The Process of the Tank Level Measuring with EL-T Sensor
ECR Visualization
no tank level display
possible failure and system warning
sensor damage connection box IO-Card failure software failure
PPC-IPC
system warning: system warning: system warning: system warning:
SF No OFF No
modbus cable (Offline)
(Sensor Failure)
Control cabinet
Bus Interface BI
check the wiring in
connection box
IO-Card IO884
2-wire cable
measure sensor Check the anologue
Local Side wiring ok?
output signal 1 input of the IO-Card
Connection Box no
check the yes signal yes yes
Status ok? call Pleiger-Service
wiring/venting filter 4…20mA?
Venting connction with filter
no no
Tank
change the sensor change the IO-Card
Tank with submerged tank
level sensor
Measuring range: 0… 0,4 the status of the LED- indication of the anologue input of the IO-Card
bar
green LED input signal meaning
Current output:
permanent ON 20,2 mA>= I >=3,8mA normal input signal
4…20mA
flashes quickly I > 20,2mA over upper limit, short circuit
flashes slowly 3,8 mA>= I >=0,2mA under lower limit
location 1 see next two pages OFF I <=0,2mA broken cable
Measuring the output current of the tank level sensor
measuring position: connection box
current measuring device
(multimeter) A
Measuring the ouput current signal of the Tank Sensor
current measuring device
current measuring device
(multimeter)
(multimeter)
Wrong! Correct!
parallel connection serial connection
Connection Box
Connection Box
Level Sensor Level Sensor
EL-T EL-T
6
Measuring the output current of the tank level sensor
measuring position: control cabinet
attention: at first you should find the correct wiring diagram and the correct connecting terminal
Sensor medium installation measuring sensor input Tank Height tank volume on
No. Tank Name remark
type density height (m) range (mWC) signal (mA) (m³) display (m³)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Calculation formula for self-check of the sensor function for example:
Parameters: Parameters:
1. Sensor input signal I (mA) 1. Sensor input signal I (mA): 12 mA
2. Measuring range P (mWC) 2. Measuring range P (mWC) : 4mWC
3. Tank height H (m) 3. Installation height h (m): 0.1 m
4. Installation height h (m) 4. Medium density ρ (g/cm³): 0.98 g/cm³
5. Medium density ρ (g/cm³)
4 12 4
∗
∗ 4
0.1 2.14
16 ∗ ρ 16 ∗ 0.98