RXYQ-U EEDEN20 Data Books English
RXYQ-U EEDEN20 Data Books English
without continuous
heating
Technical data book
RXYQ-U
RXYQ8U7Y1B
RXYQ10U7Y1B
RXYQ12U7Y1B
RXYQ14U7Y1B
RXYQ16U7Y1B
RXYQ18U7Y1B
RXYQ20U7Y1B
RXYQ22U7Y1B
RXYQ24U7Y1B
RXYQ26U7Y1B
RXYQ28U7Y1B
RXYQ30U7Y1B
RXYQ32U7Y1B
RXYQ34U7Y1B
RXYQ36U7Y1B
RXYQ38U7Y1B
RXYQ40U7Y1B
RXYQ42U7Y1B
RXYQ44U7Y1B
RXYQ46U7Y1B
RXYQ48U7Y1B
RXYQ50U7Y1B
RXYQ52U7Y1B
RXYQ54U7Y1B
EEDEN20
Table of contents
RXYQ-U
1 Features 4
4
2 5
3 22
4 23
5 26
26
27
6 40
7 41
8 42
9 43
43
44
45
10 46
11 48
48
52
56
58
60
12 62
62
63
64
13 67
14 68
3
VRV IV+ heat pump, without continuous heating • RXYQ-U
1 Features
1 - 1 RXYQ-U
Daikin’s solution for comfort & low energy consumption
1 ›› By choosing a LOOP by Daikin product you support the reuse of ›› Fits any building as also indoor installation is possible as a result
refrigerant, for more information visit www.daikin.eu/loop-by- of high external static pressure of up to 78.4 Pa. Indoor installation
daikin leads to less piping length, lower installation costs, increased
›› Covers all thermal needs of a building via a single point of contact: efficiency and better visual aesthetics
accurate temperature control, ventilation, hot water, air handling ›› Simplified installation & guaranteed optimal efficiency with
units and Biddle air curtains automatic charging & testing
›› Wide range of indoor units: possibility to combine VRV with stylish ›› Easy compliance with F-gas regulation thanks to automated
indoor units (Daikin Emura, Perfera, ...) refrigerant containment check
›› Incorporates VRV IV standards & technologies: Variable Refrigerant ›› Wide piping flexibility: 30m indoor height difference, maximum
Temperature, VRV configurator, 7 segment display and full inverter piping length: 190m, total piping length: 1,000m
compressors, 4-side heat exchanger, refrigerant cooled PCB, new ›› The ability to control each conditioned zone individually keeps VRV
DC fan motor, ... system running costs to an absolute minimum
›› Customize your VRV for best seasonal efficiency & comfort with ›› Spread your installation cost by phased installation
the weather dependant Variable Refrigerant Temperature function. ›› Keep your system in top condition via the Daikin Cloud Service:
Increased seasonal efficiency with up to 28%. No more cold draft 24/7 monitoring for maximum efficiency, extented lifetime and
by supply of high outblow temperatures immediate service support thanks to failure prediction
›› Free combination of outdoor units to meet installation space or ›› Available as heating only by irreversible field setting
efficiency requirements
Inverter
4 RXYQ-U
VRV IV+ heat pump, without continuous heating • RXYQ-U
2 Specifications
1 - 1 RXYQ-U
Technical Specifications RXYQ8U RXYQ10U RXYQ12U RXYQ14U RXYQ16U
Recommended combination 4 x FXFQ50AVEB 4 x FXFQ63AVEB 6 x FXFQ50AVEB 1 x FXFQ50AVEB + 5 4 x FXFQ63AVEB + 2
x FXFQ63AVEB x FXFQ80AVEB
Recommended combination 2 4 x FXSQ50A2VEB 4 x FXSQ63A2VEB 6 x FXSQ50A2VEB 1 x FXSQ50A2VEB +
5 x FXSQ63A2VEB
4 x FXSQ63A2VEB +
2 x FXSQ80A2VEB
2
Recommended combination 3 4 x FXMQ50P7VEB 4 x FXMQ63P7VEB 6 x FXMQ50P7VEB 1 x FXMQ50P7VEB + 4 x FXMQ63P7VEB +
5 x FXMQ63P7VEB 2 x FXMQ80P7VEB
Cooling capacity Prated,c kW 22.4 (1) 28.0 (1) 33.5 (1) 40.0 (1) 45.0 (1)
Heating capacity Nom. 6°CWB kW 22.4 (2) 28.0 (2) 33.5 (2) 40.0 (2) 45.0 (2)
Prated,h kW 13.7 16.0 18.4 20.6 23.2
Max. 6°CWB kW 25.0 (2) 31.5 (2) 37.5 (2) 45.0 (2) 50.0 (2)
COP at nom. 6°CWB kW/kW 4.15 (2) 3.69 (2) 3.47 (2) 3.74 (2) 3.59 (2)
capacity
ESEER - Automatic 7.53 7.20 6.96 6.83 6.50
ESEER - Standard 6.37 5.67 5.50 5.31 5.05
SCOP 4.3 4.1 4.0
SCOP recommended combination 2 4.2 4.3 4.1 4.0 4.1
SCOP recommended combination 3 4.2 4.1 4.0
SEER 7.6 6.8 6.3 6.0
SEER recommended combination 2 6.9 6.8 5.9 6.3 5.9
SEER recommended combination 3 7.5 6.8 6.2 5.8
ηs,c % 302.4 267.6 247.8 250.7 236.5
ηs,c recommended combination 2 273.6 270.5 233.5 250.0 234.2
ηs,c recommended combination 3 295.2 267.1 246.3 246.7 230.4
ηs,h % 167.9 168.2 161.4 155.4 157.8
ηs,h recommended combination 2 165.4 170.6 161.3 157.2 159.5
ηs,h recommended combination 3 165.6 162.0 160.6 155.7 156.8
Space cooling A Condition (35°C EERd 3.0 2.3 2.4 2.6 2.1
- 27/19) Pdc kW 22.4 28.0 33.5 40.0 45.0
B Condition (30°C EERd 5.2 4.7 4.3 4.1 3.9
- 27/19) Pdc kW 16.5 20.6 24.7 29.5 33.2
C Condition (25°C EERd 9.5 8.3 7.7 7.8 7.7
- 27/19) Pdc kW 10.6 13.3 15.9 18.9 21.3
D Condition EERd 18.8 17.0 13.9 14.3 14.2
(20°C - 27/19) Pdc kW 8.0 9.3 9.4 8.4 9.5
Space cooling A Condition (35°C EERd 2.6 2.4 2.6 2.1
recommended - 27/19) Pdc kW 22.4 28.0 33.5 40.0 45.0
combination 2 B Condition (30°C EERd 4.9 4.7 4.0 4.1 3.8
- 27/19) Pdc kW 16.5 20.6 24.7 29.5 33.2
C Condition (25°C EERd 8.8 8.5 7.1 7.9 7.6
- 27/19) Pdc kW 10.6 13.3 15.9 18.9 21.3
Space cooling D Condition EERd 15.1 17.2 13.1 14.0
recommended (20°C - 27/19) Pdc kW 8.8 9.3 9.1 8.4 9.5
combination 2
Space cooling A Condition (35°C EERd 3.0 2.3 2.4 2.6 2.1
recommended - 27/19) Pdc kW 22.4 28.0 33.5 40.0 45.0
combination 3 B Condition (30°C EERd 5.1 4.7 4.2 4.0 3.7
- 27/19) Pdc kW 16.5 20.6 24.7 29.5 33.2
C Condition (25°C EERd 9.6 8.4 7.7 7.4
- 27/19) Pdc kW 10.6 13.3 15.9 19.0 21.3
D Condition EERd 16.0 16.9 13.7 14.0 14.1
(20°C - 27/19) Pdc kW 9.1 9.3 9.4 8.4 9.5
Space heating TBivalent COPd (declared COP) 2.5 2.4 2.0 2.3 2.2
(Average climate) Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.5 2.4 2.0 2.3 2.2
Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2
Tol (temperature operating °C -10
limit)
A COPd (declared COP) 2.7 2.6 2.4 2.6
Condition Pdh (declared heating cap) kW 12.1 14.2 16.3 18.2 20.5
(-7°C)
B COPd (declared COP) 3.9 3.5
Condition Pdh (declared heating cap) kW 7.4 8.6 9.9 11.1 12.5
(2°C)
C COPd (declared COP) 6.3 6.4 6.1 6.3
Condition Pdh (declared heating cap) kW 5.0 5.5 6.4 7.1 8.0
(7°C)
D COPd (declared COP) 7.9 8.2 7.9 8.5 8.6
Condition Pdh (declared heating cap) kW 5.9 6.3 4.9
(12°C)
2 Specifications
1 - 1 RXYQ-U
Technical Specifications RXYQ8U RXYQ10U RXYQ12U RXYQ14U RXYQ16U
Space heating A COPd (declared COP) 2.7 2.4 2.6
(Average climate) Condition Pdh (declared heating cap) kW 12.1 14.2 16.3 18.2 20.5
2 recommended
combination 2
(-7°C)
B COPd (declared COP) 3.9 4.0 3.9 3.5
Condition Pdh (declared heating cap) kW 7.4 8.6 9.9 11.1 12.2
(2°C)
C COPd (declared COP) 6.3 6.5 6.1 6.3
Condition Pdh (declared heating cap) kW 5.0 5.5 6.4 7.1 8.0
(7°C)
D COPd (declared COP) 7.8 8.3 7.9 8.6 8.7
Condition Pdh (declared heating cap) kW 5.9 6.0 6.4 4.9 5.0
(12°C)
TBivalent COPd (declared COP) 2.4 1.9 2.3 2.2
Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.4 1.9 2.3 2.2
Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2
Space heating (Average climate) TOL Tol (temperature operating °C -10
recommended combination 2 limit)
Space heating A COPd (declared COP) 2.7 2.6 2.4 2.6
(Average climate) Condition Pdh (declared heating cap) kW 12.1 14.2 16.3 18.2 20.5
recommended (-7°C)
combination 3 B COPd (declared COP) 3.9 3.7 3.9 3.5
Condition Pdh (declared heating cap) kW 7.4 8.6 9.9 11.1 12.5
(2°C)
C COPd (declared COP) 6.2 6.4 6.0 6.1 6.2
Condition Pdh (declared heating cap) kW 4.9 5.5 6.4 7.1 8.0
(7°C)
D COPd (declared COP) 7.8 8.1 7.8 8.5 8.6
Condition Pdh (declared heating cap) kW 5.8 5.9 6.2 4.9
(12°C)
TBivalent COPd (declared COP) 2.5 2.4 2.0 2.3 2.2
Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.5 2.4 2.0 2.3 2.2
Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2
Tol (temperature operating °C -10
limit)
Capacity range HP 8 10 12 14 16
PED Category Category II
Most Name Accumulator
critical Ps*V Bar*l 325 415
part
Maximum number of connectable indoor units 64 (3)
Indoor index Min. 100.0 125.0 150.0 175.0 200.0
connection Max. 260.0 325.0 390.0 455.0 520.0
Dimensions Unit Height mm 1,685
Width mm 930 1,240
Depth mm 765
Packed Height mm 1,820
unit Width mm 995 1,305
Depth mm 860
Weight Unit kg 198 275
Packed unit kg 211 291
Packing Material Carton
Weight kg 1.8 2.2
Packing 2 Material Wood
Weight kg 11.0 14.0
Packing 3 Material Plastic
Weight kg 0.5 0.6
Casing Colour Daikin White
Casing Material Painted galvanized steel plate
Heat exchanger Type Cross fin coil
Indoor side Air
Outdoor side Air
Air flow Cooling Rated m³/h 9,720 10,500 11,100 13,380 15,600
rate Heating Rated m³/h 9,720 10,500 11,100 13,380 15,600
Fan Quantity 1 2
External static Max. Pa 78
pressure
Fan motor Quantity 1 2
Type DC motor
Output W 550 750
2 Specifications
1 - 1 RXYQ-U
Technical Specifications RXYQ8U RXYQ10U RXYQ12U RXYQ14U RXYQ16U
Compressor Quantity 1 2
Type Hermetically sealed scroll compressor
Crankcase heater
Operation range Cooling Min.
W
°CDB
33
-5.0
2
Max. °CDB 43.0
Heating Min. °CWB -20.0
Max. °CWB 15.5
Sound power level Cooling Nom. dBA 78.0 (4) 79.1 (4) 83.4 (4) 80.9 (4) 85.6 (4)
Heating Nom. dBA 62.7 (4) 64.8 (4) 64.9 (4) 68.3 (4) 68.6 (4)
Sound pressure Cooling Nom. dBA 57.0 (5) 61.0 (5) 60.0 (5) 63.0 (5)
level
Refrigerant Type R-410A
GWP 2,087.5
Charge TCO2Eq 12.3 12.5 13.2 21.5 23.6
Charge kg 5.9 6.0 6.3 10.3 11.3
Refrigerant oil Type Synthetic (ether) oil FVC68D
Piping connections Liquid Type Braze connection
OD mm 9,52 12.7
Gas Type Braze connection
OD mm 19.1 22.2 28.6
Total piping System Actual m 1,000 (6)
length
Defrost method Reversed cycle
Capacity control Method Inverter controlled
Indication if the heater is equipped with a supplementary heater no
Supplementary Back-up Heating elbu kW 0.0
heater capacity
Power consumption in other Crankcase Cooling PCK kW 0.000
than active mode heater Heating PCK kW 0.052 0.077
Power Off mode Cooling POFF kW 0.041 0.074
consumption in Heating POFF kW 0.052 0.077
other than active Standby Cooling PSB kW 0.041 0.074
mode mode Heating PSB kW 0.052 0.077
Thermostat-off Cooling PTO kW 0.005 0.010
mode Heating PTO kW 0.056 0.097
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
Safety devices Item 01 High pressure switch
02 Fan driver overload protector
03 Inverter overload protector
04 PC board fuse
05 Leakage current detector
2 Specifications
1 - 1 RXYQ-U
Technical Specifications RXYQ18U RXYQ20U
Space cooling A Condition (35°C EERd 1.9
- 27/19) Pdc kW 50.4 52.0
2 B Condition (30°C
- 27/19)
EERd
Pdc kW
3.8
37.1
3.7
38.3
C Condition (25°C EERd 7.5 7.3
- 27/19) Pdc kW 23.9 24.6
D Condition EERd 18.3
(20°C - 27/19) Pdc kW 11.5
Space cooling A Condition (35°C EERd 1.9
recommended - 27/19) Pdc kW 50.4 52.0
combination 2 B Condition (30°C EERd 3.7 3.6
- 27/19) Pdc kW 37.1 38.3
C Condition (25°C EERd 7.5 7.3
- 27/19) Pdc kW 23.9 24.6
Space cooling D Condition EERd 18.1 18.9
recommended (20°C - 27/19) Pdc kW 11.4 10.9
combination 2
Space cooling A Condition (35°C EERd 1.9
recommended - 27/19) Pdc kW 50.4 52.0
combination 3 B Condition (30°C EERd 3.7 3.6
- 27/19) Pdc kW 37.1 38.3
C Condition (25°C EERd 7.6 7.3
- 27/19) Pdc kW 23.9 24.6
D Condition EERd 18.3
(20°C - 27/19) Pdc kW 11.6
Space heating TBivalent COPd (declared COP) 1.9 1.8
(Average climate) Pdh (declared heating cap) kW 27.9 31.0
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 1.9 1.8
Pdh (declared heating cap) kW 27.9 31.0
Tol (temperature operating °C -10
limit)
A COPd (declared COP) 2.4 2.1
Condition Pdh (declared heating cap) kW 24.7 27.4
(-7°C)
B COPd (declared COP) 3.7 3.6
Condition Pdh (declared heating cap) kW 15.0 16.7
(2°C)
C COPd (declared COP) 6.7 6.5
Condition Pdh (declared heating cap) kW 9.7 10.7
(7°C)
D COPd (declared COP) 9.0 9.1
Condition Pdh (declared heating cap) kW 7.1
(12°C)
Space heating A COPd (declared COP) 2.4 2.2
(Average climate) Condition Pdh (declared heating cap) kW 24.7 27.4
recommended (-7°C)
combination 2 B COPd (declared COP) 3.8 3.7
Condition Pdh (declared heating cap) kW 15.0 16.7
(2°C)
C COPd (declared COP) 6.8 6.5
Condition Pdh (declared heating cap) kW 9.7 10.7
(7°C)
D COPd (declared COP) 9.1 9.2
Condition Pdh (declared heating cap) kW 7.2
(12°C)
TBivalent COPd (declared COP) 1.9 1.8
Pdh (declared heating cap) kW 27.9 31.0
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 1.9 1.8
Pdh (declared heating cap) kW 27.9 31.0
Space heating (Average climate) TOL Tol (temperature operating °C -10
recommended combination 2 limit)
2 Specifications
1 - 1 RXYQ-U
Technical Specifications RXYQ18U RXYQ20U
Space heating A COPd (declared COP) 2.4 2.1
(Average climate) Condition Pdh (declared heating cap) kW 24.7 27.4
recommended (-7°C)
combination 3 B COPd (declared COP) 3.7 3.6
2
Condition Pdh (declared heating cap) kW 15.0 16.7
(2°C)
C COPd (declared COP) 6.5 6.3
Condition Pdh (declared heating cap) kW 9.7 10.7
(7°C)
D COPd (declared COP) 8.7
Condition Pdh (declared heating cap) kW 6.9
(12°C)
TBivalent COPd (declared COP) 1.9 1.8
Pdh (declared heating cap) kW 27.9 31.0
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 1.9 1.8
Pdh (declared heating cap) kW 27.9 31.0
Tol (temperature operating °C -10
limit)
Capacity range HP 18 20
PED Category Category II
Most Name Accumulator
critical Ps*V Bar*l 493
part
Maximum number of connectable indoor units 64 (3)
Indoor index Min. 225.0 250.0
connection Max. 585.0 650.0
Dimensions Unit Height mm 1,685
Width mm 1,240
Depth mm 765
Packed Height mm 1,820
unit Width mm 1,305
Depth mm 860
Weight Unit kg 308
Packed unit kg 324
Packing Material Carton
Weight kg 2.2
Packing 2 Material Wood
Weight kg 14.0
Packing 3 Material Plastic
Weight kg 0.6
Casing Colour Daikin White
Casing Material Painted galvanized steel plate
Heat exchanger Type Cross fin coil
Indoor side Air
Outdoor side Air
Air flow Cooling Rated m³/h 15,060 15,660
rate Heating Rated m³/h 15,060 15,660
Fan Quantity 2
External static Max. Pa 78
pressure
Fan motor Quantity 2
Type DC motor
Output W 750
Compressor Quantity 2
Type Hermetically sealed scroll compressor
Crankcase heater W 33
Operation range Cooling Min. °CDB -5.0
Max. °CDB 43.0
Heating Min. °CWB -20.0
Max. °CWB 15.5
Sound power level Cooling Nom. dBA 83.8 (4) 87.9 (4)
Heating Nom. dBA 66.3 (4) 67.0 (4)
Sound pressure Cooling Nom. dBA 62.0 (5) 65.0 (5)
level
Refrigerant Type R-410A
GWP 2,087.5
Charge TCO2Eq 24.4 24.6
Charge kg 11.7 11.8
Refrigerant oil Type Synthetic (ether) oil FVC68D
2 Specifications
1 - 1 RXYQ-U
Technical Specifications RXYQ18U RXYQ20U
Piping connections Liquid Type Braze connection
OD mm 15.9
2 Gas Type
OD mm
Braze connection
28.6
Total piping System Actual m 1,000 (6)
length
Defrost method Reversed cycle
Capacity control Method Inverter controlled
Indication if the heater is equipped with a supplementary heater no
Supplementary Back-up Heating elbu kW 0.0
heater capacity
Power consumption in other Crankcase Cooling PCK kW 0.000
than active mode heater Heating PCK kW 0.089
Power Off mode Cooling POFF kW 0.075
consumption in Heating POFF kW 0.089
other than active Standby Cooling PSB kW 0.075
mode mode Heating PSB kW 0.089
Thermostat-off Cooling PTO kW 0.010
mode Heating PTO kW 0.098
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
Safety devices Item 01 High pressure switch
02 Fan driver overload protector
03 Inverter overload protector
04 PC board fuse
05 Leakage current detector
Standard accessories: Installation manual; Quantity: 1;
Standard accessories: Operation manual; Quantity: 1;
Standard accessories: Connection pipes; Quantity: 1;
2 Specifications
1 - 1 RXYQ-U
(2)Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(3)Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(4)Sound power level is an absolute value that a sound source generates. |
(5)Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(6)Refer to refrigerant pipe selection or installation manual |
(7)RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | 2
(8)In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9)MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10)MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11)FLA means the nominal running current of the fan |
MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
Maximum allowable voltage range variation between phases is 2%. |
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
Sound values are measured in a semi-anechoic room. |
Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per
phase |
Ssc: Short-circuit power |
For detailed contents of standard accessories, see installation/operation manual |
Multi combination (22~54HP) data is corresponding with the standard multi combination
2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ22U RXYQ24U RXYQ26U RXYQ28U RXYQ30U
Space heating TBivalent COPd (declared COP) 2.3 2.5 2.3 2.2 2.1
(Average climate) Pdh (declared heating cap) kW 34.4 36.9 39.0 41.6 46.3
2 TOL
Tbiv (bivalent temperature)
COPd (declared COP)
°C
2.3 2.5
-10
2.3 2.2 2.1
Pdh (declared heating cap) kW 34.4 36.9 39.0 41.6 46.3
Tol (temperature operating °C -10
limit)
A COPd (declared COP) 2.6 2.8 2.6
Condition Pdh (declared heating cap) kW 30.4 32.6 34.5 36.8 41.0
(-7°C)
B COPd (declared COP) 4.0 3.7 3.8 3.9
Condition Pdh (declared heating cap) kW 18.5 19.9 21.0 22.4 24.9
(2°C)
C COPd (declared COP) 6.3 6.1 6.2 6.5
Condition Pdh (declared heating cap) kW 11.9 13.0 13.5 14.4 16.0
(7°C)
D COPd (declared COP) 8.2 8.9 8.8 9.0
Condition Pdh (declared heating cap) kW 6.0 5.7 6.0 6.4 7.1
(12°C)
Space heating A COPd (declared COP) 2.6 2.7 2.6
(Average climate) Condition Pdh (declared heating cap) kW 30.4 32.6 34.5 36.8 41.0
recommended (-7°C)
combination 2 B COPd (declared COP) 4.1 3.7 3.8 3.9
Condition Pdh (declared heating cap) kW 18.5 19.9 21.0 22.4 24.9
(2°C)
C COPd (declared COP) 6.3 6.1 6.3 6.6
Condition Pdh (declared heating cap) kW 11.9 13.1 14.4 16.0
(7°C)
D COPd (declared COP) 8.4 9.0 8.9 9.1
Condition Pdh (declared heating cap) kW 6.0 5.7 6.0 6.4 7.2
(12°C)
TBivalent COPd (declared COP) 2.2 2.4 2.2 2.1
Pdh (declared heating cap) kW 34.4 36.9 39.0 41.6 46.3
Tbiv (bivalent temperature) °C -10
Space heating TOL COPd (declared COP) 2.2 2.4 2.2 2.1
(Average climate) Pdh (declared heating cap) kW 34.4 36.9 39.0 41.6 46.3
recommended Tol (temperature operating °C -10
combination 2 limit)
Space heating A COPd (declared COP) 2.6 2.7 2.6 2.5
(Average climate) Condition Pdh (declared heating cap) kW 30.4 32.6 34.5 36.8 41.0
recommended (-7°C)
combination 3 B COPd (declared COP) 4.0 3.7 3.8 3.9
Condition Pdh (declared heating cap) kW 18.5 19.9 21.0 22.4 24.9
(2°C)
C COPd (declared COP) 6.2 6.3 6.1 6.2 6.3
Condition Pdh (declared heating cap) kW 11.9 12.9 13.5 14.4 16.0
(7°C)
D COPd (declared COP) 8.2 8.9 8.8 9.0 8.6
Condition Pdh (declared heating cap) kW 6.0 5.7 6.0 6.4 7.1
(12°C)
TBivalent COPd (declared COP) 2.3 2.4 2.2 2.1
Pdh (declared heating cap) kW 34.4 36.9 39.0 41.6 46.3
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.3 2.4 2.2 2.1
Pdh (declared heating cap) kW 34.4 36.9 39.0 41.6 46.3
Tol (temperature operating °C -10
limit)
Capacity range HP 22 24 26 28 30
PED Category Category II
Maximum number of connectable indoor units 64 (3)
Indoor index Min. 275.0 300.0 325.0 350.0 375.0
connection Max. 715.0 780.0 845.0 910.0 975.0
Heat exchanger Indoor side Air
Outdoor side Air
Air flow Cooling Rated m³/h 21,600 25,320 24,480 26,700 26,160
rate Heating Rated m³/h 21,600 25,320 24,480 26,700 26,160
Sound power level Cooling Nom. dBA 84.8 (4) 86.3 (4) 85.3 (4) 87.6 (4) 86.6 (4)
Heating Nom. dBA 67.8 (4) 69.6 (4) 69.9 (4) 70.1 (4) 68.7 (4)
Sound pressure Cooling Nom. dBA 62.5 (5) 64.0 (5) 63.5 (5) 65.1 (5) 64.5 (5)
level
Refrigerant Type R-410A
GWP 2,087.5
Refrigerant oil Type Synthetic (ether) oil FVC68D
2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ22U RXYQ24U RXYQ26U RXYQ28U RXYQ30U
Piping connections Liquid Type Braze connection
OD mm 15.9 19.1
Gas Type
OD mm 28.6
Braze connection
34.9
2
Total pipingSystem Actual m 1,000 (6)
length
Indication if the heater is equipped with a supplementary heater no
Supplementary Back-up Heating elbu kW 0.0
heater capacity
Power Crankcase Cooling PCK kW 0.000
consumption in heater Heating PCK kW 0.103 0.129 0.141
other than active mode
mode Off mode Cooling POFF kW 0.081 0.115 0.116
Heating POFF kW 0.103 0.129 0.141
Standby Cooling PSB kW 0.081 0.115 0.116
mode Heating PSB kW 0.103 0.129 0.141
Thermostat-off Cooling PTO kW 0.009 0.014
mode Heating PTO kW 0.113 0.154 0.155
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ32U RXYQ34U RXYQ36U RXYQ38U RXYQ40U
Space cooling A Condition (35°C
EERd 2.2 2.1 2.4 2.2
recommended - 27/19) Pdc kW 90.0 95.4 97.0 102.4 111.9
2 combination 3 B Condition (30°C
- 27/19)
EERd
Pdc kW 66.3
4.1
70.3
4.0
71.5
4.5
75.5
4.4
82.5
C Condition (25°C
EERd 7.8 8.0 7.8 8.5 8.4
- 27/19) Pdc kW 42.6 45.2 45.9 48.5 53.0
D Condition
EERd 13.8 16.6 16.5 17.9 16.1
(20°C - 27/19)
Pdc kW 19.0 20.1 20.4 21.6 23.6
Space heating TBivalent COPd (declared COP) 2.4 2.2 2.1 2.2
(Average climate) Pdh (declared heating cap) kW 46.4 51.1 54.2 60.7 62.3
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.4 2.2 2.1 2.2
Pdh (declared heating cap) kW 46.4 51.1 54.2 60.7 62.3
Tol (temperature operating °C -10
limit)
A COPd (declared COP) 2.7 2.6 2.5 2.6
Condition Pdh (declared heating cap) kW 41.0 45.2 47.9 53.7 55.1
(-7°C)
B COPd (declared COP) 3.6 3.7 3.9 4.0
Condition Pdh (declared heating cap) kW 25.0 27.5 29.2 32.7 33.5
(2°C)
C COPd (declared COP) 6.3 6.5 6.4 6.5
Condition Pdh (declared heating cap) kW 16.1 17.7 18.8 21.3 21.6
(7°C)
D COPd (declared COP) 9.0 8.8 8.6 8.7
Condition Pdh (declared heating cap) kW 7.1 7.9 8.3 13.1
(12°C)
Space heating A COPd (declared COP) 2.7 2.6 2.5 2.6
(Average climate) Condition Pdh (declared heating cap) kW 41.0 45.2 47.9 53.7 55.1
recommended (-7°C)
combination 2 B COPd (declared COP) 3.6 3.8 3.7 3.9 4.0
Condition Pdh (declared heating cap) kW 25.0 27.5 29.2 32.7 33.5
(2°C)
C COPd (declared COP) 6.3 6.6 6.5
Condition Pdh (declared heating cap) kW 16.1 17.7 18.8 21.3 21.6
(7°C)
D COPd (declared COP) 9.1 8.9 8.8
Condition Pdh (declared heating cap) kW 7.1 7.9 8.3 13.2
(12°C)
TBivalent COPd (declared COP) 2.4 2.2 2.3 2.2
Pdh (declared heating cap) kW 46.4 51.1 54.2 60.7 62.3
Space heating TBivalent Tbiv (bivalent temperature) °C -10
(Average climate) TOL COPd (declared COP) 2.4 2.2 2.3 2.2
recommended Pdh (declared heating cap) kW 46.4 51.1 54.2 60.7 62.3
combination 2 Tol (temperature operating °C -10
limit)
Space heating A COPd (declared COP) 2.7 2.6 2.4 2.5 2.6
(Average climate) Condition Pdh (declared heating cap) kW 41.0 45.2 47.9 53.7 55.1
recommended (-7°C)
combination 3 B COPd (declared COP) 3.6 3.7 3.6 3.8 3.9
Condition Pdh (declared heating cap) kW 25.0 27.5 29.2 32.7 33.5
(2°C)
C COPd (declared COP) 6.3 6.4 6.3 6.4
Condition Pdh (declared heating cap) kW 16.1 17.7 18.8 21.2 21.6
(7°C)
D COPd (declared COP) 9.0 8.9 8.3 8.5 8.4
Condition Pdh (declared heating cap) kW 7.1 7.9 8.3 12.9 12.8
(12°C)
TBivalent COPd (declared COP) 2.4 2.2 2.1 2.2
Pdh (declared heating cap) kW 46.4 51.1 54.2 60.7 62.3
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.4 2.2 2.1 2.2
Pdh (declared heating cap) kW 46.4 51.1 54.2 60.7 62.3
Tol (temperature operating °C -10
limit)
Capacity range HP 32 34 36 38 40
PED Category Category II
Maximum number of connectable indoor units 64 (3)
Indoor index Min. 400.0 425.0 450.0 475.0 500.0
connection Max. 1,040.0 1,105.0 1,170.0 1,235.0 1,300.0
2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ32U RXYQ34U RXYQ36U RXYQ38U RXYQ40U
Heat exchanger Indoor side Air
Outdoor side Air
Air flow
rate
Cooling Rated
Heating Rated
m³/h
m³/h
31,200
31,200
30,660
30,660
31,260
31,260
35,880
35,880
36,660
36,660
2
Sound power level Cooling Nom. dBA 88.6 (4) 87.8 (4) 89.9 (4) 88.8 (4) 87.3 (4)
Heating Nom. dBA 71.6 (4) 70.6 (4) 70.9 (4) 69.9 (4) 70.2 (4)
Sound pressure Cooling Nom. dBA 66.0 (5) 65.5 (5) 67.1 (5) 66.2 (5) 65.2 (5)
level
Refrigerant Type R-410A
GWP 2,087.5
Refrigerant oil Type Synthetic (ether) oil FVC68D
Piping connections Liquid Type Braze connection
OD mm 19.1
Gas Type Braze connection
OD mm 34.9 41.3
Piping connections Total piping System Actual m 1,000 (6)
length
Indication if the heater is equipped with a supplementary heater no
Supplementary Back-up Heating elbu kW 0.0
heater capacity
Power Crankcase Cooling PCK kW 0.000
consumption in heater Heating PCK kW 0.154 0.166 0.192
other than active mode
mode Off mode Cooling POFF kW 0.149 0.150 0.157
Heating POFF kW 0.154 0.166 0.192
Standby Cooling PSB kW 0.149 0.150 0.157
mode Heating PSB kW 0.154 0.166 0.192
Thermostat-off Cooling PTO kW 0.019
mode Heating PTO kW 0.195 0.196 0.211
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ42U RXYQ44U RXYQ46U RXYQ48U RXYQ50U
Space cooling A Condition (35°C EERd 2.3 2.2 2.1
recommended - 27/19) Pdc kW 118.0 123.5 130.0 135.0 140.4
2 combination 2 B Condition (30°C
- 27/19)
EERd 4.4 4.3 4.2
Space cooling B Condition (30°C Pdc kW 86.9 91.0 95.8 99.5 103.5
recommended - 27/19)
combination 2 C Condition (25°C
EERd 8.2 7.9 8.1 8.0
- 27/19) Pdc kW 55.9 58.5 61.6 63.9 66.5
D Condition
EERd 15.3 14.0 15.6
(20°C - 27/19)
Pdc kW 24.8 26.0 27.4 28.4 29.6
Space cooling A Condition (35°C
EERd 2.3 2.2 2.1
recommended - 27/19) Pdc kW 118.0 123.5 130.0 135.0 140.4
combination 3 B Condition (30°C
EERd 4.3 4.2 4.1
- 27/19) Pdc kW 87.0 91.0 95.8 99.5 103.5
C Condition (25°C
EERd 8.0 7.9 7.8 7.9
- 27/19) Pdc kW 55.9 58.5 61.6 63.9 66.5
D Condition
EERd 15.2 14.2 13.9 13.8 15.6
(20°C - 27/19)
Pdc kW 24.8 26.0 27.4 28.4 29.6
Space heating TBivalent COPd (declared COP) 2.4 2.3 2.4 2.3
(Average climate) Pdh (declared heating cap) kW 62.4 64.8 67.0 69.6 74.3
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.4 2.3 2.4 2.3
Pdh (declared heating cap) kW 62.4 64.8 67.0 69.6 74.3
Tol (temperature operating °C -10
limit)
A COPd (declared COP) 2.7
Condition Pdh (declared heating cap) kW 55.2 57.3 59.3 61.6 65.7
(-7°C)
B COPd (declared COP) 3.7 3.6 3.7
Condition Pdh (declared heating cap) kW 33.6 34.9 36.1 37.5 40.0
(2°C)
C COPd (declared COP) 6.3 6.2 6.3 6.5
Condition Pdh (declared heating cap) kW 21.6 22.4 23.2 24.1 25.7
(7°C)
D COPd (declared COP) 8.6 8.7 8.8 8.9
Condition Pdh (declared heating cap) kW 9.9 10.0 10.3 10.7 12.0
(12°C)
Space heating A COPd (declared COP) 2.7
(Average climate) Condition Pdh (declared heating cap) kW 55.2 57.3 59.3 61.6 65.7
recommended (-7°C)
combination 2 B COPd (declared COP) 3.7 3.6 3.7
Condition Pdh (declared heating cap) kW 33.6 34.9 36.1 37.5 40.0
(2°C)
C COPd (declared COP) 6.4 6.3 6.5
Condition Pdh (declared heating cap) kW 21.6 22.4 22.8 24.1 25.7
(7°C)
D COPd (declared COP) 8.7 8.8 8.9 9.0
Condition Pdh (declared heating cap) kW 10.0 10.3 10.7 12.2
(12°C)
TBivalent COPd (declared COP) 2.4 2.3 2.4 2.3
Pdh (declared heating cap) kW 62.4 64.8 67.0 69.6 74.3
Space heating TBivalent Tbiv (bivalent temperature) °C -10
(Average climate) TOL COPd (declared COP) 2.4 2.3 2.4 2.3
recommended Pdh (declared heating cap) kW 62.4 64.8 67.0 69.6 74.3
combination 2 Tol (temperature operating °C -10
limit)
2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ42U RXYQ44U RXYQ46U RXYQ48U RXYQ50U
Space heating A COPd (declared COP) 2.7 2.6 2.7 2.6
(Average climate) Condition Pdh (declared heating cap) kW 55.2 57.3 59.3 61.6 65.7
recommended
combination 3
(-7°C)
B COPd (declared COP) 3.7 3.6
2
Condition Pdh (declared heating cap) kW 33.6 34.9 36.1 37.5 40.0
(2°C)
C COPd (declared COP) 6.3 6.2 6.3 6.4
Condition Pdh (declared heating cap) kW 21.6 22.4 23.2 24.1 25.7
(7°C)
D COPd (declared COP) 8.6 8.7 8.8 8.7
Condition Pdh (declared heating cap) kW 9.9 10.0 10.3 10.7 11.8
(12°C)
TBivalent COPd (declared COP) 2.4 2.3 2.4 2.2
Pdh (declared heating cap) kW 62.4 64.8 67.0 69.6 74.3
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.4 2.3 2.4 2.2
Pdh (declared heating cap) kW 62.4 64.8 67.0 69.6 74.3
Tol (temperature operating °C -10
limit)
Capacity range HP 42 44 46 48 50
PED Category Category II
Maximum number of connectable indoor units 64 (3)
Indoor index Min. 525.0 550.0 575.0 600.0 625.0
connection Max. 1,365.0 1,430.0 1,495.0 1,560.0 1,625.0
Heat exchanger Indoor side Air
Outdoor side Air
Air flow Cooling Rated m³/h 41,700 42,300 44,580 46,800 46,260
rate Heating Rated m³/h 41,700 42,300 44,580 46,800 46,260
Sound power level Cooling Nom. dBA 89.1 (4) 89.8 (4) 89.3 (4) 90.4 (4) 89.8 (4)
Heating Nom. dBA 72.4 (4) 73.3 (4) 73.4 (4) 72.7 (4)
Sound pressure Cooling Nom. dBA 66.5 (5) 67.2 (5) 67.0 (5) 67.8 (5) 67.5 (5)
level
Refrigerant Type R-410A
GWP 2,087.5
Refrigerant oil Type Synthetic (ether) oil FVC68D
Piping connections Liquid Type Braze connection
OD mm 19.1
Gas Type Braze connection
OD mm 41.3
Piping connections Total piping System Actual m 1,000 (6)
length
Indication if the heater is equipped with a supplementary heater no
Supplementary Back-up Heating elbu kW 0.0
heater capacity
Power Crankcase Cooling PCK kW 0.000
consumption in heater Heating PCK kW 0.206 0.231 0.243
other than active mode
mode Off mode Cooling POFF kW 0.190 0.223 0.224
Heating POFF kW 0.206 0.231 0.243
Standby Cooling PSB kW 0.190 0.223 0.224
mode Heating PSB kW 0.206 0.231 0.243
Thermostat-off Cooling PTO kW 0.024 0.029
mode Heating PTO kW 0.251 0.292 0.293
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ52U RXYQ54U
ESEER - Standard 4.99 4.97
SCOP 4.3
2 SCOP recommended combination 2
SCOP recommended combination 3
4.3
4.2
SEER 6.4
SEER recommended combination 2 6.4
SEER recommended combination 3 6.4
ηs,c % 253.7 254.1
ηs,c recommended combination 2 251.6 252.5
ηs,c recommended combination 3 251.5 253.9
ηs,h % 167.2 169.4
ηs,h recommended combination 2 168.7 170.8
ηs,h recommended combination 3 164.4 166.0
Space cooling A Condition (35°C EERd 2.0 1.9
- 27/19) Pdc kW 145.8 151.2
B Condition (30°C EERd 4.2 4.1
- 27/19) Pdc kW 107.4 111.4
C Condition (25°C EERd 8.1
- 27/19) Pdc kW 69.1 71.6
D Condition EERd 17.6 19.1
(20°C - 27/19) Pdc kW 30.7 34.4
Space cooling A Condition (35°C EERd 2.0 1.9
recommended - 27/19) Pdc kW 145.8 151.2
combination 2 B Condition (30°C EERd 4.1
- 27/19)
Space cooling B Condition (30°C Pdc kW 107.4 111.4
recommended - 27/19)
combination 2 C Condition (25°C EERd 8.1
- 27/19) Pdc kW 69.0 71.6
D Condition EERd 17.4 18.9
(20°C - 27/19) Pdc kW 30.7 34.1
Space cooling A Condition (35°C EERd 2.0 1.9
recommended - 27/19) Pdc kW 145.8 151.2
combination 3 B Condition (30°C EERd 4.1
- 27/19) Pdc kW 107.4 111.4
C Condition (25°C EERd 8.0 8.2
- 27/19) Pdc kW 69.1 71.6
D Condition EERd 17.5 19.1
(20°C - 27/19) Pdc kW 30.7 34.7
Space heating TBivalent COPd (declared COP) 2.2 2.1
(Average climate) Pdh (declared heating cap) kW 79.0 83.7
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.2 2.1
Pdh (declared heating cap) kW 79.0 83.7
Tol (temperature operating °C -10
limit)
A COPd (declared COP) 2.6
Condition Pdh (declared heating cap) kW 69.9 74.0
(-7°C)
B COPd (declared COP) 3.8 3.9
Condition Pdh (declared heating cap) kW 42.5 45.1
(2°C)
C COPd (declared COP) 6.6 6.8
Condition Pdh (declared heating cap) kW 27.4 29.0
(7°C)
D COPd (declared COP) 9.0
Condition Pdh (declared heating cap) kW 14.2
(12°C)
Space heating A COPd (declared COP) 2.6
(Average climate) Condition Pdh (declared heating cap) kW 69.9 74.0
recommended (-7°C)
combination 2 B COPd (declared COP) 3.8 3.9
Condition Pdh (declared heating cap) kW 42.6 45.1
(2°C)
C COPd (declared COP) 6.7 6.8
Condition Pdh (declared heating cap) kW 27.4 29.0
(7°C)
D COPd (declared COP) 9.1
Condition Pdh (declared heating cap) kW 14.4
(12°C)
TBivalent COPd (declared COP) 2.2 2.1
Pdh (declared heating cap) kW 79.0 83.7
2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ52U RXYQ54U
Space heating TBivalent Tbiv (bivalent temperature) °C -10
(Average climate) TOL COPd (declared COP) 2.2 2.1
recommended
combination 2
Pdh (declared heating cap)
Tol (temperature operating
kW
°C
79.0
-10
83.7
2
limit)
Space heating A COPd (declared COP) 2.6 2.5
(Average climate) Condition Pdh (declared heating cap) kW 69.9 74.0
recommended (-7°C)
combination 3 B COPd (declared COP) 3.7 3.8
Condition Pdh (declared heating cap) kW 42.5 45.1
(2°C)
C COPd (declared COP) 6.4 6.5
Condition Pdh (declared heating cap) kW 27.3 29.0
(7°C)
D COPd (declared COP) 8.7
Condition Pdh (declared heating cap) kW 13.7
(12°C)
TBivalent COPd (declared COP) 2.2 2.1
Pdh (declared heating cap) kW 79.0 83.7
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.2 2.1
Pdh (declared heating cap) kW 79.0 83.7
Tol (temperature operating °C -10
limit)
Capacity range HP 52 54
PED Category Category II
Maximum number of connectable indoor units 64 (3)
Indoor index Min. 650.0 675.0
connection Max. 1,690.0 1,755.0
Heat exchanger Indoor side Air
Outdoor side Air
Air flow Cooling Rated m³/h 45,720 45,180
rate Heating Rated m³/h 45,720 45,180
Sound power level Cooling Nom. dBA 89.3 (4) 88.6 (4)
Heating Nom. dBA 72.0 (4) 71.1 (4)
Sound pressure Cooling Nom. dBA 67.1 (5) 66.8 (5)
level
Refrigerant Type R-410A
GWP 2,087.5
Refrigerant oil Type Synthetic (ether) oil FVC68D
Piping connections Liquid Type Braze connection
OD mm 19.1
Gas Type Braze connection
OD mm 41.3
Piping connections Total piping System Actual m 1,000 (6)
length
Indication if the heater is equipped with a supplementary heater no
Supplementary Back-up Heating elbu kW 0.0
heater capacity
Power Crankcase Cooling PCK kW 0.000
consumption in heater Heating PCK kW 0.255 0.267
other than active mode
mode Off mode Cooling POFF kW 0.225 0.226
Heating POFF kW 0.255 0.267
Standby Cooling PSB kW 0.225 0.226
mode Heating PSB kW 0.255 0.267
Thermostat-off Cooling PTO kW 0.029
mode Heating PTO kW 0.294
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
2 Specifications
1 - 1 RXYQ-U
Electrical specifications System RXYQ22U RXYQ24U RXYQ26U RXYQ28U RXYQ30U
Current - 50Hz Starting current (MSC) - remark See note 8
Zmax List No requirements
2 Minimum Ssc value
Minimum circuit amps (MCA)
kVa
A
11,573 (8)
46.0 (9)
11,597 (8) 12,831 (8)
51.0 (9)
13,585 (8)
55.0 (9)
14,843 (8)
59.0 (9)
Maximum fuse amps (MFA) A 63 (10) 80 (10)
Wiring For power Quantity 5G
connections - 50Hz supply
For connection Quantity 2
with indoor Remark F1,F2
2 Specifications
1 - 1 RXYQ-U
3 Options
3 - 1 Options
RXYQ-U
RYYQ-U
RYMQ-U
3 RXYQQ-U
RXYQ8U RXYQ10-12U RXYQ14-18U RXYQ20U RYYQ22~54U
RYYQ8U RYYQ10-12U RYYQ14-18U RYYQ20U RXYQ22~54U
RXYQQ8U RXYQQ10-12U RXYQQ14-18U RXYQQ20U RXYQQ22~42U
No Item
I. Refnet header KHRQ22M29H
KHRQ22M64H
--- --- --- KHRQ22M75H
II. Refnet joint KHRQ22M20T
KHRQ22M29T9
KHRQ22M64T
--- --- --- KHRQ22M75T
III. Outdoor multi-connection kit See note ·2·. --- --- --- --- BHFQ22P1007
IV. Outdoor multi-connection kit See note ·2·. --- --- --- --- BHFQ22P1517
No Item 8HP 10HP 12HP 14HP 16HP 18HP 20HP
1a Cool/heat selector (switch) See note ·3·. KRC19-26A
1b Cool/heat selector (PCB) BRP2A81
1c Cool/heat selector (fixing box) KJB111A
2 VRV configurator EKPCCAB*
3 Heater tape kit PCB EKBPH012T7A EKBPH020T7A
4 Demand PCB See DTA104A61/62*
5 Demand PCB mounting plate See note ·4·. --- KKSB26B1*
Notes
1 All options are kits
2 Only for multi units
3 To mount option ·1a·, option ·1c· is required.
4 To install the demand PCB on the large casing type, the demand PCB mounting plate is required.
3D120006B
4 Combination table
4 - 1 Combination Table
REMQ5U
REYQ8-20U
RXYQQ8-20U 4
RXYTQ8-16UYF
RYYQ8-20U
RYMQ8-20U
Unit combination restrictions: VRV4 outdoor units (all models) + 15-class indoor units
Units in scope: FXZQ15A and FXAQ15A.
1. In case the system contains these indoor units and the total connection ratio (CR) ≤ 100%: no special restrictions.
Follow the restrictions that apply to regular VRV DX indoor units.
2. In case the system contains these indoor units and the total connection ratio (CR) > 100%: special restrictions apply.
A. When the connection ratio (CR1) of the sum of all FXZQ15A and/or FXAQ15A units in the system ≤ 70%, and ALL other VRV DX
indoor units have an individual capacity class > 50: no special restrictions.
B. When the connection ratio (CR1) of the sum of all FXZQ15A and/or FXAQ15A units in the system ≤ 70%, and NOT ALL other
VRV DX indoor units have an individual capacity class > 50: the restrictions below apply.
• 100% < CR ≤ 105% → CR1 of the sum of all FXZQ15A and/or FXAQ15A indoor units in the system must be ≤ 70%.
• 105% < CR ≤ 110% → CR1 of the sum of all FXZQ15A and/or FXAQ15A indoor units in the system must be ≤ 60%.
• 110% < CR ≤ 115% → CR1 of the sum of all FXZQ15A and/or FXAQ15A indoor units in the system must be ≤ 40%.
• 115% < CR ≤ 120% → CR1 of the sum of all FXZQ15A and/or FXAQ15A indoor units in the system must be ≤ 25%.
• 120% < CR ≤ 125% → CR1 of the sum of all FXZQ15A and/or FXAQ15A indoor units in the system must be ≤ 10%.
• 125% < CR ≤ 130% → FXZQ15A andFXAQ15A cannot be used
REMARK
Only the 15-class indoor units explicitly mentioned on this page are in scope. Other indoor units follow the rules that apply to regular
VRV DX indoor units.
3D104665
RXYQQ-U
RXYQ-U Heat pump VRV4
RYYQ-U Multi-unit standard combinations table
RYMQ-U
10HP
12HP
14HP
16HP
18HP
20HP
8HP
1
RXYQ8* / RYYQ8* / RXYQQ8*
1
RXYQ10* / RYYQ10* / RXYQQ10*
1
Heat pump
RXYQ44* / RYYQ44* 1 2
RXYQ46* / RYYQ46* 1 2
RXYQ48* / RYYQ48* 3
RXYQ50* / RYYQ50* 2 1
RXYQ52* / RYYQ52* 1 2
RXYQ54* / RYYQ54* 3
Remark
RYYQ8~20 = Single continuous heating
RYYQ22~54 =Multi continuous heating
RXYQ8~20 = Single non-continuous heating
RXYQ22~54 =Multi non-continuous heating
RXYQQ8~20 =Single non-continuous heating replacement (VRV4-Q)
RXYQQ22~42Multi= non-continuous heating replacement (VRV4-Q)
1) For single unit installation RYYQ* units (continuous heating) and RXYQ* units (non-continuous heating)
2) "Non-continuous heating" multi-outdoor-unit combinations consist of RXYQ8~20 units (e.g. RXYQ36*=RXYQ16*+RXYQ20*).
3) "Continuous heating" multi-outdoor-unit combinations consist of RYMQ8~20 units (e.g. RYYQ36*=RYMQ16*+RYMQ20*).
→ RYMQ* units can only be used in multi-outdoor-unit combinations and cannot be used as standalone units.
4) RYYQ8~20* units cannot be used in multi-outdoor-unit combinations.
5) RYYQ8~20 "Continuous heating" multi-outdoor-unit combinations cannot contain RXYQ* units.
6) RXYQ8~20 "Non-continuous heating" multi-outdoor-unit combinations cannot contain RYMQ* units.
7) Multi "non-continuous heating" replacement models only consist of RXYQQ8-20 modules (e.g. RXYQQ36*=RXYQQ16*+RXYQQ20*).
8) Replacement units cannot be combined with other units.
9) T-series outdoor units and U-series outdoor units cannot share the same refrigerant circuit. When combining these units, make sure they are part of separate refrigerant circuits.
3D120060
4 Combination table
4 - 1 Combination Table
RXYQ-U
RYYQ-U
VRV4
RYMQ-U Heat pump
4 Indoor unit combination restrictions
(1/2)
(3)
Indoor unit combination pattern ·VRV* DX· indoor unit ·RA DX· indoor unit Hydrobox unit Air handling unit (AHU)
Notes
1. ·VRV* DX· indoor unit
- When combining ·VRV DX· indoor units with other types of indoor units, respect the following combination patterns:
Example
Allowed : (·VRV DX· indoor unit + ·Hydrobox· unit) or (·VRV DX· indoor unit + ·RA DX· indoor unit) or (·VRV DX· indoor unit + ·AHU·)
Not allowed : [·VRV DX· indoor unit + (·RA DX· indoor unit & (·Hydrobox· unit or ·AHU·))] or [·VRV DX· indoor unit + (·Hydrobox· unit & (·RA DX· indoor unit or ·AHU·))]
2. O1
- Only connect ·Hydrobox· units to a ·VRV IV· Heat Pump in combination with a ·VRV DX· indoor unit.
→ Refer to the connection ratio restrictions (·3D079540 & 3D117169·).
→ Connection with only Hydrobox units: refer to the Daikin Altherma solutions.
- Only connect ·Hydrobox· units of the ·HXY*· series.
→ ·HXHD*· series ·Hydrobox· units are not allowed.
3. O2
- Combination of ·AHU· only + control box ·EKEQFA· (the combination with ·VRV DX· indoor units is not allowed; maximum ·54·HP for ·400 + 2x500· class ·EKEXV· kit)
→ ·X·-control is possible (up to ·3x· [·EKEXV+EKEQFA*· boxes] can be connected to one outdoor unit (system)). No Variable Refrigerant Temperature control possible.
→ ·Y·-control is possible (up to ·3x· [·EKEXV+EKEQFA*· boxes] can be connected to one outdoor unit (system)). No Variable Refrigerant Temperature control possible.
→ ·W·-control is possible (up to ·3x· [·EKEXV+EKEQFA*· boxes] can be connected to one outdoor unit (system)). No Variable Refrigerant Temperature control possible.
- Combination of ·AHU· only + control box ·EKEQMA· (not combined with ·VRV DX· indoor units)
→ Z-control is possible (the allowed number of [·EKEXV + EKEQMA· boxes] is determined by the connection ratio (·90-110%·) and the capacity of the outdoor unit.
5. The combination of ·AHU· with ·Hydrobox· units or ·RA DX· indoor units is not allowed.
VRV4
Heat pump
Indoor unit combination restrictions
(2/2)
RXYQ* RXYQ*
RYYQ* RYYQ* RXMLQ* RXMLQ*
Combination table RXYLQ* RXYLQ*
Single non-continuous Multi non-continuous
Single continuous heating Multi continuous heating
heating heating
·VRV* DX· indoor unit O O O O
·RA DX· indoor unit O X O X
Hydrobox unit O O1 O O1
Air handling unit (AHU) (2) O O O O
O: Allowed
X: Not allowed
Notes
1. O1
- Available upon request through the ·SPN· procedure.
3D079543F
4 Combination table
4 - 1 Combination Table
RXYQ-U
RYYQ-U
RYMQ-U Compatibility list: ·VRV4· heat pump - ·RA DX· indoor unit 4
RXYLQ-T
RXMLQ-T
Configuration Unit type
Wall mounted type Emura FTXJ20M
FTXJ25M
FTXJ35M
FTXJ50M
Stylish FTXA20
FTXA25
FTXA35
FTXA42
FTXA50
Ceiling/wall mounted Flex FLXS25B
FLXS35B
FLXS50B
FLXS60B
Floor standing type FVXM FVXM25F
FVXM35F
FVXM50F
CVXM20A
FVXM25A
FVXM35A
FVXM50A
FVXM60A
Nexura FVXG25K
FVXG35K
FVXG50K
Remark
The limitations on the use of ·RA DX· indoor units with the ·VRV4· Heat Pump are subject to the rules set out in drawings ·3D079543· and ·3D079540·.
If you want to connect ·RA·/·SA· ·DX· cassette, ceiling-mounted, or duct indoor units, use their ·VRV DX· indoor unit equivalents instead.
3D082373E
5 Capacity tables
5 - 1 Capacity Table Legend
,QRUGHUWRIXO¿OOPRUH\RXUUHTXLUHPHQWVRQTXLFNDFFHVVRIGDWDLQWKHIRUPDW\RXUHTXLUHZHKDYHGHYHORSHGDWRROWR
FRQVXOWFDSDFLW\WDEOHV
5 %HORZ\RXFDQ¿QGWKHOLQNWRWKHFDSDFLW\WDEOHGDWDEDVHDQGDQRYHUYLHZRIDOOWKHWRROVZHKDYHWRKHOS\RXVHOHFWWKH
FRUUHFWSURGXFW
5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ-U
RXYQ-U
RYYQ-U VRV4
5
RYMQ-U Heat pump
Integrated heating capacity coefficient
The heating capacity tables do not take into account the capacity reduction in case of frost accumulation or defrost operation.
The capacity values that take these factors into account, or in other words, the integrated heating capacity values, can be calculated as follows:
Formula
A = Integrated heating capacity
B = Capacity characteristics value (see table)
C = Integrated correction factor for frost accumulation (see table)
A=B*C
Heating capacity
34HP 0,95 0,92 0,87 0,78 0,79 0,87 1,00 Time
36HP 0,95 0,92 0,87 0,78 0,79 0,87 1,00
38HP 0,95 0,93 0,88 0,83 0,84 0,89 1,00
40HP 0,95 0,93 0,87 0,80 0,81 0,88 1,00
42HP 0,95 0,92 0,86 0,73 0,74 0,84 1,00
44HP 0,95 0,92 0,86 0,72 0,73 0,84 1,00
46HP 0,95 0,92 0,86 0,72 0,72 0,83 1,00
48HP 0,95 0,92 0,86 0,71 0,72 0,83 1,00
50HP 0,95 0,92 0,87 0,76 0,77 0,86 1,00 1 cycle
52HP 0,95 0,93 0,87 0,80 0,81 0,88 1,00
54HP 0,95 0,93 0,88 0,84 0,85 0,90 1,00
Notes
The figure shows the integrated heating capacity for a single cycle (from one defrost operation to the next).
When there is an accumulation of snow against the outdoor unit heat exchanger, there will always be a temporary reduction in capacity depending on the outdoor
temperature (°C DB), relative humidity (RH) and the amount of frosting which occurs.
The multi-combination data 22~54HP corresponds with the standard multi-combination of drawing 3D079534.
3D079898A
5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ8U
RXYQ8U
RYYQ8U
5 RYMQ8U
Indoor (m)
Indoor (m)
NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
8HP 22.2 12.7
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for deicated indoor connection types.
6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =
Choose the correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ10U
RXYQ10U
RYYQ10U
RYMQ10U 5
Correction ratio for cooling capacity Correction ratio for heating capacity
Height Difference between outdoor and farest
Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)
NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased. For new diameters, see below.
Model Gas Liquid
RXYQ10P 25.4* 12.7
*If not available on site, do not increase. If not increased correction factor should be applied to the equivalent length (see note 6).
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
10 HP 22.2 9.5
6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =
Choose the correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ12,14,16,24,36U
RXYQ12,14,24,36U
RYYQ12,14,24,36U
RYMQ12,14U
5
Correction ratio for cooling capacity Correction ratio for heating capacity
Height Difference between outdoor and farest
Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)
NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased. For new diameters, see below.
Model Gas Liquid
12 HP 28.6 15.9
14 HP 28.6 15.9
24 HP 34.9 19.1
36 HP 41.3 22.2
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
12 HP 28.6 12.7
14 HP 28.6 12.7
24 HP 34.9 15.9
36 HP 41.3 19.1
6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =
Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard Size
size increase
Cooling (gas pipe) 1,0
Heating (liquid pipe) 1,0 0,5
80 m 40 m
5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ16U
RXYQ16U
RYYQ16U
RYMQ16U Correction ratio for cooling capacity Correction ratio for heating capacity 5
Height Difference between outdoor and farest
Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)
NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased. For new diameters, see below.
Model Gas Liquid
16 HP 31.8* 15.9
*If not available on site, do not increase. If not increased correction factor should be applied to the equivalent length (see note 6).
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
16 HP 28.6 12.7
6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =
Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
Example
Main gas pipe size increase
Main Liquid pipe size increase Equivalent length branch
80 m 40 m
3D079897A
5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ18,26,28,30,38,40,42,44U
RXYQ18,26,28,30,38,40,42,44U
RYYQ18,26,28,30,38,40,42,44U
RYMQ18U
5 Correction ratio for cooling capacity Correction ratio for heating capacity
Height Difference between outdoor and farest
Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)
NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
18 HP 31.8* 19.1
26~30 HP 38.1* 22.2
38~44 HP 41.3 22.2
*If not available on site, do not increase. If not increased correction factor should be applied to the equivalent length (see note 6).
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
18 HP 28.6 15.9
26~30 HP 34.9 19.1
38~44 HP 41.3 19.1
6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =
Choose the correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
In the above case (for RXYQ38-44) (Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m
(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 1.0
3D079897A
5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ20,32,34U
RXYQ20,32,34U
RYYQ20,32,34U
RYMQ20,32,34U
Correction ratio for cooling capacity Correction ratio for heating capacity 5
Height Difference between outdoor and farest
Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)
NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
20 HP 31.8* 19.1
32/34 HP 38.1* 22.2
*If not available on site, do not increase. If not increased correction factor should be applied to the equivalent length (see note 6).
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
20 HP 28.6 15.9
32/34 HP 34.9 19.1
6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =
Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
Example
Main gas pipe size increase
Main Liquid pipe size increase Equivalent length branch
80 m 40 m
3D079897A
5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ22U
RXYQ22U
RYYQ22U
5 RYMQ22U Correction ratio for cooling capacity Correction ratio for heating capacity
Height Difference between outdoor and farest
Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)
NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
22 HP 31.8* 19.1
* If not available on site, do not increase, if not increased, no correction factor should be applied to the equivalent length (see note 6).
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
22 HP 28.6 15.9
6. Equivalent length used in the above figures is based upon the following equivalent length
Overal equivalent length =
Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
Example
Main gas pipe size increase
Main Liquid pipe size increase Equivalent length branch
80 m 40 m
3D079897A
5 Capacity tables
5 - 2 Capacity Correction Factor
RYYQ46U
RXYQ46U Correction ratio for cooling capacity Correction ratio for heating capacity
5
Height Difference between outdoor and farest
Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)
NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
46 HP 41.3 22.2
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
46 HP 41.3 19.1
6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =
Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0
Heating (liquid pipe) 1.0 0.5
80 m 40 m
3D079897A
5 Capacity tables
5 - 2 Capacity Correction Factor
RYYQ48U
RXYQQ48U Correction ratio for heating capacity
5 RXYQ48U
Indoor (m)
Indoor (m)
NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
48 HP 41.3 22.2
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
48 HP 41.3 19.1
6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =
Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0
Heating (liquid pipe) 1.0 0.5
Example
Main gas pipe size increase
Main Liquid pipe size increase Equivalent length branch
80 m 40 m
3D079897A
5 Capacity tables
5 - 2 Capacity Correction Factor
RYYQ50U
RXYQQ50U
RXYQ50U Correction ratio for cooling capacity Correction ratio for heating capacity 5
Indoor (m)
Indoor (m)
NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
50 HP 41.3 22.2
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
50 HP 41.3 19.1
6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =
Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0
Heating (liquid pipe) 1.0 0.5
Example
Main gas pipe size increase
Main Liquid pipe size increase Equivalent length branch
80 m 40 m
3D079897A
5 Capacity tables
5 - 2 Capacity Correction Factor
RYYQ52U
RXYQQ52U
5 RXYQ52U
Indoor (m)
Indoor (m)
NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
52 HP 41.3 22.2
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
52 HP 41.3 19.1
6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =
Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0
Heating (liquid pipe) 1.0 0.5
Example
Main gas pipe size increase
Main Liquid pipe size increase Equivalent length branch
80 m 40 m
3D079897A
5 Capacity tables
5 - 2 Capacity Correction Factor
RYYQ54U
RXYQQ54U
RXYQ54U Correction ratio for cooling capacity Correction ratio for heating capacity 5
Height Difference between outdoor and farest
Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)
NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
54 HP 41.3 22.2
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =
Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0
Heating (liquid pipe) 1.0 0.5
Example
Main gas pipe size increase
Main Liquid pipe size increase Equivalent length branch
80 m 40 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 0.83
3D079897A
6 Dimensional drawings
6 - 1 Dimensional Drawings
REMQ5U
Pitch of foundation bolt holes
REYQ8-12U 1 2 766
3
RXYQQ8-12U
RXYTQ8-UYF
729
8
AA
134
190
125
RYYQ8-12U
100
107
112
66
160
106
AB
70
Detail ·A· Detail ·B·
4-15x22.5mm
Oblong hole 10
View ·C·
Foundation bolt hole
11
1685
7
9 6
122
515
276
259
179
131
76 76
5
Model
97 107
137 Detail ·B· Detail ·A· AA AB
272
Notes 765
328 RYYQ8-12U, RXYQ8-12U, RXYQQ8-12U,RXYTQ8U - -
1.Detail ·A· and detail ·B· indicate the dimensions after fixing the attached piping. C
2. Items ·4 - 10:· Knockout hole.
373 REMQ5U, RYMQ8-12U, REYQ8-12U 246 240
930
3. Gas pipe
RYYQ8U, RYMQ8U, RXYQ8U, RXYQQ8U, RXYTQ8U : Ø ·19.1· brazing connection 11 Grounding terminal
RYYQ10U, RYMQ10U, RXYQ10U, RXYQQ10U : Ø ·22.2· brazing connection Pipe routing hole (bottom)
: 10
REMQ5U, REYQ8-12U Ø ·25.4· brazing connection
RYYQ12U, RYMQ12U, RXYQ12U, RXYQQ12U : Ø ·28.6· brazing connection 9 Pipe routing hole (front) Inside of the switch box (·M8·)
Liquid pipe
8 Power cord routing hole (bottom) Ø65
RYYQ8-10U, RYMQ8-10U, RXYQ8-10U, RXYQQ8-10U, : Ø ·9.5· brazing connection 7 Power cord routing hole (front) Ø27
REMQ5U, REYQ8-12U, RXYTQ8U
6 Power cord routing hole (front) Ø65
RYYQ12U, RYMQ12U, RXYQ12U, RXYQQ12U : Ø ·12.7· brazing connection 5 Power cord routing hole (front) Ø80
Equalising pipe 4 Power cord routing hole (side) Ø65
RYMQ8-10U : Ø ·19.1· brazing connection Equalising pipe connection port See note ·3·.
3
High pressure/low pressure gas pipe See note ·3·.
RYMQ12U : Ø ·22.2· brazing connection
2 Gas pipe connection port See note ·3·.
High pressure/low pressure gas pipe 1 Liquid pipe connection port Remark
No. Part name
REMQ5U, REYQ8-12U : Ø ·19.1· brazing connection 2D119001
1076
RXYTQ10-16U 3
RYYQ14-20U 393
RYMQ14-20U
134
125 8
729
310
210
107
112
AB
70
100 71
160 106
10
AA
4-15x22.5mm - Oblong hole
Detail A Detail B View C
Foundation bolt hole
11
1685
7 6
9
122
515
276
259
179
131
76 76 97 107 5 Model AA AB
DETAIL A
137 DETAIL B 272
RXYQ14-20U, RYYQ14-20U, RXYQQ14-20U, RXYTQ10-16U - -
Notes 765 328
C RYMQ14-16U, REYQ14-20U 240 155
1. Detail A and detail B indicate the dimensions after fixing the attached piping. 1. 373
7 Centre of gravity
7 - 1 Centre of Gravity
RXYQQ8-12U
RXYQ8-12U
RXYTQ8UYF
RYYQ8-12U
Unit AA AB AC
RYMQ8-12U 7
REMQ5U RYYQ8-12U
REYQ8-12U 328 366 565
REMQ5U / REYQ8-12U
RYMQ8-12U 354 443 565
RXYQ8-12U
RXYQQ8-12U 339 448 565
RXYTQ8U
View ·A·
AC
View ·A·
AA AB
729 766 Foundation bolt hole
RXYQQ14-20U
RXYQ14-20U Unit AA AB AC
RXYTQ10-16UYF RYYQ14-20U 334 470 610
REYQ14-20U 334 470 610
RYYQ14-20U Foundation bolt hole (slot)
RYMQ14-20U 360 569 610
RYMQ14-20U View ·A· RXYQ(Q)14-20U 345 575 610
REYQ14-20U RXYTQ10-12U 350 610 810
RXYTQ14-16U 351 565 610
AC
View ·A·
AA AB
729 1076
Foundation bolt hole Foundation bolt hole
Foundation bolt hole
3D119704
8 Piping diagrams
8 - 1 Piping Diagrams
RXYQ8-12U
RXYTQ8UYF R1T
8 Y3E
R4T
M
M1F
Thermistor
Heat sink
(PCB)
Y1S
Capillary tube
Expansion valve
S1NPL S1NPH
4-way valve
Propeller fan
R3T
M
R21T Accumulator
Y3S
sv
R8T
M1C
Heat exchanger
sv
Compressor
Y2S
Gas pipe
Double tube heat exchanger
Charge port
Distributor
Solenoid valve
sv
3D118179
RXYQ14-20U
RXYQ14-16UYF
R1T
Y2E
Pressure relief valve
Thermistor
Heat sink
(PCB)
Capillary tube
Expansion valve
Y1S
4-way valve
S1NPL S1NPH
Propeller fan
M
HPS HPS
Accumulator
S1PH S2PH
R21T R22T
Heat exchanger
sv
sv
Y3S Y4S
R8T R9T
M1C M2C Compressor
sv
Oil separator
Y2S
3D118180
9 Wiring diagrams
9 Notes & Legend
RXYQ8-12U
RXYTQ8UYF
RYYQ8-12U 9
RYMQ8-12U
NOTES
2D117534
9 Wiring diagrams
9-2 Wiring Diagrams - Single Phase
RXYQ8-12U
RXYTQ8UYF
RYYQ8-12U 9
RYMQ8-12U
X23A
BLK
BLU
F403U
X37A
X3A HAP (Note 7)
GRN E1 (Note 3) X25A Y4E
Z1F 5 M
S1PH P>
X2A (Note 6)
L1B L2B L3B Z4C N=1 PS
X18A t ゜ R1T
BLK
RED
X28A
WHT
S1NPL
K7R
A3P
K11R
Z7C N=1
K6R
K4R
K5R
K9R
Z5C N=2 X31A
L1B L2B L3B X6A X20A X10A X8A X9A X13A X15A X11A
X40A S1NPH
X4A X32A
HAP
+
V1R
-
P2 Z6C t゜ t゜ t゜ t゜ t゜ t゜ t゜
N=3
V1D +C506 +C503 N32 BLK X3A X50A X19A X30A
GRN
V1R
A5P
U V W X41A (Note 4) (Note 4) (Note 4)
X1A
Z7C N=1 X1M
A4P C/H selector
Z2C N=4 A B C
P1 N1 X5A indoor outdoor outdoor
WHT
WHT
R24
L1R X3A + HAP X4A
-
A1P L1R
A5P
A2P
8,10,12 class
X3A
X1A X1M A4P
A3P
2D117534
9 Wiring diagrams
9-3 Wiring Diagrams - Three Phase
RXYQ14-20U A1P Printed circuit board (main)
A2P, A5P Printed circuit board (noise filter)
RYYQ14-20U A3P, A6P Printed circuit board (inv)
RYMQ14-20U A4P, A7P Printed circuit board (fan)
9 A8P Printed circuit board (ABC I/P)
BS1~3 (A1P) Push button switch (mode, set, return)
C503, C506, C507 (A3P, A6P) Capacitor
(NOTE 7)7)
Y2E
Y3E
Y4E
(note
5 M
5 M
5 M
5 M
S1NPH
S1NPL
t ゜ R1T
X22A
X23A
X25A
X18A
X32A
(note 4)
F3U Field fuse
(Q1)(Q2)
F101U (A4P, A7P) Fuse
outdoor
(NOTE3)3)
Q2
1234
SEG3
DS2
BS3
X37A
(note
Q1
(note 4)
BS2
X5A R L2
R L1
HAP
BS1
ON
OFF
F1
(note 4)
A2P
A3P
(F1)(F2)
indoor
X1M
PS
Z8C
N=1
el.compo.box
X6A
A5P
A6P
K6R (A1P) Magnetic relay (E3H)
(note 8)
K11R
X15A
Y5S
t゜
R6T
fan
X1A
X2A
・
K7R
E1HC
X11A
X30A
R5T
A1P
X1M
cool
t゜
K3R
Y4S
X7A
A8P
M1F, M2F Motor (fan)
t゜
R3T
Y3S
V
C
t゜
K5R
X9A
Y2S
U
R8T
A
X19A
K4R
X8A
Y1S
A8P
X1A
el.compo.box
outer shell
K6R
R21T
X10A
E3H
GRN
X4A X5A X50A
X66A
Q1LD
(note 6)
(note 6)
M2F
X40A
X28A
X2A
X3A
X1A
X101A
A1P
RED
WHT
BLU
BLK
BLK
BLK
S2PH P>
P11 RED
BLK
N31 BLK
N32
X6A
X4A
HAP
BLU F601U
K3R
Z6C
N=1
Z1C
N=5
V1R
R300
X3A
U MS W
W
V1D +C506 +C503
L1B L2B L3B
C507
WHT WHT
M1C 3~
X*A Connector
WHT
V1R
V
+
X601A
X61A
X41A
P1
P2
WHT
L1R
P11 RED
BLK
N31 BLK
N32
X6A
X4A
PS
Z7C N=1
F601U
(note
BLU
Y5S Solenoid valve (sub) (note 8)
K3R
Z2C
N=5
V1R
R300
X4A
N
-
Z*C Noise filter (ferrite core)
BLK F403U BLK - BLK
L1A L2A L3A
U MS W
W
V1D +C506 +C503
L1B L2B L3B
WHT WHT
M2C 3~
WHT
V1R
V
+
E1
X601A
P1
P2
Z9C
N=2
WHT
X37A Connector (power adapter)
L2R
WHT
X66A Connector (remote switching
Cool/heat selector)
N=1
T1A
NOTES
P11 RED
RED
N11 BLK
BLK
WHT
RED
BLU
BLK
N11
X1M
L1
L2
L3
N
X5A
X5A
2.
X3A
F101U
R24
R24
HAP
X3A
+ +
X4A
X4A
-
V1R
3. When using the optional adapter, refer to the installation manual of the optional adapter.
A7P
A4P
X1A
X1A
50Hz
60Hz
5. How to use BS1~3 switch. Refer to “service precaution” label on el. Compo. Box cover.
(note 9)
(note 9)
Power supply
X2A
X1A
M1F
MS
MS
L1
L2
L3
3~
3~
N
2D117536C
10 RYYQ8-20U 3. For details, refer to the wiring diagram attached to the outdoor unit.
RYMQ8-20U
4. Install a circuit breaker for safety.
5. All field wiring and components must be provided by an authorised electrician.
6. Unit has to be grounded in compliance with the applicable legislation.
7. The wiring shown is a general points-of-connection guide and is not intended to include all details for a specific installation.
8. Make sure to install the switch and the fuse to the power line of each equipement.
9. Install a main switch to control the multiple power sources that the various components of the system make use of.
10. The capacity of UNIT1 must be larger than that of UNIT2 when the power source is connected in series between the units.
The capacity of UNIT 2 must be larger than that of UNIT3 when the power source is connected in series between the units.
11. If there exists the possibility of reversed phase, loose phase or momentary blackout, or if the power goes on and off while the product is operating, attach a reversed
phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
12. Install an earth leakage circuit breaker.
Power supply
L1 L2 L3 N
< Power source is supplied to each outdoor unit
individually. > Power supply
L1 L2 L3 N
< Power source is connected in series between
the units. >
Main switch Outdoor units Main switch Outdoor units
2-wire cable
Transmission line
2-wire cable 2-wire cable 2-wire cable 2-wire cable 2-wire cable
2-wire cable 2-wire cable
2- wire cable Transmission line Transmission line
Transmission line Transmission line Transmission line Transmission line
Transmission line
Power line
2-wire cable L N L N L N L N L N L N L N L N
Power line Switch Switch Switch Switch Switch Switch Switch Switch
Fuse Fuse Fuse Fuse Fuse Fuse Fuse Fuse
2-wire cable
Power line
2-wire cable 2-wire cable
2-wire cable 2-wire cable 2-wire cable 2-wire cable 2-wire cable
Power line Power line
Power line Power line Power line Power line Power line
3D119200
RXYQQ8-20U Notes
RXYQ8-20U 1. All wiring, components and materials to be procured on-site must comply with the applicable legislation.
2.Use copper conductors only
RXYTQ8-16U 3. For details, refer to the wiring diagram attached to the outdoor unit.
Power supply
< Power source is supplied to each outdoor unit individually.
> Power supply
< Power source is connected in series between the units.
>
L1 L2 L3 N L1 L2 L3 N
·2·-wire cable
·2·-wire cable Transmission line
Transmission line ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable
·2·-wire cable Transmission lin Transmission lin Transmission line Transmission line Transmission line
Power line Transmission line
Power line
e e
L N L N L N L N L N L N L N L N
Switch Switch Switch Switch Switch Switch Switch Switch
Fuse Fuse Fuse Fuse Fuse Fuse Fuse Fuse
·2·-wire cable
Power line
·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable
Power line Power line Power line Power line Power line Power line Power line
3D119316
RYMQ8-20U 1. All wiring, components and materials to be procured on-site must comply with the applicable le
gislation.
10
RXYTQ8-16UYF
L1 L2 L3 N Power supply
2. Use copper conductors only
3. For details, refer to the wiring diagram attached to the outdoor unit.
Main switch
4. Install a circuit breaker for safety.
5. All field wiring and components must be provided by an authorised electrician.
6. Unit has to be grounded in compliance with the applicable legislation.
Outdoor unit
Switch 7. The wiring shown is a general points-of-connection guide and is not intended to include all details
for a specific installation.
L1 L2 L3 N
Fuse 8. Make sure to install the switch and the fuse to the power line of each equipement.
9. Install a main switch to control the multiple power sources that the various components of t
he system make use of.
Power supply 10. If there exists the possibility of reversed phase, loose phase or momentary blackout, or if the power g
oes on and off while the product is operating, attach a reversed phase protection circuit locally.
L N
Main switch Running the product in reversed phase may break the compressor and other parts.
11. Install an earth leakage circuit breaker.
2-wire cable
Transmission line
L N L N L N L N
Switch Switch Switch Switch
Indoor unit
3D119317
11 Sound data
11 - 1 Sound Power Spectrum
REMQ5U
REYQ8U
RXYQQ8U
11 RXYQ8U 90 90
RXYTQ8UYF 85 NR90
RYYQ8U 80 NR85 80
RYMQ8U 75 NR80
70 NR75 70
65 NR70
Sound power level [dB]
60 60
NR65
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR10 NR15
NR5
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119528
REYQ10U
RXYQQ10U
RXYQ10U 90 90
RYYQ10U 85 NR90
RYMQ10U 80 NR85 80
75 NR80
70 NR75 70
65 NR70
Sound power level [dB]
60 60
NR65
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR10 NR15
NR5
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119529
11 Sound data
11 - 1 Sound Power Spectrum
REYQ12U
RXYQQ12U
RXYQ12U 95
RYYQ12U
11
90 90
RYMQ12U 85 NR90
80 NR85 80
75 NR80
70 NR75 70
65
Sound power level [dB]
NR70
60 NR65 60
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0
NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119530
REYQ14U
RXYQQ14U
90 90
RXYQ14U
85 NR90
RYYQ14U
80 80
RYMQ14U NR85
75 NR80
70 NR75 70
Sound power level [dB]
65 NR70
60 60
NR65
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR10 NR15
NR5
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119531
11 Sound data
11 - 1 Sound Power Spectrum
REYQ16U
RXYQQ16U
RXYQ16U 95
11 RYYQ16U 90 90
RYMQ16U 85 NR90
80 NR85 80
75 NR80
70 NR75 70
65
Sound power level [dB]
NR70
60 NR65 60
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0
NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119532
REYQ18U
RXYQQ18U
95
RXYQ18U
90 90
RYYQ18U
85 NR90
RYMQ18U
80 NR85 80
75 NR80
70 NR75 70
Sound power level [dB]
65 NR70
60 NR65 60
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0
NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119533
11 Sound data
11 - 1 Sound Power Spectrum
REYQ20U
RXYQQ20U
100 100
RXYQ20U
RYYQ20U
95 11
90 90
RYMQ20U
85 NR90
80 NR85 80
75 NR80
70 NR75 70
Sound power level [dB]
65 NR70
60 NR65 60
55 NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR0 NR20
NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119534
11 Sound data
11 - 2 Sound Pressure Spectrum
REMQ5U
REYQ8U
RXYQQ8U
11 RXYQ8U 70 70
NR75
RXYTQ8UYF 65
NR70
RYYQ8U
60 60
RYMQ8U NR65
55
NR60
50 50
NR55
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119521
REYQ10U
RXYQQ10U 70 70
NR75
RXYQ10U
65
RYYQ10U NR70
RYMQ10U 60 60
NR65
55
NR60
50 50
NR55
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119522
11 Sound data
11 - 2 Sound Pressure Spectrum
REYQ12U
RXYQQ12U
70 NR75 70
RXYQ12U
RYYQ12U 65
11
NR70
RYMQ12U
60 60
NR65
55
NR60
50 50
NR55
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119523
REYQ14U
RXYQQ14U
RXYQ14U 70 NR75 70
RYYQ14U 65
NR70
RYMQ14U
60 60
NR65
55
NR60
50 50
NR55
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119524
11 Sound data
11 - 2 Sound Pressure Spectrum
REYQ16U
RXYQQ16U
70 70
RXYQ16U NR75
11 RYYQ16U 65
NR70
RYMQ16U
60 60
NR65
55
NR60
50 50
NR55
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119525
REYQ18U
RXYQQ18U
70 70
RXYQ18U NR75
RYYQ18U 65
NR70
RYMQ18U
60 60
NR65
55
NR60
50 50
NR55
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119526
11 Sound data
11 - 2 Sound Pressure Spectrum
REYQ20U
RXYQQ20U
75 NR80
RXYQ20U NR65 NR70 NR75
RYYQ20U 70 NR75
NR75 70 11
RYMQ20U 65
NR70
60 60
NR65
55
NR60
Sound pressure level [dB]
50 50
NR55
45 NR45 NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119527
11 Sound data
11 - 3 Sound Pressure Spectrum Quiet Mode Level 1
REMQ5U
REYQ8-12U 65
NR70
RXYQQ8-12U
11 60 60
RXYQ8-12U NR65
RXYTQ8UYF 55
NR60
RYY8-12U 50 50
NR55
RYMQ8-12U
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119535
REYQ14-16U
RXYQQ14-16U 60
NR65
60
RXYQ14-16U 55 55
RXYTQ14-16UYF NR60
RYYQ14-16U 50
NR55
50
RYMQ14-16U 45 45
NR50
Sound pressure level [dB]
40 40
NR45
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119538
11 Sound data
11 - 3 Sound Pressure Spectrum Quiet Mode Level 1
REYQ18-20U
RXYQQ18-20U 65
NR70
RXYQ18-20U
60 60 11
RYYQ18-20U NR65
RYMQ18-20U 55
NR60
50 50
NR55
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119541
11 Sound data
11 - 4 Sound Pressure Spectrum Quiet Mode Level 2
REMQ5U
REYQ8-12U 60
NR65
60
RXYQQ8-12U
11 RXYQ8-12U
55
NR60
55
RXYTQ8UYF 50
NR55
50
RYYQ8-12U 45 45
RYMQ8-12U NR50
Sound pressure level [dB]
40 40
NR45
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119536
REYQ14-16U
RXYQQ14-16U 55 55
RXYQ14-16U NR60
RXYTQ14-16UYF 50 50
NR55
RYYQ14-16U
45 45
RYMQ14-16U NR50
40 40
Sound pressure level [dB]
NR45
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR5 NR10 NR15
NR0
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119539
11 Sound data
11 - 4 Sound Pressure Spectrum Quiet Mode Level 2
REYQ18-20U
RXYQQ18-20U 60 60
NR65
RXYQ18-20U
RYYQ18-20U 55 55 11
NR60
RYMQ18-20U 50 50
NR55
45 45
NR50
Sound pressure level [dB]
40 40
NR45
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119542
11 Sound data
11 - 5 Sound Pressure Spectrum Quiet Mode Level 3
REMQ5U
REYQ8-12U 55 55
NR60
RXYQQ8-12U
11 RXYQ8-12U 50 50
NR55
RXYTQ8UYF
45 45
RYYQ8-12U NR50
RYMQ8-12U 40 40
Sound pressure level [dB]
NR45
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR5 NR10 NR15
NR0
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119537
REYQ14-16U
RXYQQ14-16U 55 55
NR60
RXYQ14U-16U
RXYTQ14-16UYF 50
NR55
50
RYYQ14-16U 45 45
RYMQ14-16U NR50
40 40
Sound pressure level [dB]
NR45
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR5 NR10 NR15
NR0
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119540
11 Sound data
11 - 5 Sound Pressure Spectrum Quiet Mode Level 3
REYQ18-20U
RXYQQ18-20U
RXYQ18-20U 50 50
RYYQ18-20U
NR55
11
45 45
RYMQ18-20U NR50
40 40
NR45
Sound pressure level [dB]
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR5 NR15
NR10
NR0
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119543
12 Installation
12 - 1 Installation Method
REMQ5U
REYQ8-20U
RXYQQ8-20U
12 RXYQ8-20U For single unit installation
For installation in rows For centralised group layout
RYYQ8-20U
RYMQ-20U Pattern 1
300 or more
Pattern 1
300 or more
Pattern 1
10 or more Front 10 or more 10 or more 20 or more Front 20 or more 10 or more 10 or more Front 20 or more 10 or more 10 or more Front 20 or more 10 or more
10 or more 20 or more 10 or more
500 or more 500 or more 600 or more 500 or more
900 or more
Pattern 2
50 or more Front 50 or more 50 or more 100 or more Front 100 or more 50 or more
Front 400 or more Front 400 or more 500 or more 50 or more 100 or more 50 or more 50 or more 50 or more
100 or more Front
200 or more 200 or more 500 or more
Notes
1. Height of the walls in case of patterns 1 and 2: < Unit : mm >
Front: 1500mm
Suction side: 500mm
Side: height unrestricted
h2
The installation space shown on this drawing is based on cooling operation at 35°C (outdoor temperature).
When the design outdoor ambient temperature exceeds 35°C or the load exceeds maximum ability of much generation load of heat in all outdoor unit, m
1555
h1
Suction side
ake sure the suction-side space is broader than the space shown on this drawing.
Front
555
2. If the walls are higher than mentioned above, then additional service space is needed: < Unit : mm >
Always keep in mind to leave sufficient space for a person to pass between unit and wall and for the air to circulate freely.
If more units are to be installed than are catered for in the above patterns, your layout should take into account of the possibility of short circuits.
4. Provide sufficient space at the front to connect refrigerant piping (comfortably). 3D118467
12 Installation
12 - 2 Fixation and Foundation of Units
REMQ5U
REYQ8-20U
RXYQQ8-20U
RXYQ8-20U Nut Foundation bolt type: JA
12
Size: M12
Spring washer
RXYTQ8-16UYF Frame
4 holes for anchor bolts
3 thread ridges or more
RYYQ8-20U
°
80
60
RYMQ8-20U
929
729
00 80
O1 80
75
X X
100
Drain ditch
Smooth downgrade of about 1/50
Y ditch AC AA Foundation bolt fixing method
AB
Drain ditch
AD AA AD AA Smooth downgrade of about 1/50
When building a foundation on the ground When building a foundation on a concrete floor
RYMQ8-12U
50
1. Provide a drain ditch around the foundation to drain water from the installation area.
2.The surface has to be finished with mortar. The corner edges have to be chamfered.
3. Build the foundation on a concrete floor or, if not possible, make sure the foundation surface has a rough finish.
4. Use a cement/sand/gravel ratio of 1/2/4 for the concrete, and a diameter of 10 mm for the reinforcement bars (approximately, 300mm intervals).
5. When installing the equipment on a roof, make sure to check the strength of the floor and take adequate water proofing measures. 3D118459
12 Installation
12 - 3 Refrigerant Pipe Selection
RXYQ-U
RYYQ-Y
RYMQ-U
12
VRV4
Heat pump
Piping restrictions 1/3
Maximum piping length Maximum height difference
Total piping length
After first branch (for (3)
For the reference drawing, see Longest pipe After first branch
multi-outdoor)
Indoor-to-outdoor Indoor-to-indoor Outdoor-to-outdoor
page 2/3. (A+[B,G,E,J]) (B,G,E,J) (D) (H1) (H2) (H3)
Actual / (Equivalent) Actual Actual / (Equivalent) Outdoor above indoor
/ (indoor above
outdoor)
Standard
VRV DX indoor units only
165/(190)m 40m(1) 10/(13)m 50/(40)m(3) 30m 5m 1000m
Standard multi-combination
Remark
(1) If all conditions below are met, the limitation can be extended up to 90 m
a. The piping length between all indoor units and the nearest branch kit is ≤ 40m.
b. It is necessary to increase the size of the gas and liquid piping if the pipe length between the first and the farthest indoor unit is >40m.
If the increased pipe size is larger than the pipe size of the main pipe, also increase the size of the main pipe.
c. When the piping size is increased, the piping length has to be counted as double.
(3) An extension to up to 90 m is possible without an additional option kit. Respect the following conditions:
-> If the outdoor units are positioned higher than the indoor units:
-> If the outdoor units are positioned lower than the indoor units:
(8) If the equivalent piping length between is > 90m, size up the main liquid and gas piping.
3D079540E
12 Installation
12 - 3 Refrigerant Pipe Selection
RXYQ-U
RYYQ-U
RYMQ-U VRV4
Heat pump
12
Piping restrictions 2/3
Outdoor
H
3
B
G
A E
D J
C
EXV BP
H
1
F
VRV indoor EXV K
H
5
Hydrobox
BP RA
H
2
AHU
H
4
Hydrobox AHU RA VRV indoor
Remark
(1) Schematic indication
Illustrations may differ from the actual appearance of the unit.
(2) This is only to illustrate piping length limitations.
Combination of indoor unit types is not allowed.
Refer to combination table 3D079543 for details about the allowed combinations.
Remark
(1) Multiple air handling units (AHU)(EKEXV + EKEQ kits).
(2) Mix of AHU units and VRV DX indoor
3D079540E
12 Installation
12 - 3 Refrigerant Pipe Selection
RXYQ-U
RYYQ-U
RYMQ-U
12
VRV4
Heat pump
Piping restrictions 3/3
(1)
RA DX indoor unit 80~130% Max.32 - 80~130% - -
AHU only
90~110%(3) Max.64(2) - - - 90~110%
Pair + multi (4)
Remark
(1) There is no restriction on the number of connectable BP boxes.
(2) For connection with AHU
EKEXV kits are also considered indoor units.
(3) Restrictions regarding the air handling unit capacity
(4) Pair AHU = system with 1 air handling unit connected to one outdoor unit
Multi AHU = system with multiple air handling units connected to one outdoor unit
II. Biddle air curtains are considered air handling units, following air handling unit limitations:
For information on the operation range, refer to the documentation of the Biddle unit.
III. [EKEXV + EKEQ] units combined with an air handling unit are considered air handling units, following air handling unit limitations.
For information on the operation range, refer to the documentation of the EKEXV-EKEQ unit.
V. Because there is no refrigerant connection with the outdoor unit (only communication F1/F2), VAM units do not have connection limitations.
However, since there is communication via F1/F2, count them as regular indoor unit when calculating the maximum allowed number of connectable indoor
units.
3D079540E
13 Operation range
13 - 1 Operation Range
RXYQQ-U
RXYQ-U
RYYQ-U Cooling Heating 13
45
RYMQ-U 43 20
40
15 15.5
35
30 10
Operation range
0
Operation range
15
-5
10
-10
5
-15
0
-5 -20
14 28 27
10 15 20 25 30 10 15 20 25 30
Indoor temperature [°C WB] Indoor temperature [°C DB]
Notes
1. These figures assume the following operation conditions
3. To reduce the freeze-up operation (indoor de-icing) frequency, it is recommended to install the outdoor unit in a location not exposed to wind.
3D118465
4.Operation range is valid in case direct expansion indoor units are used.
When using special indoor units (e.g. Hydrobox units), see the technical specifications of those units.
14 Appropriate Indoors
14 - 1 Appropriate Indoors
RXYQ-U
RYYQ-U
RYMQ-U
14
·· HP 8 10 12 14 16 18 20
1xFXMQ50 4XFXMQ63 3xFXMQ50 2xFXMQ50
4xFXMQ50 4xFXMQ63 6xFXMQ50
5XFXMQ63 2xFXMQ80 5XFXMQ63 6xFXMQ63
For multi outdoor units ·>16HP·, the recommended amount of indoor units is the sum of the indoor units defined for a single outdoor unit.
For details about the allowed combinations, see the engineering databook.
Appropriate indoor units for ·RXYQ*U* / RYYQ*U* / RYMQ*U*· outdoor units Covered by ·ENER LOT10·
FTXJ25-35-50
Covered by ·ENER LOT21· FTXA20-25-35-42-50
FXFQ20-25-32-40-50-63-80-100-125 FLXS25-35-50-60
FXZQ15-20-25-32-40-50 FVXM25-35-50
FXCQ20-25-32-40-50-63-80-125 FVXG25-35-50
FXKQ25-32-40-63 CVXM20A
FXDQ15-20-25-32-40-50-63 FVXM25A-35A-50A-60A
FXSQ15-20-25-32-40-50-63-80-100-125-140
FXMQ50-63-80-100-125-200-250 Outside the scope of ·ENER LOT21·
FXAQ15-20-25-32-40-50-63 EKEXV50-63-80-100-125-140-200-250-400-500 + EKEQM / EKEQF
FXHQ32-63-100 HXY080-125
FXUQ71-100 VKM50-80-100
FXNQ20-25-32-40-50-63 CYVS100-150-200-250
FXLQ20-25-32-40-50-63 CYVM100-150-200-250
CYVL100-150-200-250
3D118461B
The present leaflet is drawn up by way of information only and does not constitute an
offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of
this leaflet to the best of its knowledge. No express or implied warranty is given for the
completeness, accuracy, reliability or fitness for particular purpose of its content and the
products and services presented therein. Specifications are subject to change without prior
notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in
EEDEN20 10/2020
the broadest sense, arising from or related to the use and/or interpretation of this leaflet.
All content is copyrighted by Daikin Europe N.V.