VRV IV+ heat pump,

without continuous
heating
Technical data book
RXYQ-U

RXYQ8U7Y1B
RXYQ10U7Y1B
RXYQ12U7Y1B
RXYQ14U7Y1B
RXYQ16U7Y1B
RXYQ18U7Y1B
RXYQ20U7Y1B
RXYQ22U7Y1B
RXYQ24U7Y1B
RXYQ26U7Y1B
RXYQ28U7Y1B
RXYQ30U7Y1B
RXYQ32U7Y1B
RXYQ34U7Y1B
RXYQ36U7Y1B
RXYQ38U7Y1B
RXYQ40U7Y1B
RXYQ42U7Y1B
RXYQ44U7Y1B
RXYQ46U7Y1B
RXYQ48U7Y1B
RXYQ50U7Y1B
RXYQ52U7Y1B
RXYQ54U7Y1B

EEDEN20
Table of contents

RXYQ-U
1 Features 4
 4

2 5

3 22

4 23

5 26
26
27

6 40

7 41

8 42

9 43
43
44
45

10 46

11 48
48
52
56
58
60

12 62
62
63
64

13 67

14 68

3
VRV IV+ heat pump, without continuous heating • RXYQ-U

1 Features
1 - 1 RXYQ-U
Daikin’s solution for comfort & low energy consumption

1 ›› By choosing a LOOP by Daikin product you support the reuse of ›› Fits any building as also indoor installation is possible as a result
refrigerant, for more information visit www.daikin.eu/loop-by- of high external static pressure of up to 78.4 Pa. Indoor installation
daikin leads to less piping length, lower installation costs, increased
›› Covers all thermal needs of a building via a single point of contact: efficiency and better visual aesthetics
accurate temperature control, ventilation, hot water, air handling ›› Simplified installation & guaranteed optimal efficiency with
units and Biddle air curtains automatic charging & testing
›› Wide range of indoor units: possibility to combine VRV with stylish ›› Easy compliance with F-gas regulation thanks to automated
indoor units (Daikin Emura, Perfera, ...) refrigerant containment check
›› Incorporates VRV IV standards & technologies: Variable Refrigerant ›› Wide piping flexibility: 30m indoor height difference, maximum
Temperature, VRV configurator, 7 segment display and full inverter piping length: 190m, total piping length: 1,000m
compressors, 4-side heat exchanger, refrigerant cooled PCB, new ›› The ability to control each conditioned zone individually keeps VRV
DC fan motor, ... system running costs to an absolute minimum
›› Customize your VRV for best seasonal efficiency & comfort with ›› Spread your installation cost by phased installation
the weather dependant Variable Refrigerant Temperature function. ›› Keep your system in top condition via the Daikin Cloud Service:
Increased seasonal efficiency with up to 28%. No more cold draft 24/7 monitoring for maximum efficiency, extented lifetime and
by supply of high outblow temperatures immediate service support thanks to failure prediction
›› Free combination of outdoor units to meet installation space or ›› Available as heating only by irreversible field setting
efficiency requirements

Inverter

4 RXYQ-U
VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Technical Specifications RXYQ8U RXYQ10U RXYQ12U RXYQ14U RXYQ16U
Recommended combination 4 x FXFQ50AVEB 4 x FXFQ63AVEB 6 x FXFQ50AVEB 1 x FXFQ50AVEB + 5 4 x FXFQ63AVEB + 2
x FXFQ63AVEB x FXFQ80AVEB
Recommended combination 2 4 x FXSQ50A2VEB 4 x FXSQ63A2VEB 6 x FXSQ50A2VEB 1 x FXSQ50A2VEB +
5 x FXSQ63A2VEB
4 x FXSQ63A2VEB +
2 x FXSQ80A2VEB
2
Recommended combination 3 4 x FXMQ50P7VEB 4 x FXMQ63P7VEB 6 x FXMQ50P7VEB 1 x FXMQ50P7VEB + 4 x FXMQ63P7VEB +
5 x FXMQ63P7VEB 2 x FXMQ80P7VEB
Cooling capacity Prated,c kW 22.4 (1) 28.0 (1) 33.5 (1) 40.0 (1) 45.0 (1)
Heating capacity Nom. 6°CWB kW 22.4 (2) 28.0 (2) 33.5 (2) 40.0 (2) 45.0 (2)
Prated,h kW 13.7 16.0 18.4 20.6 23.2
Max. 6°CWB kW 25.0 (2) 31.5 (2) 37.5 (2) 45.0 (2) 50.0 (2)
COP at nom. 6°CWB kW/kW 4.15 (2) 3.69 (2) 3.47 (2) 3.74 (2) 3.59 (2)
capacity
ESEER - Automatic 7.53 7.20 6.96 6.83 6.50
ESEER - Standard 6.37 5.67 5.50 5.31 5.05
SCOP 4.3 4.1 4.0
SCOP recommended combination 2 4.2 4.3 4.1 4.0 4.1
SCOP recommended combination 3 4.2 4.1 4.0
SEER 7.6 6.8 6.3 6.0
SEER recommended combination 2 6.9 6.8 5.9 6.3 5.9
SEER recommended combination 3 7.5 6.8 6.2 5.8
ηs,c % 302.4 267.6 247.8 250.7 236.5
ηs,c recommended combination 2 273.6 270.5 233.5 250.0 234.2
ηs,c recommended combination 3 295.2 267.1 246.3 246.7 230.4
ηs,h % 167.9 168.2 161.4 155.4 157.8
ηs,h recommended combination 2 165.4 170.6 161.3 157.2 159.5
ηs,h recommended combination 3 165.6 162.0 160.6 155.7 156.8
Space cooling A Condition (35°C EERd 3.0 2.3 2.4 2.6 2.1
- 27/19) Pdc kW 22.4 28.0 33.5 40.0 45.0
B Condition (30°C EERd 5.2 4.7 4.3 4.1 3.9
- 27/19) Pdc kW 16.5 20.6 24.7 29.5 33.2
C Condition (25°C EERd 9.5 8.3 7.7 7.8 7.7
- 27/19) Pdc kW 10.6 13.3 15.9 18.9 21.3
D Condition EERd 18.8 17.0 13.9 14.3 14.2
(20°C - 27/19) Pdc kW 8.0 9.3 9.4 8.4 9.5
Space cooling A Condition (35°C EERd 2.6 2.4 2.6 2.1
recommended - 27/19) Pdc kW 22.4 28.0 33.5 40.0 45.0
combination 2 B Condition (30°C EERd 4.9 4.7 4.0 4.1 3.8
- 27/19) Pdc kW 16.5 20.6 24.7 29.5 33.2
C Condition (25°C EERd 8.8 8.5 7.1 7.9 7.6
- 27/19) Pdc kW 10.6 13.3 15.9 18.9 21.3
Space cooling D Condition EERd 15.1 17.2 13.1 14.0
recommended (20°C - 27/19) Pdc kW 8.8 9.3 9.1 8.4 9.5
combination 2
Space cooling A Condition (35°C EERd 3.0 2.3 2.4 2.6 2.1
recommended - 27/19) Pdc kW 22.4 28.0 33.5 40.0 45.0
combination 3 B Condition (30°C EERd 5.1 4.7 4.2 4.0 3.7
- 27/19) Pdc kW 16.5 20.6 24.7 29.5 33.2
C Condition (25°C EERd 9.6 8.4 7.7 7.4
- 27/19) Pdc kW 10.6 13.3 15.9 19.0 21.3
D Condition EERd 16.0 16.9 13.7 14.0 14.1
(20°C - 27/19) Pdc kW 9.1 9.3 9.4 8.4 9.5
Space heating TBivalent COPd (declared COP) 2.5 2.4 2.0 2.3 2.2
(Average climate) Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.5 2.4 2.0 2.3 2.2
Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2
Tol (temperature operating °C -10
limit)
A COPd (declared COP) 2.7 2.6 2.4 2.6
Condition Pdh (declared heating cap) kW 12.1 14.2 16.3 18.2 20.5
(-7°C)
B COPd (declared COP) 3.9 3.5
Condition Pdh (declared heating cap) kW 7.4 8.6 9.9 11.1 12.5
(2°C)
C COPd (declared COP) 6.3 6.4 6.1 6.3
Condition Pdh (declared heating cap) kW 5.0 5.5 6.4 7.1 8.0
(7°C)
D COPd (declared COP) 7.9 8.2 7.9 8.5 8.6
Condition Pdh (declared heating cap) kW 5.9 6.3 4.9
(12°C)

VRV IV+ heat pump, without continuous heating • RXYQ-U 5


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Technical Specifications RXYQ8U RXYQ10U RXYQ12U RXYQ14U RXYQ16U
Space heating A COPd (declared COP) 2.7 2.4 2.6
(Average climate) Condition Pdh (declared heating cap) kW 12.1 14.2 16.3 18.2 20.5
2 recommended
combination 2
(-7°C)
B COPd (declared COP) 3.9 4.0 3.9 3.5
Condition Pdh (declared heating cap) kW 7.4 8.6 9.9 11.1 12.2
(2°C)
C COPd (declared COP) 6.3 6.5 6.1 6.3
Condition Pdh (declared heating cap) kW 5.0 5.5 6.4 7.1 8.0
(7°C)
D COPd (declared COP) 7.8 8.3 7.9 8.6 8.7
Condition Pdh (declared heating cap) kW 5.9 6.0 6.4 4.9 5.0
(12°C)
TBivalent COPd (declared COP) 2.4 1.9 2.3 2.2
Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.4 1.9 2.3 2.2
Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2
Space heating (Average climate) TOL Tol (temperature operating °C -10
recommended combination 2 limit)
Space heating A COPd (declared COP) 2.7 2.6 2.4 2.6
(Average climate) Condition Pdh (declared heating cap) kW 12.1 14.2 16.3 18.2 20.5
recommended (-7°C)
combination 3 B COPd (declared COP) 3.9 3.7 3.9 3.5
Condition Pdh (declared heating cap) kW 7.4 8.6 9.9 11.1 12.5
(2°C)
C COPd (declared COP) 6.2 6.4 6.0 6.1 6.2
Condition Pdh (declared heating cap) kW 4.9 5.5 6.4 7.1 8.0
(7°C)
D COPd (declared COP) 7.8 8.1 7.8 8.5 8.6
Condition Pdh (declared heating cap) kW 5.8 5.9 6.2 4.9
(12°C)
TBivalent COPd (declared COP) 2.5 2.4 2.0 2.3 2.2
Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.5 2.4 2.0 2.3 2.2
Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2
Tol (temperature operating °C -10
limit)
Capacity range HP 8 10 12 14 16
PED Category Category II
Most Name Accumulator
critical Ps*V Bar*l 325 415
part
Maximum number of connectable indoor units 64 (3)
Indoor index Min. 100.0 125.0 150.0 175.0 200.0
connection Max. 260.0 325.0 390.0 455.0 520.0
Dimensions Unit Height mm 1,685
Width mm 930 1,240
Depth mm 765
Packed Height mm 1,820
unit Width mm 995 1,305
Depth mm 860
Weight Unit kg 198 275
Packed unit kg 211 291
Packing Material Carton
Weight kg 1.8 2.2
Packing 2 Material Wood
Weight kg 11.0 14.0
Packing 3 Material Plastic
Weight kg 0.5 0.6
Casing Colour Daikin White
Casing Material Painted galvanized steel plate
Heat exchanger Type Cross fin coil
Indoor side Air
Outdoor side Air
Air flow Cooling Rated m³/h 9,720 10,500 11,100 13,380 15,600
rate Heating Rated m³/h 9,720 10,500 11,100 13,380 15,600
Fan Quantity 1 2
External static Max. Pa 78
pressure
Fan motor Quantity 1 2
Type DC motor
Output W 550 750

6 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Technical Specifications RXYQ8U RXYQ10U RXYQ12U RXYQ14U RXYQ16U
Compressor Quantity 1 2
Type Hermetically sealed scroll compressor
Crankcase heater
Operation range Cooling Min.
W
°CDB
33
-5.0
2
Max. °CDB 43.0
Heating Min. °CWB -20.0
Max. °CWB 15.5
Sound power level Cooling Nom. dBA 78.0 (4) 79.1 (4) 83.4 (4) 80.9 (4) 85.6 (4)
Heating Nom. dBA 62.7 (4) 64.8 (4) 64.9 (4) 68.3 (4) 68.6 (4)
Sound pressure Cooling Nom. dBA 57.0 (5) 61.0 (5) 60.0 (5) 63.0 (5)
level
Refrigerant Type R-410A
GWP 2,087.5
Charge TCO2Eq 12.3 12.5 13.2 21.5 23.6
Charge kg 5.9 6.0 6.3 10.3 11.3
Refrigerant oil Type Synthetic (ether) oil FVC68D
Piping connections Liquid Type Braze connection
OD mm 9,52 12.7
Gas Type Braze connection
OD mm 19.1 22.2 28.6
Total piping System Actual m 1,000 (6)
length
Defrost method Reversed cycle
Capacity control Method Inverter controlled
Indication if the heater is equipped with a supplementary heater no
Supplementary Back-up Heating elbu kW 0.0
heater capacity
Power consumption in other Crankcase Cooling PCK kW 0.000
than active mode heater Heating PCK kW 0.052 0.077
Power Off mode Cooling POFF kW 0.041 0.074
consumption in Heating POFF kW 0.052 0.077
other than active Standby Cooling PSB kW 0.041 0.074
mode mode Heating PSB kW 0.052 0.077
Thermostat-off Cooling PTO kW 0.005 0.010
mode Heating PTO kW 0.056 0.097
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
Safety devices Item 01 High pressure switch
02 Fan driver overload protector
03 Inverter overload protector
04 PC board fuse
05 Leakage current detector

Technical Specifications RXYQ18U RXYQ20U


Recommended combination 3 x FXFQ50AVEB + 5 x FXFQ63AVEB 2 x FXFQ50AVEB + 6 x FXFQ63AVEB
Recommended combination 2 3 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 2 x FXSQ50A2VEB + 6 x FXSQ63A2VEB
Recommended combination 3 3 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 2 x FXMQ50P7VEB + 6 x FXMQ63P7VEB
Cooling capacity Prated,c kW 50.4 (1) 52.0 (1)
Heating capacity Nom. 6°CWB kW 50.4 (2) 56.0 (2)
Prated,h kW 27.9 31.0
Max. 6°CWB kW 56.5 (2) 63.0 (2)
COP at nom. 6°CWB kW/kW 3.54 (2) 3.20 (2)
capacity
ESEER - Automatic 6.38 5.67
ESEER - Standard 4.97 4.42
SCOP 4.2 4.0
SCOP recommended combination 2 4.2 4.0
SCOP recommended combination 3 4.1 3.9
SEER 6.0 5.9
SEER recommended combination 2 6.0 5.9
SEER recommended combination 3 6.0 5.9
ηs,c % 238.3 233.7
ηs,c recommended combination 2 236.8 233.9
ηs,c recommended combination 3 238.2 233.1
ηs,h % 163.1 156.6
ηs,h recommended combination 2 164.8 158.2
ηs,h recommended combination 3 159.6 153.4

VRV IV+ heat pump, without continuous heating • RXYQ-U 7


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Technical Specifications RXYQ18U RXYQ20U
Space cooling A Condition (35°C EERd 1.9
- 27/19) Pdc kW 50.4 52.0
2 B Condition (30°C
- 27/19)
EERd
Pdc kW
3.8
37.1
3.7
38.3
C Condition (25°C EERd 7.5 7.3
- 27/19) Pdc kW 23.9 24.6
D Condition EERd 18.3
(20°C - 27/19) Pdc kW 11.5
Space cooling A Condition (35°C EERd 1.9
recommended - 27/19) Pdc kW 50.4 52.0
combination 2 B Condition (30°C EERd 3.7 3.6
- 27/19) Pdc kW 37.1 38.3
C Condition (25°C EERd 7.5 7.3
- 27/19) Pdc kW 23.9 24.6
Space cooling D Condition EERd 18.1 18.9
recommended (20°C - 27/19) Pdc kW 11.4 10.9
combination 2
Space cooling A Condition (35°C EERd 1.9
recommended - 27/19) Pdc kW 50.4 52.0
combination 3 B Condition (30°C EERd 3.7 3.6
- 27/19) Pdc kW 37.1 38.3
C Condition (25°C EERd 7.6 7.3
- 27/19) Pdc kW 23.9 24.6
D Condition EERd 18.3
(20°C - 27/19) Pdc kW 11.6
Space heating TBivalent COPd (declared COP) 1.9 1.8
(Average climate) Pdh (declared heating cap) kW 27.9 31.0
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 1.9 1.8
Pdh (declared heating cap) kW 27.9 31.0
Tol (temperature operating °C -10
limit)
A COPd (declared COP) 2.4 2.1
Condition Pdh (declared heating cap) kW 24.7 27.4
(-7°C)
B COPd (declared COP) 3.7 3.6
Condition Pdh (declared heating cap) kW 15.0 16.7
(2°C)
C COPd (declared COP) 6.7 6.5
Condition Pdh (declared heating cap) kW 9.7 10.7
(7°C)
D COPd (declared COP) 9.0 9.1
Condition Pdh (declared heating cap) kW 7.1
(12°C)
Space heating A COPd (declared COP) 2.4 2.2
(Average climate) Condition Pdh (declared heating cap) kW 24.7 27.4
recommended (-7°C)
combination 2 B COPd (declared COP) 3.8 3.7
Condition Pdh (declared heating cap) kW 15.0 16.7
(2°C)
C COPd (declared COP) 6.8 6.5
Condition Pdh (declared heating cap) kW 9.7 10.7
(7°C)
D COPd (declared COP) 9.1 9.2
Condition Pdh (declared heating cap) kW 7.2
(12°C)
TBivalent COPd (declared COP) 1.9 1.8
Pdh (declared heating cap) kW 27.9 31.0
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 1.9 1.8
Pdh (declared heating cap) kW 27.9 31.0
Space heating (Average climate) TOL Tol (temperature operating °C -10
recommended combination 2 limit)

8 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Technical Specifications RXYQ18U RXYQ20U
Space heating A COPd (declared COP) 2.4 2.1
(Average climate) Condition Pdh (declared heating cap) kW 24.7 27.4
recommended (-7°C)
combination 3 B COPd (declared COP) 3.7 3.6
2
Condition Pdh (declared heating cap) kW 15.0 16.7
(2°C)
C COPd (declared COP) 6.5 6.3
Condition Pdh (declared heating cap) kW 9.7 10.7
(7°C)
D COPd (declared COP) 8.7
Condition Pdh (declared heating cap) kW 6.9
(12°C)
TBivalent COPd (declared COP) 1.9 1.8
Pdh (declared heating cap) kW 27.9 31.0
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 1.9 1.8
Pdh (declared heating cap) kW 27.9 31.0
Tol (temperature operating °C -10
limit)
Capacity range HP 18 20
PED Category Category II
Most Name Accumulator
critical Ps*V Bar*l 493
part
Maximum number of connectable indoor units 64 (3)
Indoor index Min. 225.0 250.0
connection Max. 585.0 650.0
Dimensions Unit Height mm 1,685
Width mm 1,240
Depth mm 765
Packed Height mm 1,820
unit Width mm 1,305
Depth mm 860
Weight Unit kg 308
Packed unit kg 324
Packing Material Carton
Weight kg 2.2
Packing 2 Material Wood
Weight kg 14.0
Packing 3 Material Plastic
Weight kg 0.6
Casing Colour Daikin White
Casing Material Painted galvanized steel plate
Heat exchanger Type Cross fin coil
Indoor side Air
Outdoor side Air
Air flow Cooling Rated m³/h 15,060 15,660
rate Heating Rated m³/h 15,060 15,660
Fan Quantity 2
External static Max. Pa 78
pressure
Fan motor Quantity 2
Type DC motor
Output W 750
Compressor Quantity 2
Type Hermetically sealed scroll compressor
Crankcase heater W 33
Operation range Cooling Min. °CDB -5.0
Max. °CDB 43.0
Heating Min. °CWB -20.0
Max. °CWB 15.5
Sound power level Cooling Nom. dBA 83.8 (4) 87.9 (4)
Heating Nom. dBA 66.3 (4) 67.0 (4)
Sound pressure Cooling Nom. dBA 62.0 (5) 65.0 (5)
level
Refrigerant Type R-410A
GWP 2,087.5
Charge TCO2Eq 24.4 24.6
Charge kg 11.7 11.8
Refrigerant oil Type Synthetic (ether) oil FVC68D

VRV IV+ heat pump, without continuous heating • RXYQ-U 9


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Technical Specifications RXYQ18U RXYQ20U
Piping connections Liquid Type Braze connection
OD mm 15.9
2 Gas Type
OD mm
Braze connection
28.6
Total piping System Actual m 1,000 (6)
length
Defrost method Reversed cycle
Capacity control Method Inverter controlled
Indication if the heater is equipped with a supplementary heater no
Supplementary Back-up Heating elbu kW 0.0
heater capacity
Power consumption in other Crankcase Cooling PCK kW 0.000
than active mode heater Heating PCK kW 0.089
Power Off mode Cooling POFF kW 0.075
consumption in Heating POFF kW 0.089
other than active Standby Cooling PSB kW 0.075
mode mode Heating PSB kW 0.089
Thermostat-off Cooling PTO kW 0.010
mode Heating PTO kW 0.098
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
Safety devices Item 01 High pressure switch
02 Fan driver overload protector
03 Inverter overload protector
04 PC board fuse
05 Leakage current detector
Standard accessories: Installation manual; Quantity: 1;
Standard accessories: Operation manual; Quantity: 1;
Standard accessories: Connection pipes; Quantity: 1;

Electrical Specifications RXYQ8U RXYQ10U RXYQ12U RXYQ14U RXYQ16U


Power supply Name Y1
Phase 3N~
Frequency Hz 50
Voltage V 380-415
Power supply intake Both indoor and outdoor unit
Voltage range Min. % -10
Max. % 10
Current Nominal running Cooling A 7.2 (7) -
current (RLA)
Current - 50Hz Starting current (MSC) - remark See note 8
Zmax List No requirements
Minimum Ssc value kVa 4,050 (8) 5,535 (8) 6,038 (8) 6,793 (8) 7,547 (8)
Minimum circuit amps (MCA) A 16.1 (9) 22.0 (9) 24.0 (9) 27.0 (9) 31.0 (9)
Maximum fuse amps (MFA) A 20 (10) 25 (10) 32 (10) 40 (10)
Full load amps Total A 1.2 (11) 1.3 (11) 1.5 (11) 1.8 (11) 2.6 (11)
(FLA)
Wiring For power Quantity 5G
connections - 50Hz supply
For connection Quantity 2
with indoor Remark F1,F2

Electrical Specifications RXYQ18U RXYQ20U


Power supply Name Y1
Phase 3N~
Frequency Hz 50
Voltage V 380-415
Power supply intake Both indoor and outdoor unit
Voltage range Min. % -10
Max. % 10
Current - 50Hz Starting current (MSC) - remark See note 8
Zmax List No requirements
Minimum Ssc value kVa 8,805 (8) 9,812 (8)
Minimum circuit amps (MCA) A 35.0 (9) 39.0 (9)
Maximum fuse amps (MFA) A 40 (10) 50 (10)
Full load amps Total A 2.6 (11)
(FLA)
Wiring For power Quantity 5G
connections - 50Hz supply
For connection Quantity 2
with indoor Remark F1,F2
(1)Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |

10 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
(2)Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(3)Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(4)Sound power level is an absolute value that a sound source generates. |
(5)Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(6)Refer to refrigerant pipe selection or installation manual |
(7)RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | 2
(8)In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9)MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10)MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11)FLA means the nominal running current of the fan |
MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
Maximum allowable voltage range variation between phases is 2%. |
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
Sound values are measured in a semi-anechoic room. |
Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per
phase |
Ssc: Short-circuit power |
For detailed contents of standard accessories, see installation/operation manual |
Multi combination (22~54HP) data is corresponding with the standard multi combination

Technical specifications System RXYQ22U RXYQ24U RXYQ26U RXYQ28U RXYQ30U


System Outdoor unit module 1 RXYQ10U RXYQ8U RXYQ12U
Outdoor unit module 2 RXYQ12U RXYQ16U RXYQ14U RXYQ16U RXYQ18U
Recommended combination 6 x FXFQ50AVEB + 4 4 x FXFQ50AVEB + 4 x 7 x FXFQ50AVEB + 5 6 x FXFQ50AVEB + 4 x 9 x FXFQ50AVEB + 5
x FXFQ63AVEB FXFQ63AVEB + 2 x FXFQ80AVEB x FXFQ63AVEB FXFQ63AVEB + 2 x FXFQ80AVEB x FXFQ63AVEB
Recommended combination 2 6 x FXSQ50A2VEB + 4 x FXSQ50A2VEB + 4 7 x FXSQ50A2VEB + 6 x FXSQ50A2VEB + 4 9 x FXSQ50A2VEB +
4 x FXSQ63A2VEB x FXSQ63A2VEB + 2 x 5 x FXSQ63A2VEB x FXSQ63A2VEB + 2 x 5 x FXSQ63A2VEB
Recommended combination 3 6 x FXMQ50P7VEB + 4 x FXMQ50P7VEB + 4 7 x FXMQ50P7VEB + 6 x FXMQ50P7VEB + 4 9 x FXMQ50P7VEB +
4 x FXMQ63P7VEB x FXMQ63P7VEB + 2 x 5 x FXMQ63P7VEB x FXMQ63P7VEB + 2 x 5 x FXMQ63P7VEB
Cooling capacity Prated,c kW 61.5 (1) 67.4 (1) 73.5 (1) 78.5 (1) 83.9 (1)
Heating capacity Nom. 6°CWB kW 61.5 (2) 67.4 (2) 73.5 (2) 78.5 (2) 83.9 (2)
Prated,h kW 34.4 36.9 39.0 41.6 46.3
Max. 6°CWB kW 69.0 (2) 75.0 (2) 82.5 (2) 87.5 (2) 94.0 (2)
COP at nom. 6°CWB kW/kW 3.57 (2) 3.76 (2) 3.61 (2) 3.54 (2) 3.51 (2)
capacity
ESEER - Automatic 7.07 6.81 6.89 6.69 6.60
ESEER - Standard 5.58 5.42 5.39 5.23 5.17
SCOP 4.4 4.3 4.2 4.3
SCOP recommended combination 2 4.4 4.3 4.2 4.3
SCOP recommended combination 3 4.3 4.2 4.3
SEER 6.9 6.8 6.7 6.5
SEER recommended combination 2 6.7 6.6 6.5 6.3
SEER recommended combination 3 6.9 6.7 6.6 6.4 6.5
ηs,c % 274.5 269.9 264.2 257.8 256.8
ηs,c recommended combination 2 266.5 262.6 256.1 249.3 249.8
ηs,c recommended combination 3 273.3 265.3 261.1 253.1 256.1
ηs,h % 171.2 167.0 164.6 166.0 169.8
ηs,h recommended combination 2 172.3 167.1 165.4 166.8 170.6
ηs,h recommended combination 3 170.2 165.5 164.5 165.0 167.0
Space cooling A Condition (35°C EERd 2.6 2.5 2.6 2.3 2.1
- 27/19) Pdc kW 61.5 67.4 73.5 78.5 83.9
B Condition (30°C EERd 4.8 4.6 4.4 4.3
- 27/19) Pdc kW 45.3 49.7 54.2 57.8 61.8
C Condition (25°C EERd 8.5 8.6 8.2 8.1 8.2
- 27/19) Pdc kW 29.1 31.9 34.8 37.2 39.7
D Condition EERd 16.0 15.2 14.2 14.3 16.8
(20°C - 27/19) Pdc kW 18.8 15.8 16.2 16.5 21.0
Space cooling A Condition (35°C EERd 2.6 2.4 2.6 2.3 2.1
recommended - 27/19) Pdc kW 61.5 67.4 73.5 78.5 83.9
combination 2 B Condition (30°C EERd 4.6 4.5 4.4 4.3 4.2
- 27/19) Pdc kW 45.3 49.7 54.1 57.8 61.8
Space cooling C Condition (25°C EERd 8.2 8.4 7.9 7.8 7.9
recommended - 27/19) Pdc kW 29.1 31.9 34.8 37.2 39.7
combination 2 D Condition EERd 15.6 14.7 13.6 13.8 16.1
(20°C - 27/19) Pdc kW 18.4 15.4 15.7 16.5 20.5
Space cooling A Condition (35°C EERd 2.5 2.3 2.1
recommended - 27/19) Pdc kW 61.5 67.4 73.5 78.5 83.9
combination 3 B Condition (30°C EERd 4.8 4.5 4.3
- 27/19) Pdc kW 45.3 49.7 54.2 57.8 61.8
C Condition (25°C EERd 8.5 8.4 8.1 8.0 8.2
- 27/19) Pdc kW 29.1 31.9 34.8 37.2 39.7
D Condition EERd 15.8 15.2 14.0 14.1 16.6
(20°C - 27/19) Pdc kW 18.8 15.7 16.0 16.6 21.0

VRV IV+ heat pump, without continuous heating • RXYQ-U 11


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ22U RXYQ24U RXYQ26U RXYQ28U RXYQ30U
Space heating TBivalent COPd (declared COP) 2.3 2.5 2.3 2.2 2.1
(Average climate) Pdh (declared heating cap) kW 34.4 36.9 39.0 41.6 46.3
2 TOL
Tbiv (bivalent temperature)
COPd (declared COP)
°C
2.3 2.5
-10
2.3 2.2 2.1
Pdh (declared heating cap) kW 34.4 36.9 39.0 41.6 46.3
Tol (temperature operating °C -10
limit)
A COPd (declared COP) 2.6 2.8 2.6
Condition Pdh (declared heating cap) kW 30.4 32.6 34.5 36.8 41.0
(-7°C)
B COPd (declared COP) 4.0 3.7 3.8 3.9
Condition Pdh (declared heating cap) kW 18.5 19.9 21.0 22.4 24.9
(2°C)
C COPd (declared COP) 6.3 6.1 6.2 6.5
Condition Pdh (declared heating cap) kW 11.9 13.0 13.5 14.4 16.0
(7°C)
D COPd (declared COP) 8.2 8.9 8.8 9.0
Condition Pdh (declared heating cap) kW 6.0 5.7 6.0 6.4 7.1
(12°C)
Space heating A COPd (declared COP) 2.6 2.7 2.6
(Average climate) Condition Pdh (declared heating cap) kW 30.4 32.6 34.5 36.8 41.0
recommended (-7°C)
combination 2 B COPd (declared COP) 4.1 3.7 3.8 3.9
Condition Pdh (declared heating cap) kW 18.5 19.9 21.0 22.4 24.9
(2°C)
C COPd (declared COP) 6.3 6.1 6.3 6.6
Condition Pdh (declared heating cap) kW 11.9 13.1 14.4 16.0
(7°C)
D COPd (declared COP) 8.4 9.0 8.9 9.1
Condition Pdh (declared heating cap) kW 6.0 5.7 6.0 6.4 7.2
(12°C)
TBivalent COPd (declared COP) 2.2 2.4 2.2 2.1
Pdh (declared heating cap) kW 34.4 36.9 39.0 41.6 46.3
Tbiv (bivalent temperature) °C -10
Space heating TOL COPd (declared COP) 2.2 2.4 2.2 2.1
(Average climate) Pdh (declared heating cap) kW 34.4 36.9 39.0 41.6 46.3
recommended Tol (temperature operating °C -10
combination 2 limit)
Space heating A COPd (declared COP) 2.6 2.7 2.6 2.5
(Average climate) Condition Pdh (declared heating cap) kW 30.4 32.6 34.5 36.8 41.0
recommended (-7°C)
combination 3 B COPd (declared COP) 4.0 3.7 3.8 3.9
Condition Pdh (declared heating cap) kW 18.5 19.9 21.0 22.4 24.9
(2°C)
C COPd (declared COP) 6.2 6.3 6.1 6.2 6.3
Condition Pdh (declared heating cap) kW 11.9 12.9 13.5 14.4 16.0
(7°C)
D COPd (declared COP) 8.2 8.9 8.8 9.0 8.6
Condition Pdh (declared heating cap) kW 6.0 5.7 6.0 6.4 7.1
(12°C)
TBivalent COPd (declared COP) 2.3 2.4 2.2 2.1
Pdh (declared heating cap) kW 34.4 36.9 39.0 41.6 46.3
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.3 2.4 2.2 2.1
Pdh (declared heating cap) kW 34.4 36.9 39.0 41.6 46.3
Tol (temperature operating °C -10
limit)
Capacity range HP 22 24 26 28 30
PED Category Category II
Maximum number of connectable indoor units 64 (3)
Indoor index Min. 275.0 300.0 325.0 350.0 375.0
connection Max. 715.0 780.0 845.0 910.0 975.0
Heat exchanger Indoor side Air
Outdoor side Air
Air flow Cooling Rated m³/h 21,600 25,320 24,480 26,700 26,160
rate Heating Rated m³/h 21,600 25,320 24,480 26,700 26,160
Sound power level Cooling Nom. dBA 84.8 (4) 86.3 (4) 85.3 (4) 87.6 (4) 86.6 (4)
Heating Nom. dBA 67.8 (4) 69.6 (4) 69.9 (4) 70.1 (4) 68.7 (4)
Sound pressure Cooling Nom. dBA 62.5 (5) 64.0 (5) 63.5 (5) 65.1 (5) 64.5 (5)
level
Refrigerant Type R-410A
GWP 2,087.5
Refrigerant oil Type Synthetic (ether) oil FVC68D

12 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ22U RXYQ24U RXYQ26U RXYQ28U RXYQ30U
Piping connections Liquid Type Braze connection
OD mm 15.9 19.1
Gas Type
OD mm 28.6
Braze connection
34.9
2
Total pipingSystem Actual m 1,000 (6)
length
Indication if the heater is equipped with a supplementary heater no
Supplementary Back-up Heating elbu kW 0.0
heater capacity
Power Crankcase Cooling PCK kW 0.000
consumption in heater Heating PCK kW 0.103 0.129 0.141
other than active mode
mode Off mode Cooling POFF kW 0.081 0.115 0.116
Heating POFF kW 0.103 0.129 0.141
Standby Cooling PSB kW 0.081 0.115 0.116
mode Heating PSB kW 0.103 0.129 0.141
Thermostat-off Cooling PTO kW 0.009 0.014
mode Heating PTO kW 0.113 0.154 0.155
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25

Technical specifications System RXYQ32U RXYQ34U RXYQ36U RXYQ38U RXYQ40U


System Outdoor unit module 1 RXYQ16U RXYQ8U RXYQ10U
Outdoor unit module 2 RXYQ16U RXYQ18U RXYQ20U RXYQ10U RXYQ12U
Outdoor unit module 3 - RXYQ20U RXYQ18U
Recommended combination 8 x FXFQ63AVEB + 4 3 x FXFQ50AVEB + 9 x 2 x FXFQ50AVEB + 10 x 6 x FXFQ50AVEB + 9 x FXFQ50AVEB + 9
x FXFQ80AVEB FXFQ63AVEB + 2 x FXFQ80AVEB FXFQ63AVEB + 2 x FXFQ80AVEB 10 x FXFQ63AVEB x FXFQ63AVEB
Recommended combination 2 8 x FXSQ63A2VEB + 3 x FXSQ50A2VEB + 9 2 x FXSQ50A2VEB + 10 6 x FXSQ50A2VEB + 9 x FXSQ50A2VEB +
4 x FXSQ80A2VEB x FXSQ63A2VEB + 2 x x FXSQ63A2VEB + 2 x 10 x FXSQ63A2VEB 9 x FXSQ63A2VEB
Recommended combination 3 8 x FXMQ63P7VEB + 3 x FXMQ50P7VEB + 9 2 x FXMQ50P7VEB + 10 6 x FXMQ50P7VEB + 9 x FXMQ50P7VEB
4 x FXMQ80P7VEB x FXMQ63P7VEB + 2 x x FXMQ63P7VEB + 2 x 10 x FXMQ63P7VEB + 9 x FXMQ63P7VEB
Cooling capacity Prated,c kW 90.0 (1) 95.4 (1) 97.0 (1) 102.4 (1) 111.9 (1)
Heating capacity Nom. 6°CWB kW 90.0 (2) 95.4 (2) 101.0 (2) 106.4 (2) 111.9 (2)
Prated,h kW 46.4 51.1 54.2 60.7 62.3
Max. 6°CWB kW 100.0 (2) 106.5 (2) 113.0 (2) 119.5 (2) 125.5 (2)
COP at nom. 6°CWB kW/kW 3.59 (2) 3.56 (2) 3.36 (2) 3.49 (2) 3.56 (2)
capacity
ESEER - Automatic 6.50 6.44 6.02 6.36 6.74
ESEER - Standard 5.05 5.01 4.68 5.03 5.29
SCOP 4.2 4.1 4.3
SCOP recommended combination 2 4.2 4.3 4.2 4.3 4.4
SCOP recommended combination 3 4.1 4.2 4.1 4.2 4.3
SEER 6.4 6.3 6.9 6.7
SEER recommended combination 2 6.3 6.8 6.6
SEER recommended combination 3 6.2 6.3 6.9 6.7
ηs,c % 251.7 253.3 250.8 272.4 263.5
ηs,c recommended combination 2 248.3 250.9 248.7 269.2 259.2
ηs,c recommended combination 3 244.2 249.8 247.2 272.2 263.2
ηs,h % 163.1 166.2 162.4 167.5 170.0
ηs,h recommended combination 2 164.6 167.7 164.1 168.4 171.3
ηs,h recommended combination 3 161.9 164.2 159.9 164.8 167.8
Space cooling A Condition (35°C EERd 2.3 2.1 2.4 2.2
- 27/19) Pdc kW 90.0 95.4 97.0 102.4 111.9
B Condition (30°C EERd 4.3 4.2 4.1 4.5
- 27/19) Pdc kW 66.3 70.3 71.5 75.5 82.5
C Condition (25°C EERd 8.1 7.9 8.5 8.3
- 27/19) Pdc kW 42.6 45.2 45.9 48.5 53.0
D Condition EERd 14.3 16.8 16.7 17.9 16.0
(20°C - 27/19) Pdc kW 19.0 20.1 20.4 21.6 23.6
Space cooling A Condition (35°C EERd 2.2 2.1 2.3 2.2
recommended - 27/19) Pdc kW 90.0 95.4 97.0 102.4 111.9
combination 2 B Condition (30°C EERd 4.2 4.1 4.5 4.4
- 27/19)
Space cooling B Condition (30°C Pdc kW 66.3 70.3 71.5 75.4 82.4
recommended - 27/19)
combination 2 C Condition (25°C EERd 8.0 8.1 7.9 8.4 8.1
- 27/19) Pdc kW 42.6 45.2 45.9 48.5 53.0
D Condition EERd 14.0 16.5 17.8 15.9
(20°C - 27/19) Pdc kW 18.9 20.1 20.4 21.6 23.6

VRV IV+ heat pump, without continuous heating • RXYQ-U 13


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ32U RXYQ34U RXYQ36U RXYQ38U RXYQ40U
Space cooling A Condition (35°C
EERd 2.2 2.1 2.4 2.2
recommended - 27/19) Pdc kW 90.0 95.4 97.0 102.4 111.9
2 combination 3 B Condition (30°C
- 27/19)
EERd
Pdc kW 66.3
4.1
70.3
4.0
71.5
4.5
75.5
4.4
82.5
C Condition (25°C
EERd 7.8 8.0 7.8 8.5 8.4
- 27/19) Pdc kW 42.6 45.2 45.9 48.5 53.0
D Condition
EERd 13.8 16.6 16.5 17.9 16.1
(20°C - 27/19)
Pdc kW 19.0 20.1 20.4 21.6 23.6
Space heating TBivalent COPd (declared COP) 2.4 2.2 2.1 2.2
(Average climate) Pdh (declared heating cap) kW 46.4 51.1 54.2 60.7 62.3
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.4 2.2 2.1 2.2
Pdh (declared heating cap) kW 46.4 51.1 54.2 60.7 62.3
Tol (temperature operating °C -10
limit)
A COPd (declared COP) 2.7 2.6 2.5 2.6
Condition Pdh (declared heating cap) kW 41.0 45.2 47.9 53.7 55.1
(-7°C)
B COPd (declared COP) 3.6 3.7 3.9 4.0
Condition Pdh (declared heating cap) kW 25.0 27.5 29.2 32.7 33.5
(2°C)
C COPd (declared COP) 6.3 6.5 6.4 6.5
Condition Pdh (declared heating cap) kW 16.1 17.7 18.8 21.3 21.6
(7°C)
D COPd (declared COP) 9.0 8.8 8.6 8.7
Condition Pdh (declared heating cap) kW 7.1 7.9 8.3 13.1
(12°C)
Space heating A COPd (declared COP) 2.7 2.6 2.5 2.6
(Average climate) Condition Pdh (declared heating cap) kW 41.0 45.2 47.9 53.7 55.1
recommended (-7°C)
combination 2 B COPd (declared COP) 3.6 3.8 3.7 3.9 4.0
Condition Pdh (declared heating cap) kW 25.0 27.5 29.2 32.7 33.5
(2°C)
C COPd (declared COP) 6.3 6.6 6.5
Condition Pdh (declared heating cap) kW 16.1 17.7 18.8 21.3 21.6
(7°C)
D COPd (declared COP) 9.1 8.9 8.8
Condition Pdh (declared heating cap) kW 7.1 7.9 8.3 13.2
(12°C)
TBivalent COPd (declared COP) 2.4 2.2 2.3 2.2
Pdh (declared heating cap) kW 46.4 51.1 54.2 60.7 62.3
Space heating TBivalent Tbiv (bivalent temperature) °C -10
(Average climate) TOL COPd (declared COP) 2.4 2.2 2.3 2.2
recommended Pdh (declared heating cap) kW 46.4 51.1 54.2 60.7 62.3
combination 2 Tol (temperature operating °C -10
limit)
Space heating A COPd (declared COP) 2.7 2.6 2.4 2.5 2.6
(Average climate) Condition Pdh (declared heating cap) kW 41.0 45.2 47.9 53.7 55.1
recommended (-7°C)
combination 3 B COPd (declared COP) 3.6 3.7 3.6 3.8 3.9
Condition Pdh (declared heating cap) kW 25.0 27.5 29.2 32.7 33.5
(2°C)
C COPd (declared COP) 6.3 6.4 6.3 6.4
Condition Pdh (declared heating cap) kW 16.1 17.7 18.8 21.2 21.6
(7°C)
D COPd (declared COP) 9.0 8.9 8.3 8.5 8.4
Condition Pdh (declared heating cap) kW 7.1 7.9 8.3 12.9 12.8
(12°C)
TBivalent COPd (declared COP) 2.4 2.2 2.1 2.2
Pdh (declared heating cap) kW 46.4 51.1 54.2 60.7 62.3
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.4 2.2 2.1 2.2
Pdh (declared heating cap) kW 46.4 51.1 54.2 60.7 62.3
Tol (temperature operating °C -10
limit)
Capacity range HP 32 34 36 38 40
PED Category Category II
Maximum number of connectable indoor units 64 (3)
Indoor index Min. 400.0 425.0 450.0 475.0 500.0
connection Max. 1,040.0 1,105.0 1,170.0 1,235.0 1,300.0

14 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ32U RXYQ34U RXYQ36U RXYQ38U RXYQ40U
Heat exchanger Indoor side Air
Outdoor side Air
Air flow
rate
Cooling Rated
Heating Rated
m³/h
m³/h
31,200
31,200
30,660
30,660
31,260
31,260
35,880
35,880
36,660
36,660
2
Sound power level Cooling Nom. dBA 88.6 (4) 87.8 (4) 89.9 (4) 88.8 (4) 87.3 (4)
Heating Nom. dBA 71.6 (4) 70.6 (4) 70.9 (4) 69.9 (4) 70.2 (4)
Sound pressure Cooling Nom. dBA 66.0 (5) 65.5 (5) 67.1 (5) 66.2 (5) 65.2 (5)
level
Refrigerant Type R-410A
GWP 2,087.5
Refrigerant oil Type Synthetic (ether) oil FVC68D
Piping connections Liquid Type Braze connection
OD mm 19.1
Gas Type Braze connection
OD mm 34.9 41.3
Piping connections Total piping System Actual m 1,000 (6)
length
Indication if the heater is equipped with a supplementary heater no
Supplementary Back-up Heating elbu kW 0.0
heater capacity
Power Crankcase Cooling PCK kW 0.000
consumption in heater Heating PCK kW 0.154 0.166 0.192
other than active mode
mode Off mode Cooling POFF kW 0.149 0.150 0.157
Heating POFF kW 0.154 0.166 0.192
Standby Cooling PSB kW 0.149 0.150 0.157
mode Heating PSB kW 0.154 0.166 0.192
Thermostat-off Cooling PTO kW 0.019
mode Heating PTO kW 0.195 0.196 0.211
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25

Technical specifications System RXYQ42U RXYQ44U RXYQ46U RXYQ48U RXYQ50U


System Outdoor unit module 1 RXYQ10U RXYQ12U RXYQ14U RXYQ16U
Outdoor unit module 2 RXYQ16U
Outdoor unit module 3 RXYQ16U RXYQ18U
Recommended combination 12 x FXFQ63AVEB + 6 x FXFQ50AVEB + 8 x 1 x FXFQ50AVEB + 13 x 12 x FXFQ63AVEB + 3 x FXFQ50AVEB + 13 x
4 x FXFQ80AVEB FXFQ63AVEB + 4 x FXFQ80AVEB FXFQ63AVEB + 4 x FXFQ80AVEB 6 x FXFQ80AVEB FXFQ63AVEB + 4 x FXFQ80AVEB
Recommended combination 2 12 x FXSQ63A2VEB 6 x FXSQ50A2VEB + 8 1 x FXSQ50A2VEB + 13 12 x FXSQ63A2VEB 3 x FXSQ50A2VEB + 13
+ 4 x FXSQ80A2VEB x FXSQ63A2VEB + 4 x x FXSQ63A2VEB + 4 x + 6 x FXSQ80A2VEB x FXSQ63A2VEB + 4 x
Recommended combination 3 12 x FXMQ63P7VEB 6 x FXMQ50P7VEB + 8 1 x FXMQ50P7VEB + 13 12 x FXMQ63P7VEB 3 x FXMQ50P7VEB + 13
+ 4 x FXMQ80P7VEB x FXMQ63P7VEB + 4 x x FXMQ63P7VEB + 4 x + 6 x FXMQ80P7VEB x FXMQ63P7VEB + 4 x
Cooling capacity Prated,c kW 118.0 (1) 123.5 (1) 130.0 (1) 135.0 (1) 140.4 (1)
Heating capacity Nom. 6°CWB kW 118.0 (2) 123.5 (2) 130.0 (2) 135.0 (2) 140.4 (2)
Prated,h kW 62.4 64.8 67.0 69.6 74.3
Max. 6°CWB kW 131.5 (2) 137.5 (2) 145.0 (2) 150.0 (2) 156.5 (2)
COP at nom. 6°CWB kW/kW 3.61 (2) 3.56 (2) 3.63 (2) 3.59 (2) 3.57 (2)
capacity
ESEER - Automatic 6.65 6.62 6.60 6.50 6.46
ESEER - Standard 5.19 5.17 5.13 5.05 5.02
SCOP 4.2 4.1 4.2
SCOP recommended combination 2 4.3 4.2
SCOP recommended combination 3 4.2 4.1 4.2
SEER 6.6 6.5 6.4
SEER recommended combination 2 6.6 6.3 6.4 6.3
SEER recommended combination 3 6.5 6.3 6.2 6.3
ηs,c % 261.2 255.9 254.9 251.7 252.8
ηs,c recommended combination 2 259.3 249.2 252.2 248.3 250.0
ηs,c recommended combination 3 255.4 250.1 248.3 244.2 248.0
ηs,h % 165.5 164.5 162.0 162.8 165.2
ηs,h recommended combination 2 167.3 165.6 163.5 164.3 166.7
ηs,h recommended combination 3 164.4 163.5 161.3 161.7 163.2
Space cooling A Condition (35°C EERd 2.3 2.4 2.3 2.1
- 27/19) Pdc kW 118.0 123.5 130.0 135.0 140.4
B Condition (30°C EERd 4.4 4.3 4.2
- 27/19) Pdc kW 86.9 91.0 95.8 99.5 103.4
C Condition (25°C EERd 8.2 8.1
- 27/19) Pdc kW 55.9 58.5 61.6 64.0 66.5
D Condition EERd 15.4 14.4 14.3 15.9
(20°C - 27/19) Pdc kW 24.8 26.0 27.4 28.4 29.6

VRV IV+ heat pump, without continuous heating • RXYQ-U 15


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ42U RXYQ44U RXYQ46U RXYQ48U RXYQ50U
Space cooling A Condition (35°C EERd 2.3 2.2 2.1
recommended - 27/19) Pdc kW 118.0 123.5 130.0 135.0 140.4
2 combination 2 B Condition (30°C
- 27/19)
EERd 4.4 4.3 4.2

Space cooling B Condition (30°C Pdc kW 86.9 91.0 95.8 99.5 103.5
recommended - 27/19)
combination 2 C Condition (25°C
EERd 8.2 7.9 8.1 8.0
- 27/19) Pdc kW 55.9 58.5 61.6 63.9 66.5
D Condition
EERd 15.3 14.0 15.6
(20°C - 27/19)
Pdc kW 24.8 26.0 27.4 28.4 29.6
Space cooling A Condition (35°C
EERd 2.3 2.2 2.1
recommended - 27/19) Pdc kW 118.0 123.5 130.0 135.0 140.4
combination 3 B Condition (30°C
EERd 4.3 4.2 4.1
- 27/19) Pdc kW 87.0 91.0 95.8 99.5 103.5
C Condition (25°C
EERd 8.0 7.9 7.8 7.9
- 27/19) Pdc kW 55.9 58.5 61.6 63.9 66.5
D Condition
EERd 15.2 14.2 13.9 13.8 15.6
(20°C - 27/19)
Pdc kW 24.8 26.0 27.4 28.4 29.6
Space heating TBivalent COPd (declared COP) 2.4 2.3 2.4 2.3
(Average climate) Pdh (declared heating cap) kW 62.4 64.8 67.0 69.6 74.3
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.4 2.3 2.4 2.3
Pdh (declared heating cap) kW 62.4 64.8 67.0 69.6 74.3
Tol (temperature operating °C -10
limit)
A COPd (declared COP) 2.7
Condition Pdh (declared heating cap) kW 55.2 57.3 59.3 61.6 65.7
(-7°C)
B COPd (declared COP) 3.7 3.6 3.7
Condition Pdh (declared heating cap) kW 33.6 34.9 36.1 37.5 40.0
(2°C)
C COPd (declared COP) 6.3 6.2 6.3 6.5
Condition Pdh (declared heating cap) kW 21.6 22.4 23.2 24.1 25.7
(7°C)
D COPd (declared COP) 8.6 8.7 8.8 8.9
Condition Pdh (declared heating cap) kW 9.9 10.0 10.3 10.7 12.0
(12°C)
Space heating A COPd (declared COP) 2.7
(Average climate) Condition Pdh (declared heating cap) kW 55.2 57.3 59.3 61.6 65.7
recommended (-7°C)
combination 2 B COPd (declared COP) 3.7 3.6 3.7
Condition Pdh (declared heating cap) kW 33.6 34.9 36.1 37.5 40.0
(2°C)
C COPd (declared COP) 6.4 6.3 6.5
Condition Pdh (declared heating cap) kW 21.6 22.4 22.8 24.1 25.7
(7°C)
D COPd (declared COP) 8.7 8.8 8.9 9.0
Condition Pdh (declared heating cap) kW 10.0 10.3 10.7 12.2
(12°C)
TBivalent COPd (declared COP) 2.4 2.3 2.4 2.3
Pdh (declared heating cap) kW 62.4 64.8 67.0 69.6 74.3
Space heating TBivalent Tbiv (bivalent temperature) °C -10
(Average climate) TOL COPd (declared COP) 2.4 2.3 2.4 2.3
recommended Pdh (declared heating cap) kW 62.4 64.8 67.0 69.6 74.3
combination 2 Tol (temperature operating °C -10
limit)

16 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ42U RXYQ44U RXYQ46U RXYQ48U RXYQ50U
Space heating A COPd (declared COP) 2.7 2.6 2.7 2.6
(Average climate) Condition Pdh (declared heating cap) kW 55.2 57.3 59.3 61.6 65.7
recommended
combination 3
(-7°C)
B COPd (declared COP) 3.7 3.6
2
Condition Pdh (declared heating cap) kW 33.6 34.9 36.1 37.5 40.0
(2°C)
C COPd (declared COP) 6.3 6.2 6.3 6.4
Condition Pdh (declared heating cap) kW 21.6 22.4 23.2 24.1 25.7
(7°C)
D COPd (declared COP) 8.6 8.7 8.8 8.7
Condition Pdh (declared heating cap) kW 9.9 10.0 10.3 10.7 11.8
(12°C)
TBivalent COPd (declared COP) 2.4 2.3 2.4 2.2
Pdh (declared heating cap) kW 62.4 64.8 67.0 69.6 74.3
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.4 2.3 2.4 2.2
Pdh (declared heating cap) kW 62.4 64.8 67.0 69.6 74.3
Tol (temperature operating °C -10
limit)
Capacity range HP 42 44 46 48 50
PED Category Category II
Maximum number of connectable indoor units 64 (3)
Indoor index Min. 525.0 550.0 575.0 600.0 625.0
connection Max. 1,365.0 1,430.0 1,495.0 1,560.0 1,625.0
Heat exchanger Indoor side Air
Outdoor side Air
Air flow Cooling Rated m³/h 41,700 42,300 44,580 46,800 46,260
rate Heating Rated m³/h 41,700 42,300 44,580 46,800 46,260
Sound power level Cooling Nom. dBA 89.1 (4) 89.8 (4) 89.3 (4) 90.4 (4) 89.8 (4)
Heating Nom. dBA 72.4 (4) 73.3 (4) 73.4 (4) 72.7 (4)
Sound pressure Cooling Nom. dBA 66.5 (5) 67.2 (5) 67.0 (5) 67.8 (5) 67.5 (5)
level
Refrigerant Type R-410A
GWP 2,087.5
Refrigerant oil Type Synthetic (ether) oil FVC68D
Piping connections Liquid Type Braze connection
OD mm 19.1
Gas Type Braze connection
OD mm 41.3
Piping connections Total piping System Actual m 1,000 (6)
length
Indication if the heater is equipped with a supplementary heater no
Supplementary Back-up Heating elbu kW 0.0
heater capacity
Power Crankcase Cooling PCK kW 0.000
consumption in heater Heating PCK kW 0.206 0.231 0.243
other than active mode
mode Off mode Cooling POFF kW 0.190 0.223 0.224
Heating POFF kW 0.206 0.231 0.243
Standby Cooling PSB kW 0.190 0.223 0.224
mode Heating PSB kW 0.206 0.231 0.243
Thermostat-off Cooling PTO kW 0.024 0.029
mode Heating PTO kW 0.251 0.292 0.293
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25

Technical specifications System RXYQ52U RXYQ54U


System Outdoor unit module 1 RXYQ16U RXYQ18U
Outdoor unit module 2 RXYQ18U
Outdoor unit module 3 RXYQ18U
Recommended combination 6 x FXFQ50AVEB + 14 x FXFQ63AVEB + 2 x 9 x FXFQ50AVEB + 15 x FXFQ63AVEB
FXFQ80AVEB
Recommended combination 2 6 x FXSQ50A2VEB + 14 x FXSQ63A2VEB + 2 x 9 x FXSQ50A2VEB + 15 x FXSQ63A2VEB
FXSQ80A2VEB
Recommended combination 3 6 x FXMQ50P7VEB + 14 x FXMQ63P7VEB + 2 x 9 x FXMQ50P7VEB + 15 x FXMQ63P7VEB
FXMQ80P7VEB
Cooling capacity Prated,c kW 145.8 (1) 151.2 (1)
Heating capacity Nom. 6°CWB kW 145.8 (2) 151.2 (2)
Prated,h kW 79.0 83.7
Max. 6°CWB kW 163.0 (2) 169.5 (2)
COP at nom. 6°CWB kW/kW 3.56 (2) 3.54 (2)
capacity
ESEER - Automatic 6.42 6.38

VRV IV+ heat pump, without continuous heating • RXYQ-U 17


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ52U RXYQ54U
ESEER - Standard 4.99 4.97
SCOP 4.3
2 SCOP recommended combination 2
SCOP recommended combination 3
4.3
4.2
SEER 6.4
SEER recommended combination 2 6.4
SEER recommended combination 3 6.4
ηs,c % 253.7 254.1
ηs,c recommended combination 2 251.6 252.5
ηs,c recommended combination 3 251.5 253.9
ηs,h % 167.2 169.4
ηs,h recommended combination 2 168.7 170.8
ηs,h recommended combination 3 164.4 166.0
Space cooling A Condition (35°C EERd 2.0 1.9
- 27/19) Pdc kW 145.8 151.2
B Condition (30°C EERd 4.2 4.1
- 27/19) Pdc kW 107.4 111.4
C Condition (25°C EERd 8.1
- 27/19) Pdc kW 69.1 71.6
D Condition EERd 17.6 19.1
(20°C - 27/19) Pdc kW 30.7 34.4
Space cooling A Condition (35°C EERd 2.0 1.9
recommended - 27/19) Pdc kW 145.8 151.2
combination 2 B Condition (30°C EERd 4.1
- 27/19)
Space cooling B Condition (30°C Pdc kW 107.4 111.4
recommended - 27/19)
combination 2 C Condition (25°C EERd 8.1
- 27/19) Pdc kW 69.0 71.6
D Condition EERd 17.4 18.9
(20°C - 27/19) Pdc kW 30.7 34.1
Space cooling A Condition (35°C EERd 2.0 1.9
recommended - 27/19) Pdc kW 145.8 151.2
combination 3 B Condition (30°C EERd 4.1
- 27/19) Pdc kW 107.4 111.4
C Condition (25°C EERd 8.0 8.2
- 27/19) Pdc kW 69.1 71.6
D Condition EERd 17.5 19.1
(20°C - 27/19) Pdc kW 30.7 34.7
Space heating TBivalent COPd (declared COP) 2.2 2.1
(Average climate) Pdh (declared heating cap) kW 79.0 83.7
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.2 2.1
Pdh (declared heating cap) kW 79.0 83.7
Tol (temperature operating °C -10
limit)
A COPd (declared COP) 2.6
Condition Pdh (declared heating cap) kW 69.9 74.0
(-7°C)
B COPd (declared COP) 3.8 3.9
Condition Pdh (declared heating cap) kW 42.5 45.1
(2°C)
C COPd (declared COP) 6.6 6.8
Condition Pdh (declared heating cap) kW 27.4 29.0
(7°C)
D COPd (declared COP) 9.0
Condition Pdh (declared heating cap) kW 14.2
(12°C)
Space heating A COPd (declared COP) 2.6
(Average climate) Condition Pdh (declared heating cap) kW 69.9 74.0
recommended (-7°C)
combination 2 B COPd (declared COP) 3.8 3.9
Condition Pdh (declared heating cap) kW 42.6 45.1
(2°C)
C COPd (declared COP) 6.7 6.8
Condition Pdh (declared heating cap) kW 27.4 29.0
(7°C)
D COPd (declared COP) 9.1
Condition Pdh (declared heating cap) kW 14.4
(12°C)
TBivalent COPd (declared COP) 2.2 2.1
Pdh (declared heating cap) kW 79.0 83.7

18 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Technical specifications System RXYQ52U RXYQ54U
Space heating TBivalent Tbiv (bivalent temperature) °C -10
(Average climate) TOL COPd (declared COP) 2.2 2.1
recommended
combination 2
Pdh (declared heating cap)
Tol (temperature operating
kW
°C
79.0
-10
83.7
2
limit)
Space heating A COPd (declared COP) 2.6 2.5
(Average climate) Condition Pdh (declared heating cap) kW 69.9 74.0
recommended (-7°C)
combination 3 B COPd (declared COP) 3.7 3.8
Condition Pdh (declared heating cap) kW 42.5 45.1
(2°C)
C COPd (declared COP) 6.4 6.5
Condition Pdh (declared heating cap) kW 27.3 29.0
(7°C)
D COPd (declared COP) 8.7
Condition Pdh (declared heating cap) kW 13.7
(12°C)
TBivalent COPd (declared COP) 2.2 2.1
Pdh (declared heating cap) kW 79.0 83.7
Tbiv (bivalent temperature) °C -10
TOL COPd (declared COP) 2.2 2.1
Pdh (declared heating cap) kW 79.0 83.7
Tol (temperature operating °C -10
limit)
Capacity range HP 52 54
PED Category Category II
Maximum number of connectable indoor units 64 (3)
Indoor index Min. 650.0 675.0
connection Max. 1,690.0 1,755.0
Heat exchanger Indoor side Air
Outdoor side Air
Air flow Cooling Rated m³/h 45,720 45,180
rate Heating Rated m³/h 45,720 45,180
Sound power level Cooling Nom. dBA 89.3 (4) 88.6 (4)
Heating Nom. dBA 72.0 (4) 71.1 (4)
Sound pressure Cooling Nom. dBA 67.1 (5) 66.8 (5)
level
Refrigerant Type R-410A
GWP 2,087.5
Refrigerant oil Type Synthetic (ether) oil FVC68D
Piping connections Liquid Type Braze connection
OD mm 19.1
Gas Type Braze connection
OD mm 41.3
Piping connections Total piping System Actual m 1,000 (6)
length
Indication if the heater is equipped with a supplementary heater no
Supplementary Back-up Heating elbu kW 0.0
heater capacity
Power Crankcase Cooling PCK kW 0.000
consumption in heater Heating PCK kW 0.255 0.267
other than active mode
mode Off mode Cooling POFF kW 0.225 0.226
Heating POFF kW 0.255 0.267
Standby Cooling PSB kW 0.225 0.226
mode Heating PSB kW 0.255 0.267
Thermostat-off Cooling PTO kW 0.029
mode Heating PTO kW 0.294
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25

Electrical specifications System RXYQ22U RXYQ24U RXYQ26U RXYQ28U RXYQ30U


Power supply Name Y1
Phase 3N~
Frequency Hz 50
Voltage V 380-415
Power supply intake Both indoor and outdoor unit
Voltage range Min. % -10
Max. % 10

VRV IV+ heat pump, without continuous heating • RXYQ-U 19


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U
Electrical specifications System RXYQ22U RXYQ24U RXYQ26U RXYQ28U RXYQ30U
Current - 50Hz Starting current (MSC) - remark See note 8
Zmax List No requirements
2 Minimum Ssc value
Minimum circuit amps (MCA)
kVa
A
11,573 (8)
46.0 (9)
11,597 (8) 12,831 (8)
51.0 (9)
13,585 (8)
55.0 (9)
14,843 (8)
59.0 (9)
Maximum fuse amps (MFA) A 63 (10) 80 (10)
Wiring For power Quantity 5G
connections - 50Hz supply
For connection Quantity 2
with indoor Remark F1,F2

Electrical specifications System RXYQ32U RXYQ34U RXYQ36U RXYQ38U RXYQ40U


Power supply Name Y1
Phase 3N~
Frequency Hz 50
Voltage V 380-415
Power supply intake Both indoor and outdoor unit
Voltage range Min. % -10
Max. % 10
Current - 50Hz Starting current (MSC) - remark See note 8
Zmax List No requirements
Minimum Ssc value kVa 15,094 (8) 16,352 (8) 17,359 (8) 19,397 (8) 20,378 (8)
Minimum circuit amps (MCA) A 62.0 (9) 66.0 (9) 70.0 (9) 76.0 (9) 81.0 (9)
Maximum fuse amps (MFA) A 80 (10) 100 (10)
Wiring For power Quantity 5G
connections - 50Hz supply
For connection Quantity 2
with indoor Remark F1,F2

Electrical specifications System RXYQ42U RXYQ44U RXYQ46U RXYQ48U RXYQ50U


Power supply Name Y1
Phase 3N~
Frequency Hz 50
Voltage V 380-415
Power supply intake Both indoor and outdoor unit
Voltage range Min. % -10
Max. % 10
Current - 50Hz Starting current (MSC) - remark See note 8
Zmax List No requirements
Minimum Ssc value kVa 20,629 (8) 21,132 (8) 21,887 (8) 22,641 (8) 23,899 (8)
Minimum circuit amps (MCA) A 84.0 (9) 86.0 (9) 89.0 (9) 93.0 (9) 97.0 (9)
Maximum fuse amps (MFA) A 100 (10) 125 (10)
Wiring For power Quantity 5G
connections - 50Hz supply
For connection Quantity 2
with indoor Remark F1,F2

Electrical specifications System RXYQ52U RXYQ54U


Power supply Name Y1
Phase 3N~
Frequency Hz 50
Voltage V 380-415
Power supply intake Both indoor and outdoor unit
Voltage range Min. % -10
Max. % 10
Current - 50Hz Starting current (MSC) - remark See note 8
Zmax List No requirements
Minimum Ssc value kVa 25,157 (8) 26,415 (8)
Minimum circuit amps (MCA) A 101.0 (9) 105.0 (9)
Maximum fuse amps (MFA) A 125 (10)
Wiring For power Quantity 5G
connections - 50Hz supply
For connection Quantity 2
with indoor Remark F1,F2

20 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

2 Specifications
1 - 1 RXYQ-U

VRV IV+ heat pump, without continuous heating • RXYQ-U 21


VRV IV+ heat pump, without continuous heating • RXYQ-U

3 Options
3 - 1 Options
RXYQ-U
RYYQ-U
RYMQ-U
3 RXYQQ-U
RXYQ8U RXYQ10-12U RXYQ14-18U RXYQ20U RYYQ22~54U
RYYQ8U RYYQ10-12U RYYQ14-18U RYYQ20U RXYQ22~54U
RXYQQ8U RXYQQ10-12U RXYQQ14-18U RXYQQ20U RXYQQ22~42U
No Item
I. Refnet header KHRQ22M29H
KHRQ22M64H
--- --- --- KHRQ22M75H
II. Refnet joint KHRQ22M20T
KHRQ22M29T9
KHRQ22M64T
--- --- --- KHRQ22M75T
III. Outdoor multi-connection kit See note ·2·. --- --- --- --- BHFQ22P1007
IV. Outdoor multi-connection kit See note ·2·. --- --- --- --- BHFQ22P1517
No Item 8HP 10HP 12HP 14HP 16HP 18HP 20HP
1a Cool/heat selector (switch) See note ·3·. KRC19-26A
1b Cool/heat selector (PCB) BRP2A81
1c Cool/heat selector (fixing box) KJB111A
2 VRV configurator EKPCCAB*
3 Heater tape kit PCB EKBPH012T7A EKBPH020T7A
4 Demand PCB See DTA104A61/62*
5 Demand PCB mounting plate See note ·4·. --- KKSB26B1*

Notes
1 All options are kits
2 Only for multi units
3 To mount option ·1a·, option ·1c· is required.
4 To install the demand PCB on the large casing type, the demand PCB mounting plate is required.

Medium casing type ·VRV4· heat pump: modules ·8~12·HP


Large casing type ·VRV4· heat pump: modules ·14~20·HP

3D120006B

22 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

4 Combination table
4 - 1 Combination Table
REMQ5U
REYQ8-20U
RXYQQ8-20U 4
RXYTQ8-16UYF
RYYQ8-20U
RYMQ8-20U
Unit combination restrictions: VRV4 outdoor units (all models) + 15-class indoor units
Units in scope: FXZQ15A and FXAQ15A.
1. In case the system contains these indoor units and the total connection ratio (CR) ≤ 100%: no special restrictions.
Follow the restrictions that apply to regular VRV DX indoor units.
2. In case the system contains these indoor units and the total connection ratio (CR) > 100%: special restrictions apply.
A. When the connection ratio (CR1) of the sum of all FXZQ15A and/or FXAQ15A units in the system ≤ 70%, and ALL other VRV DX
indoor units have an individual capacity class > 50: no special restrictions.
B. When the connection ratio (CR1) of the sum of all FXZQ15A and/or FXAQ15A units in the system ≤ 70%, and NOT ALL other
VRV DX indoor units have an individual capacity class > 50: the restrictions below apply.
• 100% < CR ≤ 105% → CR1 of the sum of all FXZQ15A and/or FXAQ15A indoor units in the system must be ≤ 70%.
• 105% < CR ≤ 110% → CR1 of the sum of all FXZQ15A and/or FXAQ15A indoor units in the system must be ≤ 60%.
• 110% < CR ≤ 115% → CR1 of the sum of all FXZQ15A and/or FXAQ15A indoor units in the system must be ≤ 40%.
• 115% < CR ≤ 120% → CR1 of the sum of all FXZQ15A and/or FXAQ15A indoor units in the system must be ≤ 25%.
• 120% < CR ≤ 125% → CR1 of the sum of all FXZQ15A and/or FXAQ15A indoor units in the system must be ≤ 10%.
• 125% < CR ≤ 130% → FXZQ15A andFXAQ15A cannot be used

REMARK

Only the 15-class indoor units explicitly mentioned on this page are in scope. Other indoor units follow the rules that apply to regular
VRV DX indoor units.
3D104665
RXYQQ-U
RXYQ-U Heat pump VRV4
RYYQ-U Multi-unit standard combinations table
RYMQ-U
10HP

12HP

14HP

16HP

18HP

20HP
8HP

1
RXYQ8* / RYYQ8* / RXYQQ8*
1
RXYQ10* / RYYQ10* / RXYQQ10*
1
Heat pump

RXYQ12* / RYYQ12* / RXYQQ12*


1
RXYQ14* / RYYQ14* / RXYQQ14*
1
RXYQ16* / RYYQ16* / RXYQQ16*
1
RXYQ18* / RYYQ18* / RXYQQ18*
1
RXYQ20* / RYYQ20* / RXYQQ20*

RXYQ22* / RYYQ22* / RXYQQ22* 1 1


Multi-combination with 2 outdoor units

RXYQ24* / RYYQ24* / RXYQQ24* 1 1

RXYQ26* / RYYQ26* / RXYQQ26* 1 1

RXYQ28* / RYYQ28* / RXYQQ28* 1 1

RXYQ30* / RYYQ30* / RXYQQ30* 1 1

RXYQ32* / RYYQ32* / RXYQQ32* 2

RXYQ34* / RYYQ34* / RXYQQ34* 1 1

RXYQ36* / RYYQ36* / RXYQQ36* 1 1

RXYQ38* / RYYQ38* / RXYQQ38* 1 1 1


Multi-combination with 3 outdoor units

RXYQ40* / RYYQ40* / RXYQQ40* 1 1 1

RXYQ42* / RYYQ42* / RXYQQ42* 1 2

RXYQ44* / RYYQ44* 1 2

RXYQ46* / RYYQ46* 1 2

RXYQ48* / RYYQ48* 3

RXYQ50* / RYYQ50* 2 1

RXYQ52* / RYYQ52* 1 2

RXYQ54* / RYYQ54* 3

Remark
RYYQ8~20 = Single continuous heating
RYYQ22~54 =Multi continuous heating
RXYQ8~20 = Single non-continuous heating
RXYQ22~54 =Multi non-continuous heating
RXYQQ8~20 =Single non-continuous heating replacement (VRV4-Q)
RXYQQ22~42Multi= non-continuous heating replacement (VRV4-Q)
1) For single unit installation RYYQ* units (continuous heating) and RXYQ* units (non-continuous heating)
2) "Non-continuous heating" multi-outdoor-unit combinations consist of RXYQ8~20 units (e.g. RXYQ36*=RXYQ16*+RXYQ20*).
3) "Continuous heating" multi-outdoor-unit combinations consist of RYMQ8~20 units (e.g. RYYQ36*=RYMQ16*+RYMQ20*).
→ RYMQ* units can only be used in multi-outdoor-unit combinations and cannot be used as standalone units.
4) RYYQ8~20* units cannot be used in multi-outdoor-unit combinations.
5) RYYQ8~20 "Continuous heating" multi-outdoor-unit combinations cannot contain RXYQ* units.
6) RXYQ8~20 "Non-continuous heating" multi-outdoor-unit combinations cannot contain RYMQ* units.
7) Multi "non-continuous heating" replacement models only consist of RXYQQ8-20 modules (e.g. RXYQQ36*=RXYQQ16*+RXYQQ20*).
8) Replacement units cannot be combined with other units.
9) T-series outdoor units and U-series outdoor units cannot share the same refrigerant circuit. When combining these units, make sure they are part of separate refrigerant circuits.
3D120060

VRV IV+ heat pump, without continuous heating • RXYQ-U 23


VRV IV+ heat pump, without continuous heating • RXYQ-U

4 Combination table
4 - 1 Combination Table
RXYQ-U
RYYQ-U
VRV4
RYMQ-U Heat pump
4 Indoor unit combination restrictions
(1/2)
(3)
Indoor unit combination pattern ·VRV* DX· indoor unit ·RA DX· indoor unit Hydrobox unit Air handling unit (AHU)

·VRV* DX· indoor unit O O O O


·RA DX· indoor unit O O X X
Hydrobox unit O X O1 X
Air handling unit (3) ( O X X O2
3
)
O: Allowed
X: Not allowed

Notes
1. ·VRV* DX· indoor unit
- When combining ·VRV DX· indoor units with other types of indoor units, respect the following combination patterns:
Example
Allowed : (·VRV DX· indoor unit + ·Hydrobox· unit) or (·VRV DX· indoor unit + ·RA DX· indoor unit) or (·VRV DX· indoor unit + ·AHU·)
Not allowed : [·VRV DX· indoor unit + (·RA DX· indoor unit & (·Hydrobox· unit or ·AHU·))] or [·VRV DX· indoor unit + (·Hydrobox· unit & (·RA DX· indoor unit or ·AHU·))]

2. O1
- Only connect ·Hydrobox· units to a ·VRV IV· Heat Pump in combination with a ·VRV DX· indoor unit.
→ Refer to the connection ratio restrictions (·3D079540 & 3D117169·).
→ Connection with only Hydrobox units: refer to the Daikin Altherma solutions.
- Only connect ·Hydrobox· units of the ·HXY*· series.
→ ·HXHD*· series ·Hydrobox· units are not allowed.
3. O2
- Combination of ·AHU· only + control box ·EKEQFA· (the combination with ·VRV DX· indoor units is not allowed; maximum ·54·HP for ·400 + 2x500· class ·EKEXV· kit)
→ ·X·-control is possible (up to ·3x· [·EKEXV+EKEQFA*· boxes] can be connected to one outdoor unit (system)). No Variable Refrigerant Temperature control possible.
→ ·Y·-control is possible (up to ·3x· [·EKEXV+EKEQFA*· boxes] can be connected to one outdoor unit (system)). No Variable Refrigerant Temperature control possible.
→ ·W·-control is possible (up to ·3x· [·EKEXV+EKEQFA*· boxes] can be connected to one outdoor unit (system)). No Variable Refrigerant Temperature control possible.

- Combination of ·AHU· only + control box ·EKEQMA· (not combined with ·VRV DX· indoor units)
→ Z-control is possible (the allowed number of [·EKEXV + EKEQMA· boxes] is determined by the connection ratio (·90-110%·) and the capacity of the outdoor unit.

4. Combination of ·AHU· and ·VRV DX· indoor units


→ Z-control is possible (·EKEQMA*· boxes are allowed, but with a limited connection ratio).

5. The combination of ·AHU· with ·Hydrobox· units or ·RA DX· indoor units is not allowed.

6. (3) The following units are considered AHUs:


→ ·EKEXV + EKEQ(MA/FA) + AHU· coil
→ ·Biddle· air curtain
→ ·FXMQ_MF· units
Information
- ·VKM· units are considered to be regular ·VRV DX· indoor units. 3D079543F
RXYQ-U
RYYQ-U
RYMQ-U

VRV4
Heat pump
Indoor unit combination restrictions
(2/2)
RXYQ* RXYQ*
RYYQ* RYYQ* RXMLQ* RXMLQ*
Combination table RXYLQ* RXYLQ*
Single non-continuous Multi non-continuous
Single continuous heating Multi continuous heating
heating heating
·VRV* DX· indoor unit O O O O
·RA DX· indoor unit O X O X
Hydrobox unit O O1 O O1
Air handling unit (AHU) (2) O O O O

O: Allowed
X: Not allowed

Notes
1. O1
- Available upon request through the ·SPN· procedure.

2. (2) The following units are considered AHUs:


→ ·EKEXV + EKEQ(MA/FA) + AHU· coil
→ ·Biddle· air curtain
→ ·FXMQ_MF· units

3D079543F

24 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

4 Combination table
4 - 1 Combination Table
RXYQ-U
RYYQ-U
RYMQ-U Compatibility list: ·VRV4· heat pump - ·RA DX· indoor unit 4
RXYLQ-T
RXMLQ-T
Configuration Unit type
Wall mounted type Emura FTXJ20M
FTXJ25M
FTXJ35M
FTXJ50M
Stylish FTXA20
FTXA25
FTXA35
FTXA42
FTXA50
Ceiling/wall mounted Flex FLXS25B
FLXS35B
FLXS50B
FLXS60B
Floor standing type FVXM FVXM25F
FVXM35F
FVXM50F
CVXM20A
FVXM25A
FVXM35A
FVXM50A
FVXM60A
Nexura FVXG25K
FVXG35K
FVXG50K

Remark

The limitations on the use of ·RA DX· indoor units with the ·VRV4· Heat Pump are subject to the rules set out in drawings ·3D079543· and ·3D079540·.
If you want to connect ·RA·/·SA· ·DX· cassette, ceiling-mounted, or duct indoor units, use their ·VRV DX· indoor unit equivalents instead.

3D082373E

VRV IV+ heat pump, without continuous heating • RXYQ-U 25


VRV IV+ heat pump, without continuous heating • RXYQ-U

5 Capacity tables
5 - 1 Capacity Table Legend
,QRUGHUWRIXO¿OOPRUH\RXUUHTXLUHPHQWVRQTXLFNDFFHVVRIGDWDLQWKHIRUPDW\RXUHTXLUHZHKDYHGHYHORSHGDWRROWR
FRQVXOWFDSDFLW\WDEOHV

5 %HORZ\RXFDQ¿QGWKHOLQNWRWKHFDSDFLW\WDEOHGDWDEDVHDQGDQRYHUYLHZRIDOOWKHWRROVZHKDYHWRKHOS\RXVHOHFWWKH
FRUUHFWSURGXFW

• Capacity table database:OHWV\RX¿QGEDFNDQGH[SRUWTXLFNO\WKHFDSDFLW\LQIRUPDWLRQ\RXDUHORRNLQJIRUEDVHGXSRQ


XQLWPRGHOUHIULJHUDQWWHPSHUDWXUHDQGFRQQHFWLRQUDWLR
• <RXFDQDFFHVVWKHFDSDFLW\WDEOHYLHZHUKHUH
KWWSVP\GDLNLQHXFRQWHQWGHQYHQB86KRPHDSSOLFDWLRQVVRIWZDUH¿QGHUFDSDFLW\WDEOHYLHZHUKWPO

• $QRYHUYLHZRIall software toolsWKDWZHRႇHUFDQEHIRXQGKHUH


KWWSVP\GDLNLQHXGHQYHQB86KRPHDSSOLFDWLRQVVRIWZDUH¿QGHUKWPO

26 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ-U
RXYQ-U
RYYQ-U VRV4
5
RYMQ-U Heat pump
Integrated heating capacity coefficient
The heating capacity tables do not take into account the capacity reduction in case of frost accumulation or defrost operation.
The capacity values that take these factors into account, or in other words, the integrated heating capacity values, can be calculated as follows:

Formula
A = Integrated heating capacity
B = Capacity characteristics value (see table)
C = Integrated correction factor for frost accumulation (see table)
A=B*C

Inlet air temperature of heat exchanger


[°CDB/°CWB] -7/-7,6 or less -5/-5,6 -3/-3,7 0/-0,7 3/2,2 5/4,1 7/6
Integrated correction factor for frost accumulation C
8HP 0,95 0,93 0,88 0,84 0,85 0,90 1,00
10HP 0,95 0,93 0,87 0,79 0,80 0,88 1,00
12HP 0,95 0,92 0,87 0,75 0,76 0,85 1,00
14HP 0,95 0,92 0,86 0,72 0,73 0,84 1,00
16HP 0,95 0,92 0,86 0,72 0,72 0,83 1,00
18HP 0,95 0,93 0,88 0,84 0,85 0,90 1,00 Defrost operation
20HP 0,95 0,93 0,88 0,84 0,85 0,90 1,00
22HP 0,95 0,92 0,87 0,77 0,78 0,86 1,00
24HP 0,95 0,92 0,87 0,75 0,76 0,85 1,00
26HP 0,95 0,92 0,86 0,73 0,74 0,84 1,00
28HP 0,95 0,92 0,86 0,73 0,74 0,84 1,00
30HP 0,95 0,93 0,87 0,80 0,81 0,88 1,00
32HP 0,95 0,92 0,86 0,71 0,72 0,83 1,00

Heating capacity
34HP 0,95 0,92 0,87 0,78 0,79 0,87 1,00 Time
36HP 0,95 0,92 0,87 0,78 0,79 0,87 1,00
38HP 0,95 0,93 0,88 0,83 0,84 0,89 1,00
40HP 0,95 0,93 0,87 0,80 0,81 0,88 1,00
42HP 0,95 0,92 0,86 0,73 0,74 0,84 1,00
44HP 0,95 0,92 0,86 0,72 0,73 0,84 1,00
46HP 0,95 0,92 0,86 0,72 0,72 0,83 1,00
48HP 0,95 0,92 0,86 0,71 0,72 0,83 1,00
50HP 0,95 0,92 0,87 0,76 0,77 0,86 1,00 1 cycle
52HP 0,95 0,93 0,87 0,80 0,81 0,88 1,00
54HP 0,95 0,93 0,88 0,84 0,85 0,90 1,00

Notes

The figure shows the integrated heating capacity for a single cycle (from one defrost operation to the next).

When there is an accumulation of snow against the outdoor unit heat exchanger, there will always be a temporary reduction in capacity depending on the outdoor
temperature (°C DB), relative humidity (RH) and the amount of frosting which occurs.

The multi-combination data 22~54HP corresponds with the standard multi-combination of drawing 3D079534.
3D079898A

VRV IV+ heat pump, without continuous heating • RXYQ-U 27


VRV IV+ heat pump, without continuous heating • RXYQ-U

5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ8U
RXYQ8U
RYYQ8U
5 RYMQ8U

Height Difference between outdoor and farest


Correction ratio for cooling capacity Correction ratio for heating capacity
Height Difference between outdoor and farest

Indoor (m)
Indoor (m)

Equivalent piping length (m) Equivalent piping length (m)

NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.

2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.

3. Method of calculating the capacity of the outdoor units


The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.

Condition: Indoor connection ratio does not exceed 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at the 100% connection ratio

x Correction ratio of piping to furthest indoor


Condition: Indoor connection ratio exceeds 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio

x Correction ratio of piping to furthest indoor

4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
8HP 22.2 12.7

5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for deicated indoor connection types.

Diameter of main pipes (standard size)


Model Gas Liquid
8HP 19.1 9.5

6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =

Equivalent length of main pipe x Correction factor


+
Equivalent length of branch pipes

Choose the correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5

Example Main gas pipe size increase


Main Liquid pipe size increase Equivalent length branch

80 m 40 m

In the above case (Cooling) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rete of change in cooling capacity when height difference = 0 is thus approximately 0.86
heating capacity when height difference = 0 is thus approximately 1.0 3D079897A

28 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ10U
RXYQ10U
RYYQ10U
RYMQ10U 5
Correction ratio for cooling capacity Correction ratio for heating capacity
Height Difference between outdoor and farest

Height Difference between outdoor and farest


Indoor (m)

Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)

NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.

2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.

3. Method of calculating the capacity of the outdoor units


The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.

Condition: Indoor connection ratio does not exceed 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at the 100% connection ratio

x Correction ratio of piping to furthest indoor


Condition: Indoor connection ratio exceeds 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio

x Correction ratio of piping to furthest indoor

4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased. For new diameters, see below.
Model Gas Liquid
RXYQ10P 25.4* 12.7
*If not available on site, do not increase. If not increased correction factor should be applied to the equivalent length (see note 6).
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
10 HP 22.2 9.5

6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =

Equivalent length of main pipe x Correction factor


+
Equivalent length of branch pipes

Choose the correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5

Example Main gas pipe size increase


Main Liquid pipe size increase Equivalent length branch

80 m 40 m

In the above case (Cooling) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rete of change in cooling capacity when height difference = 0 is thus approximately 0.87
heating capacity when height difference = 0 is thus approximately 0.90
3D079897A

VRV IV+ heat pump, without continuous heating • RXYQ-U 29


VRV IV+ heat pump, without continuous heating • RXYQ-U

5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ12,14,16,24,36U
RXYQ12,14,24,36U
RYYQ12,14,24,36U
RYMQ12,14U
5
Correction ratio for cooling capacity Correction ratio for heating capacity
Height Difference between outdoor and farest

Height Difference between outdoor and farest


Indoor (m)

Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)

NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.

Condition: Indoor connection ratio does not exceed 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at the 100% connection ratio
x Correction ratio of piping to furthest indoor
Condition: Indoor connection ratio exceeds 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio
x Correction ratio of piping to furthest indoor

4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased. For new diameters, see below.
Model Gas Liquid
12 HP 28.6 15.9
14 HP 28.6 15.9
24 HP 34.9 19.1
36 HP 41.3 22.2

5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
12 HP 28.6 12.7
14 HP 28.6 12.7
24 HP 34.9 15.9
36 HP 41.3 19.1

6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =

Equivalent length of main pipe x Correction factor


+
Equivalent length of branch pipes

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard Size
size increase
Cooling (gas pipe) 1,0
Heating (liquid pipe) 1,0 0,5

Example Main gas pipe size increase


Main Liquid pipe size increase Equivalent length branch

80 m 40 m

In the above case (Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.89
heating capacity when height difference = 0 is thus approximately 1.0 3D079897A

30 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ16U
RXYQ16U
RYYQ16U
RYMQ16U Correction ratio for cooling capacity Correction ratio for heating capacity 5
Height Difference between outdoor and farest

Height Difference between outdoor and farest


Indoor (m)

Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)

NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.

Condition: Indoor connection ratio does not exceed 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at the 100% connection ratio
x Correction ratio of piping to furthest indoor
Condition: Indoor connection ratio exceeds 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio
x Correction ratio of piping to furthest indoor

4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased. For new diameters, see below.
Model Gas Liquid
16 HP 31.8* 15.9
*If not available on site, do not increase. If not increased correction factor should be applied to the equivalent length (see note 6).
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
16 HP 28.6 12.7

6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =

Equivalent length of main pipe x Correction factor


+
Equivalent length of branch pipes

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5

Example
Main gas pipe size increase
Main Liquid pipe size increase Equivalent length branch

80 m 40 m

In the above case (Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 80 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.88
heating capacity when height difference = 0 is thus approximately 0.99

3D079897A

VRV IV+ heat pump, without continuous heating • RXYQ-U 31


VRV IV+ heat pump, without continuous heating • RXYQ-U

5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ18,26,28,30,38,40,42,44U
RXYQ18,26,28,30,38,40,42,44U
RYYQ18,26,28,30,38,40,42,44U
RYMQ18U
5 Correction ratio for cooling capacity Correction ratio for heating capacity
Height Difference between outdoor and farest

Height Difference between outdoor and farest


Indoor (m)

Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)

NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.

Condition: Indoor connection ratio does not exceed 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at the 100% connection ratio
x Correction ratio of piping to furthest indoor
Condition: Indoor connection ratio exceeds 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio
x Correction ratio of piping to furthest indoor

4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
18 HP 31.8* 19.1
26~30 HP 38.1* 22.2
38~44 HP 41.3 22.2
*If not available on site, do not increase. If not increased correction factor should be applied to the equivalent length (see note 6).
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
18 HP 28.6 15.9
26~30 HP 34.9 19.1
38~44 HP 41.3 19.1

6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =

Equivalent length of main pipe x Correction factor


+
Equivalent length of branch pipes

Choose the correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5

Example Main gas pipe size increase


Main Liquid pipe size increase Equivalent length branch

80 m 40 m

In the above case (for RXYQ38-44) (Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m
(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 1.0
3D079897A

32 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ20,32,34U
RXYQ20,32,34U
RYYQ20,32,34U
RYMQ20,32,34U
Correction ratio for cooling capacity Correction ratio for heating capacity 5
Height Difference between outdoor and farest

Height Difference between outdoor and farest


Indoor (m)

Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)

NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.

Condition: Indoor connection ratio does not exceed 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at the 100% connection ratio
x Correction ratio of piping to furthest indoor
Condition: Indoor connection ratio exceeds 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio
x Correction ratio of piping to furthest indoor

4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
20 HP 31.8* 19.1
32/34 HP 38.1* 22.2
*If not available on site, do not increase. If not increased correction factor should be applied to the equivalent length (see note 6).
5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
20 HP 28.6 15.9
32/34 HP 34.9 19.1

6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =

Equivalent length of main pipe x Correction factor


+
Equivalent length of branch pipes

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5

Example
Main gas pipe size increase
Main Liquid pipe size increase Equivalent length branch

80 m 40 m

In the above case (Cooling) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.88
heating capacity when height difference = 0 is thus approximately 1.0

3D079897A

VRV IV+ heat pump, without continuous heating • RXYQ-U 33


VRV IV+ heat pump, without continuous heating • RXYQ-U

5 Capacity tables
5 - 2 Capacity Correction Factor
RXYQQ22U
RXYQ22U
RYYQ22U
5 RYMQ22U Correction ratio for cooling capacity Correction ratio for heating capacity
Height Difference between outdoor and farest

Height Difference between outdoor and farest


Indoor (m)

Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)

NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.

Condition: Indoor connection ratio does not exceed 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at the 100% connection ratio
x Correction ratio of piping to furthest indoor
Condition: Indoor connection ratio exceeds 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio
x Correction ratio of piping to furthest indoor

4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
22 HP 31.8* 19.1
* If not available on site, do not increase, if not increased, no correction factor should be applied to the equivalent length (see note 6).

5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
22 HP 28.6 15.9

6. Equivalent length used in the above figures is based upon the following equivalent length
Overal equivalent length =

Equivalent length of main pipe x Correction factor


+
Equivalent length of branch pipes

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5

Example
Main gas pipe size increase
Main Liquid pipe size increase Equivalent length branch

80 m 40 m

In the above case (Cooling) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.88
heating capacity when height difference = 0 is thus approximately 1.0

3D079897A

34 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

5 Capacity tables
5 - 2 Capacity Correction Factor
RYYQ46U
RXYQ46U Correction ratio for cooling capacity Correction ratio for heating capacity
5
Height Difference between outdoor and farest

Height Difference between outdoor and farest


Indoor (m)

Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)

NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.

Condition: Indoor connection ratio does not exceed 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at the 100% connection ratio
x Correction ratio of piping to furthest indoor
Condition: Indoor connection ratio exceeds 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio
x Correction ratio of piping to furthest indoor

4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
46 HP 41.3 22.2

5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
46 HP 41.3 19.1

6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =

Equivalent length of main pipe x Correction factor


+
Equivalent length of branch pipes

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0
Heating (liquid pipe) 1.0 0.5

Example Main gas pipe size increase


Main Liquid pipe size increase Equivalent length branch

80 m 40 m

In the above case (Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 1.0

3D079897A

VRV IV+ heat pump, without continuous heating • RXYQ-U 35


VRV IV+ heat pump, without continuous heating • RXYQ-U

5 Capacity tables
5 - 2 Capacity Correction Factor
RYYQ48U
RXYQQ48U Correction ratio for heating capacity
5 RXYQ48U

Height Difference between outdoor and farest


Correction ratio for cooling capacity
Height Difference between outdoor and farest

Indoor (m)
Indoor (m)

Equivalent piping length (m) Equivalent piping length (m)

NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.

Condition: Indoor connection ratio does not exceed 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at the 100% connection ratio
x Correction ratio of piping to furthest indoor
Condition: Indoor connection ratio exceeds 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio
x Correction ratio of piping to furthest indoor

4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
48 HP 41.3 22.2

5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
48 HP 41.3 19.1

6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =

Equivalent length of main pipe x Correction factor


+
Equivalent length of branch pipes

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0
Heating (liquid pipe) 1.0 0.5

Example
Main gas pipe size increase
Main Liquid pipe size increase Equivalent length branch

80 m 40 m

In the above case (Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 0.97

3D079897A

36 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

5 Capacity tables
5 - 2 Capacity Correction Factor
RYYQ50U
RXYQQ50U
RXYQ50U Correction ratio for cooling capacity Correction ratio for heating capacity 5

Height Difference between outdoor and farest


Height Difference between outdoor and farest

Indoor (m)
Indoor (m)

Equivalent piping length (m) Equivalent piping length (m)

NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.

Condition: Indoor connection ratio does not exceed 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at the 100% connection ratio
x Correction ratio of piping to furthest indoor
Condition: Indoor connection ratio exceeds 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio
x Correction ratio of piping to furthest indoor

4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
50 HP 41.3 22.2

5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
50 HP 41.3 19.1

6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =

Equivalent length of main pipe x Correction factor


+
Equivalent length of branch pipes

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0
Heating (liquid pipe) 1.0 0.5

Example
Main gas pipe size increase
Main Liquid pipe size increase Equivalent length branch

80 m 40 m

In the above case (Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 0.92

3D079897A

VRV IV+ heat pump, without continuous heating • RXYQ-U 37


VRV IV+ heat pump, without continuous heating • RXYQ-U

5 Capacity tables
5 - 2 Capacity Correction Factor
RYYQ52U
RXYQQ52U
5 RXYQ52U

Height Difference between outdoor and farest


Correction ratio for cooling capacity Correction ratio for heating capacity
Height Difference between outdoor and farest

Indoor (m)
Indoor (m)

Equivalent piping length (m) Equivalent piping length (m)

NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.

Condition: Indoor connection ratio does not exceed 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at the 100% connection ratio
x Correction ratio of piping to furthest indoor
Condition: Indoor connection ratio exceeds 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio
x Correction ratio of piping to furthest indoor

4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
52 HP 41.3 22.2

5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model Gas Liquid
52 HP 41.3 19.1

6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =

Equivalent length of main pipe x Correction factor


+
Equivalent length of branch pipes

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0
Heating (liquid pipe) 1.0 0.5

Example
Main gas pipe size increase
Main Liquid pipe size increase Equivalent length branch

80 m 40 m

In the above case (Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 0.88

3D079897A

38 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

5 Capacity tables
5 - 2 Capacity Correction Factor
RYYQ54U
RXYQQ54U
RXYQ54U Correction ratio for cooling capacity Correction ratio for heating capacity 5
Height Difference between outdoor and farest

Height Difference between outdoor and farest


Indoor (m)

Indoor (m)
Equivalent piping length (m) Equivalent piping length (m)

NOTES
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.
2. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.

Condition: Indoor connection ratio does not exceed 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at the 100% connection ratio
x Correction ratio of piping to furthest indoor
Condition: Indoor connection ratio exceeds 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio
x Correction ratio of piping to furthest indoor

4. When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model Gas Liquid
54 HP 41.3 22.2

5. When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.

Diameter of main pipes (standard size)


Model Gas Liquid
54 HP 41.3 19.1

6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =

Equivalent length of main pipe x Correction factor


+
Equivalent length of branch pipes

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0
Heating (liquid pipe) 1.0 0.5

Example
Main gas pipe size increase
Main Liquid pipe size increase Equivalent length branch

80 m 40 m

In the above case (Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m

The rate of change in cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 0.83

3D079897A

VRV IV+ heat pump, without continuous heating • RXYQ-U 39


VRV IV+ heat pump, without continuous heating • RXYQ-U

6 Dimensional drawings
6 - 1 Dimensional Drawings
REMQ5U
Pitch of foundation bolt holes
REYQ8-12U 1 2 766
3
RXYQQ8-12U

Pitch of foundation bolt holes


6 RXYQ8-12U
RYMQ8-12U
353
335

RXYTQ8-UYF

729
8
AA

134
190

125
RYYQ8-12U
100

107
112
66
160
106
AB

70
Detail ·A· Detail ·B·
4-15x22.5mm
Oblong hole 10
View ·C·
Foundation bolt hole

11
1685

7
9 6
122
515

276

259

179

131

76 76
5
Model
97 107
137 Detail ·B· Detail ·A· AA AB
272
Notes 765
328 RYYQ8-12U, RXYQ8-12U, RXYQQ8-12U,RXYTQ8U - -
1.Detail ·A· and detail ·B· indicate the dimensions after fixing the attached piping. C
2. Items ·4 - 10:· Knockout hole.
373 REMQ5U, RYMQ8-12U, REYQ8-12U 246 240
930
3. Gas pipe
RYYQ8U, RYMQ8U, RXYQ8U, RXYQQ8U, RXYTQ8U : Ø ·19.1· brazing connection 11 Grounding terminal
RYYQ10U, RYMQ10U, RXYQ10U, RXYQQ10U : Ø ·22.2· brazing connection Pipe routing hole (bottom)
: 10
REMQ5U, REYQ8-12U Ø ·25.4· brazing connection
RYYQ12U, RYMQ12U, RXYQ12U, RXYQQ12U : Ø ·28.6· brazing connection 9 Pipe routing hole (front) Inside of the switch box (·M8·)
Liquid pipe
8 Power cord routing hole (bottom) Ø65
RYYQ8-10U, RYMQ8-10U, RXYQ8-10U, RXYQQ8-10U, : Ø ·9.5· brazing connection 7 Power cord routing hole (front) Ø27
REMQ5U, REYQ8-12U, RXYTQ8U
6 Power cord routing hole (front) Ø65
RYYQ12U, RYMQ12U, RXYQ12U, RXYQQ12U : Ø ·12.7· brazing connection 5 Power cord routing hole (front) Ø80
Equalising pipe 4 Power cord routing hole (side) Ø65

RYMQ8-10U : Ø ·19.1· brazing connection Equalising pipe connection port See note ·3·.
3
High pressure/low pressure gas pipe See note ·3·.
RYMQ12U : Ø ·22.2· brazing connection
2 Gas pipe connection port See note ·3·.
High pressure/low pressure gas pipe 1 Liquid pipe connection port Remark
No. Part name
REMQ5U, REYQ8-12U : Ø ·19.1· brazing connection 2D119001

REYQ14-20U Pitch of foundation bolt holes


RXYQQ14-20U
RXYQ14-20U 1 2
Pitch of foundation bolt holes

1076

RXYTQ10-16U 3
RYYQ14-20U 393

RYMQ14-20U
134

125 8
729
310
210

107
112
AB

70

100 71
160 106
10
AA
4-15x22.5mm - Oblong hole
Detail A Detail B View C
Foundation bolt hole

11
1685

7 6
9
122
515

276

259

179

131

76 76 97 107 5 Model AA AB
DETAIL A
137 DETAIL B 272
RXYQ14-20U, RYYQ14-20U, RXYQQ14-20U, RXYTQ10-16U - -
Notes 765 328
C RYMQ14-16U, REYQ14-20U 240 155
1. Detail A and detail B indicate the dimensions after fixing the attached piping. 1. 373

2. Items 4 - 10: 1240 RYMQ18-20U 240 192


Knockout hole.
3. Gas pipe 11 Grounding terminal
Ø 22.2 brazing connection 10 Pipe routing hole (bottom)
RXYTQ10U
REYQ14-20U Ø 25.4 brazing connection 9 Pipe routing hole (front) Inside of the switch box (M8)
RYYQ14-20U, RYMQ14-20U RXYQ14-20U, RXYQQ14-20U, Ø 28.6 brazing connection 8 Power cord routing hole (bottom) Ø65
RXYTQ12-16U Liquid pipe 7 Power cord routing hole (front) Ø27
RXYTQ10U Ø 9.5 brazing connection 6 Power cord routing hole (front) Ø65
RYYQ14-16U, RYMQ14-16U, RXYQ14-16U, RXYQQ14-16U, REYQ14-20U, Ø 12.7 brazing connection 5 Power cord routing hole (front) Ø80
RXYTQ12-16U Ø 15.9 brazing connection 4 Power cord routing hole (side) Ø65
RYYQ18-20U, RYMQ18-20U, RXYQ18-20U, RXYQQ18-20U Equalising pipe Equalising pipe connection port
RYMQ14-16U Ø 22.2 brazing connection 3
High pressure/low pressure gas pipe See note 3.
RYMQ18-20U Ø 28.6 brazing connection
2 Gas pipe connection port See note 3.
High pressure/low pressure gas pipe
1 Liquid pipe connection port See note 3.
REYQ14-20U Part name
Ø 22.2 brazing connection No. Remark 2D119091

40 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

7 Centre of gravity
7 - 1 Centre of Gravity
RXYQQ8-12U
RXYQ8-12U
RXYTQ8UYF
RYYQ8-12U
Unit AA AB AC
RYMQ8-12U 7
REMQ5U RYYQ8-12U
REYQ8-12U 328 366 565
REMQ5U / REYQ8-12U
RYMQ8-12U 354 443 565
RXYQ8-12U
RXYQQ8-12U 339 448 565
RXYTQ8U

Foundation bolt hole (slot)

View ·A·

AC

View ·A·

AA AB
729 766 Foundation bolt hole

Foundation bolt hole Foundation bolt hole 3D119703

RXYQQ14-20U
RXYQ14-20U Unit AA AB AC
RXYTQ10-16UYF RYYQ14-20U 334 470 610
REYQ14-20U 334 470 610
RYYQ14-20U Foundation bolt hole (slot)
RYMQ14-20U 360 569 610
RYMQ14-20U View ·A· RXYQ(Q)14-20U 345 575 610
REYQ14-20U RXYTQ10-12U 350 610 810
RXYTQ14-16U 351 565 610
AC

View ·A·

AA AB
729 1076
Foundation bolt hole Foundation bolt hole
Foundation bolt hole
3D119704

VRV IV+ heat pump, without continuous heating • RXYQ-U 41


VRV IV+ heat pump, without continuous heating • RXYQ-U

8 Piping diagrams
8 - 1 Piping Diagrams
RXYQ8-12U
RXYTQ8UYF R1T

8 Y3E
R4T
M
M1F

Y1E Charge port / Service port


R5T R6T R7T
Stop valve
Filter
Y2E
Check valve

Pressure relief valve

Thermistor
Heat sink
(PCB)
Y1S
Capillary tube
Expansion valve
S1NPL S1NPH
4-way valve

Propeller fan
R3T
M

HPS High pressure switch


Low pressure sensor
HPS High pressure sensor
S1PH

R21T Accumulator
Y3S
sv

R8T
M1C
Heat exchanger

sv
Compressor
Y2S

Liquid pipe Oil separator

Gas pipe
Double tube heat exchanger
Charge port
Distributor

Solenoid valve
sv

3D118179
RXYQ14-20U
RXYQ14-16UYF

R1T

Charge port / Service port


Y3E M M
R4T M1F M2F Stop valve
Y1E
Filter
R5T R6T R7T Check valve

Y2E
Pressure relief valve
Thermistor
Heat sink
(PCB)

Capillary tube
Expansion valve
Y1S
4-way valve

S1NPL S1NPH
Propeller fan
M

HPS High pressure switch


R3T
Low pressure sensor
High pressure sensor

HPS HPS
Accumulator
S1PH S2PH

R21T R22T
Heat exchanger
sv

sv

Y3S Y4S
R8T R9T
M1C M2C Compressor

sv
Oil separator
Y2S

Liquid pipe Double tube heat exchanger

Gas pipe Distributor


Charge port Solenoid valve
sv

3D118180

42 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

9 Wiring diagrams
9 Notes & Legend
RXYQ8-12U
RXYTQ8UYF
RYYQ8-12U 9
RYMQ8-12U

A1P Printed Circuit Board (Main) R3T Thermistor (Accumulator)


A2P Printed Circuit Board (Noise Filter) R4T Thermistor (Heat Exc,Liq,Pipe)
A3P Printed Circuit Board (Inv) R5T Thermistor (Subcool,Liq,Pipe)
A4P Printed Circuit Board (Fan) R6T Thermistor (Heat Exc,Gas Pipe)
A5P Printed Circuit Board (ABC I/P)(Option) R7T Thermistor (Heat Exc,Deicer)
BS1~3 (A1P) Push Button Switch (Mode,Set,Return) R8T Thermistor (M1C body)
C503,C506,C507 (A3P) Capacitor R21T Thermistor (M1C discharge)
DS1,DS2 (A1P) DIP Switch S1NPH Pressure Sensor (High)
E1HC Crankcase Heater S1NPL Pressure Sensor (Low)
E3H Drainpan Heater (Option) S1PH Pressure Switch (Disch)
F1U,F2U (A1P) Fuse (T,3,15A,250V) SEG1~SEG3 (A1P) 7-Segment Display
F3U Field Fuse T1A Current Sensor
F101U (A4P) Fuse V1D (A3P) Diode
F401U,F403U (A2P) Fuse V1R (A3P,A4P) Power Module
F601U (A3P) Fuse X*A Connector
HAP (A1P,A3P, A4P) Pilotlamp (Service Monitor-Green) X1M (A1P) Terminal Block (Control)
K3R (A3P) Magnetic Relay X1M (A5P) Terminal Block (Power Supply)(Option)
K4R (A1P) Magnetic Relay (Y1S) Y1E Electronic Expansion Valve(Main)
K5R (A1P) Magnetic Relay (Y2S) Y2E Electronic Expansion Valve (Injection)
K6R (A1P) Magnetic Relay (E3H) Y3E Electronic Expansion Valve (Refrigerant Jacket)
K7R (A1P) Magnetic Relay (E1HC) Y4E Electronic Expansion Valve (Storage Vessel)
K9R (A1P) Magnetic Relay (Y3S) Y1S Solenoid Valve (Main)
K11R (A1P) Magnetic Relay (Y5S) Y2S Solenoid Valve (Accumulator Oil Return)
L1R Reactor Y3S Solenoid Valve (Oil1)
M1C Motor (Compressor) Y5S Solenoid Valve (Sub)
M1F Motor (Fan) Z*C Noise Filter (Ferrite Core)
PS (A1P,A3P) Switching Power Supply Z*F (A2P) Noise Filter (With Surge Absorber)
Q1DI Field Earth Leakage Breaker Connector For Optional Accessories
Q1LD (A1P) Field Earth Current Detector X10A Connector (Drainpan Heater)
R24 (A4P) Resistor (Current Sensor) X37A Connector (Power Adapter)
R300 (A3P) Resistor (Current Sensor) Connector (Remote Switching
X66A
R1T Thermistor (Air) Cool/Heat Selector)

NOTES

1. This wiring diagram applies only to the outdoor unit.


2. :field wiring, : terminal block, : connector, : terminal, : protective earth (screw), : functional earth,
: earth wiring, : field supply, : PCB, : switch box, : option
3. When using the optional adapter, refer to the installation manual of the optional adapter.
4. For connection wiring to indoor-outdoor transmission F1-F2, outdoor-outdoor transmission F1-F2, outdoor-multi transmission Q1-Q2, refer to the
installation manual.
5. How to use BS1~3 switch. Refer to “service precaution” label on el. compo. box cover.
6. When operating, don’t shortcircuit the protection devices (S1PH).
7. Only for RYYQ model.
8. Only for RYYQ/RYMQ model.
9. Colors: BLK: Black, RED: Red, BLU: Blue, WHT: White, GRN: Green.

2D117534

VRV IV+ heat pump, without continuous heating • RXYQ-U 43


VRV IV+ heat pump, without continuous heating • RXYQ-U

9 Wiring diagrams
9-2 Wiring Diagrams - Single Phase
RXYQ8-12U
RXYTQ8UYF
RYYQ8-12U 9
RYMQ8-12U

Power supply 3N~ 380-415V 50Hz


3N~ 380V 60Hz
Wiring diagram
X1M T1A A1P
Q1DI F3U N=1 X1A F1U
L1 L1 RED RED
BLU X21A
L2 L2 WHT BLK F2U Y1E
6 M
L3 L3 BLK Z8C N=3
BLU SEG1 SEG2 SEG3
N N X101A
X22A Y2E
Q1LD 6 M
Z9C N=1 BS1 BS2 BS3
DS1 DS2
X5A ON ON
WHT
RED

X23A
BLK
BLU

A2P Z3C N=1 OFF OFF Y3E


1234 1234 5 M
L1A L2A L3A N X4A
F401U

F403U

X37A
X3A HAP (Note 7)
GRN E1 (Note 3) X25A Y4E
Z1F 5 M
S1PH P>
X2A (Note 6)
L1B L2B L3B Z4C N=1 PS
X18A t ゜ R1T
BLK
RED

X28A
WHT

S1NPL

K7R
A3P

K11R
Z7C N=1
K6R

K4R

K5R

K9R
Z5C N=2 X31A
L1B L2B L3B X6A X20A X10A X8A X9A X13A X15A X11A
X40A S1NPH
X4A X32A
HAP
+

V1R
-

PS X63A E3H Y1S Y2S Y3S Y5S E1HC


P1 (Note 8)
C507 K3R
+ X601A R21T R8T R3T R4T R5T R6T R7T
F601U

P2 Z6C t゜ t゜ t゜ t゜ t゜ t゜ t゜
N=3
V1D +C506 +C503 N32 BLK X3A X50A X19A X30A
GRN

P12 RED X1M


X66A to in/d unit to out/d unit to multi unit
N31 BLK F1 F2 F1 F2 Q1 Q2
(Note 3)
R300 P11 RED
+

V1R
A5P
U V W X41A (Note 4) (Note 4) (Note 4)
X1A
Z7C N=1 X1M
A4P C/H selector
Z2C N=4 A B C
P1 N1 X5A indoor outdoor outdoor
WHT
WHT

(F1)(F2) (F1)(F2) (Q1)(Q2)


F101U
RED
WHT
BLK

R24
L1R X3A + HAP X4A
-

V V1R Terminal of M1C Layout of M1C


U MS W X1A heat
M1C 3~ cool W M1F el. compo.box
Z1C N=2 cool S2S -
heat U
fan V M1C
X1A
S1S
outer shell
MS Cool/heat selector
El. compo.box
3~ (Optional accessory)(Note 3)
M1F

A1P L1R

A5P
A2P
8,10,12 class
X3A
X1A X1M A4P

A3P

(Front side) (Rear side)

2D117534

VRV IV+ heat pump, without continuous heating • RXYQ-U 44


VRV IV+ heat pump, without continuous heating • RXYQ-U

9 Wiring diagrams
9-3 Wiring Diagrams - Three Phase
RXYQ14-20U A1P Printed circuit board (main)
A2P, A5P Printed circuit board (noise filter)
RYYQ14-20U A3P, A6P Printed circuit board (inv)
RYMQ14-20U A4P, A7P Printed circuit board (fan)
9 A8P Printed circuit board (ABC I/P)
BS1~3 (A1P) Push button switch (mode, set, return)
C503, C506, C507 (A3P, A6P) Capacitor
(NOTE 7)7)

DS1, DS2 (A1P) Dip switch S1PH,


Y1E

Y2E

Y3E

Y4E
(note
5 M

5 M

5 M

5 M

S1NPH
S1NPL
t ゜ R1T

E1HC, E2HC Crankcase heater


E3H Drainpan heater (option)
F1U, F2U (A1P) Fuse (T, 3, 15A, 250V)
X21A

X22A

X23A

X25A

X18A

to in/d unit to out/d unit to multi unit X31A

X32A

(note 4)
F3U Field fuse

(Q1)(Q2)
F101U (A4P, A7P) Fuse
outdoor
(NOTE3)3)

Q2
1234
SEG3

DS2
BS3

X37A
(note

F401U, F403U (A2P, A5P) Fuse


ON
OFF

Q1

(note 4)

F601U (A3P, A6P) Fuse


SEG2

BS2

HAP (A1P, A3P, A4P, A6P, A7P) Pilotlamp (service monitor-green)


(F1)(F2)
outdoor
F2
1234
DS1

X5A R L2

R L1
HAP

K3R (A3P, A6P) Magnetic relay


SEG1

BS1
ON
OFF

F1

(note 4)

K3R (A1P) Magnetic relay (Y4S)

A2P

A3P
(F1)(F2)

K4R (A1P) Magnetic relay (Y1S)


F2

indoor
X1M
PS

Z8C
N=1

K5R (A1P) Magnetic relay (Y2S)


F1
Wiring diagram

el.compo.box

X6A
A5P

A6P
K6R (A1P) Magnetic relay (E3H)
(note 8)

K11R
X15A

Y5S

K7R (A1P) Magnetic relay (E1HC)


t゜
R7T

cool/heat selector (optional accessory) (note 3)


S1S

K8R (A1P) Magnetic relay (E2HC)


A4P
A7P
K8R
E2HC
X12A

t゜
R6T

K9R (A1P) Magnetic relay (Y3S)


S2S heat
cool

fan

X1A
X2A

K11R (A1P) Magnetic relay (Y5S)


t゜

K7R
E1HC
X11A

X30A
R5T

L1R, L2R Reactor


heat

A1P

X1M
cool
t゜

M1C, M2C Motor (compressor)


R4T

K3R
Y4S
X7A

A8P
M1F, M2F Motor (fan)
t゜
R3T

K9R PS (A1P, A3P, A6P) Switching power supply


X13A

Y3S

Q1DI Field earth leakage breaker


terminal of
M1C,M2C
C/H selector

V
C
t゜

Q1LD (A1P) Field earth current detector


R9T

K5R
X9A

Y2S

R24 (A4P, A7P) Resistor (current sensor)


B
t゜

U
R8T

R300 (A3P, A6P) Resistor (current sensor)


X1M

A
X19A

K4R
X8A

Y1S

R1T Thermistor (air)


t゜
R22T

A8P
X1A

el.compo.box

outer shell

R3T Thermistor (accumulator)


M1C,M2C,M1F,M2F
t゜

K6R
R21T
X10A

E3H

R4T Thermistor (heat exc, liq, pipe)


M1C
M2C

R5T Thermistor (subcool, liq, pipe)


layout of
X20A (note 3)

GRN
X4A X5A X50A
X66A
Q1LD

R6T Thermistor (heat exc, gas pipe)


F2U
F1U

(note 6)

(note 6)

M2F

R7T Thermistor (heat exc, deicer)


X41A

X40A

X28A
X2A

X3A
X1A

X101A
A1P

R8T, R9T Thermistor (M1C, M2C body)


M1F
RED

RED

WHT
BLU
BLK

BLK

BLK

R21T, R22T Thermistor (M1C, M2C discharge)


X5A
S1PH P>

S2PH P>

S1NPH Pressure sensor (high)


P12 RED

P11 RED
BLK

N31 BLK

S1NPL Pressure sensor (low)


N=1
Z5C

N32

S1PH, S2PH Pressure switch (disch)


X63A

X6A

X4A

SEG1~SEG3 (A1P) 7-segment display


Z4C
N=2

HAP

T1A Current sensor


PS

BLU F601U
K3R
Z6C
N=1

Z1C
N=5
V1R
R300

X3A

V1D (A3P, A6P) Diode


N

BLK F403U BLK - - BLK


V1R (A3P, A4P, A6P, A7P) Power module
L1A L2A L3A

U MS W
W
V1D +C506 +C503
L1B L2B L3B

L1B L2B L3B


Z1F

C507

WHT WHT
M1C 3~

X*A Connector
WHT
V1R

V
+

X1M (A1P) Terminal block (control)


RED F401U RED + + RED
U
A2P

X1M (A8P) Terminal block (power supply)


E1

X601A
X61A
X41A

Y1E Electronic expansion valve (main)


A3P
GRN

P1

P2

WHT
L1R

WHT Y2E Electronic expansion valve (injection)


Y3E Electronic expansion valve (refrigerant jacket)
X6A

Y4E Electronic expansion valve (storage vessel (note 7)


P12 RED

P11 RED
BLK

N31 BLK

Y1S Solenoid valve (main)


Y2S Solenoid valve (accumulator oil return)
X63A

N32
X6A
X4A

Y3S Solenoid valve (oil1)


11)
(NOTE11)

Y4S Solenoid valve (oil2)


HAP

PS
Z7C N=1

F601U
(note

BLU
Y5S Solenoid valve (sub) (note 8)
K3R

Z2C
N=5
V1R
R300

X4A
N

-
Z*C Noise filter (ferrite core)
BLK F403U BLK - BLK
L1A L2A L3A

U MS W
W
V1D +C506 +C503
L1B L2B L3B

X41A L1B L2B L3B


Z1F

Z*F (A2P, A5P) Noise filter (with surge absorber)


C507

WHT WHT
M2C 3~

WHT
V1R

V
+

RED F401U RED + + RED


U

Connector for optional accessories


A5P

E1

X601A

X10A Connector (drainpan heater)


A6P
GRN

P1

P2
Z9C
N=2

WHT
X37A Connector (power adapter)
L2R

WHT
X66A Connector (remote switching
Cool/heat selector)
N=1
T1A

NOTES
P11 RED

RED
N11 BLK

BLK
WHT
RED

BLU
BLK

1. This wiring diagram applies only to the outdoor unit.


P11

N11
X1M
L1
L2
L3
N

X5A

X5A

2.
X3A

: Field wiring, : terminal block, : connector, :terminal,


F101U

F101U
R24

R24

: protective earth (screw), : functional earth, : earth wiring,


HAP

HAP
X3A

+ +
X4A

X4A
-

: field supply, : pcb, : switch box, : option


V1R

V1R

3. When using the optional adapter, refer to the installation manual of the optional adapter.
A7P

A4P
X1A

X1A
50Hz
60Hz

4. For connection wiring to indoor-outdoor transmission F1-F2, outdoor-outdoor


Z3C
N=1

transmission F1-F2, outdoor-multi transmission Q1-Q2, refer to the installation manual.


Q1DI F3U
3N~ 380-415V

5. How to use BS1~3 switch. Refer to “service precaution” label on el. Compo. Box cover.
(note 9)

(note 9)
Power supply

X2A

X1A

6. When operating, don’t shortcircuit the protection devices (S1PH,S2PH)


3N~ 380V

7. Only for RYYQ model.


8. Only for RYYQ/RYMQ model.
M2F

M1F
MS

MS
L1
L2
L3

3~

3~
N

9. Connector X1A (M1F) is red, connector X2A (M2F) is white.


10. Colors: BLK:black, RED:red, BLU:blue, WHT:white, GRN:green.
11. Only for 14,16 class

2D117536C

45 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

10 External connection diagrams


10 - 1 External Connection Diagrams
RXYQQ8-20U Notes
RXYQ8-20U 1. All wiring, components and materials to be procured on-site must comply with the applicable legislation.

RXYTQ8-16UYF 2. Use copper conductors only

10 RYYQ8-20U 3. For details, refer to the wiring diagram attached to the outdoor unit.

RYMQ8-20U
4. Install a circuit breaker for safety.
5. All field wiring and components must be provided by an authorised electrician.
6. Unit has to be grounded in compliance with the applicable legislation.
7. The wiring shown is a general points-of-connection guide and is not intended to include all details for a specific installation.
8. Make sure to install the switch and the fuse to the power line of each equipement.
9. Install a main switch to control the multiple power sources that the various components of the system make use of.
10. The capacity of UNIT1 must be larger than that of UNIT2 when the power source is connected in series between the units.
The capacity of UNIT 2 must be larger than that of UNIT3 when the power source is connected in series between the units.
11. If there exists the possibility of reversed phase, loose phase or momentary blackout, or if the power goes on and off while the product is operating, attach a reversed
phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
12. Install an earth leakage circuit breaker.

Power supply
L1 L2 L3 N
< Power source is supplied to each outdoor unit
individually. > Power supply
L1 L2 L3 N
< Power source is connected in series between
the units. >
Main switch Outdoor units Main switch Outdoor units

2-wire cable 2-wire cable 2-wire cable 2-wire cable


Transmission line Transmission line Transmission line Transmission line
Unit 1 Unit 2 Unit 3 Unit 1 Unit 2 Unit 3
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
Switch Switch Switch Switch

Fuse Fuse Fuse Fuse

Power supply Power supply


L N L N

Main switch Main switch

2-wire cable
Transmission line
2-wire cable 2-wire cable 2-wire cable 2-wire cable 2-wire cable
2-wire cable 2-wire cable
2- wire cable Transmission line Transmission line
Transmission line Transmission line Transmission line Transmission line
Transmission line
Power line

2-wire cable L N L N L N L N L N L N L N L N

Power line Switch Switch Switch Switch Switch Switch Switch Switch
Fuse Fuse Fuse Fuse Fuse Fuse Fuse Fuse
2-wire cable
Power line
2-wire cable 2-wire cable
2-wire cable 2-wire cable 2-wire cable 2-wire cable 2-wire cable
Power line Power line
Power line Power line Power line Power line Power line

Indoor units Indoor units

3D119200

RXYQQ8-20U Notes

RXYQ8-20U 1. All wiring, components and materials to be procured on-site must comply with the applicable legislation.
2.Use copper conductors only
RXYTQ8-16U 3. For details, refer to the wiring diagram attached to the outdoor unit.

RYYQ8-20U 4. Install a circuit breaker for safety.


5.All field wiring and components must be provided by an authorised electrician.
RYMQ8-26U 6. Unit has to be grounded in compliance with the applicable legislation.
7.The wiring shown is a general points-of-connection guide and is not intended to include all details for a specific installation.
8. Make sure to install the switch and the fuse to the power line of each equipement.
9.Install a main switch to control the multiple power sources that the various components of the system make use of.
10.The capacity of UNIT1 must be larger than that of UNIT2 when the power source is connected in series between the units.
11. If there exists the possibility of reversed phase, loose phase or momentary blackout, or if the power goes on and off while the product is operating, attach a reversed phase
protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
12.Install an earth leakage circuit breaker.

Power supply
< Power source is supplied to each outdoor unit individually.
> Power supply
< Power source is connected in series between the units.
>
L1 L2 L3 N L1 L2 L3 N

Main switch Outdoor units Main switch Outdoor units


·2·-wire cable ·2·-wire cable
Transmission lin Transmission line
Unit ·1· e Unit ·2· Unit ·1· Unit ·2·
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
Switch Switch Switch
Fuse Fuse Fuse

Power supply PowerL Nsupply


L N

Main switch Main switch

·2·-wire cable
·2·-wire cable Transmission line
Transmission line ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable
·2·-wire cable Transmission lin Transmission lin Transmission line Transmission line Transmission line
Power line Transmission line
Power line
e e
L N L N L N L N L N L N L N L N
Switch Switch Switch Switch Switch Switch Switch Switch
Fuse Fuse Fuse Fuse Fuse Fuse Fuse Fuse
·2·-wire cable
Power line
·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable
Power line Power line Power line Power line Power line Power line Power line

Indoor units Indoor units

3D119316

46 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

10 External connection diagrams


10 - 1 External Connection Diagrams
RXYQQ8-20U
RXYQ8-20U
RYYQ8-20U Notes

RYMQ8-20U 1. All wiring, components and materials to be procured on-site must comply with the applicable le
gislation.
10
RXYTQ8-16UYF
L1 L2 L3 N Power supply
2. Use copper conductors only
3. For details, refer to the wiring diagram attached to the outdoor unit.
Main switch
4. Install a circuit breaker for safety.
5. All field wiring and components must be provided by an authorised electrician.
6. Unit has to be grounded in compliance with the applicable legislation.
Outdoor unit

Switch 7. The wiring shown is a general points-of-connection guide and is not intended to include all details
for a specific installation.
L1 L2 L3 N
Fuse 8. Make sure to install the switch and the fuse to the power line of each equipement.
9. Install a main switch to control the multiple power sources that the various components of t
he system make use of.

Power supply 10. If there exists the possibility of reversed phase, loose phase or momentary blackout, or if the power g
oes on and off while the product is operating, attach a reversed phase protection circuit locally.

L N
Main switch Running the product in reversed phase may break the compressor and other parts.
11. Install an earth leakage circuit breaker.

2-wire cable
Transmission line

2-wire cable 2-wire cable 2-wire cable


Transmission line Transmission line Transmission line
2-wire cable
Power line

L N L N L N L N
Switch Switch Switch Switch

Fuse Fuse Fuse Fuse

2-wire cable 2-wire cable 2-wire cable 2-wire cable


Power line Power line Power line
Power line

Indoor unit
3D119317

VRV IV+ heat pump, without continuous heating • RXYQ-U 47


VRV IV+ heat pump, without continuous heating • RXYQ-U

11 Sound data
11 - 1 Sound Power Spectrum
REMQ5U
REYQ8U
RXYQQ8U
11 RXYQ8U 90 90
RXYTQ8UYF 85 NR90
RYYQ8U 80 NR85 80
RYMQ8U 75 NR80
70 NR75 70

65 NR70
Sound power level [dB]

60 60
NR65
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR10 NR15
NR5
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119528
REYQ10U
RXYQQ10U
RXYQ10U 90 90
RYYQ10U 85 NR90
RYMQ10U 80 NR85 80

75 NR80
70 NR75 70

65 NR70
Sound power level [dB]

60 60
NR65
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR10 NR15
NR5
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119529

48 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

11 Sound data
11 - 1 Sound Power Spectrum
REYQ12U
RXYQQ12U
RXYQ12U 95
RYYQ12U
11
90 90
RYMQ12U 85 NR90
80 NR85 80
75 NR80
70 NR75 70
65
Sound power level [dB]

NR70
60 NR65 60
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0
NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119530
REYQ14U
RXYQQ14U
90 90
RXYQ14U
85 NR90
RYYQ14U
80 80
RYMQ14U NR85
75 NR80
70 NR75 70
Sound power level [dB]

65 NR70
60 60
NR65
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR10 NR15
NR5
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119531

VRV IV+ heat pump, without continuous heating • RXYQ-U 49


VRV IV+ heat pump, without continuous heating • RXYQ-U

11 Sound data
11 - 1 Sound Power Spectrum
REYQ16U
RXYQQ16U
RXYQ16U 95
11 RYYQ16U 90 90
RYMQ16U 85 NR90
80 NR85 80
75 NR80
70 NR75 70
65
Sound power level [dB]

NR70
60 NR65 60
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0
NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119532
REYQ18U
RXYQQ18U
95
RXYQ18U
90 90
RYYQ18U
85 NR90
RYMQ18U
80 NR85 80
75 NR80
70 NR75 70
Sound power level [dB]

65 NR70
60 NR65 60
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0
NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119533

50 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

11 Sound data
11 - 1 Sound Power Spectrum
REYQ20U
RXYQQ20U
100 100
RXYQ20U
RYYQ20U
95 11
90 90
RYMQ20U
85 NR90
80 NR85 80
75 NR80
70 NR75 70
Sound power level [dB]

65 NR70
60 NR65 60
55 NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR0 NR20
NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119534

VRV IV+ heat pump, without continuous heating • RXYQ-U 51


VRV IV+ heat pump, without continuous heating • RXYQ-U

11 Sound data
11 - 2 Sound Pressure Spectrum
REMQ5U
REYQ8U
RXYQQ8U
11 RXYQ8U 70 70
NR75

RXYTQ8UYF 65
NR70
RYYQ8U
60 60
RYMQ8U NR65

55
NR60

50 50
NR55
Sound pressure level [dB]

45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119521
REYQ10U
RXYQQ10U 70 70
NR75
RXYQ10U
65
RYYQ10U NR70
RYMQ10U 60 60
NR65

55
NR60

50 50
NR55
Sound pressure level [dB]

45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119522

52 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

11 Sound data
11 - 2 Sound Pressure Spectrum
REYQ12U
RXYQQ12U
70 NR75 70
RXYQ12U
RYYQ12U 65
11
NR70
RYMQ12U
60 60
NR65

55
NR60

50 50
NR55
Sound pressure level [dB]

45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa

3D119523
REYQ14U
RXYQQ14U
RXYQ14U 70 NR75 70

RYYQ14U 65
NR70
RYMQ14U
60 60
NR65

55
NR60

50 50
NR55
Sound pressure level [dB]

45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119524

VRV IV+ heat pump, without continuous heating • RXYQ-U 53


VRV IV+ heat pump, without continuous heating • RXYQ-U

11 Sound data
11 - 2 Sound Pressure Spectrum
REYQ16U
RXYQQ16U
70 70
RXYQ16U NR75
11 RYYQ16U 65
NR70
RYMQ16U
60 60
NR65

55
NR60

50 50
NR55
Sound pressure level [dB]

45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa

3D119525
REYQ18U
RXYQQ18U
70 70
RXYQ18U NR75

RYYQ18U 65
NR70
RYMQ18U
60 60
NR65

55
NR60

50 50
NR55
Sound pressure level [dB]

45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa

3D119526

54 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

11 Sound data
11 - 2 Sound Pressure Spectrum
REYQ20U
RXYQQ20U
75 NR80
RXYQ20U NR65 NR70 NR75
RYYQ20U 70 NR75
NR75 70 11
RYMQ20U 65
NR70

60 60
NR65
55
NR60
Sound pressure level [dB]

50 50
NR55
45 NR45 NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119527

VRV IV+ heat pump, without continuous heating • RXYQ-U 55


VRV IV+ heat pump, without continuous heating • RXYQ-U

11 Sound data
11 - 3 Sound Pressure Spectrum Quiet Mode Level 1
REMQ5U
REYQ8-12U 65
NR70
RXYQQ8-12U
11 60 60
RXYQ8-12U NR65

RXYTQ8UYF 55
NR60

RYY8-12U 50 50
NR55
RYMQ8-12U
Sound pressure level [dB]

45
NR50

40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25

15 NR20
NR0 NR5 NR10 NR15

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119535

REYQ14-16U
RXYQQ14-16U 60
NR65
60

RXYQ14-16U 55 55
RXYTQ14-16UYF NR60

RYYQ14-16U 50
NR55
50

RYMQ14-16U 45 45
NR50
Sound pressure level [dB]

40 40
NR45

35 35
NR40

30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR0 NR5 NR10 NR15

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119538

56 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

11 Sound data
11 - 3 Sound Pressure Spectrum Quiet Mode Level 1
REYQ18-20U
RXYQQ18-20U 65
NR70
RXYQ18-20U
60 60 11
RYYQ18-20U NR65

RYMQ18-20U 55
NR60

50 50
NR55
Sound pressure level [dB]

45
NR50

40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25

15 NR20
NR0 NR5 NR10 NR15

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119541

VRV IV+ heat pump, without continuous heating • RXYQ-U 57


VRV IV+ heat pump, without continuous heating • RXYQ-U

11 Sound data
11 - 4 Sound Pressure Spectrum Quiet Mode Level 2
REMQ5U
REYQ8-12U 60
NR65
60

RXYQQ8-12U
11 RXYQ8-12U
55
NR60
55

RXYTQ8UYF 50
NR55
50

RYYQ8-12U 45 45
RYMQ8-12U NR50
Sound pressure level [dB]

40 40
NR45

35 35
NR40

30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR0 NR5 NR10 NR15

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119536
REYQ14-16U
RXYQQ14-16U 55 55
RXYQ14-16U NR60

RXYTQ14-16UYF 50 50
NR55
RYYQ14-16U
45 45
RYMQ14-16U NR50

40 40
Sound pressure level [dB]

NR45

35 35
NR40

30 30
NR35

25 25
NR30

20 20
NR25
NR20
15 15
NR5 NR10 NR15
NR0

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119539

58 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

11 Sound data
11 - 4 Sound Pressure Spectrum Quiet Mode Level 2
REYQ18-20U
RXYQQ18-20U 60 60
NR65
RXYQ18-20U
RYYQ18-20U 55 55 11
NR60

RYMQ18-20U 50 50
NR55

45 45
NR50
Sound pressure level [dB]

40 40
NR45

35 35
NR40

30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR0 NR5 NR10 NR15

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119542

VRV IV+ heat pump, without continuous heating • RXYQ-U 59


VRV IV+ heat pump, without continuous heating • RXYQ-U

11 Sound data
11 - 5 Sound Pressure Spectrum Quiet Mode Level 3
REMQ5U
REYQ8-12U 55 55
NR60
RXYQQ8-12U
11 RXYQ8-12U 50 50
NR55
RXYTQ8UYF
45 45
RYYQ8-12U NR50

RYMQ8-12U 40 40
Sound pressure level [dB]

NR45

35 35
NR40

30 30
NR35

25 25
NR30

20 20
NR25
NR20
15 15
NR5 NR10 NR15
NR0

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119537
REYQ14-16U
RXYQQ14-16U 55 55
NR60
RXYQ14U-16U
RXYTQ14-16UYF 50
NR55
50

RYYQ14-16U 45 45
RYMQ14-16U NR50

40 40
Sound pressure level [dB]

NR45

35 35
NR40

30 30
NR35

25 25
NR30

20 20
NR25
NR20
15 15
NR5 NR10 NR15
NR0

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119540

60 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

11 Sound data
11 - 5 Sound Pressure Spectrum Quiet Mode Level 3
REYQ18-20U
RXYQQ18-20U
RXYQ18-20U 50 50

RYYQ18-20U
NR55
11
45 45
RYMQ18-20U NR50

40 40
NR45
Sound pressure level [dB]

35 35
NR40

30 30
NR35

25 25
NR30

20 20
NR25

NR20
15 15
NR5 NR15
NR10
NR0

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119543

VRV IV+ heat pump, without continuous heating • RXYQ-U 61


VRV IV+ heat pump, without continuous heating • RXYQ-U

12 Installation
12 - 1 Installation Method
REMQ5U
REYQ8-20U
RXYQQ8-20U
12 RXYQ8-20U For single unit installation
For installation in rows For centralised group layout
RYYQ8-20U
RYMQ-20U Pattern 1

300 or more
Pattern 1

300 or more
Pattern 1

300 or more 300 or more


Front 500 or more

10 or more Front 10 or more 10 or more 20 or more Front 20 or more 10 or more 10 or more Front 20 or more 10 or more 10 or more Front 20 or more 10 or more
10 or more 20 or more 10 or more
500 or more 500 or more 600 or more 500 or more
900 or more

Pattern 2 100 or more


Pattern 2 100 or more 300 or more Front
10 or more
Front 20 or more 10 or more
10 or more 20 or more 10 or more
500 or more
10 or more 10 or more 500 or more
20 or more Front

Pattern 2
50 or more Front 50 or more 50 or more 100 or more Front 100 or more 50 or more

500 or more 500 or more


Front 500 or more
100 or more 100 or more

Wall height unrestricted


Pattern 3 Pattern 3 50 or more Front 100 or more 50 or more 50 or more Front 100 or more 50 or more

500 or more 500 or more 50 or more 50 or more


100 or more
300 or more Wall height unrestricted 300 or more
600 or more

50 or more Front 100 or more 50 or more

Front 400 or more Front 400 or more 500 or more 50 or more 100 or more 50 or more 50 or more 50 or more
100 or more Front
200 or more 200 or more 500 or more

Notes
1. Height of the walls in case of patterns 1 and 2: < Unit : mm >

Front: 1500mm
Suction side: 500mm
Side: height unrestricted

h2
The installation space shown on this drawing is based on cooling operation at 35°C (outdoor temperature).
When the design outdoor ambient temperature exceeds 35°C or the load exceeds maximum ability of much generation load of heat in all outdoor unit, m

1555

h1
Suction side
ake sure the suction-side space is broader than the space shown on this drawing.

Front

555
2. If the walls are higher than mentioned above, then additional service space is needed: < Unit : mm >

- suction side: service space + h1/2


- front side: service space + h2/2
3. When installing the units, select the pattern that best fits the available space.

Always keep in mind to leave sufficient space for a person to pass between unit and wall and for the air to circulate freely.
If more units are to be installed than are catered for in the above patterns, your layout should take into account of the possibility of short circuits.

4. Provide sufficient space at the front to connect refrigerant piping (comfortably). 3D118467

62 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

12 Installation
12 - 2 Fixation and Foundation of Units
REMQ5U
REYQ8-20U
RXYQQ8-20U
RXYQ8-20U Nut Foundation bolt type: JA
12
Size: M12
Spring washer
RXYTQ8-16UYF Frame
4 holes for anchor bolts
3 thread ridges or more
RYYQ8-20U
°

80
60
RYMQ8-20U
929

729

00 80
O1 80

75
X X
100

Drain ditch
Smooth downgrade of about 1/50
Y ditch AC AA Foundation bolt fixing method
AB

Drain ditch
AD AA AD AA Smooth downgrade of about 1/50
When building a foundation on the ground When building a foundation on a concrete floor

Y ditch Y ditch Drain ditch For multi-unit installation


100 50 Model AA AB AC AD
RYYQ8-12U
50

RYMQ8-12U
50

RXYQ8-12U 766 992


Floor
RXYQQ8-12U
REMQ5T/REYQ8-12U
Cross section X - X RXYTQ8U
113 185
RYYQ14-20U
RYMQ14-20U
RXYQ14-20U 1076 1076
RXYQQ14-20U
REYQ14-20U
Notes RXYTQ10-16U

1. Provide a drain ditch around the foundation to drain water from the installation area.
2.The surface has to be finished with mortar. The corner edges have to be chamfered.
3. Build the foundation on a concrete floor or, if not possible, make sure the foundation surface has a rough finish.
4. Use a cement/sand/gravel ratio of 1/2/4 for the concrete, and a diameter of 10 mm for the reinforcement bars (approximately, 300mm intervals).
5. When installing the equipment on a roof, make sure to check the strength of the floor and take adequate water proofing measures. 3D118459

VRV IV+ heat pump, without continuous heating • RXYQ-U 63


VRV IV+ heat pump, without continuous heating • RXYQ-U

12 Installation
12 - 3 Refrigerant Pipe Selection
RXYQ-U
RYYQ-Y
RYMQ-U
12

VRV4
Heat pump
Piping restrictions 1/3
Maximum piping length Maximum height difference
Total piping length
After first branch (for (3)
For the reference drawing, see Longest pipe After first branch
multi-outdoor)
Indoor-to-outdoor Indoor-to-indoor Outdoor-to-outdoor
page 2/3. (A+[B,G,E,J]) (B,G,E,J) (D) (H1) (H2) (H3)
Actual / (Equivalent) Actual Actual / (Equivalent) Outdoor above indoor
/ (indoor above
outdoor)
Standard
VRV DX indoor units only
165/(190)m 40m(1) 10/(13)m 50/(40)m(3) 30m 5m 1000m
Standard multi-combination

All multi-outdoor-unit combinations except


135/(160)m 40m(1) 10/(13)m 50/(40)m(3) 30m 5m 500m
standard multi-outdoor-unit combinations
(5)
Hydrobox connection 135/(160)m 40m 10/(13)m 50/(40)m 15m 5m 300-500m
(2)
RA connection 100/(120)m 50m - 50/(40)m 15m - 250m
(4)
Pair 50/(55)m - - 40/(40)m - - -
AHU connection Multi (6) 165/(190)m 40m 10/13m 40/(40)m 15m 5m 1000m
Mix (7) 165/(190)m 40m 10/13m 40/(40)m 15m 5m 1000m

Remark

For standard multi-outdoor-unit combinations, see 3D079534.

(1) If all conditions below are met, the limitation can be extended up to 90 m

a. The piping length between all indoor units and the nearest branch kit is ≤ 40m.

b. It is necessary to increase the size of the gas and liquid piping if the pipe length between the first and the farthest indoor unit is >40m.

If the increased pipe size is larger than the pipe size of the main pipe, also increase the size of the main pipe.

c. When the piping size is increased, the piping length has to be counted as double.

The total piping length has to be within limitations.


d. The piping length difference between the nearest indoor unit from the first branch to the outdoor unit and the farthest indoor unit to the outdoor unit is ≤ 40m.
If the piping length between the first branch and the BP box or VRV indoor unit is more than 20m, increase the length of the gas and liquid piping between the first branch and the BP box or VRV
(2)
indoor unit.

(3) An extension to up to 90 m is possible without an additional option kit. Respect the following conditions:

-> If the outdoor units are positioned higher than the indoor units:

a. Size up the liquid piping

b. A dedicated setting on the outdoor unit is required.

-> If the outdoor units are positioned lower than the indoor units:

a. 40~60m Minimum connection ratio: 80%

60~65m Minimum connection ratio: 90%

65~80m Minimum connection ratio: 100%

80~90m Minimum connection ratio: 110%

b. Size up the liquid piping

A dedicated setting on the outdoor unit is required.

(4) The allowable minimum length is 5 m.

(5) In case of multi-outdoor-unit combinations.

(6) Multiple air handling units (AHU)(EKEXV + EKEQ kits).

(7) Mix of AHU units and VRV DX indoor

(8) If the equivalent piping length between is > 90m, size up the main liquid and gas piping.

3D079540E

64 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

12 Installation
12 - 3 Refrigerant Pipe Selection
RXYQ-U
RYYQ-U
RYMQ-U VRV4
Heat pump
12
Piping restrictions 2/3

Outdoor
H
3

B
G
A E
D J

C
EXV BP
H
1

F
VRV indoor EXV K

H
5
Hydrobox
BP RA
H
2

AHU

H
4
Hydrobox AHU RA VRV indoor

Remark
(1) Schematic indication
Illustrations may differ from the actual appearance of the unit.
(2) This is only to illustrate piping length limitations.
Combination of indoor unit types is not allowed.
Refer to combination table 3D079543 for details about the allowed combinations.

Allowed piping length Maximum height difference


BP to RA EXV to AHU BP to RA EXV to AHU
(F) (K) (H4) (H5)
RA connection 2~15m - 5m -
AHU connection Pair - ≦5m - 5m
(1)
Multi - ≦5m - 5m
Mix (2) - ≦5m - 5m

Remark
(1) Multiple air handling units (AHU)(EKEXV + EKEQ kits).
(2) Mix of AHU units and VRV DX indoor
3D079540E

VRV IV+ heat pump, without continuous heating • RXYQ-U 65


VRV IV+ heat pump, without continuous heating • RXYQ-U

12 Installation
12 - 3 Refrigerant Pipe Selection
RXYQ-U
RYYQ-U
RYMQ-U
12

VRV4
Heat pump
Piping restrictions 3/3

System pattern Total Allowed capacity


Allowed connection ratio (CR)

Other combinations are not allowed. Indoor unit quantity


Air handling unit
Capacity (VRV, RA, AHU, VRV DX indoor unit RA DX indoor unit Hydrobox unit
(AHU)
Hydrobox)

VRV DX indoor units only 50~130% Max.64 50~130% - - -

VRV DX indoor unit + RA DX 80~130% Max.32(1) 0~130% 0~130% - -

(1)
RA DX indoor unit 80~130% Max.32 - 80~130% - -

VRV DX indoor unit + LT hydrobox 50~130% Max.32 50~130% - 0~80% -

VRV DX indoor unit + AHU 50~110%(3) Max.64(2) 50~110% - - 0~110%

AHU only
90~110%(3) Max.64(2) - - - 90~110%
Pair + multi (4)

Remark
(1) There is no restriction on the number of connectable BP boxes.
(2) For connection with AHU
EKEXV kits are also considered indoor units.
(3) Restrictions regarding the air handling unit capacity
(4) Pair AHU = system with 1 air handling unit connected to one outdoor unit
Multi AHU = system with multiple air handling units connected to one outdoor unit

About ventilation applications


I. FXMQ_MF units are considered air handling units, following air handling unit limitations.
Maximum connection ratio when combined with VRV DX indoor units: <30%.
Maximum connection ratio when only air handling units are connected: <100%.
For information on the operation range, refer to the documentation of the FXMQ_MF unit.

II. Biddle air curtains are considered air handling units, following air handling unit limitations:
For information on the operation range, refer to the documentation of the Biddle unit.

III. [EKEXV + EKEQ] units combined with an air handling unit are considered air handling units, following air handling unit limitations.
For information on the operation range, refer to the documentation of the EKEXV-EKEQ unit.

IV. VKM units are considered to be regular VRV DX indoor units.


For information on the operation range, refer to the documentation of the VKM unit.

V. Because there is no refrigerant connection with the outdoor unit (only communication F1/F2), VAM units do not have connection limitations.
However, since there is communication via F1/F2, count them as regular indoor unit when calculating the maximum allowed number of connectable indoor
units.

3D079540E

66 VRV IV+ heat pump, without continuous heating • RXYQ-U


VRV IV+ heat pump, without continuous heating • RXYQ-U

13 Operation range
13 - 1 Operation Range
RXYQQ-U
RXYQ-U
RYYQ-U Cooling Heating 13
45
RYMQ-U 43 20
40

15 15.5
35

30 10

Pull-down operation range


25 5

Outdoor temperature [°C WB]


Outdoor temperature [°C DB]

Warm-up operation range


20

Operation range
0
Operation range

15
-5
10
-10
5

-15
0

-5 -20
14 28 27
10 15 20 25 30 10 15 20 25 30
Indoor temperature [°C WB] Indoor temperature [°C DB]

Notes
1. These figures assume the following operation conditions

Indoor and outdoor units


Equivalent piping length: 5m
Level difference: 0m
2. Depending on operation and installation conditions, the indoor unit can change over to freeze-up operation (indoor de-icing).

3. To reduce the freeze-up operation (indoor de-icing) frequency, it is recommended to install the outdoor unit in a location not exposed to wind.

3D118465
4.Operation range is valid in case direct expansion indoor units are used.

When using special indoor units (e.g. Hydrobox units), see the technical specifications of those units.

VRV IV+ heat pump, without continuous heating • RXYQ-U 67


VRV IV+ heat pump, without continuous heating • RXYQ-U

14 Appropriate Indoors
14 - 1 Appropriate Indoors
RXYQ-U
RYYQ-U
RYMQ-U
14

Recommended indoor units for ·RXYQ*U* / RYYQ*U* / RYMQ*U*· outdoor units

·· HP 8 10 12 14 16 18 20
1xFXMQ50 4XFXMQ63 3xFXMQ50 2xFXMQ50
4xFXMQ50 4xFXMQ63 6xFXMQ50
5XFXMQ63 2xFXMQ80 5XFXMQ63 6xFXMQ63

For multi outdoor units ·>16HP·, the recommended amount of indoor units is the sum of the indoor units defined for a single outdoor unit.
For details about the allowed combinations, see the engineering databook.

Appropriate indoor units for ·RXYQ*U* / RYYQ*U* / RYMQ*U*· outdoor units Covered by ·ENER LOT10·
FTXJ25-35-50
Covered by ·ENER LOT21· FTXA20-25-35-42-50
FXFQ20-25-32-40-50-63-80-100-125 FLXS25-35-50-60
FXZQ15-20-25-32-40-50 FVXM25-35-50
FXCQ20-25-32-40-50-63-80-125 FVXG25-35-50
FXKQ25-32-40-63 CVXM20A
FXDQ15-20-25-32-40-50-63 FVXM25A-35A-50A-60A
FXSQ15-20-25-32-40-50-63-80-100-125-140
FXMQ50-63-80-100-125-200-250 Outside the scope of ·ENER LOT21·
FXAQ15-20-25-32-40-50-63 EKEXV50-63-80-100-125-140-200-250-400-500 + EKEQM / EKEQF
FXHQ32-63-100 HXY080-125
FXUQ71-100 VKM50-80-100
FXNQ20-25-32-40-50-63 CYVS100-150-200-250
FXLQ20-25-32-40-50-63 CYVM100-150-200-250
CYVL100-150-200-250

3D118461B

68 VRV IV+ heat pump, without continuous heating • RXYQ-U


Daikin Europe N.V.  Naamloze Vennootschap · Zandvoordestraat 300 · 8400 Oostende · Belgium · www.daikin.eu · BE 0412 120 336 · RPR Oostende (Responsible Editor)

The present leaflet is drawn up by way of information only and does not constitute an
offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of
this leaflet to the best of its knowledge. No express or implied warranty is given for the
completeness, accuracy, reliability or fitness for particular purpose of its content and the
products and services presented therein. Specifications are subject to change without prior
notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in
EEDEN20 10/2020
the broadest sense, arising from or related to the use and/or interpretation of this leaflet.
All content is copyrighted by Daikin Europe N.V.

You might also like