TCW241
Ethernet I/O module
Overview
TCW241 is an Ethernet I/O module. It provides four digital “dry contact” inputs and four analog 0-60V inputs, with 10-
bit resolution. The controller supports up to 8 TERACOM 1-Wire sensors for temperature, humidity, carbon dioxide,
0/20mA, AC/DC current, etc.
The Ethernet I/O module has 4 relays with normally open and normally close contacts.
TCW241has real-time clock (RTC) with time server synchronization (NTP) for advanced relay scheduler.
The relays of Ethernet I/O module can be activated either remotely or locally. So called remote activation includes WEB
interface or M2M protocols – MODBUS TCP/IP, SNMP and HTTP API.
The local activation is possible from scheduler, status of single parameter or by custom made functions. The custom
made functions can include up to four parameters.
Applications
• Server room monitoring - The device can monitor AC power supply, smoke concentration, door opening, battery
voltage, room temperature and control the cooling system.
• M2M systems - The device can send periodically information to dedicated server and execute its commands.
• Scheduled control - The device can be used for one-time or repetitive (weekly) tasks to turn on/off relays at
previous set times.
• Environmental monitoring – The device can monitor temperature, humidity, barometric pressure, CO2 etc.
• HVAC systems – with its 4 relays, scheduler and custom made functions the device is right choice for climate control.
Interfaces
1-Wire
0-60V
100 Mbit 4x 4x 4x 8x
Ethernet Digital Inputs Analog Inputs Relay Îutputs 1-Wire Sensors
Basic features
• WEB server for simple configuration and control; • HTTP Post service with API commands;
• Multiplier and offset for analog inputs and some sensors; • XML/JSON status report files;
• MODBUS/TCP support; • NTP protocol support for time synchronization;
• SNMP v2 support with trap alert; • Scheduled control;
• SMTP support for e-mail alert • Custom functions.
www.teracom.cc
TCW241 - Ethernet I/O module
Short specification
Supply voltage, VDC 10 - 32
Maximum current (with all relays ON), mA 350@12VDC
Weight, g 230
Dimensions, mm 145 x 90 x 40
Operating temperature, °C -20 to +55
Maximum humidity, %RH 70
Supply voltage for 1-Wire bus (VDD), VDC 5.0 ± 0.3
Maximum output current for 1-Wire bus (VDD), A 0.2
Analog inputs range, VDC 0 to 60
Analog inputs resolution, VDC 0.01
Analog inputs accuracy, % ±1
Maximum switchable relay current, À 3
Maximum switchable relay voltage, VAC/VDC 42/60
Typical application
TCW241
HTTP POST
Router
Dynamic IP Address
HT
TP
PO
ST
INTERNET
Router
HTTP POST HTTP POST
Commands Commands
ST
PO
L
TCW241 XM nd
s Public IP Address
a
Router mm TC Monitor
XML POST Co
or other SCADA software
Commands
Dynamic IP Address
Supported sensors and detectors
A
Temperature Humidity Barometric CO2 AC/DC Detectors
pressure current with
relay output
Software
• TC Monitor
• TCW Control for Android
• TCW Control for iOS
• Third party software applications
www.teracom.cc