PSOC 2020 2021 Class Test 1
PSOC 2020 2021 Class Test 1
Class Test 1
Full Marks: 15, Time: 1 Hour
L INSTITUTE OF TECHNOLOGY Write Roll Number on each page of your answer script. Save the file as your rollno.pdf and upload.
ROURKELA
1. Refer the network shown below. Per-unit impedance of each circuit of the double-circuit line 1-2 is given in Annexure 1.
Full-line charging admittance of the transmission line (ȳ120 ), reactance of the generator and that of the transformer are
given in per-unit on a common MVA base. Off-nominal tap ratio of the regulating transformer is as marked. Bus 1 is a
voltage controlled bus. [4+5+6]
(a) If V̄1 = 1.0∠0o pu and V̄2 = 0.98∠ − 2o pu, calculate active and reactive power drawn by the load at bus 3.
(b) If the active power demand at bus 3 is increased by 20% keeping the reactive power same as above, determine voltage
magnitude and angle of all buses using two iterations of FDLF. Take the initial value of voltages equal to the voltages
obtained in 1(a). Consider bus 1 as reference.
(c) Positive and negative sequence reactance of the generator are same as xg , zero sequence and neutral reactances are
0.03 pu, 0.02 pu, respectively. Zero sequence impedance of the transmission line is 2.5 times of the positive sequence
(1)
impedance (z̄12 ). Positive, negative and zero sequence reactance of the transformer are same as xt . A bolted double-
line-to-ground fault occurs at bus 3. Ignoring charging admittance of the transmission line and off-nominal tap ratio
of the transformer, find fault current in each phase of the transformer. Assume pre-fault voltage same as given in 1(a).