
15 16 43 44 between 30-32)
1A
17 18 45 46
54
55 19 20 47 48
42
43 (b) Short terminals break before (c)
Module terminal blocks
5A (c) Long terminals
viewed from rear
44 (d)
45 (with integral case earth link) Pins terminals (pcb type)
(4) The MICOM P120/P121 relays are shown with supply off.
USER SHOULD BE FAMILIAR WITH THE CONTENTS OF THE
5A
48
P0045ENb
BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE
36
voltage
_
}
C C 6
S2 S1
{ 34
Programmable tripping
49 49 4
RL1 output
2 }
1A 1A
50 50 12
51 51 10
RL2 Programmable output
1A 1A 8
A
}
52 52 16
P12x/EN CO/G86
+ P122/123
Programmable 22
input L1
24 Case earth connection
-
Alternative : Connection to 2 phases CTs + a core balanced CT.
{ +
Programmable 26
P2 P1 P2 P1 input L2
28
A -
{ +
S2 S1 Case earth Programmable 17
B L3 29
input 19 Communication
-
C
S2 S1 1 2 29 30
{ + 30 cable shield
49 Programmable 21 *
3 4 31 32 input L4
1A 23 31 _
- RS 485
5 6 33 34
{ +
50 Programmable 25 Port communication
7 8 35 36
51 input L5
9 10 37 38 27 32
-
1A
{ +
}
11 12 39 40 ( : terminating resistor for the
52 13 14 41 42 *
53 P123 only last relay to be connected
15 16 43 44 between 30-32)
1A
17 18 45 46
54
55 19 20 47 48
42
43 (b) Short terminals break before (c)
Module terminal blocks
5A (c) Long terminals
viewed from rear
44 (d)
45 (with integral case earth link) Pins terminals (pcb type)
48
P0046ENb
Connection Diagrams
MiCOM P120/P121/P122/P123
Installation P64x/EN IN/C52
10P64301-1
IN
P2386ENa
Figure 18: Two bias input transformer differential (8 I/P & 8 O/P) with1 pole VT inputs (40TE)
Installation P64x/EN IN/C52
10P64301-1
IN
P2386ENa
Figure 18: Two bias input transformer differential (8 I/P & 8 O/P) with1 pole VT inputs (40TE)
A MiCOM P441 (PART)
DIRECTION OF FORWARD CURRENT FLOW F11
WATCHDOG
P2 P1 F12 CONTACT
A
F13
S2 S1 WATCHDOG
B F14 CONTACT
C B
PHASE ROTATION E1
C
E2 RELAY 1
E3
TECHNICAL GUIDE
IB D4 OPTO 2
+ E11 RELAY 5
n C5 D5 E12
-
C6 1A D6 OPTO 3 E13
+ E14
DISTANCE PROTECTION RELAYS
a b c C7 5A D7 RELAY 6
IC - E15
D8 OPTO 4 F17
+ E16
C8
D9 E17
1A - RS485 RELAY 7
C9 F18 E18
D10 OPTO 5 PORT
C10 5A +
D11 B1
IM - F16 RELAY 8
OPTO 6 SCN B2
C11 D12
SEE NOTE 2. + B3
D13 DATA READY 1 SK2
1A B4 RELAY 9
C12 -
DIRECTION OF FORWARD CURRENT FLOW D14 OPTO 7 DATA 10 B5
+ ACKNOWLEDGE
A B6 RELAY 10
P2 P1 D15 EXTERNAL
A - RESET 16 B7
D16 OPTO 8
S2 S1 + DOWNLOAD B8
B 17 RELAY 11
D17 TEST/ COMMAND B9
C B COMMON DOWNLOAD
C DO-D7 2-9 B10
PHASE ROTATION D18 CONNECTION
11,12,15,13, B11 RELAY 12
PARALLEL LINE TO-T7
PROTECTION 20,21,23,24 B12
B13
0V 19,18,22,25 B14
RELAY 13
NOT B15
CONNECTED 14
B16
B17 RELAY 14
C19 1 SK1 B18
TX 2
RX 3
VA
4
SERIAL
0V 5
C20 PORT
6
CTS 7
RTS 8
VB
9
C21 *
F1
AC OR DC -
VC
Vx AUX SUPPLY + F2
C22
F7
+
MiCOM P441 – Wiring Diagram (1/2)
C23
+ F8
48V DC FIELD
V BUSBAR VOLTAGE OUT - F9
(SEE NOTE 3.)
NOTES 1. C24 F10
-
(a) C.T. SHORTING LINKS
CASE
EARTH
Page 2
Appendix B
TG 1.1671-B
A
MiCOM P442 (PART)
DIRECTION OF FORWARD CURRENT FLOW F1 J11
RELAY 15 WATCHDOG
P2 P1 F2 J12 CONTACT
A F3 J13
S2 S1 RELAY 16 WATCHDOG
B F4 J14 CONTACT
C B
C PHASE ROTATION F5 H1
RELAY 17 F6 H2 RELAY 1
F7 H3
MiCOM P442 (PART) F8 H4 RELAY 2
RELAY 18
C1 5A F9 H5
IA F10 H6 RELAY 3
TECHNICAL GUIDE
C2 D1 F11 H7
A B C - RELAY 19
1A D2 OPTO 1 F12 H8
NOTE 4. C3 + RELAY 4
F13 H9
C4 5A D3
N - RELAY 20 F14 H10
IB D4 OPTO 2
+ F15 H11 RELAY 5
n C5 D5 F16 H12
-
C6 1A D6 OPTO 3 F17 H13
MiCOM P441, P442 & P444
RELAY 21
+ F18 H14
a b c C7 5A D7 RELAY 6
IC - H15
D8 OPTO 4 J17
+ H16
C8
DISTANCE PROTECTION RELAYS
D9 H17
1A - RS485 RELAY 7
C9 OPTO 5 J18 H18
D10 PORT
C10 5A +
D11 G1
IM - J16 RELAY 8
OPTO 6 SCN G2
C11 D12
SEE NOTE 2. + G3
D13 DATA READY 1 SK2
C12 1A G4 RELAY 9
-
DIRECTION OF FORWARD CURRENT FLOW D14 OPTO 7 DATA 10 G5
+ ACKNOWLEDGE
A G6 RELAY 10
P2 P1 D15 EXTERNAL
A - RESET 16 G7
D16 OPTO 8
S2 S1 + DOWNLOAD G8
B 17 RELAY 11
D17 TEST/ COMMAND G9
C C B COMMON DOWNLOAD
PHASE ROTATION D18 CONNECTION DO-D7 2-9 G10
11,12,15,13, G11 RELAY 12
PARALLEL LINE E1 TO-T7
- 20,21,23,24 G12
PROTECTION E2 OPTO 9
+ G13
E3 0V 19,18,22,25 G14
- RELAY 13
E4 OPTO 10 NOT G15
+ CONNECTED 14
G16
E5
- G17 RELAY 14
C19 E6 OPTO 11 1 SK1 G18
+
E7 TX 2
-
E8 OPTO 12 RX 3
VA + 4
E9 SERIAL
- 0V 5
C20 E10 OPTO 13 PORT
6
+
E11 CTS 7
- RTS 8
VB E12 OPTO 14
+ 9
E13
C21 - *
E14 OPTO 15 J1
AC OR DC -
+ Vx
E15 AUX SUPPLY J2
VC +
- TX
C22 E16 OPTO 16 FIBRE OPTIC
+ J7 COMMUNICATION
+
C23 E17 (OPTIONAL)
COMMON J8 RX
48V DC FIELD +
E18
MiCOM P442 – Wiring Diagram (1/2)
CONNECTION
V BUSBAR VOLTAGE OUT - J9
(SEE NOTE 3.) IRIG-B INPUT
NOTES 1. C24 J10 (OPTIONAL)
-
(a) C.T. SHORTING LINKS
CASE
EARTH
Page 5
Appendix B
TG 1.1671-B
A
N11
DIRECTION OF FORWARD CURRENT FLOW WATCHDOG
N12 CONTACT
P2 P1
A N13
S2 S1 WATCHDOG
B C B N14 CONTACT
PHASE ROTATION
C
J1 L1
MV PLATFORM J2 RELAY 25 L2 RELAY 9
DISTANCE PROTECTION (PART) D1
- J3 L3
D2 OPTO 1
C1 5A
TECHNICAL GUIDE
+ J4 RELAY 26 L4 RELAY 10
D3
IA - J5 L5
D4 OPTO 2
A B C C2 + J6 RELAY 27 L6 RELAY 11
D5
1A - J7 L7
NOTE 4. C3 D6 OPTO 3
+ J8 RELAY 28 L8 RELAY 12
C4 5A D7
N - J9 L9
IB D8 OPTO 4
+ J10 RELAY 29 L10 RELAY 13
n C5 D9
- J11 L11
MiCOM P441, P442 & P444
1A D10 OPTO 5
C6 + J12 RELAY 30 L12 RELAY 14
D11
a b c C7 5A - J13 L13
D12 OPTO 6
IC + N17 J14 L14
D13
RELAY 31 RELAY 15
C8 - J15 L15
DISTANCE PROTECTION RELAYS
D14 OPTO 7
+ RS485 J16 L16
C9 1A N18
D15 PORT
- J17 RELAY 32 L17 RELAY 16
C10 5A D16 OPTO 8
+ N16 J18 L18
IM D17 SCN
COMMON
C11 D18
CONNECTION SK2
SEE NOTE 2. DATA READY 1
1A E1
C12 - DATA
DIRECTION OF FORWARD CURRENT FLOW E2 OPTO 9 10
+
ACKNOWLEDGE
E3 EXTERNAL
A - 16 K1 M1
P2 P1 E4 OPTO 10 RESET
A + K2 RELAY 17 M2 RELAY 1
S2 S2 E5 DOWNLOAD 17
B - TEST/ COMMAND K3 M3
E6 OPTO 11 RELAY 18 RELAY 2
+ DOWNLOAD K4 M4
C C B DO-D7 2-9
E7
PHASE ROTATION - K5 M5
E8 OPTO 12 11,12,15,13, RELAY 19 RELAY 3
+ TO-T7 K6 M6
PARALLEL LINE E9 20,21,23,24
PROTECTION - K7 M7
E10 OPTO 13 RELAY 20 RELAY 4
+ 0V 19,18,22,25 K8 M8
E11
- K9 M9
E12 OPTO 14 NOT 14 RELAY 21 RELAY 5
+ CONNECTED K10 M10
E13
- K11 M11
E14 OPTO 15 RELAY 22 RELAY 6
+ SK1 K12 M12
C19 E15
1
-
K13 M13
E16 OPTO 16
TX 2
+
K14 RELAY 23 M14 RELAY 7
E17
RX 3
K15 M15
VA COMMON 4
E18 CONNECTION SERIAL K16 M16
F1 PORT 0V 5
C20 -
K17 RELAY 24 M17 RELAY 8
6
F2 OPTO 17 K18 M18
+ CTS 7
F3
- RTS 8
F4 OPTO 18
VB + 9
F5
-
C21 F6 OPTO 19 N1 *
+ - TX
AC OR DC FIBRE OPTIC
F7
- Vx AUX SUPPLY N2 COMMUNICATION
F8 OPTO 20 + (OPTIONAL)
VC + RX
F9
C22 - N7
F10 OPTO 21 +
C23 +
F11
N8 IRIG-B INPUT
- 48V DC FIELD +
F12 OPTO 22 N9 (OPTIONAL)
V BUSBAR +
VOLTAGE OUT -
F13
(SEE NOTE 3.) - N10 CASE
NOTES 1. C24 F14 OPTO 23
-
+
EARTH
(a) C.T. SHORTING LINKS F15
-
MiCOM P444 – Wiring Diagram (1/2)
F16 OPTO 24
+
F17 POWER SUPPLY VERSION 24/54V D.C. ONLY
COMMON *
(b) PIN TERMINAL (P.C.B. TYPE) F18 CONNECTION
Page 8
Appendix B
TG 1.1671-B
PR 13 14 PR 13 14
MVTT 14 MCTI 39
1 3 13 14 1 3 13 14
MCTI 39 MVTT 14
2 4 1 3 2 4 1 3
Figure 2: DC connections for local breaker back-up relay MCTI 39 for use with time delay relay Type MVTT 14
Notes
P1 P2 1(a) CT shorting links make 2 CT connections are typical only
A before (b) & (c) disconnect
A S1 S2 3 Earthing connections are typical only
B
(b) Short terminals break before (c)
C
See Note 3 (c) Long terminals
C B
Phase rotation
Case earth 13
Power +
1 2
Supply Vx
3 4 14
5 6 Output Circuits –
7 8 Circuits 1
9 10 RL 1-1 3
11 12 RL1
27 Is 2 5
13 14
x Is >I 2
15 16 RL 2
17 18 28 2 RL 1-2 4
19 20 6
21 22 7
Output
23 24 RL 2-1 9
Contacts
11
25 26
8
27 28 MCTI
Case earth RL 2-2 10
See Note 3 12
Module terminal
block viewed from rear
Figure 3: Application diagram: static modular local breaker back- up relay type MCTI 19 (single phase tripping)
Notes
P1 P2 1(a) CT shorting links make 2 CT connections are typical only
A before (b) & (c) disconnect 3 Earthing connections are typical only
A S1 S2
B
(b) Short terminals break before (c)
C
C B See Note 3 (c) Long terminals
Phase rotation
Case earth 13
Power +
1 2 Vx
3 4
23 Is (A) Supply 14
5 6
x Is (A) Output Circuits –
7 8 24 Circuits 1
9 10 RL 1-1 3
11 12 RL1
13 14
25 Is (B) 2 5
15 16
x Is (B) >I 2
RL 2
17 18 26 2 RL 1-2 4
19 20 6
21 22 Output
27 Is (C) 7
Contacts
23 24 x Is (C) RL 2-1 9
11
25 26 28
8
27 28 MCTI RL 2-2
Case earth 10
See Note 3 12
Module terminal
block viewed from rear
Figure 4: Application diagram: static modular local breaker back-up relay type MCTI 39 (three phase tripping)
3
Time multiplier setting Each measuring board provides a Power supply healthy test
The time given by each of the setting range of 0.05 x In to 2.4 x I n If, whilst the relay is in service, the
operating characteristics must be in steps of 0.05 x In. reset button is pressed, all the leds
multiplied by the time multiplier to Instantaneous element are iluminated, indicating that there
give the actual operating time of the The setting control of the is power to the measuring boards.
relay. This control is marked xt = Σ instantaneous element is marked The leds are reset on releasing the
where Σ is the sum of all the switch Iinst = Σ x Is where Σ is the sum of the push button. During this test, normal
positions. switch positions and Is is the time current measurement is not inhibited.
The range of multiplication is from delayed element setting.
0.05x to 1.0x in steps of 0.025. When all switches are set to the left
This acts as a conventional time (at zero), or when the lowest switch is
multiplier on the current dependent set to infinity regardless of the
characteristics and gives the following positions of the other five switches, the
time ranges for the definite time instantaneous feature is rendered
characteristics. inoperable. The range of adjustment
Operating Time range of finite settings is from 1x to 31x in
characteristics unity steps.
s s Trip test
2 0.1 to 2.0 in 0.05s steps
Current measurement is inhibited by
4 0.2 to 4.0 in 0.1s steps
setting the curve selection switches to
8 0.4 to 8.0 in 0.2s steps
111. This causes all three led to flash
once per second. If the reset push
Current setting button is then pressed for
approximately six seconds, both
Time delayed element output relays associated with that
The current setting control is marked measuring board will operate.
Is = Σ x In where Is is the current
setting in amps, Σ is the sum of all the
switch positions and In is the relay
Figure 2: Type MCGG 22 nameplate
rated current in amps.
A
P2 P1
A
S2 S1
B
C B
C Phase rotation
Directional
control
PhA Indicator
24 TMS Inst Curve reset
setting setting selection
(See Note 4) 23
(See Note 2) 27 Time delayed trip
µC
IA Is Inst. trip
PhA RL1–1 7
28
6
Input Current I>Is Phase fault
circuit setting 5
time delayed
Ph Ph RL1–2 2 trip output
RL1 contacts
Case earth 2 1
13
1 2 +VE Output
Power RL2–1
Vx –VE
14
supply
circuits
Ph
8
5 6 26 10
circuits
7 8 RL2 9 Phase fault
2 instantaneous
9 10 trip output
Case earth RL2–2 16
contacts
(See Note 3)
13 14 15
15 16
MCGG 22
23 24 Notes:
26 1. (a) CT shorting links make 2. When directional control is required the contacts
27 28 before (b) and (c) disconnect. of the directional relays should be connected as shown.
(b) Short terminals break before (c). Contacts must close to inhibit overcurrent relay.
(c) Long terminals 3. Earthing connections (CTs) are typical only.
Module terminal block
viewed from rear 4. CT connections are typical only.
Figure 3: Application diagram: static modular overcurent relay type MCGG 22. Single phase with instantaneous element.
4
A
P2 P1
A
S2 S1 13
B Directional Indicator
Power +VE
TMS Inst Curve reset
control setting setting selection supply
14 Vx
C B C PhA –VE
49 circuits 1
Phase rotation
(See Note 4) 50
RL1
(See Note 2) 21 Case earth
Time delayed trip 2
µC
IA Is Inst. trip
PhA Output RL1–1 35
22 circuits
Ph 33
23 Input Current Phase fault
circuit setting I>Is 34
RL2 time delayed
Ph Ph RL1–2 29 trip output
2
24 contacts
30
Directional RL2–1 36
control
PhC TMS Inst Curve 37
45 setting setting selection
Case earth 38 Phase fault
46 instantaneous
1 2 29 30 RL2–2 41 trip output
Time
3 4 25 delayed trip contacts
µC
5 6 33 34 IC Inst. trip 42
Is PhC
7 8 35 36
26
9 10 37 38
27 Input Current
11 12 circuit setting I>Is
13 14 41 42 Ph Ph
15 16 28
17 18 45 46
19 20 47 48 Case earth MCGG 42
21 22 49 50 (See Note 3)
23 24
Notes:
25 26
1. (a) CT shorting links make 2. When directional control is required the contacts
27 28 before (b) and (c) disconnect. of the directional relays should be connected as shown.
(b) Short terminals break before (c). Contacts must close to inhibit overcurrent relay.
Module terminal blocks (c) Long terminals 3. Earthing connections are typical only.
viewed from rear 4. CT connections are typical only.
Figure 4: Application diagram: static modular overcurent relay type MCGG 42. Two phase with instantaneous element.
P2 P1
A 13
S2 S1 Directional Indicator +VE
A control
Power 14
B reset supply Vx
PhA TMS Inst Curve –VE
C 49 setting setting selection circuits 17
50 RL1
C B (See Note 2) 21 Time delayed trip 2 Case earth
(See Note 4) RL1–1 35
Phase rotation µC
IA Inst. trip
Is PhA Output 33
22 circuits Phase fault
Ph 34 time delayed
23 Input Current I>Is RL2
circuit setting RL1–2 29 trip output
Ph Ph 2 contacts
Directional 24 30
control
PhC TMS Inst Curve RL2–1 36
45
setting setting selection
46 37
Time 38 Phase fault
25
delayed trip instantaneous
µC RL2–2 42 trip output
IC Inst. trip
Is PhC contacts
26
41
Input Current I>Is
circuit setting
Case earth Ph Ph RL3–1 7
1 2 29 30 Directional
control 6
3 4 E/F 5 Earth fault
43 TMS Inst Curve time delayed
5 6 33 34 setting setting selection
RL3–2 2 trip output
7 8 35 36 44 RL3 contacts
9 10 37 38 27 2
Time delayed trip 1
11 12 µC
E/F Inst. trip Output
13 14 41 42 Is circuits
28 RL4–1 8
15 16 43 44
Input Current I>Is RL4 10
17 18 45 46 circuit setting
2 9 Earth fault
19 20 47 48 instantaneous
21 22 49 50 RL4–2 16 trip output
Case earth contacts
23 24
(See Note 3) 15
25 26
MCGG 52
27 28 Notes:
1. (a) CT shorting links make 2. When directional control is required the contacts 3. Earthing connections are typical only.
before (b) and (c) disconnect. of the directional relays should be connected as shown. 4. CT connections are typical only.
Module terminal blocks Contacts must close to inhibit overcurrent relay.
(b) Short terminals break before (c).
viewed from rear
(c) Long terminals
Figure 5: Application diagram: static modular overcurent relay type MCGG 52. Two phase plus earth fault with instantaneous elements.
5
P2 P1
A 13
S2 S1 Directional Indicator +VE
A control
Power 14
B reset supply Vx
PhA TMS Inst Curve –VE
C 49 setting setting selection circuits 17
50 RL1
C B (See Note 2) 21 Time delayed trip 2 Case earth
(See Note 4) RL1–1 35
Phase rotation µC
IA Inst. trip
Is Ph Output 33
22 circuits Phase fault
Ph 34 time delayed
23 Current I>Is RL2
setting RL1–2 29 trip output
Ph 2 contacts
Directional 24 30
control
PhC RL2–1 36
45
46 37
38 Phase fault
25
instantaneous
IC RL2–2 41 trip output
contacts
26
42
Input
circuit
Case earth
Ph RL3–1 7
1 2 29 30 Directional
control 6
3 4 E/F 5 Earth fault
43 TMS Inst Curve time delayed
5 6 33 34 setting setting selection
RL3–2 2 trip output
7 8 35 36 44 RL3 contacts
9 10 37 38 27 2
Time delayed trip 1
11 12 µC
E/F Inst. trip Output
13 14 41 42 Is circuits
28 RL4–1 8
15 16 43 44
Input Current I>Is RL4 10
17 18 45 46 circuit setting
2 9 Earth fault
19 20 47 48 instantaneous
21 22 49 50 RL4–2 16 trip output
Case earth contacts
23 24
(See Note 3) 15
25 26
MCGG 53
27 28 Notes:
1. (a) CT shorting links make 2. When directional control is required the contacts 3. Earthing connections are typical only.
before (b) and (c) disconnect. of the directional relays should be connected as shown. 4. CT connections are typical only.
Module terminal blocks Contacts must close to inhibit overcurrent relay.
(b) Short terminals break before (c).
viewed from rear
(c) Long terminals
Figure 6: Application diagram: static modular overcurent relay type MCGG 53. Two phase (with polyphase measurement), plus earth
fault with instantaneous elements.
P2 P1
A 13
S2 S1 Directional Indicator +VE
A control
Power 14
B reset supply Vx
PhA TMS Inst Curve –VE
C 49 setting setting selection circuits 17
50
Figure 7: Application diagram: static modular overcurent relay type MCGG 62. Three phase with instantaneous element.
6
P2 P1
A 13
S2 S1 Directional Indicator +VE
A control
Power 14
B reset supply Vx
PhA TMS Inst Curve –VE
C 49 setting setting selection circuits 1
50 RL1
C B (See Note 2) 21 Time delayed trip 2 Case earth
(See Note 4) RL1–1 35
Phase rotation µC
IA Inst. trip
Is Ph Output 33
22 circuits Phase fault
Ph 34 time delayed
Current I>Is RL2
setting RL1–2 29 trip output
Ph 2 contacts
Directional 30
control
PhB RL2–1 36
47
48 37
38 Phase fault
23
instantaneous
IB RL2–2 41 trip output
contacts
24
42
Case earth
1 2 29 30 Directional
control
3 4 PhC
5 6 33 34 45
7 8 35 36 46
9 10 37 38 25
11 12 IC
13 14 41 42
26
15 16
27 Input
17 18 45 46 circuit
19 20 47 48
21 22 49 50 28
Case earth
23 24
25 26 (See Note 3) MCGG 63
27 28 Notes:
1. (a) CT shorting links make 2. When directional control is required the contacts 3. Earthing connections are typical only.
before (b) and (c) disconnect. of the directional relays should be connected as shown. 4. CT connections are typical only.
Module terminal blocks Contacts must close to inhibit overcurrent relay.
(b) Short terminals break before (c).
viewed from rear
(c) Long terminals
Figure 8: Application diagram: static modular overcurent relay type MCGG 63. Three phase (with polyphase measurement) with
instantaneous element.
A P2 P1
A Directional 13
S2 S1 control Indicator Power +VE
B reset 14 Vx
PhA supply
49 –VE
C TMS Inst Curve circuits 17
setting setting selection
C B N 50 RL1
Phase rotation (See Note 2) 21 2
Time delayed trip Case earth
(See Note 4) µC RL1–1 35
IA Inst. trip
Is PhA Output
circuits 33
22 Phase fault
Input circuit Current setting Ph
34 time delayed
Ph Ph I>Is RL2
Directional trip output
control 2 RL1–2 29
contacts
PhB
47 TMS Inst Curve 30
setting setting selection
48
RL2–1 36
23 Time delayed trip
µC 37
IB Inst. trip Phase fault
Is PhB
38
24 instantaneous
Input circuit Current setting RL2–2 41 trip output
Ph Ph I>Is contacts
Directional
control 42
phase PhC
45 TMS Inst Curve
Case earth setting setting selection RL3–1 7
46
1 2 29 30 6
25 Time delayed trip Earth fault
3 4
µC 5
time delayed
5 6 33 34 IC Inst. trip
Is PhC trip output
RL3–2 2
7 8 35 36 26 contacts
Input circuit Current setting
9 10 37 38 Ph Ph I>Is 1
11 12
Directional
13 14 41 42 control E/F
43 TMS Inst
RL4–1 8
15 16 43 44 Curve RL3
setting setting selection 10
17 18 45 46 44 2
9
Earth fault
19 20 47 48 27 Time delayed trip Output instantaneous
µC circuits RL4–2 16 trip output
21 22 49 50 Inst. trip
Is E/F E/F contacts
23 24 28 RL4
Input circuit Current setting 15
25 26 Case earth E/F E/F I>Is 2
MCGG 82
27 28 Notes:
(See Note 3)
1. (a) CT shorting links make 2. When directional control is required the contacts 3. Earthing connections are typical only.
Module terminal blocks before (b) and (c) disconnect. of the directional relays should be connected as shown. 4. CT connections are typical only.
viewed from rear (b) Short terminals break before (c). Contacts must close to inhibit overcurrent relay.
(c) Long terminals.
Figure 9: Application diagram: static modular overcurent relay type MCGG 82. Three phase plus earth fault with instantaneous elements.
7
A
A1 85X–1 B1
Reset Z1 ext A2 B2 Signal send (1)
C B A3 85X–2 B3
Phase rotation Breaker open
(See Note 2) A4 B4 Signal send (2)
Direction of power A5 94A–1 B5
flow for operation Inhibit power swing blocking
(See Note 6) A6 B6 Trip A (1)
A7 94A–2 B7
P2 P1 Channel A8
A A in service B8 Trip A (2)
S2 S1 A9 94B–1
B B B9
Signal receive A10 B10 Trip B (1)
C C
94B–2 B11
Va A11 IZ1
B12 Trip B (2)
Vb A13 IZ2
94C–1 B13
VT secondaries
Vc A15 IZ3 B14 Trip C (1)
94C–2 B15 (See Note 7)
Vn A12 IZ4
B16 Trip C (2)
DC +VE A17 IZ5 94T–1 B17
DC –VE A18 IZ6 B18 Trip 3PH (1)
94T–2 B19
A19 IY1 B20 Trip 3PH (2)
94–1 IZ7 B21
A20 IY2 IZ8 B22 Any trip (1)
A21 IY3 94–2 B23
B24 Any trip (2)
A22 IY4 96–1 B25
B26 Block A/R
A23 IY5
19A–1 C1
A24 IY6 C2 Fault locator A
A25 IY7 19B–1 C3
C4 Fault locator B
A26 IY8 19C–1 C5
C6 Fault locator C
19E–1 C7
Fault locator
C8
ground faults
Z2–1 C9
0V IZ10 Output relays C10 Zone 2 trip alarm
common Z3–1 C11
C12 Zone 3 trip alarm
94Y–1 C13
C14 Aided trip alarm
98–1 C15
C16 SOTF trip alarm
(See Note 5) 97X–1 C17
C18 Fuse fail alarm
95–1 C19
C20 Power swing alarm
97Y–1 C21 Relay inoperative
C22 alarm (See Note 3)
Notes
1. Heavy duty connectors. 3. Under healthy operating conditions this contact is held open.
a) Closes when heavy duty connector is removed. 4. Removal of IZ heavy duty connector disables all auxiliary relay
output contacts and closes relay inoperative alarm.
b) Opens when heavy duty connector is removed.
c) Opens after operation of a) and b) when heavy 5. Connections shown are typical only.
duty connector is removed. 6. When busbar VT’s and a single phase tripping scheme
incorporating P.S.B. are used this opto must be energised during
2. Breaker open opto must be connected if busbar VT’s
single pole dead times.
are used or if the weak infeed or echo feature of the
permissive overreach scheme are required. 7. When 3 phase tripping scheme is used Trip A, Trip B, Trip C and
CB auxiliary contacts must be connected in series to Any Trip respond as Trip 3 Phase.
indicate ‘all poles open’.
Figure 11: External connection diagram: Quadramho static distance protection relay. Single and three phase tripping.
17
3.2 WIRING 3 HARDWARE
The purpose of this diagram is to provide an example of how the relay is typically wired, not specifically how to wire your own relay. Please refer to the following pages for exam-
TRIPPING DIRECTION
TYPICAL CONFIGURATION
THE AC SIGNAL PATH IS CONFIGURABLE
A (5 Amp)
B
52 52
C
A B C
CURRENT
POLARIZATION
SOURCE
F 1b
F 2b
F 3b
F 4b
F 1a
F 2a
F 3a
F 4a
F 5a
F 6a
F 7a
F 8a
F 1c
F 2c
F 3c
F 4c
F 5c
F 6c
F 7c
F 8c
3
VX
VB
VC
VA
VX
VB
VC
IG5
IG1
VA
IG
IA5
IA1
IA
IB
IB5
IB1
IC5
IC
IC1
CURRENT SUPV.
VOLT &
CURRENT INPUTS VOLTAGE INPUTS
8F / 8G
H 7a CONTACT IN H 7a DIGITAL I/O 6H I H 1a TC1
H 7c CONTACT IN H 7c H1 H 1b
V
H 8a CONTACT IN H 8a H 1c
H 8c CONTACT IN H 8c I H 2a
H 7b COMMON H7b H2 H 2b
V
VOLTAGE SUPV.
H 8b SURGE H 2c
I H 3a
H3 H 3b
V TC2
H 3c
I H 4a
H4 H 4b
V
GE Multilin H 4c
I H 5a
H5 H 5b
D60 LINE DISTANCE RELAY V
I
H 5c
H 6a
H6 H 6b
V
H 6c
W 5a CONTACT IN W 5a DIGITAL I/O 6A I W1a
W 5c CONTACT IN W 5c W1 W1b
V
W 6a CONTACT IN W 6a W1c
ples to help you wire your relay correctly based on your own relay configuration and order code.
W 6c CONTACT IN W 6c I W2a
P 1a
6C
P1 P 1b
P 1c
P 2a
P2 P 2b
U 1a CONTACT IN U1a P 2c
6D
U 1c CONTACT IN U1c P 3a
U 2a CONTACT IN U2a P3 P 3b
U 2c CONTACT IN U2c P 3c
U 1b COMMON U1b P 4a
P4 P 4b
U 3a CONTACT IN U3a
U 3c CONTACT IN U3c
P 4c
U 4a CONTACT IN U4a
P 5a
P5 P 5b
U 4c CONTACT IN U4c
U 3b COMMON U3b
P 5c
P 6a
U 5a CONTACT IN U5a P6 P 6b
U 5c CONTACT IN U5c P 6c
U 6a CONTACT IN U6a P 7a
U 6c CONTACT IN U6c P7
DIGITAL I/O
P 7b
U 5b COMMON U5b P 7c
U 7a CONTACT IN U7a P 8a
U 7c CONTACT IN U7c P8 P 8b
DIGITAL I/O
RS-232 M1 M1b
B 1b M1c 9 PIN 25 PIN
1
CRITICAL DB-9
B 1a M2a CONNECTOR CONNECTOR
FAILURE
B 2b (front) M2 M2b 1 1 8
B 3a 48 VDC M2c TXD 2 2 3 RXD
POWER SUPPLY
B 3b OUTPUT M3a
DC RXD 3 3 2 TXD
B5b HI M3 M3b 4 4 20
CONTROL
B 6b LO CONTACTS SHOWN M3c
AC or DC POWER SGND 5 5 7 SGND
B 6a WITH NO M4a 6 6 6
B 8a SURGE CONTROL POWER M4 M4b 7 7
Shielded 4
B 8b FILTER M4c 8 8 5
twisted pairs
M5a 9 9 22
D1b M5 M5b
9E
RS485 UR COMPUTER
D2b M5c
Ground at COM 1
D3b COM M6a
Remote
D1a M6 M6b
Device RS485
D2a
COM 2 M6c
D3a COM
D4b
M7a
M7
DIGITAL I/O
BNC
Output M8c
Co-axial
Co-axial * - For IRIG-B Input No. 10AWG GROUND BUS MODULE ARRANGEMENT 837774A3.CDR
only use one Minimum
X W V U T S R P N M L K J H G F D B
terminal as input 6 6 6 6 6 8 9 1
MODULES MUST BE
GROUNDED IF
CAUTION
TYPICAL CONFIGURATION
THE AC SIGNAL PATH IS CONFIGURABLE
OPEN DELTA
VT CONNECTION (ABC)
(5 amp CTs)
A A
B B
C C
WINDING 1
WINDING 2
(5 amp CTs)
A
B
C
WINDING 3
F5a
F5c
F6a
F6c
F7a
F7c
F5a
F5c
F6a
F6c
F7a
F7c
F8a
F8c
F1a
F1b
F1c
F2a
F2b
F2c
F3a
F3b
F3c
F4a
F4b
F4c
M 8c
M 1a
M 1b
M 1c
M 2a
M 2b
M 2c
M 3a
M 3b
M 3c
M 4a
M 4b
M 4c
M 5a
M 5b
M 5c
M 6a
M 6b
M 6c
M 7a
M 7b
M 7c
M 8a
M 8b
VX
VA
VB
VC
VA
VB
VC
IB
IC
IA
IG
IB
IB
IC
IC
IA
IA
IG
IG
VX
VA
VB
VC
VA
VB
VC
IA5
IA1
IG5
IG1
IB5
IB1
IC5
IC1
IA5
IA1
IA5
IA1
IG5
IG1
IG5
IG1
IB5
IB1
IB5
IB1
IC5
IC1
IC5
IC1
8F / 8G 8H/ 8J
V
H8a CONTACT INPUT H8a H1c
H8c CONTACT INPUT H8c I H2a
H7b COMMON H7b 2 H2b
V
H2c
H8b SURGE
I H3a
3 H3b
V TC 2
B1b H3c T60 COMPUTER
1
CRITICAL
( DC ONLY )
B1a FAILURE
I H4a 1 1 8
B2b GE Consumer & Industrial 4 H4b
V TXD 2 2 3 RXD
B3a 48 VDC H4c
VOLTAGE SUPERVISION
POWER SUPPLY
twisted pairs B8b FILTER
9 9 22
DIGITAL INPUTS/OUTPUTS 6D
D1b
9E
RS485 9 PIN 25 PIN
D2b COM 1
Ground at com DIGITAL INPUTS/OUTPUTS 6C CONNECTOR CONNECTOR
remote
D3b
P2
P5
P1
P7
P6
P8
P4
D2a
SURGE
COM 2
D4b com
COMMON U1b
COMMON U3b
COMMON U5b
COMMON U7b
IRIG-B (front)
Co-axial BNC
P1a
P1b
P1c
P2a
P2b
P2c
P3a
P3b
P3c
P4a
P4b
P4c
P5a
P5b
P5c
P6a
P6b
P6c
P7a
P7b
P7c
P8a
P8b
P8c
U1a
U1c
U2a
U2c
U1b
U3a
U3c
U4a
U4c
U3b
U5a
U5c
U6a
U6c
U5b
U7a
U7c
U8a
U8c
U7b
U8b
output
CPU
No. 10AWG
Co-axial * - For IRIG-B Input minimum 828749A6.CDR
only use one
GROUND BUS CONTACTS SHOWN
terminal as input WITH NO MODULE ARRANGEMENT
MODULES MUST BE CONTROL POWER
GROUNDED IF X W V U T S R P N M L K J H G F D B
TERMINAL IS 6 6 6 6 8 9 1
PROVIDED Inputs/ Inputs/
outputs outputs CT Inputs/ CT/VT CPU Power
* * outputs supply This diagram is based on the following order code:
(Rear view) T60-E00-HCL-F8F-H6H-M8H-P6C-U6D-WXX
* Optional This diagram provides an example of how the device
is wired, not specifically how to wire the device. Please
refer to the Instruction Manual for additional details on
wiring based on various configurations.
3.2 WIRING
3-9
3.2.1 TYPICAL WIRING
3
3 HARDWARE 3.2 WIRING
TYPICAL CONFIGURATION
THE AC SIGNAL PATH IS CONFIGURABLE
TRIPPING DIRECTION
A B C (5 Amp)
52
OPTIONAL
F1a
F1b
F2a
F2b
F3a
F3b
F4a
F4b
F5a
F6a
F7a
F8a
F1c
F2c
F3c
F4c
F5c
F6c
F7c
F8c
VX
VB
VC
VA
VX
IG5
IG1
VB
VC
IG
VA
IA5
IA1
IB
IC
IA
IC5
IC1
IB5
IB1
CURRENT SUPERVISION
VOLTAGE AND
CURRENT INPUTS VOLTAGE INPUTS
8F
This diagram is based on the following order code: H5a CONTACT INPUT H5a DIGITAL INPUTS/OUTPUTS 6G I H1a TC 1
L90-E00-HCL-F8F-H6G-L6D-N6K-S6C-U6H-W7A H5c CONTACT INPUT H5c H1
V
H1b
This diagram provides an example of how the device H6a CONTACT INPUT H6a H1c
is wired, not specifically how to wire the device. Please H6c CONTACT INPUT H6c I H2a
refer to the Instruction Manual for additional details on H5b COMMON H5b H2 H2b
VOLTAGE SUPERVISION
V
wiring based on various configurations. H2c
H7a CONTACT INPUT H7a
I H3a
H7c CONTACT INPUT H7c
H3 H3b TC 2
H8a CONTACT INPUT H8a V
H3c
H8c CONTACT INPUT H8c
I H4a
H7b COMMON H7b
H4 H4b
V
H8b SURGE H4c
U7a CONTACT INPUT U7a DIGITAL INPUTS/OUTPUTS 6H I U1a
U7c CONTACT INPUT U7c U1 U1b
V
U8a CONTACT INPUT U8a U1c
U8c CONTACT INPUT U8c I U2a
U7b COMMON U7b U2 U2b
V
U2c
U8b SURGE
I U3a
U3 U3b
V
U3c
I U4a
U4 U4b
V
GE Consumer & Industrial U4c
Multilin I U5a
U5 U5b
V
U5c
L90 LINE DIFFERENTIAL RELAY U6
I U6a
U6b
V
U6c
N1a
( DC ONLY )
6K
N1 N1b
L1a CONTACT INPUT L1a
6D
N1c
L1c CONTACT INPUT L1c
N2a
L2a CONTACT INPUT L2a N2 N2b
L2c CONTACT INPUT L2c
N2c
L1b COMMON L1b
N3a
L3a CONTACT INPUT L3a N3 N3b
L3c CONTACT INPUT L3c N3c
L4a CONTACT INPUT L4a N4a
L4c CONTACT INPUT L4c UR COMPUTER
N4 N4b
L3b COMMON L3b 1 1 8
N4c
TXD 2 2 3 RXD
L5a CONTACT INPUT L5a N5a
N5 N5b RXD 3 3 2 TXD
L5c CONTACT INPUT L5c
N5c 4 4 20
L6a CONTACT INPUT L6a
SGND 5 5 7 SGND
DIGITAL INPUTS/OUTPUTS
N6 N6b 6 6 6
L5b COMMON L5b
N6c 7 7 4
L7a CONTACT INPUT L7a 8 8 5
N7a
L7c CONTACT INPUT L7c 9 9 22
N7 N7b
L8a CONTACT INPUT L8a
L8c CONTACT INPUT L8c N7c
N8a 9 PIN 25 PIN
L7b COMMON L7b CONNECTOR CONNECTOR
N8 N8b
L8b SURGE
N8c
INTER-RELAY
FIBER
Tx1 Rx1
COMMS.
TO CHANNEL 1
W7A
REMOTE S1a
6C
S3c
B5b HI S4a
AC or DC CONTROL
B6b LO S4 S4b
POWER
B6a S4c
B8a SURGE S5a
B8b FILTER S5 S5b
S5c
S6a
DIGITAL INPUTS/OUTPUTS
S6 S6b
S6c
Shielded
S7a
twisted pairs
CONTACTS SHOWN S7 S7b
WITH NO
S7c
D1b CONTROL POWER
S8a
9E
RS485
D2b COM 1 S8 S8b
Ground at com
Remote
D3b S8c
Device D1a
RS485
D2a COM 2
D3a com
Co-axial *
D4b
D4a IRIG-B
Input
Co-axial BNC
IRIG-B
CPU
Connection diagram
Connection diagram
Fig. 8/41a
Additional setting by jumpers:
8 Separation of common circuit of fast BO1 to
BO5 with jumpers X80, X81, X82. Switching
of fast BO7, BO8 as NO contact or NC contact
with jumpers X41, X42, X43.
Connection diagram
Fig. 8/42a
Additional setting by jumpers:
Separation of common circuit of fast BO1 to
8
BO5 with jumpers X80, X81, X82. Switching
of fast BO7, BO8 as NO contact or NC contact
with jumpers X41, X42, X43.
Connection diagram
Connection diagram
7SJ621*-*D/E
Figure A-1 General diagram for 7SJ621*–*D/E (panel flush mounting or cubicle mounting)
Figure A-1 Connection Diagram For 7VH60 (Panel Flush Mounted or Cubicle Mounted)
Appendix
SURFACE MOUNTING CASE 7VH600*-0BA*0-*AA0
FLUSH MOUNTING CASE 7VH600*-0EA*0-*AA0
CT INPUT 1
1
CT INPUT 2
2
1) X51 1 23
1) SETTING VOLTAGE 24V 7
7 COMMAND
SETTING VOLTAGE 24V
1) 9
1K2 23
9 TRIP
23
1K2 22
SETTING VOLTAGE 24V 11 22
11 24 K1: 24
SETTING VOLTAGE 24V 1K2 25 TRIP
13 25
13
SETTING VOLTAGE 24V 1K2
15 15
1) Delivery condition
E2:BLOCKED FROM EXTERNAL 2) 21
21 of plugs for 24V
30
V+ POWER SUPPLY 30
= 2) Input and contacts only
31 UH V- 31 = available with buswire
supervision (ordering
option)
C53000-B1176-C136-1
7VH60 Manual
Features
● Fast reset time-typically 15ms
● Low burden
● Compact design
● Mechanically stable
● Low overshoot
● Suitable for breaker fail schemes
Models Available
Type MCTI 19
This is a single phase relay with 4
change-over contacts.
Type MCTI 39
This is a three phase device with a
common output element for all three
phases, giving 4 change-over
contacts.
Type MCTI 40
This is a three phase device with an
independent output element for each
phase, giving 2 normally open
contacts per phase.
All relay types are available with a
rated current of either 1A or 5A.
Figure 1: Type MCTI 39 Relay withdrawn from case.
Application B
D
Relay types MCTI 39 and MCTI 40 fault current under normal
F A
are three phase or two phase and circumstances.
E
earth fault instantaneous overcurrent LBB
C A particular feature of the relay is a
relays and the MCTI 19 is a single fast reset. This is important in a
phase relay. The relays have been scheme such as that shown in Figure
designed to be applied as current In the substation single line diagram 2, Alternative (b) since it will be
detectors in breaker fail protection shown above: possible to set the time delay closer to
schemes. The MCTI 40 is particularly the breaker trip time.
if breaker A fails to remove the fault at
suitable for breaker fail applications
F, breakers B, C, D and E should be For details of a suitable time delay
where single/three pole breaker
tripped simultaneously by breaker fail relay see Publication R6012, relay
tripping is possible, since control of
protection for breaker A, to isolate the types MVTT 14 and MVTT 15.
the current detector is provided on a
busbar. The breaker fail timer relay
per phase basis. Simple application
should be set in excess of the time
diagrams are shown in Figure 2.
required for the breaker to clear the
2
PR 13 14 PR 13 14
MVTT 14 MCTI 39
1 3 13 14 1 3 13 14
MCTI 39 MVTT 14
2 4 1 3 2 4 1 3
Figure 2: DC connections for local breaker back-up relay MCTI 39 for use with time delay relay Type MVTT 14
Notes
P1 P2 1 (a) CT shorting links make 2 Earthing connections are typical only
A before (b) & (c) disconnect
A S1 S2 3 CT connections are typical only
B
(b) Short terminals break before (c)
C
See Note 3 (c) Long terminals
C B
Phase rotation
Case earth
1 2
3 4
5 6 Output
7 8 Circuits 5
9 10 RL 1-1 1
11 12 RL1
27 Is 2 3
x Is >I 6
28
RL 2
2
RL 1-2 2
4
22 13 11
Output
+ ve Contacts
23 24 Vx 14
Power RL 2-1 7
25 26
– ve Supply 9
22 Circuits 12
27 28 MCTI
(See note 2) RL 2-2 8
Module terminal
block viewed from rear
(with integral case
earth strap)
Figure 3: Application diagram (10 MCTI 19 03): static modular local breaker back-up relay type MCTI 19 (single phase tripping)
Notes
A P1 P2 1 (a) CT shorting links make 2 Earthing connections are typical only
A before (b) & (c) disconnect
S1 S2 3 CT connections are typical only
B
B (b) Short terminals break before (c)
C C
Phase rotation See Note 3 (c) Long terminals
Case earth
1 2
3 4
5 6
23 Is (A)
7 8
x Is (A) Output
9 10
11 12 24 Circuits 5
RL1 RL 1-1 1
2
25 Is (B) 3
x Is (B) >I 6
22 26 RL 2 RL 1-2 2
2
1
23 24 Output
27 Is (C) 11
Contacts
25 26
x Is (C) RL 2-1 7
27 28 9
28
12
13
+ ve MCTI RL 2-2 8
Module terminal Vx 14
Power
10
block viewed from rear – ve Supply
(with integral case
22 Circuits
earth strap)
(See note 2) Case earth connection
Figure 4: Application diagram (10 MCTI 39 03): static modular local breaker back-up relay type MCTI 39 (three phase tripping)
3
Description Technical Data
For breaker fail applications Ratings
The MCTI is enabled/disabled by AC Current (In) 1A or 5A
application/removal of the dc DC Auxiliary voltages Vx dc Operative range
auxiliary supply to the relay (on a per 30/34V 24 - 40V
phase basis for the MCTI 40). The 48/54V 37.5 - 66V
relay will quickly reset when the 110/125V 87.5 - 150V
protected circuit breaker interrupts 220/250V 175 - 300V
primary current.
Rated frequency 50 or 60Hz
For other applications
The relay operates when the current Burdens
exceeds setting (Is) and resets when Setting Rated Tap At setting current At rated
the current reduces to less than 96% range current Setting Multiplier Setting current
of setting current. amps 1x 2x (maximum)
A tapped primary on the input current 5% to 40% 1A Min 0.05VA 0.12VA 2.64VA
transformer is used in conjunction with Max 0.08VA 0.22VA 0.15VA
a 1x to 2x multiplier potentiometer to 5A Min 0.05VA 0.11VA 4.37VA
give a continuously variable setting Max 0.12VA 0.43VA 0.73VA
range. The relay input current is fed
10% to 80% 1A Min 0.05VA 0.12VA 1.50VA
into a tapped interposing CT. A
Max 0.09VA 0.28VA 0.14VA
proportion of the secondary current,
set by the xIs potentiometer, is 5A Min 0.05VA 0.12VA 1.97VA
rectified and fed into a peak Max 0.26VA 0.96VA 0.43VA
measuring circuit which incorporates 20% to160% 1A Min 0.05VA 0.12VA 0.68VA
a time delay to prevent reset between Max 0.13VA 0.44VA 0.05VA
the peaks. The output of this circuit 5A Min 0.07VA 0.22VA 1.07VA
energises a miniature relay output Max 1.10VA 4.29VA 0.39VA
element.
DC Auxiliary Nominal Quiescent Operated
A feedback circuit is used to provide supply voltage current drain current drain
hysteresis such that the drop off to
30/34V 25mA 100mA For MCTI 19 or
pick up ratio is about 96%, thus
48/54V 20mA 85mA MCTI 39 relays
making the relay more stable at
110/125V 12mA 60mA or per phase for
current values near to pick up.
220/250V 12mA 45mA MCTI 40 relay.
The MCTI 19, 39, 40 relays are not
NOTE: For breaker fail schemes, the quiescent current drain is zero.
suitable for use in applications where
the output relays are to be energised Setting ranges
continuously.
Tap setting (Is) 20%, 40% 80%, 160% In.
The 220/250V dc auxiliary version of 10%, 20%, 40%, 80% In.
the MCTI 40 is only suitable for use in 5%, 10%, 20%, 40% In.
applications where the dc auxiliary
Current setting multiplier 1-2x tap setting
supply is not continuously applied.
This gives effective setting ranges of:
20 - 320% In.
10 - 160% In.
5 - 80% In.
Operating time
Operate time <10ms
Reset time <15ms, typically 12ms
Accuracy
Current setting (Is) ±5%
Contacts
MCTI 19, 39 4 Changeover self reset
MCTI 40 2 normally open or 1 normally
open and 1 normally closed per
phase or earth fault element
4
13
A Phase +ve
P1 P2 power 16
supply +ve
A circuits
A S1 S2
B B Phase
15
+ve Vx
power
C supply 14
circuits -ve
C B See Note 3 MCTI 17
C Phase +ve
Phase rotation power Timer start
18
supply
circuits
Case earth
23 Is (A) RL A
1 2
x Is (A) >I 2
3 4
5 6 24
RLA-1 1
Output Circuits
7 8
3
A Phase
9 10 25 Is (B) RL B RLA-2 2 output
>I 2
11 12
x Is (B) 4 contacts
13 14
26
15 16
Output Circuits RLB-1 5
17 18
19 20 27 Is (C) RL C
7 B Phase
21 22
x Is (C) >I 2 RLB-2 6 output
23 24
8 contacts
28
22 Output Circuits RLC-1 9
25 26 Module earth
27 28
11
C Phase
Case earth connection RLC-2 10 output
See Note 2 contacts
12
Module terminal
block viewed from rear
(with integral case earth strap) Notes
1 (a) CT shorting links make 2 Earthing connections are typical only
before (b) & (c) disconnect
3 CT connections are typical only
(b) Short terminals break before (c) 4 All 3 output relays operate
simultaneously for a 3 phase trip
(c) Long terminals
Figure 5: Application diagram (10 MCTI 40 03): static modular local breaker back-up relay type MCTI 40 (single and three phase tripping)
Contact ratings
Current Make and carry Make and carry Break
continuously for 0.2s
AC 1250VA with 7500VA with 1250VA with
maxima of 5A maxima of 30A maxima of 5A
and 300V and 300V and 300V
DC 1250W with 7500W with 50W (Resistive)
maxima of 5A maxima of 30A 25W (Inductive)
and 300V and 300V with L/R=40ms
with maxima
of 5A and 300V
Durability
Loaded contact 10,000 operations minimum
Unloaded contact 100,000 operations minimum
Thermal withstand
AC current 2x rated current continuously
maximum application time = 10,000
I2
where I is the multiple of rated current
High voltage withstand
Dielectric withstand
IEC 255-5: 1977 2kV rms for 1 minute between all
terminals and case earth
2kV rms for 1 minute between terminals of
independent circuits including contact circuits, with
terminals on each independent circuit
connected together.
1kV rms for 1 minute across open
contacts of output relays.
High voltage impulse
IEC 255-5:1977 Three positive and three negative impulses of
5kV peak, 1.2/50 µs. 0.5J between all terminals
and all terminals and case earth.
5
Electrical environment
DC supply interruption The unit will withstand a 10ms interruption in
IEC 255-11:1979 the auxiliary supply, under normal operating
conditions, without de-energising.
AC ripple on DC supply The unit will withstand 12% AC ripple on the DC supply.
IEC 255-11:1979
High frequency disturbance 2.5kV peak between independent circuits
IEC 255-22-1:1988 Class III and case.
1.0kV peak across terminals of the same circuit.
Electrostatic discharge
IEC 255-22-2:1989 Class II 4.0kV discharge in air with cover in place
IEC 801-2:1991 Level 2 4.0kV point contact discharge
with cover removed.
Surge immunity
IEC 1000-4-5:1995 Level 3 2.0kV peak, 1.2/50µs between all groups and
case earth
. 2.0kV peak, 1.2/50µs between terminals of
each group
Fast transient disturbance
IEC 255-22-4:1992 Class IV 4.0kV, 2.5Hz applied directly to auxiliary supply
IEC 801-4:1988 Level 4 4.0kV, 2.5Hz applied directly to all inputs
EMC compliance
89/336/EEC Compliance with the European Commission
Directive on EMC is claimed via the Technical
Construction File route.
EN 50080-2:1994 Generic Standards were used to establish conformity
EN 5008-2:1995
Product safety
73/23/EEC Compliance with the European Commission Low
Voltage Directive.
EN 61010-1:1993/A2:1995 Compliance is demonstrated by
EN 60950:1992/A3:1995 reference to generic safety standards
71 26
4 holes 4.4 23.5
168 159
Push button
projection 10 max
Panel cut-out:
73 Flush mounting fixing details
32 212 25 min.
177
157 max.
Reset
77
6
Cases Atmospheric environment
Temperature
Relay type Case size IEC 255-6:1988 Storage and transit -25°C to +70°C
MCTI 19 3 Operating -25°C to +55°C
MCTI 39 4 IEC 68-2-1:1990 Cold
MCTI 40 6 IEC 68-2-2:1974 Dry Heat
Outline drawings are shown in Humidity
Figures 6, 7 and 8. IEC 68-2-3:1969 56 days at 93% RH and 40°C
Enclosure protection
Information Required IEC 529:1989 IP50 (dust protected)
with Order
Mechanical environment
Relay type
Vibration
CT Secondary rating IEC 255-21-1:1988 Response Class I
Setting range Endurance Class I
Auxiliary supply voltage
97 52
4 holes 4.4 23.5
168 159
Push button
projection 10 max
Panel cut-out:
99 Flush mounting fixing details
32 212 25 min.
177
157 max.
Reset
103
All dimensions in mm Flush mounting 11
149 103.6
4 holes 4.4 24
149 103.6
4 holes 4.4 24
168 159
Push button
projection 10 max
151
Panel cut-out:
Flush mounting fixing details
32 212 25 min.
177
157 max.
Reset
155
All dimensions in mm Flush mounting 11
168 159
Push button
projection 10 max
151
Panel cut-out:
Flush mounting fixing details
32 212 25 min.
177
157 max.
Reset
155
7
PROTECTION
MCAG 14/34
#4 " + (
$
' ' ) $ +
'
% '
- $' '
& %
& ' (
* ' % ' ( (
( ( ( , -. /
' $
* )
$ (
( ! "# 01 ! "# 21
' ' $
(
CUSTOMER BENEFITS
%
'
' )
,3 3
''( # "! ++ , + ++ , +
. !
" / *
! 0
"" ! "
*
"
* * "
! ! )1)
* " ! ' !
(-
" )2#1#3#,4 ++
+ # , +
0 ""
#%
! " 0
* ! ! !
*
!"#$
" " &" "
&
! "
)**$!# #* !+ "* $*
*$,) *$ $!#+
)4
5 )0 ) ) " 0
5 6' 5 6'
" " !
0
* ! !
"
!
" ! "
!
" " * 7
*
+& +&
! ' !
" " " ! ' ! = 7 ? +&
+&
' !
#+ 5588 ,+ = 7 ?
%90 " 0
7 "
7 : ;
* ! #+
: ; * ! !
" ! *
5< & * !
5< & % # &
7 * !
! =( >? " " ": ;
* ! =(:? @ # $ !
$ !
( > # = A ? %$" &" "
( ) $ () A #
(: ( )
# $ & ' ! " 0
() $ !
@# $" &" " ! ( )$ * ! !
PROTECTION /#012 3042 -053
MCAG 14/34
- ( "-# 9 5- $
! &! '
"# $ % -# ( . " 6 . . $
& ' - ( . < . . . " $
5(
# ( ) *+) ,- (
-
&! '
) *( % ! " # " $ " %
. 6 % ! .
) ( ! 7 . ") $ . ! 8 7) ! .
- ( . 7 ") $ '
) (
340 ) (- "# 9# 9# 9) $
-
&! '
- (
6;
)7 ( 7 + .
! 6 .& ! !
& . '
.
# . ") $
6 "- $
! . . & . ! 6
! ! ! . ! & :.
! < .
! !
!
; = :
! &! !
% .
!
- !
< .
& ! ! 6 > ,8 "
. < . $
! !
&
<
! . * " + !
. & . !
< . ! &
:. 8
% &' ( &'
)*
% + ,
# -% * * %* . /
0 /
1 -
% % -
# %-
2 /
% !
#
' 2
3 # $ #
/ 3
/ -4
/
3 5
# 1 -
. 2
" $ / /
*. % )* 3 6 #%*
) 7. % 8 3 6 #
%* )
" $ /#
*. 9% )* 3 6 # * " # $
) 7. 9% 83 6 #
* )
: $
*. % )* 3 6 #%*
) 7. 8 % 8
3 6 #%*
)-
PROTECTION /01 2 ) 3142) 153
MCAG 14/34
6* 6*
!
" " #4 ( $ (
! 5 6*7 # 5 *7 & "
" # !% $ % &
"
$
" ) "
" % & 3 $ 8 9 8 # 1" $ 8 9 8 #
:
'$ ( $ " : %
' %
) " ( $ ( : 6 % 6; 0' 9< 8
" " # & * # & + "
! / , " .
, - " " .
! " #
! !
$ & & $! 'B 'B
? ! %
'$ = % ! 4 # "
2 # "
? "
: *66 *
" "
( ?
( )
@ &A
3 !
%&
5 : <
5 : &
PROTECTION
MCAG 14/34
PROTECTION
MCAG 14/34
! """# # $
% ! &'' ()* +,-. /.) ),)
Features
MBCI Pilot wire differential A
protection relay
B
● High stability for through faults
C
● High speed operation for in-zone
faults
Trip Trip
● Simultaneous tripping of relays at Rpp Rpp
T2 T2
each line end T1 T1
Tr Tr
● Low current transformer Rs Tt øc øc Rs
requirements To To
Pilot wires
● Low earth fault settings RVD Ro Ro RVD
Ts
● Designed for the unit protection of V V
2
Application detect short circuit and cross- Emergency use for overcurrent
connected pilot conditions which protection
The Translay S differential schemes would not otherwise be detected. In the event of a pilot failure which
have been designed for the unit Indication is also provided for loss of cannot quickly be rectified, the
protection of overhead and the supervision supply. Translay S scheme may be adapted
underground feeders and transformer for use as a definite time overcurrent
feeders. Destabilising/intertripping
relay as follows:
When the protected line is connected
Plain Feeders to a busbar system, a fault on the If overcurrent relay is fitted
Differential protection busbars will in general be cleared by ● disconnect pilot wires and leave
Differential feeder protection requires the busbar protection by opening terminals open circuited
a comparison of the currents entering some or all of the local circuit
● set Kt to 3(300ms)
and leaving the protected zone. For breakers. Although such faults will
usually appear to the feeder ● check that overcurrent elements are
faults occurring within the protected
protection as through faults, with on the required setting above
feeder it is desirable to trip the circuit
resultant stability of the feeder maximum anticipated load current.
breakers at each end to isolate the
fault. Two MBCI relays are therefore protection, it may be desirable to If overcurrent relay is not fitted
required, one for each end of the open the remote line circuit breaker ● disconnect pilot wires and connect
feeder. A pair of pilot wires is used to also, to clear the line completely. a 1kΩ resistor across pilot terminals
transmit information between the two The remote unit of the differential of relay
relays so that each may be able to feeder protection can be caused to ● set padding resistors Rpp to
compare the current flowing at its operate, provided sufficient line maximum (600Ω)
respective end with the current at the current is flowing, by open circuiting
● set Kt to 3 (300ms)
other. the pilots. If line current is not flowing,
the remote unit can be operated ● set Ks to required open circuit
The relays at both line ends operate
(intertripped) by injecting a current setting: Ks = 1 gives three phase
simultaneously, providing rapid fault
into the pilots. equal to rated load Ιn.
clearance irrespective of whether the
NOTE: Other fault settings will
fault current is fed from both line ends
Overcurrent check/starting depend upon the summation ratio.
or only one line end.
Although the supervision scheme
When applying this protection to
provides indication of pilot failure it
overhead lines the limiting factor is
does not prevent the protection
generally the length of the pilot
operating if primary current above
circuits: for cable feeders the limiting
setting is flowing. Where this hazard
factors are more likely to be the level
is unacceptable it is necessary to add
of line charging current and the
an overcurrent check feature.
method of system earthing.
The current transformer requirements
Pilot supervision are not modified by the addition of
Correct interchange of information overcurrent elements since they
over the pilot circuit is essential for the present a very low burden.
proper functioning of any differential When the starting feature is used the
feeder protection. overall operation time of the scheme
Pilots may be exposed to hazards and is increased by 3-5ms. However,
some risk of damage and failure there is no increase in the overall
always exists. The most common pilot operation time when the overcurrent
failure is to the open circuit state, protection performs a check function
caused by the accidental excavation only.
of buried pilots or storm damage to When overcurrent relays are used the
overhead pilots. With the pilots open protection cannot be intertripped by
circuited the differential protection will ac injection into the pilots, and
be unstable and will trip the feeder if destabilising the protection will result
sufficient through current is flowing. in tripping only if an overcurrent
For this reason the circulating current condition exists simultaneously.
system is often preferred as such
schemes will fail safe and trip so that
attention is immediately drawn to the
fault. The addition of pilot supervision
will not prevent tripping for pilot faults
but will indicate the cause. It will also
3
Protected Zone Protected Zone
P1 P2 P2 P1
A
S1 S2 S2 S1
B
C
12
See
RS Note 5 RS
MBCI 13 + MBCI
Power
23 Supply VX
Circuits 14
ΙA –
See
Note 4
24
25
& Enable 11
See
23
24 ΙA
Squarer Kt 1
ΙB
RL1
2 Note 2 25
RL1–1 3
26
5 26 ΙB
27 Enable
A 27
ΙC 2
Level RL2 28 ΙC
ΙN 28 2 RL1–2 4
C B Detector 6 ΙN
Phase OP
Trip/
&
RL3
Rotation 1 Alarm
KS RES 7
RO Outputs
RL2–1 9
Squarer
Case Earth
See Note 3 8
Case earth
RL2–2
1 2
3 4
10
RPP 17
5 6
7 8
9 10 18 Pilot
11 12
Wires
13 14 19
15 16
17 18
Notes
19 20
1. (a) C.T. shorting links make before (b) & (c) disconnect. 3. Earthing connections are typical only.
21 22 Module
23 24 terminal block (b) Short terminals break before (c) 4. C.T. connections are typical only.
25 26
viewed from (c) Long terminal. 5. For overcurrent start schemes, terminal 12 must be
rear connected directly to D.C. +VE to provide a supply for
27 28
2. Link terminals 11 and 13 except when used with overcurrent the L.E.D. and reset circuits.
check replay type MCRI.
17 17
18 18
17 18 17 18
19
Case 20
Earth MRTP02
20
RL2 OP RL7
2 1 Supply
19 Reset
Fail
A.C. 27 OP
A.C. RL1 RL3 RL6 1
Auxiliary 2 2 1 Pilot
28 Power Reset RL4–1 3
Supply Supply S/C Output
13 OP RL8
5 Contacts
D.C. Reset 1 Pilot 2 Change
Case earth Vx 14 Power O/C RL4–2 4 state for
Supply
1 2 RL4 6 pilot fail
3 4 2
7
5 6
RL5–1 9 Output
7 8
9 10 11
Contacts
11 12
MRTP01 Change
8
13 14 +VE
RL5 state for
2 RL5–2 10
supply
15 16
RL1 RL2 RL3 RL1 RL2 RL3 12
17 18 Case fail
–1 –1 –1 Start –2 –2 –2
19 20
Earth t
21 22
23 24
25 26 Module terminal block Note 1.
27 28
viewed from rear (a) C.T. shorting links make before (b) & (c) disconnect.
(b) Short terminals break before (c).
(c) Long terminal.
Figure 3: Application diagram: pilot supervision relay and injection filter type MRTP 01
4
Pilot isolation Pilot isolation
transformer transformer
P6 S2 S1 P1
17 17
P5
P4 X2 X1
P3
P2
MBCI Pilots MBCI
P2
X2 P3
X1 P4
P1 S1 S2 P5
18 18
P6
S1 S2 Supervision
isolation
P1 P2 transformer
20 OP
RL2 RL7
2 1 Supply
19 Reset See
Fail
A.C. 27 OP Note 7
A.C. RL1 RL3 RL6 1
Auxiliary 2 2 1 Pilot
28 Power Reset RL4–1 3
Supply Supply S/C Output
13 OP RL8
5 Contacts
D.C. Reset 1 Pilot 2 Change
Vx 14 Power O/C RL4–2 4 state for
Case earth Supply
RL4 6 pilot fail
1 2 2
3 4
7
RL5–1 9
Output
5 6
Contacts
7 8 11
9 10 MRTP 03 Change
8
11 12 +VE
RL5 state for
13 14
2 RL5–2 10
supply
16
RL1 RL2 RL3 RL1 RL2 RL3 12 fail
15 Case –1 –1 –1 Start –2 –2 –2
17 18
Earth t
19 20
21 22
23 24 Note 1.
25 26
(a) C.T. shorting links make before (b) & (c) disconnect.
27 28
Module terminal block (b) Short terminals break before (c).
viewed from rear (c) Long terminal.
Figure 4: Application diagram: pilot supervision relay 15kV isolation type MRTP 03
P1 P2
A A
S1 S2
B
C C B +
D.C. _
See Phase
Note 4 Rs Rotation
See Note 2(B)
13 See Note
Power 23 11
2(A)
supply 24
14 13
circuits 25
23 ΙS (A) 26 14
27
Case earth 24 28
1 2
25
3 4 ΙS ( ) RL1
5 6 2 5
26 RL1–1 1 MBCI
7 8
27 3
9 10
ΙS (C)
11 12 6
13 14 RL1–2 2
28
15 16 Case earth MCRI 4
17 18 See Note 3
19 20
Case earth
21 22
See Note 3
23 24 Notes
25 26
1. (a) C.T. shorting links make before (b) & (c) disconnect. 2. (A) Connection for overcurrent start
27 28
Module terminal block (b) Short terminals break before (c). (B) Connection for overcurrent check
viewed from rear (c) Long terminals. 3. Earthing connections are typical only
4. C.T. connections are typical only
5
Transformer Feeders
Scheme Pilot Supervision O/C
(Use of transformer inrush current Insulation Start/Check Arrangement of Equipment
detector) Level (kV) (Viewed from front)
In the case of transformer feeders
A 5kV — —
where there is no circuit breaker 1 1
side only.
1 8 4 9 7 1 8
When the feeder transformer is L 15kV ●
energised any resulting inrush current
M 5kV — 1 8 1 8
will be detected by the MCTH relay,
the output blocking unit of which will
N 15kV — 1 8 1 8
pick-up causing the pilot wires of the
Translay S to be short-circuited. This 1 8 2 1 8 3
O 5kV ●
will stabilise the differential relay and
prevent it from responding to what 1 8 4 1 8
P 15kV ●
would otherwise appear to be an in-
zone fault. Table 2. Typical scheme arragements for transformer feeders. See key below.
The immunity to operation due to No. Type of relay
inrush current is coupled with fast fault
1 MBCI 01/02 Differential
clearance times and the built-in
2 MRTP 01 Pilot supervision and injection filter
overcurrent detectors of the MCTH
3 MRTP 02 Injection filter
relay ensure that the blocking feature
4 MRTP 03 Pilot supervision
is overridden if a fault is detected in
5 MCRI 01 Overcurrent start/check
one phase whilst inrush is present in
another. 6 MVTW 01 Destabilising
7 MVTW 03 Destabilising and Intertripping
Symbols: Schemes A to D can be fitted with relay types 6 or 7.
Schemes E to H can be fitted with type 6 which will provide
destabilising if the overcurrent start/check relays (MCRI 01)
have operated. Schemes I to L must use type 7 or 8.
15kV Isolating transformer 8 MCTH 01 Transformer inrush current detector
9 MFAC 14 High impedance earth fault relay
10 MMLG Test plug/block
It is advisable on all schemes to include the test unit to
15kV Isolating transformer with facilitate commissioning and routine testing. The unit will be
injection filter situated on the right–hand side of the scheme.
6
Description faults ΙX=ΙY). The expressions are of Pilot supervision
opposite sign for values of ΙY which Figure 3 shows the arrangement for
Differential protection are negative relative to ΙX and are pilot supervision in a pilot circuit
The differential feeder protection between 0.5ΙX and 2ΙX in value. The insulated for 5kV. In this instance the
circuit is derived from the well known system is stable with this relative injection filters and the supervision
Merz-Price circulating current system polarity and operates for all values of unit are assembled with the relay
but employs phase comparators as the ΙY outside the limits. case. (Types MRTP 01/02). Figure 4
measuring elements. This novel The phase comparator has angular shows the similar arrangement for
combination provides high stability limits of ± 90° giving a circular bias pilot circuits insulated for 15kV (Type
performance for external faults with characteristic in the complex plane. MRTP 03). The injection filters are
the minimum of bias (restraint) If the pilots are open circuited, current then assembled as part of the isolation
quantity thereby ensuring that the low input will tend to operate the relay. transformer and have to be isolated
earth fault settings are effectively Conversely, short-circuited pilots will from the supervision relay. The
retained even when load current is cause the relay to restrain, holding its supervision isolation transformer
flowing. contacts open. provides the necessary 15kV isolation
Figure 1 shows the basic circuit barrier. For further technical
Transformers T1 and T2 also provide
arrangement. A summation current information see Publication R6026.
the necessary insulation barriers for
transformer T1 at each line end static circuitry. Destabilise and Intertrip Facilities
produces a single phase current
The input circuits of the phase MVTW01
proportional to the summated three
comparator are tuned to the power
phase currents in the protected line. Refer to Figure 6.
frequency so that the threshold of
The neutral section of the summation Operation of the destabilising relay
operation increases with frequency.
winding is tapped to provide (UN) results in the summation current
This de-sensitises the relay to the
alternative sensitivities for earth faults. transformer in the differential relay
transient high frequency charging
The secondary winding supplies current that flows into the line when it being short circuited and the local
current to the relay and the pilot is energised. A further advantage relay prevented from tripping. The
circuit in parallel with a non-linear provided by the tuned input is that the remote relay then sees a single end
resistor (RVD). The non-linear resistor waveform of the derived signal, which feed condition and trips, provided the
can be considered to be non- may be severely distorted by current through current exceeds the no-load
conducting at load current levels. transformer saturation, is improved, fault setting of the protection (see
Under heavy fault conditions it ensuring high speed operation under Table 5 page 16). Typical operating
conducts an increasing current and adverse conditions. times are shown in Figure 7.
thereby limits the maximum secondary In order to maintain the bias Terminals 17 and 20 should normally
voltage. At normal current levels the characteristic at the designed value it be linked together on the destabilising
secondary current flows through the is necessary to pad the pilot loop relay. However, the operating level of
operating winding To on transformer resistance to 1kΩ. the remote equipment can be reduced
T2 and then divides into two separate to one half of the normal fault setting
A padding resistor Rpp is provided in
paths, one through Ro and the other (under destabilising operation only) if
the relay for this purpose.
through the restraint winding Tr of T2, this link is omitted.
the pilot circuit and resistor Ro of the Pilot isolation transformers It should be noted that, with this link
remote relay. omitted, if the destabilising relay UN
When pilot isolation transformers are
The resultant of the currents flowing in used, the range of primary taps is operated for longer than the
Tr and To is delivered by the third enables pilots of loop resistance up to supervision time delay (6-10 seconds)
winding on T2 to the phase 2.5kΩ to be matched to the relay. an indication of pilot failure will be
comparator and is compared with the The pilot insulation level is also raised given. This does not apply if pilot
voltage across Tt of Transformer T1. to 15kV by these transformers. isolating transformers are used.
The emf developed across Tt is in When overcurrent elements are used
phase with that across the secondary Telephone type pilots to provide a starting or check function
winding Ts which is in turn When the pilots to be used are of the there is no advantage in removing this
substantially the voltage across Ro. telephone type, an alternative limiter link since, for operation, the through
Taking into account the relative values based on a zener diode is available current must exceed the overcurrent
of winding ratios and circuit to ensure that the maximum voltage setting.
resistance values, it can be shown that which can appear on the pilot system
the quantities delivered for is within prescribed limits. Pilot
comparison in phase are: isolating transformers can be used in
(ΙX + 2ΙY) and 2ΙX + ΙY) this arrangement also, both to provide
insulation to 15kV and also indirectly
where ΙX and ΙY are the currents fed
to enable pilots of relatively high
into the line at each end (for through
resistance to be used.
7
MVTW 03
Pilot isolation transformer P6 S2
A circuit diagram for the MVTW 03 17
type relay which depicts the Pilots
destabilising, intertrip and inverter P1 S1
function is shown in Figure 8. MBCI
On energising the relay, a green led 17 UN-1
illuminates and the normally closed
18
contacts of RL1 open to indicate the 18 UN-2
supply is healthy and the inverter is 19
19
operating. UN-3
20
The MVTW 03 incorporates a full Case earth
1 2
bridge inverter, which receives 11 UN
3 4 Vx(1)+ 3
complementary square wave signals 5 6
Vx(2)+
12
7 8 13
from the oscillator circuit at a 9 10
Vx(3)+
14
frequency of 80Hz. This frequency 11 12
13 14
was chosen because it lies sufficiently 15 16 MVTW 01
far from the pilot frequency of 50 or 17 18
8
Pilot isolation transformer P6 S2
17
Pilots
P1 S1
MBCI
17
18
18
19
19
11+VE
Trip send
Case earth RL2
2
1 2 RL2-2
3 4
5 6
7 8
9 10 RL2-1
11 12 13+VE
13 14 RL1-1 1
Power
15 16 Vx RL1
2 Supply fail
14–VE supply 1
17 18 MVTW 03
19 20
Supply
21 22
23 Case earth See note 2 healthy
24
25 26
27 28 Notes
1. (a) CT shorting links make 2. Earthing connections as shown is typical only
before (b) & (c) disconnect
Module terminal block
(b) Short terminals break before (c)
viewed from rear
(c) Long terminals
P2 P2 P1
A I i A
S1 S2 S2 S1
B II ii B
C III iii C
yn
N.E.R.
23 MCTH MCTH 23
24 24
17 17
25 25
26 26
19 19
27 27
28 28
23 MBCI 17 17 MBCI 23
24 24
25 Pilots 25
26 26
27 18 18 17 18 27
28 19 19 28
MVTW03
MFAC14 1
27
RVD3 3
28 11
Note1: It is essential that the current transformer connections are earthed at one point only.
9
N = 6 A–N
15 3
10 2
N = 3 B–N
5 1
A–C
A–B
1 2 1A relay
0
5 10 5A relay
Current in summation current transformer primary – Amps
200 Metrosil
Limiter
160
Pilot Voltage (V Peak)
120
Zener
80
Limiter
40
0 10 20 30
A-N fault current (x In)
10
2.0
1.8
1.4
1.2
1.0
0 1 2 3 4 5
Pilot intercore capacitance -µF
Figure 12: Effect of pilot capacitance and pilot isolating transformers on setting
20 10
Figure 13: Minimum earth fault current for operation with through load
11
CTs
CTs
RL RL RL
CTs
End A End B
Pilots
Relay Relay
240
200
Operation time (Milliseconds)
160
120
80 Kt = 6
Kt = 14
40 Kt = 20
Kt = 40
0
1 2 3 4 5 6 10 20 30 40 50 60 80 100
Current (multiples of setting)
60
Induced pilot loop voltage to operate
40
20
0
0.5 1.0 1.5 2.0
Setting multiplier – Ks
12
Transformer (Dy 11)
Feeder
Delta Star
23 25 27 17 17 23 25 27
MFAC N.E.R.
MCTH MCTH
inrush A B C REF inrush A B C
detector detector
24 26 28 19 19 24 26 28
MBCI MBCI
23 23
25 1.25 17 17 1.25 25
27 1 1 27
24 6 6 24
18 Pilots 18
26 26
28 28
Figure 17: Overall protection of transformer feeders showing connections to MBCI relays
13
Contacts
Contact arrangements 2 make and 2 change-over
(See Figure 2)
Contact ratings
Make and carry for 0.2s 7500VA subject to maxima of 30A
and 300V ac or dc
Carry continuously 5A ac or dc
Break ac 1250VA
dc 50W resistive
25W inductive
L/R = 0.045s
subject to maxima of 5A and 300V
Durability
Loaded contact 10,000 operations minimum
Unloaded contact 100,000 operations minimum
Reset time Less than 100ms
Indication A non-volatile led trip indicator is used.
If the auxiliary supply is lost the led will
return to the same state when the supply
is restored.
Stability level The stability of the protection for through
faults is greater than 50Ιn
High voltage withstand
Dielectric withstand
IEC 255-5: 1977 2.0kV rms for 1 minute between all
terminals and case earth.
2.0kV rms for 1 minute between all
terminals of independent circuits, with
terminals on each independent circuit
connected together.
5.0kV rms for 1 minute between pilot
terminals and all other terminals and
case earth.
1.0kV rms for 1 minute across
normally open contacts.
High voltage impulse
IEC 255-5: 1977 Three positive and three negative
impulses of 5.0kV peak, 1.2/50µs,
0.5J between all terminals and all
terminals and case earth.
Electrical environment
DC supply interruption
IEC 255-11: 1979 The unit will withstand a 10ms
interruption in the auxiliary supply,
under normal operating conditions,
without de-energising.
AC ripple on dc supply
IEC 255-11: 1979 The unit will withstand 12% ac ripple
on the dc supply.
High frequency disturbance
IEC 255-22-1: 1988 Class III 2.5kV peak between independent
circuits and case.
1.0kV peak across terminals of the
same circuit.
14
Fast transient disturbance
IEC 255-22-4: 1992 Class IV 4.0kV, 2.5kHz applied directly to
auxiliary supply.
IEC 801-4: 1988 Level 4 4.0kV, 2.5kHz applied to all inputs.
Surge immunity
IEC 1000-4-5: 1995 Level 3 2.0kV peak, 1.2/50µs between all
groups and case earth.
2.0kV peak, 1.2/5-µs between
terminals of each group.
EMC compliance
89/336/EEC Compliance to the European
Commission Directive on EMC is
claimed via the Technical Construction
File route.
EN 50082-2: 1994 Generic Standards were used to
EN 50082-2: 1995 establish conformity.
Product safety
73/23/EEC Compliance with European Commission
Low Voltage Directive.
EN 61010-1: 1993/A2: 1995 Compliance is demonstrated by
EN 60950: 1992/A3: 1995 reference to generic safety standards.
Atmospheric environment
Temperature
IEC 255-6: 1988 Storage and transit –25°C to +70°C
Operating –25°C to +55°C
IEC 68-2-1: 1990 Cold
IEC 68-2-2: 1974 Dry heat
Humidity
IEC 68-2-3: 1969 56 days at 93% RH and 40°C
Enclosure protection
IEC 529: 1989 IP50 (dust protected)
Mechanical environment
Vibration
IEC 255-21-1: 1988 Response Class 1
Pilots
Pilots isolation
Pilot isolation transformers are required when any longitudinally induced voltage
in the pilot circuit is likely to exceed 5kV: in effect this means when protecting
feeders operating at voltages in excess of 33kV, unless these are short in length.
The use of pilot isolation transformers also extends the acceptable range of pilots.
This is achieved by the matching ratios available as shown in Table 4.
Pilots
KM 0.8 1.0 1.2 1.5 2.5 Matching ratio
Loop resistance 800 1000 1200 1500 2500 Ω
Capacitance 6.25 5 4.2 3.3 2 µF
Terminals P1-P6 P1-P5 P1-P4 P1-P3 P1-P2
Table 4
15
Rp
The optimum value for KM is the nearest value in Table 4, where Rp is the
1000
measured pilot loop resistance.
There are two types of pilot isolation transformers: ZC0244-002 for schemes
without pilot supervision: HN0068-001 for schemes with pilot supervision.
The latter includes the injection filter for the pilot supervision circuit.
1 R
The pilot padding resistor (Rpp) at each end should be set to: 1000 – p
2 KM
Pilot voltage
The voltage applied across the pilots varies with fault current as shown in
Figure 12. For normal through load conditions the peak pilot voltage will be in
the order of 50V rising to a maximum of: 200V for MBCI 01, 80V for MBCI 02
under fault conditions.
When pilot isolation transformers are used this value of voltage is multiplied
by √ KM.
Note: Types MBCI 01 and 02 are not compatible. Relays should be of the same
type at either end.
Pilot current
The pilot current is typically 30mA for normal through load conditions and rises
to a maximum of 300mA under through fault conditions.
16
phases involved in the fault. The minimum earth fault current (Ιf) should be greater
than twice the least sensitive earth fault setting to ensure rapid fault clearance.
The range setting of fault settings is shown in Table 5.
Differential
(Summation ratio = 1.25/1/N) Fault Settings
N=3 N=6
Ks is a setting multiplier A–N 0.19Ks.Ιn 0.12Ks.Ιn
and may be varied B–N 0.25Ks.Ιn 0.14Ks.Ιn
from 0.5-2.0 C–N 0.33Ks.Ιn 0.17Ks.Ιn
Ιn is the A–B 0.8Ks.Ιn
rated relay B–C 1.0Ks.Ιn
current C–A 0.44Ks.Ιn
A–B–C 0.5Ks.Ιn
Table 5
The minimum operating current of the relay will be increased by any shunt
impedance connected across the pilot wires, for example, pilot capacitance and
the magnetising path of the pilot isolation transformers. The effect of the pilot
capacitance is shown in Figure 12.
Values of Ks from 0.5 to 1.0 are provided to achieve effective fault setting equal
to the nominal value indicated in Table 5. This is achieved by single end injection
tests during commissioning. Values of Ks from 1.0 to 2.0 are used to increase the
setting when the application demands. Refer to section: Line Charging current.
17
Magnetising current:
In order that the minimum effective operating current of the relay remains low, it
is necessary to apply a limit to the value of the magnetising current demanded
by the line current transformers:
10
IM ≤ 0.05 In at V
In
Mesh type switchgear arrangements
The relay may be fed by parallel connected current transformers as shown in
Figure 15. It is essential to balance the lead resistance in the circulating
secondary current path to ensure stability for a through busbar fault. Connecting
the current transformers as shown in Figure 15 will result in the required balance
being obtained. It is essential that the current transformers at the same end
should have similar magnetising characteristics. The value of RCT to be used in
calculations should be the resistance of one current transformer plus the
resistance of one lead between the two parallel connected current transformers.
The value of RL should be the resistance of a single lead from the common
connection of the current transformers to the relay.
Methods of reducing the current transformer requirements:
In general the larger the current transformer the better the overall performance.
However, when current transformer size is critical the following notes should
prove helpful.
● The operation time varies with fault current as shown in Figure 16. Stability is
maintained with smaller current transformers if the value of Kt is reduced. This
will of course result in the operation time increasing, typical operation times
being:
Kt 40 20 14 6 3
Time at 5x setting 30 50 65 90 300 (ms)
● Kt= 20 will suit most current transformers on distribution systems
Kt = 40 is the preferred setting for EHV systems where high speed operation
is required
● It should be noted that the knee point requirement increases with the nominal
current rating Ιn. Advantage is therefore obtained by using a low value of
rated current eg. 1A or even 0.5A.
● Wires may be connected in parallel to reduce the lead resistant (RL ) and
hence the current transformer requirements.
● If the relay is fed from delta connected line current transformer then N = 1.
● If one relay is used per phase then assume N = 1
Stabilising resistance
VK 12
Rs = Ω but not greater than Ω
40 In In2
Note: This resistor is not required for single phase protection or when Translay S
is fed from delta connected current transformers.
Additional requirements:
● It is a stability requirement that the relays at both ends have the same value of
N & Kt selected.
● It is preferred, although not absolutely essential, that the equipment at the two
line ends have the same rated current Ιn.
18
current in the relay: this current must cause the fuse to operate quickly enough to
discriminate. Most fusing time curves show pre-arcing time and some allowance
must be made for the arcing period.
To accommodate the largest teed load, use may be made of the Ks (setting
multiplier) adjustment, and/or selection of a value of Kt corresponding to a lower
operating speed.
The particulars tabulated below for teed loads connected to a fused 11kV feeder
may be helpful as a general example.
Feeder 11kV 300A rating
Tee Transformer rating(kVA) Fuse rating (A) Ks Kt
300 20 1 40
400 25 1.7 40
400 25 1.5 6
500 30 1.75 3
Table 6
The table above refers to individual teed loads. When smaller loads are connected
at separate locations, on the basis that only one will be subject to a fault at any
instant, the aggregate load may be greater. For example twelve 100kVA
transformers each protected by 10A fuses could be connected to the above line,
with main protection settings Ks = 1 and Kt = 40. Similarly for ten 300kVA
transformers each protected by 20A fuses, relay settings Ks = 2.0 and Kt = 20
would be suitable. In general the aggregate tee-off load should not exceed 0.25Ks x
current transformer rating.
19
Line Current Transformer Requirements for Transformer Feeders:
Operating times less than 80ms will be achieved and through fault stability assured
provided the following CT requirements are satisfied (Kt = 14):
Vs = If (I3 + R
n2
)
CT + RL
The effective primary operating circuit (Ιop) of the MFAC 14 is given by:
Iop = n(IR + NIIu)
Where IR = relay operating current and metrosil current at setting voltage
(see MFAC publication)
Iu = current transformer magnetising current at setting voltage (A)
Nl = number of connected current transformers
n = current transformer turns ratio
The following notes on this application are also important:
– A setting of 14 is recommended for Kt to ensure sufficient time for inrush blocking.
Tripping for internal faults will then occur (typically) within
60-80 ms.
– The N = 6 setting on the MBCI relay must be used to achieve increased sensitivity.
– Where the CT lead resistance is a predominant part of the CT burden at one, or
both, line ends then the use of 1A line CT’s is recommended. The selected rating
of current transformers must be the same as the relays (MBCI and MCTH) which
they supply.
– Additional conductors may be connected in parallel in order to reduce the lead
resistance (RL) and, hence, the current transformer requirements.
– The pilot resistance should not exceed 700Ω.
20
– With 15kV pilots, the MCTH output contacts should be connected on the relay
side of the isolating transformer to terminate numbers 17 and 18 of the MBCI
relay.
– The MCTH overcurrent settings for each phase, set by 3 front-mounted
potentiometers (one per phase), should be set at least 50% above the
maximum possible load current.
– The steady state magnetising current must not exceed the three phase fault
setting of the MCBI relay. For a Ks = 1 setting, the three phase fault setting is
14% of rated current. If the transformer is likely to be subjected to overfluxing,
with the corresponding increase in steady state magnetising current, then the
three phase setting must be permanently set above this higher magnetising
current by increasing Ks.
Cases
103.6
Relay type MBCI is provided in case 149 4 holes 4.4
23.5
size 6 as shown in Figure 18.
21
P1 2.5 1.5
1.2 1.0 0.9 S1 S2
Injections 172 mm
Inputs
X1 X2
340 mm
64.5 mm
154 mm
30 mm 116 mm 9 mm
176 mm
Figure 19: Pilot isolation transformer with filter. With insulation for 15kV
244 mm
176 mm 190 mm
45 mm
171.5 mm
8-M6 Terminals
9 mm
4 Fixing holes, M6 clearance
64.5 mm
30 mm 116 mm
Figure 20: Pilot isolation transformer without filter. With insulation for 15kV
22
19 mm 134 mm 19 mm 69 mm
S2
98 mm
S2
2 off M5 studs
2 off M5 studs
52 mm 69 mm
8.5 mm 50 mm 52 mm
Figure 21: Pilot supervision isolation transformer. With insulation for 15kV
2BA connection
screws
354 mm
48 mm
2 holes
6.5 mm 310 mm 48
mm
342 mm
23