Diesel Generator Maintenance Checklist
16 Mar 2022 / Yeesvaran Narayanasamy Incomplete
Score 0% Failed items 0 Actions 0
Customer
Conducted on (Date and Time) 16 Mar 2022 22:09 +08
Job Number
Generator Model & Serial Number
Engine Model & Serial Number
Service Meter Unit
Inspector Full Name Yeesvaran Narayanasamy
Address
CRANKING TEST PROCEDURE
1. Turn the selector switch from trickle to boost on AMF Board, 2 hours before conducting the cranking test.
AMF Board Battery Charger Selector switch. (TURN BOOST)
2. To perform a cranking test, press the genset controller to stop button and turn on the MCB.
The genset will automatically crank for 15 seconds and then rest for 5 seconds for six cycles.
Genset controller( STOP) cranking relay & MCB (ON)
3. Upon completion of the cranking, Switch off the MCB and start the generator by pressing the start button on the
genset controller.
MCB (OFF) Genset controller (START)
4. To shut down the generator, press the Auto button and then switch the AMF board's selection switch from boost to
trickle for normalize.
Genset controller (AUTO) AMF Board Battery Charger Selector switch. (TURN TRICKLE)
Please don't hesitate to contact us at +60166829492 if you have any queries.
Clean and tighten electrical connections, clean crankcase breather, check and
tighten mounting bolts
Fan belt drive tension (mm) and condition
Alternator Inspection 0%
Coupling arrangement
Environmental conditions & cleanliness
Check earth bonds
Check guard, screens, warning and safety labels
Operating Inspection 0%
Check Engine for Exhaust, Fuel, Lube, and coolant leakage
Any abnormal sound or vibration
Smoke Colour
Any abnormal alarm from the generator control panel
Run generator set (under load) to check voltage, check frequency, check
instrument system and make adjustments.
Inspect safety shutdown devices. This includes simulated faults on Low Oil
Pressure Shutdown, High Water Temperature Shutdown, Over Speed
Shutdown and Emergency Stop Shutdown.
Other Services 0%
Wipe up Generator surface
Dispose all waste items
Check Air inlet and outlet Ducts
Clean the Exterior of the Generator
Completion
Recommendations and Overall Condition Assessment
Next maintenance service date
Full Name and Signature
Appendix
Photo 1
Photo 2
Photo 3
Photo 4
Photo 5
Photo 6
Photo 7