MPS 3000
Motor Protection and Control Relay
The MPS-3000 is an ideal solution for Medium and Low
Voltage motors because it provides a comprehensive
control and protection package. The MPS-3000
monitors 3-phase currents and voltage using 10 RTD/
Thermistor temperature inputs.
The MPS-3000 is available in two configurations - as a
protection relay and as a motor controller. The unit can
also be mounted vertically or horizontally based upon
the system configuration.
Certified Protection Advanced Features
Monitoring 10 temperature inputs, 3-phase current,
ANSI/IEEE
C37.2
PROTECTIONS MPS 3000 voltage and energy
3 Communication failure / Internal failure √ Power measurement (3-phase voltage measurement)
27 Under-voltage √ Statistical data of last 10 trips with time and
32L Under Power Level 1/2 √ date stamp
37 Under current Level 1/2 √ RTD bias for thermal overload
46 Current Imbalance Level 1/2 √
Multiple Thermal Overload curves
47 Phase sequence/loss √
48 Max. Start Time √
Too Many Starts pre-alarm, configurable to energize
49R High Temp. Level 1/2, sensors 1-10 √ dedicated output relay
49/51 Thermal Capacity Level 1/2 √ Capture and display of min and max RMS, average of
50 Over Current Level 2 - Short √ 3-phase current, one voltage, min and max frequency
50G Ground Fault Level during starting √ Ground Fault setting during start eliminates
50G/N Ground Fault Level 1/2 √
nuisance trips
51L Load Increase - Alarm √
MODBUS communication, remote parameter
51R Over Current Level 1 - Jam √
55 Lead / Lag PF / Low Power Factor √
programming, control and supervision.
59 Over-voltage Level 1/2 √ Programmable discrete inputs/output
66 Too Many Starts Level 1 √ 4 programmable analog outputs
49R RTD 1-10 Level 1/3 √ 4 programmable analog inputs
74 Control Circuit Open √
74 Welded Contactor √
86 or 94 External Fault 1/2/3 √
MPS 3000-C
Motor Protection Controller
The MPS-3000-C includes the same functionality as
the standard MPS-3000, but it incorporates motor
control capabilities. It includes various starting methods
including Direct Online, Star Delta, Soft Starters,
Reversing and Two Speed. The MPS-3000-C includes
twenty dry optically isolated logic inputs that are used
to enable different types of control.
How To Order
Example:
MPS-3000 P - V - 1P - 2 - 3P
Relay Type Construction Thermal Sensor Control Voltage Options
P - Motor Protection V - Vertical 1P - 10 RTD Platinum 2 - 110-230VAC 2- Trip on disconnected
Relay H - Horizontal 1C - 10 RTD Copper 2S - 110-230V AC/DC RTD
C - Motor Protection TP - 4 Thermistors+ w/ separate AUX M- Modbus
Controller 6 RTD (Pt100) 3 - 19-60VDC P- Profibus
TC - 4 Thermistors+
6 RTD (Copper)
Unit Dimensions (mm)
Model Weight (kg)
H W D
Vertical 310 134 140
3.1
Horizon 140 310 134
Meeting your needs across industries
WATER OIL & GAS INDUSTRY MINING MARINE
For More Information
www.solcon.com.
[email protected]