0% found this document useful (0 votes)
374 views3 pages

Ontario Pressure Piping Registration Guide

The document provides a flowchart guide for determining the scope of pressure piping systems in Ontario that require registration and inspection by the Boilers and Pressure Vessels Safety Division (BPVSD). The flowchart examines factors like design pressure and temperature, material type, size, and application to determine if a system is exempt or requires BPVSD registration and inspection according to CSA B51 standards. Exempt systems that do not require registration include those with low pressure or temperature such as buried water piping under 600 PSIG or hot water heating systems below 250 degrees Fahrenheit.

Uploaded by

Bill Murray
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
374 views3 pages

Ontario Pressure Piping Registration Guide

The document provides a flowchart guide for determining the scope of pressure piping systems in Ontario that require registration and inspection by the Boilers and Pressure Vessels Safety Division (BPVSD). The flowchart examines factors like design pressure and temperature, material type, size, and application to determine if a system is exempt or requires BPVSD registration and inspection according to CSA B51 standards. Exempt systems that do not require registration include those with low pressure or temperature such as buried water piping under 600 PSIG or hot water heating systems below 250 degrees Fahrenheit.

Uploaded by

Bill Murray
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Technical Standards &

Safety Authority
4th Floor, West Tower
3300 Bloor Street West
Toronto, ON M8X 2X4
Tel: (416) 325-1943
Fax: (416) 326-1662

SAFETY INFORMATION BULLETIN: SB00-7 Rev. 4


(Supersedes Safety Information Bulletin: SB00-7 Rev.3, issued September 27, 2001)

October 4, 2001

Subject: Guide for the Scope of Services Requiring Registration and Inspection of
Pressure Piping Systems by Boilers and Pressure Vessels Safety Division
(BPVSD) for Installations in the Province of Ontario

START LEGEND
Yes D.P. = Design Pressure
D.P. < 15 PSIG STOP D.T. = Design Temperature
STOP = Exempt from
Registration and Inspection by
No BPVSD

Hot water Heating Yes Yes


System for Building D.T. > 250° F
Services?
No
Yes
D.T. < -20° F

No
No Yes
D.P. > 160 PSIG

No

STOP

Hydraulic Fluid for Yes Yes


Cylinder Operation? D.T. > 150° F

No

No STOP

Continued BPVSD: REGISTRATION AND


INSPECTION AS PER CSA B51
ARE APPLICABLE
Yes Yes
OIL? (NON-FUEL
APPLICATION) (D.T.+ 50°F)>(FLASH POINT OF OIL)
NO
Yes
D.P. > 100 PSIG

NO NO

STOP

Yes Yes
LIQUIDS NOT MORE D.T. > 150°F
HAZARDOUS THAN WATER?
NO
NO Yes Yes
BURIED WATER
D.P.>600 PSIG
PIPING?
NO
NO
STOP

Yes
D.P. > 250 PSIG

NO

STOP

Yes
Yes
COMPRESSED AIR? FLEXIBLE HOSES AND STOP
PORTABLE AIR PIPING
USED IN MINES?
NO
NO
Yes
NOMINAL PIPE DIA.>3/4”

NO

STOP

BPVSD: REGISTRATION AND


INSPECTION AS PER CSA B51
ARE APPLICABLE

CONTINUED
REFRIGERATION Yes CAPACITY >3 Yes
PIPING TONS (11 KW)

No
No

AUTOMATIC FIRE PROTECTION STOP


SYSTEMS PER ONT. REG’N
403/97 (Building Code) and Yes
388/97 (Fire Code) STOP

No

Yes
SYSTEM REGULATED UNDER ANY
ACT OR REGULATION OF THE STOP
GOVERNMENT OF CANADA.
(EXEMPT WHERE SPECIFICALLY
REQUESTED BY THE
GOVERNMENT OF CANADA)

NO

SYSTEM REGULATED UNDER THE


TECHNICAL STANDARDS AND Yes
SAFETY ACT 2000, ONTARIO STOP
REGULATION NOS. 210/01 for Oil
and Gas Pipeline Systems, 211/01 for
Propane Storage and Handling, 212/01
for Gaseous Fuels, 213/01 for Fuel Oil
or 214/01 for Compressed Natural Gas.

NO

BPVSD: REGISTRATION AND


INSPECTION AS PER CSA B51 ARE
APPLICABLE

Original Document Signed


______________________
Director
Boilers and Pressure Vessels Safety Division