Product Data Sheet

Product Sinopec Insulated Transformer Oil


Summary Product description
Sinopec Insulated Transformer Oil is a series of products blended using highly
refined mineral oil and a selected antioxidant. It is designed for insulating and
cooling transformers, oil-immersed switch-gear and other electrical insulating
applications. There are four grades, I-0℃, I-10℃, I-30℃ and I-40℃, which
are selected on the basis of their low-temperature performance. None of the
grades contain harmful polychlorinated biphenyls (PCBs).

Available sizes
Also
available
in bulk

DRUM – 200L IBC – 1000L

Applications
Sinopec Insulated Transformer Oil is suitable for use in:
 Oil-filled transformers, operating at 330 kV or less, where it acts as a non-conducting insulating and cooling
medium.
 Oil-immersed switch-gear.
 Other electrical insulating applications.

Features and benefits


 Excellent dielectric (insulating) properties, effectively prevent discharge in an electric field.
 Low viscosity and low density lead to the oils having good cooling properties and good heat transfer
characteristics at room temperature and below, and so ensure effective cooling of transformer core and coils.
 Even at very low temperatures the oil viscosity remains low, and therefore allows the transformer to be started
up under very cold conditions without problem.
 Excellent oxidation stability characteristics are provided by the stable base oil together with the high-
performance oxidation inhibitor system, and prevent the formation of acidic material and sludge in service,
extending the life of the oil.
 All four grades meet the requirements of IEC 60296:2003 for transformer oils.

The information contained herein is subject to change without notification due to continuing
research & development therefore properties may be subject to slight variations.

PERFORMANCE IN MOTION
Page 1
Product Data Sheet
Typical Data
Sinopec Insulated Transformer Oil
Grade I-0℃ I-10℃ I-30℃ I-40℃
2
Kinematic viscosity,mm /s, ASTM D 445
cSt @ 40℃ 8.93 9.34 9.91 9.68
cSt @ -10℃ - 116.0 - -
cSt @ -30℃ - - 423.4 753.0
Corrosive sulfur, ASTM D 1275 B not corrosive not corrosive not corrosive not corrosive
Dielectric Breakdown (as received) , kV, IEC
50 47 50 53
60156
Dielectric dissipation factor @ 90℃, IEC 60247 0.0009 0.0007 0.0008 0.0001

Interfacial tension, mN/m, ISO6295 49.1 47.3 47.1 48.7

Oxidation stability, 164 h @ 120℃, IEC 61125C


total acidity, mg KOH/g 0.09 0.02 0.0822 0.0218
sludge, wt% 0.04 0.008 0.0075 0.0175
Pour point,℃, ISO 3016 -39 -42 -45 -54

Flash point (PMCC), ℃, ISO 2719 162 153 158 154

Density @ 20℃, g/mL, ISO 3675 0.8486 0.8330 0.8378 0.8354


These data are given as an indication of typical values and not as exact specifications.

Industry and OEM specifications


Sinopec Insulated Transformer Oil meets the performance requirements of the following industry
specifications:

IEC 60296:2003
1
GB 2536-2011

Sinopec Q/SH 303 525-2009


1
Note: ‘GB’ standards are the National Standards of the People’s Republic of China.

Sinopec Insulated Transformer Oil holds the following formal OEM approvals:

ABB Specification 1ZBA117001-1:


1
HI-B (Sinopec 25 Transformer Oil )
1
HI-A (Sinopec 45 Transformer Oil )
1
Siemens TUN 901 293 (2007) (Sinopec 25 and 45 Transformer Oil )
1
Note: Sinopec 25 and 45 Transformer oil is now changed the name as Sinopec I-10℃ and I-40℃ general
Transformer Oil, the process and properties are the same.

The information contained herein is subject to change without notification due to continuing
research & development therefore properties may be subject to slight variations.

PERFORMANCE IN MOTION
Page 2
Product Data Sheet
Accuracy of information
Data provided in this PDS is typical and subject to change as a result of continuing product research and development.
The information given was correct at the time of printing. The typical values given are subject to variations in the testing
procedures and the manufacturing process may also result in slight variations. Sinopec guarantees that its lubricants
meet any industry and OEM specifications referred to on this data sheet.
Sinopec cannot be held responsible for any deterioration in the product due to incorrect storage or handling. Information
on best practice is available from your local distributor.

Product and environmental safety


This product should not cause any health problems when used in the applications suggested and when the guidance
provided in the Material Safety Data Sheet (MSDS) is followed. Please consult the MSDS for more detailed advice on
handling; MSDSs are available from your local distributor. Do not use the product in applications other than those
suggested.
As with all products, please take care to avoid environmental contamination when disposing of this product. Used oil
should be sent for reclamation/recycling or, if not possible, must be disposed of according to relevant
government/authority regulations.
The SINOPEC trademark is registered and protected.

Issued: March 2017


© Sinopec 2017 Sinopec Insulated Transformer Oil

The information contained herein is subject to change without notification due to continuing
research & development therefore properties may be subject to slight variations.

PERFORMANCE IN MOTION
Page 3