100% found this document useful (1 vote)
171 views9 pages

Generator Vibration Monitoring Insights

This document summarizes a paper on monitoring generator stator end-winding vibration using fiber optic sensors. It discusses how existing monitoring systems may not fully capture vibrations and describes a fiber optic system that can measure vibrations at all frequencies, providing a more accurate assessment of stresses. The system was installed on a generator at Mississippi Power's Plant Daniel where it detected significant 60 Hz vibrations that had been previously undetected, showing the importance of monitoring overall vibration spectra.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
171 views9 pages

Generator Vibration Monitoring Insights

This document summarizes a paper on monitoring generator stator end-winding vibration using fiber optic sensors. It discusses how existing monitoring systems may not fully capture vibrations and describes a fiber optic system that can measure vibrations at all frequencies, providing a more accurate assessment of stresses. The system was installed on a generator at Mississippi Power's Plant Daniel where it detected significant 60 Hz vibrations that had been previously undetected, showing the importance of monitoring overall vibration spectra.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

Monitoring of Generator Stator End – Winding Vibration

How Reliable Are Existing Monitoring Systems?


EPRI
Generator Predictive Maintenance and Refurbishment
January 15 – 18, 2000 New Orleans, LA

Donald P. Creel Klaus Weigelt C. M. Rose


Southern Company Generator & Motor Services Generator & Motor Services
Daniel Generating Station D-79774 Albbruck-Buch 601 Braddock Ave.
P.O. Box 950 Germany Turtle Creek, PA 15145
Escatawpa, MI 39552-0950
[email protected] [email protected] [email protected]

ABSTRACT

The economic performance of turbo generators and hydro generators can be enhanced considerably
using on-line monitoring techniques. Parameters routinely monitored on-line include vibration signals,
temperature, hydrogen pressure, hydrogen purity, flow rate, partial discharge, shaft voltage and field
winding shorted-turns. These data are used for condition assessment of the entire generator.

Vibration, especially stator end-winding vibration, is an extremely important index of the overall
soundness of rotating electrical machines and can be used for the early detection of abnormalities and
trouble. High vibration can lead to loosening of the entire end-winding support system, deterioration of
supports, insulation wear, rupture of coil conductors or fatigue cracking of conductors. All of these
conditions require extensive out-of-service repairs.

In recent years Fiber Optic Vibration Systems have been developed to measure the stator end-winding
vibrations in high voltage generators where conventional hardwired transducers cannot be safely
mounted. Because of their importance, vibration process data are frequently integrated into the on-line
monitoring system of many generators. A modern Fiber Optic Vibration System provides a data base
which is helpful in anticipating generator end-winding vibration problems and predicting future
maintenance needs, extending inspection and minimizing down time for maintenance.

The generator end-windings of the stator experience forced mechanical vibrations during operation. The
frequency of vibrations excited by the stator current is twice the electrical synchronous frequency of the
generator (120 Hz in the United States). In addition, single frequency vibrations (60 Hz) can be
transmitted from the rotor to the stator end-winding support system. These two vibration sources are
superimposed on one another and in some cases, displacements produced by the single frequency
approach, or even exceed displacements produced by the double frequency vibrations

Most installed fiber optic sensors pick up only the double frequency vibration (120 Hz) and thereby ignore
rotor-induced phenomenon. These sensors do not give a full or accurate picture of the total vibrations
exciting stator end-windings. Because end-winding mechanical stresses are defined by the total vibration
amplitude, accurate stator end-winding lifetime assessment requires monitoring of the entire spectrum of
frequencies exciting the end-winding.

In many cases the composite peak-to-peak end-winding deflections exceed manufacturer’s established
limits and concern must be expressed. Measuring results confirm that 60 Hz vibrations affect stator end-
winding lifetime and that modern reliable instrumentation should be available to monitor this condition.
This paper describes a Fiber Optic Vibration Sensor System that is capable of measuring vibrations at all
frequencies. The paper provides an example of an operating generator where a newly installed system
revealed significant 60 Hz vibration which had been undetected using the previous sensors.
Displacements resulting from 60 Hz vibration – previously assumed to be negligible - are shown to be
comparable in magnitude to those of the 120 Hz vibration and must be taken into consideration.
Measuring results confirm that 60 Hz vibrations affect stator end-winding lifetime and that modern reliable
instrumentation should be available to monitor this condition.

FIBER OPTIC VIBRATION SYSTEM

On-line monitoring system can considerably enhance the economical operation of turbo and hydro
generators. Vibration and process data (e.g. temperature, partial discharge, hydrogen pressure,
hydrogen purity, flow rate, shaft voltage and field winding shorted-turns etc.) can be monitored and used
for evaluation of complete generator condition. This is very significant when users tend to stretch the
overhaul intervals more and more: ten (10) to twelve (12 ) year intervals are not rare.

Since vibrations - particularly in stator end-windings - are very important for the detection of premature
anomalies and problems, vibration measurements are vital in evaluating the generator condition. Stator
end-windings are excited by both electromagnetic and mechanical forces during operation.
Electromagnetic vibration amplitudes are proportional to the square of the generated current and the
frequency is twice the electrical line frequency. On end-windings with loose supports, larger vibration
amplitudes can be measured at partial load than at full load. High end- winding vibration quickly leads to
loosening of the end-winding basket, insulation abrasion or cracks, as well as fatigue rupture of bars and
solder links. Any of these failures entail long shutdowns and considerable repair costs. Consequently, a
vibration monitoring system not only provides valuable data to plan revision and maintenance measures,
but also helps reduce downtime in case of failure shutdowns.

Because end-winding vibration depends on generator operating conditions, a reliable monitoring system
was designed to integrate additional process parameters (Fig. 1). It allows trending and statistic reports
regarding the end-winding vibration behavior. This provides comprehensive data presentation correlated
with machine operating conditions without the long and difficult interpretation of printed data.

Fig. 1: Fiber Optic Measuring System


A typical fiber optic accelerometer is shown in Fig. 2. Its uni-body design consists of a small size sensor
head of non-conducting material, a fiber optic cable, and a feed-through connector with built-in opto-
electronic circuitry. It is sensitive to vibration in a single axis. The sensor head is located at the end of a
three single strand, multimode, optical fiberglass cable. One fiber carries the light generated by the
conditioning electronics for illumination. The sensor head returns two optical signals of variable intensity
through the remaining fibers. When the fiber-optics accelerometer is subjected to vibrations, the force
proportional to the absolute acceleration encountered caused angular deflection of an elastic cantilever.
This angular variation changes the angular position of a mirror mounted on the cantilever. The incoming
beam is reflected at an angle proportional to the magnitude of acceleration. The electrical isolation of the
optical circuit allows the sensor to be mounted directly to the stator coil ends.

Fig. 2: Fiber Optic Accelerometer with Feed-through Conditioner

In the conditioning electronics, the optical signal is converted to an electrical signal by optoelectronic
circuitry, processed and amplified to an acceptable level. The resultant measured signal is proportional to
vibration acceleration that can be further processed by a computer. The analog output is a signal that is
factory-calibrated to produce 100 mV when the detector senses an acceleration of 1g. An appropriate
bandpass filter attenuates the noise and resonance frequency of the cantilever. Specially designed
software provides signal processing, display and data storage. In addition, vibration velocity and
displacement are processed. After Fast Fourier Transform (FFT), the measured signals are displayed as
amplitude-frequency spectrum (Fig. 3). The system can be used in stand-alone operation or linked to
plant control system.

Fig. 3: Overview of software user interface


INSTALLATION OF FIBER OPTIC ACCELEROMETERS

The fiber optic system as shown in Fig. 1 consists of fiber optic accelerometers and cables, power supply
and a computer. Such a system can be installed on generators in about seven days during an overhaul.
Usually, twelve (12) accelerometers are installed per turbo-generator, six (6) sensors on each side.
Sensors are required for each group of phases in radial and/or tangential directions. On pump generating
sets, large generators, and depending on winding design six (6) to twelve (12) or more accelerometers
may be necessary.

Fiber optic accelerometers are used for vibration measurements where conventional accelerometers are
precluded. Because the accelerometer is sensitive in only one direction, it is possible to monitor vibration
of an installation in radial, axial and tangential directions. Fig. 4 shows how accelerometers and cables
are installed on the end-windings. It is important to respect the minimum bending radius of the optical
cable to avoid breaking. It is also important to mention that the feed-through units must be equipped with
O-rings capable of withstanding the hydrogen environment of the generator and must be mounted on a
flange as shown in Fig. 5. The output electrical signals are available at the feed-through conditioning unit.

Fig. 4: Installed Fibre Optic Accelerometer Fig. 5: Sealed Flange with Six Feed-through
for Radial Measurement Conditioners and Cable
IMPLEMENTATION AT MISSISSIPPI POWER’S PLANT DANIEL

This section of paper presents results of vibration testing performed on Mississippi Power’s Plant Daniel
Unit #1 generator. The purpose of the test was to further investigate high end turn vibration readings
recorded using conventional Westinghouse accelerometers which respond only to 120 Hz vibrations
thereby ignoring rotor-induced phenomena . General information on the site and specific generator under
test is given in Table 1

Table 1: Site Information

Station Name Daniel Generating Station


(Mississippi Power Company)
Unit Number 1
Power Rating 548 MW
Voltage Rating 18 kV
Test Date June 5, 2000
Performed by Generator & Motor Services
Equipment Used GMS Fiber-Optic Accelerometer
Test System

The fiber-optic accelerometer used for this test consisted of three parts:

• optical sensor head,


$ fiber-optic integral cable, and
$ a sealed feed-through connector/conditioner.

This portion of the system was installed in the Daniels #1 unit on May 12, 2000 during a scheduled
outage. The sensor head was installed on the Group 8 end-winding at the turbine end of the Unit #1
generator. The feed-though was positioned to be accessible from the left side of the generator as viewed
from the exciter end. Vibration data from the fiber-optics accelerometer was recorded on June 5, 2000
during a visit to the plant by GMS engineering personnel.

TEST RESULTS AND ANALYSIS

Figure 6 shows the resultant scope display of the GMS fiber-optic accelerometer as recorded during the
test. The rms voltage reading corresponding to the signal shown in Figure 6 was .708 volts as displayed
by the GMS equipment display software.

An initial evaluation of the data confirms that the primary signal is 120 Hz as expected. However, the
shape of the Figure 6 trace (alternating high and low peaks in the 120 Hz waveform) indicates an
appreciable 60 Hz content in the signal. From the trace it is clear that the 60 Hz amplitude is significantly
smaller than the primary 120 Hz signal, but it must be remembered that displacements are inversely
proportional to the square of the frequency. Accordingly, there will be four times as much displacement at
60 Hz than at 120 Hz for a given measured acceleration.
Figure 6: Scope Display of the GMS Fiber-Optic Accelerometer Data

A spectral analysis of the accelerometer readings is required accurately evaluate deflections. This
analysis can be completed automatically using the Fast Fourier Transform (FFT) algorithm that is built
into the software, but to better understand the interactions of vibrations a regression analysis has been
performed.

The spectral analysis involves separating the composite signal show in Figure 6 into its primary
components. Since the two major components are at 60 Hz and 120 Hz, the signal can be represented
by an equation of the form:

V = A sin (Tt +*) + B sin (2Tt)

where T = 2 B 60 and * is the phase angle between the 60 Hz and 120 Hz vibrations.

A regression technique was used to determine the “best” values for A, B and * to fit the waveform
produced by the experimental accelerometer data. This evaluation yielded the following results:
A = 165 mV (i.e., the amplitude of the 60 cycle vibration was 165 mV),

B = 1005 mV (i.e., the amplitude of the 120 cycle vibration was 1005 mV), and

* = -B radians (i.e., the two signals were 180 degrees out of phase).

There is no particular significance to the phase angle between the two signals because the 120 Hz signal
changes phase twice during each cycle of the 60 Hz signal. Thus if the data acquisition had begun one
cycle later in the 120 Hz signal, the phase angle would have been zero.

Figure 7 displays the “goodness-of-fit” between the measured voltage and the synthesized voltage trace
calculated using the Equation (1) expression with the regression analysis constants. The calculated
expression consisting of 60 and 120 Hz components can be seen to agree very closely with the
measured values.

Figure 7: Comparison of Calculated and Measured Voltage Traces

The rms voltages related to the calculated amplitudes are as follows:

Vrms at 60 Hz = 117 mV, and

Vrms at 120 Hz = 711 mV.


Given the calibrated value of 100 mV per g of acceleration, displacements associated with these
vibrational modes can be calculated as follows:

Displacement at 60 Hz = 9.0 mils (peak-to-peak), and

Displacement at 120 Hz = 13.7 mils (peak-to-peak).

The calculated 120 Hz displacement agrees well with data from the previously installed accelerometer.
On the day GMS fiber-optics accelerometer measurements described in this paper were taken, the
conventional accelerometer located on the same end-winding (Group 8 on the turbine end of the Unit #1
generator) recorded a 12.8 mil displacement. A displacement of 13.8 mils was recorded by the
conventional accelerometer positioned on the adjacent Group 7 end-winding. This correlation is expected
since the conventional accelerometer is designed to respond to 120 Hz vibrations only. However,
displacements resulting from the 60 Hz vibration are found to be nearly comparable in magnitude to those
of the 120 Hz vibrations and cannot be ignored.

Since the 60 Hz and 120 Hz signals do not peak simultaneously, the resultant maximum displacement
cannot be determined by simple addition. Rather, it is necessary to superimpose the displacements on
one another as a vector sum. This is shown graphically in Figure 8. In this plot, the 60 Hz and 120 Hz
displacements are plotted along with the resultant. The composite displacement, which is the sum of the
instantaneous component displacements, actually peaks at " 10 mils (20 mils peak-to-peak).

Figure 8: Calculated Displacements


Because the measured vibration amplitude of 20 mils exceeds guidelines set by generator manufacturers,
concern must be expressed. The 60 Hz component is most likely present as a result of rotor bearing
wear or rotor imbalance being transmitted to the stator end-windings.

Since no previous 60 Hz vibration readings are available, it is not possible to determine whether this
phenomenon has developed recently, or if it is a long-term situation. In light of this, has been
recommended that the GMS fiber-optics accelerometer be monitored at least monthly.

CONCLUSIONS

These results confirm clearly that significant 60 Hz vibrations produced by rotor bearing wear or rotor
imbalance can be transmitted to generator stator end-windings. In some cases, these rotor-induced
vibrations can produce end-winding displacements that approach, or perhaps exceed generator
manufacturer guidelines. This condition can be assessed only if on-line monitoring techniques capable of
responding at 60 Hz are incorporated. The GMS fiber-optic accelerometer system described in this paper
is sensitive to vibrations at all frequencies and is clearly superior to conventional vibration monitoring
systems which measure vibrations at 120 Hz only.

Results of the GMS fiber-optics accelerometer tests confirmed the high end-winding displacement
measurements associated with 120 Hz vibrations observed by Mississippi Power for the Unit #1
Generator. The 120 Hz displacement measured using the GMS equipment was 13.7 mils compared with
12.8 mils recorded on the same generator end-winding at roughly the same time using the previously
installed accelerometer which senses only 120 Hz vibrations.

The GMS fiber-optic accelerometer tests also revealed a significant amount of 60 Hz vibration which had
been previously undetected. These 60 Hz end-winding vibrations are most likely transmitted
mechanically from the rotor and produce independent deflections of 9.0 mils. A composite peak-to-peak
end-winding deflection of 20 mils is calculated when considering vibrations at both frequencies. This 20
mil vibration amplitude of 20 mils exceeds guidelines set by generator manufacturers, and indicates that
the situation must be monitored closely to ensure that the situation does not worsen.

It is important to distinguish between 60 Hz and 120 Hz vibrations because the conventional blocking
techniques used to control stator current induced vibrations will not be effective in reducing the lower
frequency vibrations that are mechanically induced from the generator rotor. Elimination of the 60 Hz
vibrations requires that rotor repairs be completed.

On the basis of this work it is concluded that use of the GMS fiber-optics accelerometer system can
significantly improve the reliability of generator stator end-winding vibration monitoring systems.

Common questions

Powered by AI

Fiber Optic Vibration Systems offer several advantages over conventional hardwired transducers for monitoring generator stator end-winding vibrations. They can measure vibrations at all frequencies, including 60 Hz and 120 Hz, which are significant for comprehensive assessment of generator condition . Conventional transducers typically measure only the dominant 120 Hz component and may miss rotor-induced vibrations at 60 Hz, leading to incomplete assessments . Additionally, the electrical isolation provided by fiber optics allows them to be safely mounted directly on the stator coil ends, which is not possible with conventional sensors . These systems improve the reliability of vibration monitoring and aid in preventing costly maintenance by providing an accurate understanding of vibrational contributions affecting generator health .

Ignoring 60 Hz vibrations in the evaluation of generator stator end-windings can lead to severe consequences, including premature failure due to underestimated mechanical stresses. The 60 Hz vibration can contribute significantly to overall displacement, which if unmonitored, might exceed established safety guidelines, leading to fatigue failures such as insulation wear or fatigue cracking, ultimately causing extensive out-of-service repairs . Moreover, since 60 Hz vibrations arise from rotor-induced phenomena such as bearing wear or imbalance, ignoring them can obscure critical underlying mechanical issues needing rectification . Hence, comprehensive monitoring that includes these vibrations is essential for accurate lifetime evaluation and preventive maintenance planning .

The GMS fiber-optics accelerometer system improves the reliability of generator end-winding monitoring by providing sensitivity to vibrations at all frequencies, including both dominant 120 Hz vibrations and significant 60 Hz rotor-induced vibrations that conventional systems overlook . This comprehensive frequency detection allows for a more complete assessment of vibration impacts on generator health. The system's ability to accurately correlate vibrational data with machine-operating conditions without lengthy data interpretation further facilitates proactive maintenance decisions and reduces unnecessary downtimes . Additionally, the system’s optical design allows it to be mounted directly on the stator coil ends, increasing measurement accuracy and reliability .

The amplitude of 60 Hz vibrations can be nearly comparable to that of 120 Hz vibrations but must be viewed in terms of displacement resulting from each. Displacements at 60 Hz are four times as large as those at 120 Hz for a given acceleration due to the inverse relationship with the square of the frequency . This is significant because it means that while the 60 Hz amplitude might be smaller in raw terms, its contribution to end-winding displacement is considerable, potentially exceeding manufacturer guidelines if both frequencies are present . Neglecting 60 Hz vibrations could thus lead to underestimating the mechanical stresses on end-windings, posing a risk for machine integrity and requiring the use of monitoring that can detect both frequency components .

Measuring both 60 Hz and 120 Hz vibrations is crucial in assessing the condition of generator stator end-windings because these frequencies combine to reflect the complete vibrational environment. The 120 Hz vibrations result from electromagnetic forces related to the twofold electrical synchronous frequency, while the 60 Hz vibrations are mechanically transmitted from rotor phenomena like bearing wear or imbalance . An accurate assessment must consider the composite impact, as end-winding mechanical stresses derive from the total vibration amplitude. Since 60 Hz vibrations can produce comparable displacement amplitudes to 120 Hz vibrations, even if their direct measurement values differ, omitting 60 Hz assessments risks underestimating mechanical stresses and failing to meet manufacturer guidelines for end-winding health .

Spectral analysis and regression techniques were crucial in analyzing vibration data from the GMS fiber-optics accelerometer by separating composite signals into primary components. Spectral analysis, facilitated by Fast Fourier Transform (FFT), broke down the signals into distinct 60 Hz and 120 Hz components, which are fundamental for identifying individual vibration contributions . Regression techniques were used to determine the optimal parameters for the component signals' amplitudes and phase angles, resulting in an accurate representation of the measured data . These methods enabled precise calculations of displacements and validated the composite vibration impacts, which are necessary to gauge generator end-winding stress correctly and set appropriate maintenance actions .

Displaying vibration measurements as amplitude-frequency spectra is significant as it allows clear visualization and analysis of the vibrational modes impacting the generator. By breaking down complex vibrational data into distinct frequency components, operators can accurately diagnose the sources and severity of vibrations, which is critical for identifying mechanical issues such as imbalance or bearing wear . This detailed view supports strategic maintenance planning, enabling targeted interventions that can prevent severe issues before they manifest into costly repairs. Such data presentation enhances understanding of vibrational impacts, assisting in extending overhaul intervals by ensuring machines operate within safe vibrational limits .

Incorporating on-line monitoring systems for generators is necessary because they significantly enhance the economic performance by providing real-time data on vital parameters such as vibration, which is critical for evaluating generator condition and detecting early anomalies . Vibration data, especially from stator end-windings, helps predict maintenance needs and prevents extensive repairs by identifying issues such as insulation wear or coil conductor fatigue before they result in significant damage . Furthermore, modern fiber optic systems can capture a comprehensive spectrum of frequencies impacting the stator, unlike conventional systems, allowing for a more accurate lifetime assessment and reduction of unscheduled downtimes .

The effectiveness of fiber optic accelerometers in vibration monitoring of generators hinges on their design, which includes a uni-body sensor head of non-conducting material with integral fiber optic cables . This design provides electrical isolation, enabling the sensor to be directly mounted on the stator coil ends without risk of interference. The sensor captures vibrations through an angular deflection method, reflecting light in proportions to vibration-caused accelerations, and the opto-electronic circuitry converts this into electronic signals for precise analysis . This setup ensures sensitivity to a wide range of vibrational frequencies, enhancing the accuracy and reliability of condition assessments when compared to conventional systems limited to certain frequencies .

The installation of a fiber optic vibration monitoring system in a generator involves setting up fiber optic accelerometers along with the necessary cables, power supply, and computer for data processing . Typically, systems are installed during scheduled overhauls and can be positioned within approximately seven days. For a turbo-generator, it is common to use twelve accelerometers—six on each side—to capture phase group vibrations in radial, axial, and tangential directions . Care must be taken to maintain minimum bending radii for the optical cables and ensure feed-through units are equipped with O-rings for hydrogen environment resistance, and mounted on flanges for seamless integration with existing infrastructure .

You might also like