0% found this document useful (0 votes)
123 views4 pages

Fire Horn I-2447th

The Integrity Temporal Horn is a fire alarm notification device designed for indoor or outdoor wall or ceiling mounting. It can be set to sound either a temporal tone or steady tone at output levels of 104 dBA or 99 dBA. The horn operates from 20-31 Vdc or 20-27 Vfwr and can be installed in North American electrical boxes or compatible surface mounting boxes. Its installation involves setting the desired output level and tone, connecting it to the fire alarm control panel's signal circuit while observing polarity, and mounting it to the box using the included mounting plate.

Uploaded by

Jorge Chacon
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
123 views4 pages

Fire Horn I-2447th

The Integrity Temporal Horn is a fire alarm notification device designed for indoor or outdoor wall or ceiling mounting. It can be set to sound either a temporal tone or steady tone at output levels of 104 dBA or 99 dBA. The horn operates from 20-31 Vdc or 20-27 Vfwr and can be installed in North American electrical boxes or compatible surface mounting boxes. Its installation involves setting the desired output level and tone, connecting it to the fire alarm control panel's signal circuit while observing polarity, and mounting it to the box using the included mounting plate.

Uploaded by

Jorge Chacon
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Temporal Horn

Product description Specifications


Operating voltage: 20 to 31 Vdc or 20 to 27 Vfwr
The horn must be connected to a continuous voltage when
it is set to sound a temporal tone; it may be connected to
either a pulsed or continuous voltage when set to sound a
steady tone.
Horn operating current at low volume setting
20 to 31 Vdc: 20 mA
20 to 24 Vfwr: 23 mA
Horn operating current at high volume setting
20 to 31 Vdc: 48 mA
20 to 24 Vfwr: 52 mA
Synchronization: Pulses at temporal rate within 200 ms on
common circuit.
Horn temporal pattern: 0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off,
0.5 s on, 1.5 s off, repeat cycle
Sound output: See Table 2
Wire size: 12 to 18 AWG (2.50 to 0.75 sq mm)
Compatible electrical boxes
North American 2-1/2 inch (64 mm) deep 2-gang
Standard 4 in square box 2-1/8 in (54 mm) deep
Surface mounting box per Table 1
Operating humidity
Indoor: 93% relative humidity at 104 °F (40 °C)
Outdoor: 98% relative humidity at 104 °F (40 °C)
The Integrity Temporal Horn is a fire alarm notification Operating temperature
appliance designed for indoor or outdoor use. The horn can be Indoor: 32 to 120 °F (0 to 49 °C)
used for wall or ceiling mounting. See Table 1 for a list of Outdoor: –35 to 150 °F (–31 to 66 °C)
model numbers.
The horn can be set to sound a temporal tone or a steady tone. Table 2: Sound output (dBA) [1]
Its output level can be set to 104 dBA or 99 dBA. Method Temporal Continuous
Install this product in accordance with applicable requirements Low High Low High
in the latest editions of NFPA 72, National Fire Alarm Code,
and the Canadian Electrical Code, Part 1, Section 32, and in Anechoic - peak at 24 Vdc 99 104 99 104
accordance with the local authorities having jurisdiction.
Anechoic - average at 24 Vdc 94 98 94 98
Table 1: Model numbers Reverberant room per UL 464 at 75 82 82 85
24 Vdc
Model description Model numbers
ULI at 20 Vdc 75 79 79 82
Temporal Horn, Red 757-1A-T INT-T
XLS757-1A-T 2447TH-R [1] Sound level output at 10 ft (3.05m)

Temporal Horn, White 757-1A-TW INT-TW


XLS757-1A-TW 2447TH-W Installation instructions
Surface Box, Red, 757A-SB INT-SB WARNING: To reduce the risk of shock, do not tamper with the
Indoor XLS757A-SB 2459-SMB-R unit when the circuit is energized. Disconnect all power and
Surface Box, White, 757A-SBW INT-SBW allow 5 minutes for stored energy to dissipate before handling.
Indoor XLS757A-SBW 2459-SMB-W
Weatherproof Box, Red, 757A-WB INT-WB Caution: Electrical supervision requires the wire run to be
Outdoor XLS757A-WB 2459-WPB-R broken at each terminal. Do not loop the signaling circuit field
wires around the terminals.
Weatherproof Box, 757A-WBW INT-WBW
White, Outdoor XLS757A-WBW 2459-WPB-W Figure 3 shows mounting details for a standard 4 in square
Bi-directional Mounting 757A-BDF INT-BDF box. An extension ring can be used for additional wiring space.
Frame, Red, Indoor XLS757A-BDF When using a standard 2-gang electrical box that is 2-1/2 in
Bi-directional Mounting 757A-BDFW INT-BDFW (64 mm) deep, conduit entry must be from the rear of the box.
Frame, White, Indoor XLS757A-BDFW

Installation Sheet 09JUL02 P/N: P-047550-1779 REV: 4.0


Temporal Horn 1/4
Figure 3 also shows a weatherproof and surface mount boxes. Jumper setup
See Table 1 for model numbers of compatible boxes.
To install the temporal horn:

1. The unit is set to 104 dBA at the factory. To set the output
to 99 dBA, remove the low output jumper from the circuit
board on the rear of the unit (see Figure 1). REMOVE FOR REMOVE FOR
LOW OUTPUT CONT. TONE
2. The unit is set to temporal tone at the factory. To set the
output to steady tone, remove the continuous tone jumper
from the circuit board on the rear of the unit (see Figure 1).
Tip: Save each jumper by sliding it onto a single pin in

STROBE +

STROBE –
HORN +

HORN –
case you need to change the settings again.
3. Select and install a suitable electrical box.
For outdoor installations use a weatherproof backbox.
4. Bring the signal circuit field wiring into the electrical box.
4 3 2 1
5. Position the mounting plate on the electrical box with the
hook flange facing outward as shown in Figure 3. Fasten
the plate using two pan-head slotted screws (supplied). Figure 1: Jumper setup and terminal block
6. Connect the horn terminals to the signal circuit field wiring.
You must observe polarity for the unit to function properly. Wiring diagram
See the Wiring diagrams topic, below.
For additional wiring details, see the installation
+
instructions for the signaling modules or circuits used in –
the fire alarm control panel.
Horn Horn
7. After connections are complete, attach the unit to the
mounting plate. + HORN + HORN +
– HORN – HORN –
• The grille has tabs (at the top of the inner face) that
engage with the hook flange on the mounting plate.
• Angle the bottom of the grille out slightly, and slide the
To listed fire alarm control To next device or
unit into place so that the tabs engage the flange. panel signal circuit EOL resistor
• Seat the grille by pressing the bottom in.
• Fasten the bottom of the grille to the mounting plate Figure 2: Wiring diagram
by tightening the captive locking screw.
8. Apply power and activate the unit to verify that it is Maintenance
operating properly. This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.

P/N: P-047550-1779 REV: 4.0 09JUL02 Installation Sheet


2/4 Temporal Horn
5-59/64 in Weatherproof box
(150 mm)
Gasket

3-13/32 in
(87 mm)
5-59/64 in
(150 mm)
2-1/8 in
(54 mm)
Standard box

Hook flange
Knockouts for 1/2 in (13 mm) or 3/4 in
(19 mm) conduit top, bottom, back

3-5/16 in
(84 mm)
5-5/8 in
(143 mm)

5-5/8 in
5-1/2 in (143 mm)
(140 mm)
Mounting plate
8-32 screw (supplied)

5-1/2 in Surface mount box


(140 mm) 5/8 in
Captive locking screw (16 mm)

Figure 3: Mounting details

Installation Sheet 09JUL02 P/N: P-047550-1779 REV: 4.0


Temporal Horn 3/4
P/N: P-047550-1779 REV: 4.0 09JUL02 Installation Sheet
4/4 Temporal Horn

You might also like